Preparation Work
1. Connection:
Use RS232 / RS485 communication converter wire to connect fire alarm control panel and PC. (Drawing 1)
Connect to MA and
MB Control Panel, PC
programming port
RS485 / RS485
CONVERTER
Connect to USB
laptop port
Drawing 1
Power on the control panel and enter into commissioning menu and push down [8] key and come into “Exchange”
function, “standby” is displayed on the LCD screen, and the control panel enter to communication state. At this
time, we can use computer based special software to edit, upload and download associated operation
programming information. (Drawing 2)
Drawing 2
Revision No.: 00
Page 1 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Drawing 3
`
Drawing 4
Revision No.: 00
Page 2 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Function Introduction
Select location
Drawing 5
For example, when the location description of the loop 1 and Number 2 device is “Room 1”, please input as
(Drawing 6).
Revision No.: 00
Page 3 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Loop number
co
c
o
Device number
Edit Area
Drawing 6
After the user finish editing the device location descriptions, click “Write” button, select the loop number on the dialog
box, then click “OK” button of the dialog box (Drawing 7), the programming software will transmit the selected device
location description to the control panel, and hint the information in the process of transmitting and saving will be
displayed on the LCD of the control panel in return.
“Saving location information”
“Saved location information”
Note:
1. The transmitting and saving of the information will take a period of time, during that period, user cannot
have other operation.
2. Software can only read-in location description of one loop to the control panel each time.
3. The device location description will be eliminated, if there are no characters in its corresponding grid.
Revision No.: 00
Page 4 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Drawing 7
Note: Programming software can only read location description of one loop panel each time.
When the users need to load the content of the document in the editing form, click “Load” button, then select the
name of the loading document in the dialog box, click the “Open” button in the dialog box to load the document
(Drawing 9).
Revision No.: 00
Page 5 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Drawing 8
Drawing 9
Revision No.: 00
Page 6 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Drawing 10
Revision No.: 00
Page 7 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Detailed description see “linkage programming” below or section in the manual of control panel.
For Example, users need to read-in the following two linkage record to the control panel:
Panel 1, loop 1 number 1-5 and device number 10-15 of loop 1, panel 1 adopt “OR1”
Logic, to panel 1 command device number 115-120 of loop 1
Panel 1, loop 1 device number 6-8 and device number 18-22 of loop 1, panel 1 adopt “AND”
Logic to panel 1, command device number 110-125 of loop 1
As (Drawing 11).
Linkage 1 Linkage 2
Drawing 11
Note: Page 1 in the programming software is equivalent or starting number page “000” on control panel
Revision No.: 00
Page 8 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
After the user finish editing the linkage record, click “Write” button, input the linkage record number in the dialog
box (in this sample, the linkage record number is 2), click the “OK” button in the dialog box (Drawing 12), and the
programming software will transmit the linkage record of the editing form to the control panel. After the control
panel finish the saving of linkage record, the acknowledge information will be displayed on the LCD:
“Saved program information”
Note: Linkage record must be edited in sequence, blank line cannot be left in the middle.
Drawing 12
3. [History record]
Read the history record from the control panel.
Select the [History record] option in the list of [Information Type] on the software interface (Drawing 13), enter
“history record” function.
Revision No.: 00
Page 9 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Drawing 13
In the editing form, horizontal line shows history record number, and the vertical line shows the inclusive elements
in each history record. 3 elements are included in one history record:
“Alarm Type”
“Device No.”
“Alarm Time”
The first two digit of “Device No.” means loop number of device, and the last 3 digit means the device address. For
example, “01002” means “loop 1 number 2 device”.
When the alarm type of history record is “event”, different “Device No.” shows different events, detailed
description see “device address distribution list / device address assignment sheet” in the manual of control panel.
Revision No.: 00
Page 10 of 11
PROGRAMMING GUIDE
LIFECO Configuration Utility
For Models: LF-6100 Series FACP
Drawing 14
Exit:
Click “Test” button, the control panel will exit the communication state.
Revision No.: 00