SuperDuct Series
Less than
Features two inches deep!
Detector assembly
Less than 2" deep for easy installation and applications where
space is tight
PCB mounted photoelectric detector with on-board intelligence
Environmental compensation with patented differential sensing
for reliable, stable, and drift-free sensitivity
-4 oF to 158 oF operating range with 100 ft/min. to 4,000 ft/min air
velocity rating assures reliability under harsh environmental
conditions
Standard RJ45 modular interconnection cuts time off wiring and
installation, screw terminal models also available
Status LEDs remain visible through clear assembly cover – even
after installation
Cover tamper reed switch for added security
Description
Standard sampling tube and mounting holes enable spacing for EST SuperDuct smoke detectors are the most advanced and most
easy drop-in replacement of competitive detectors reliable devices in their class. Designed for easy installation and
superb reliability, SuperDuct represents the perfect balance of
May be installed in tandem with the controller assembly, or
practical design and advanced technology.
remotely from it
Sampling tubes install from front-side or back-side of housing Reliability and stability are two features built into every
SuperDuct detector. SuperDuct features environmental compen-
Magnet-activated test/dirty/reset switch – ideal for enclosed
sation with patented differential sensing. This achieves a level of
spaces and hard-to-reach locations
stability and reliability never before achieved for devices of this
No need to open the detector for installation type. With differential sensing, SuperDuct sensors are immune
from sensitivity drift – a common cause of false alarms. Every eight
minutes the SuperDuct sensor checks its environment for dirt,
Controller
humidity other conditions that normally interfere with sensor
One controller for up to two detectors operation, and automatically adjusts its sensitivity to compensate.
Standard field connections for easy drop-in migration from other The result is unparalleled reliability and rock solid stability – two
detectors features essential to any duct smoke detection application.
24 Vac, 24 Vdc, 120 Vac or 230 Vac operation Sensitivity testing and diagnostics reveal some of the most
Status LEDs remain visible through clear assembly cover – even exciting innovations built into SuperDuct. With the ingenious
after installation SuperDuct remote test station, a sensitivity test can be performed
Knockouts located on the bottom help protect components from at any time from the safety and comfort of a maintenance office or
the elements utility room. Operated either by key or by magnet, the one-gang
station also performs alarm tests for detectors connected to a
Alarm contact, trouble contact, and two robust 10 amp auxiliary single controller. Detectors may also be tested at the controller via
contacts a test switch, or they can be tested individually in the field with a
No tools required to access field connection terminals simple-to-operate magnetic test tool. Access to the magnetic reed
Able to interconnect up to 15 controllers for multiple fan shut- switch does not require the detector cover to be removed, so
down testing can be performed quickly and easily.
Exhaust Return
Controller
oil
oil
olin
atin
Co
He
Detector
2.72"
details).
Wiring between detector and controller, along with wiring
between controller and fire alarm panel (if used) is supervised.
5.45"
Assembly
1.9"
Controllers and detectors come pre-assembled for easy installation
for the RJ-45 models. They are sold separately for the terminal
versions.
1.375" 5.4"
Interconnection 8.706"
8.15"
RJ-45 Model 7.75"
Detector
Optional second sensor
2.275"
RJ-45 wiring harness
(ordered separately)
5.45"
1.9"
6.756"
6.200"
5.800" 1.9"
1.1" Controller
2.275"
3.25"
5.45"
Terminal Model
TB3 3
4
5
Nonpower-limited Power-limited 6
First sensor
7
Controller
8
+ 5 5
IDC circuit on
fire alarm Alarm Alarm
contacts contacts
control panel End-of-line resistor required on
- 4 4 last device for circuit supervision.
Use resistor value specified by the
Trouble contacts Trouble contacts EOLR fire alarm panel manufacturer.
14 3 14 3 Note: This configuration is not
allowed when using remote
test stations.
Fire alarm initiating circuit wiring
Controller
Controller 17
- 10 Auxiliary
6 equipment
24 VAC/DC
+ 9
16
L
7
120 V/220 V/24 V
N Auxiliary
18 equipment
15 1
Alarm
First Second
controller controller 4
19
12 12 Power
Next 13
controller
1 1
3 5
Trouble
17 17
2 3
6 6 Reset/Test
20 2
16 16
Note: For applications where only the Alarm LED
Fan control Fan control and Reset/Test switch is required, wiring the Power
mechanism mechanism LED and Trouble LED is optional.