FOR ROOM
AIR CONDITIONER
(Inverter Split-Type)
1. PRECAUTIONS ................................................................. 3 1.1 Safety precautions • Ensure the installation area does not deteriorate with
1.1 Safety precautions ...................................................... 3 • To prevent injury to the user or other people and age.
1.2 Warning ..................................................................... 3 property damage, the following instructions must be If the base collapses, the air conditioner could fall with it,
followed. causing property damage, product failure, and personal injury.
2. FUNCTIONS ..................................................................... 5 • Do not let the air conditioner run for a long time when
• Incorrect operation due to not following instructions
3. DIMENSIONS ................................................................... 6 may cause personal injury or damage. the humidity is very high and a door or a window is left
• Before servicing the unit, be sure to read this service open.
3.1 Indoor Unit ................................................................. 6
manual first. • Take care to ensure that the power cable cannot be
3.2 Outdoor Unit ............................................................... 7
pulled out or damaged during operation.
4. REFRIGERANT CYCLE DIAGRAM ..................................... 8 1.2 Warning Faulty cabling increases the risk of fire or electric shock.
5. WIRING DIAGRAM ........................................................... 9 ❯ INSTALLATION • Do not place anything on the power cable.
5.1 Indoor Unit ................................................................. 9 • Do not use a defective or underrated circuit breaker. Use This increases the risk of fire or electric shock.
this appliance on a dedicated circuit. • Do not plug or unplug the power supply plug during
5.2 Outdoor Unit ............................................................. 11
If these directions are not followed, you run the risk of starting operation.
6. INSTALLATION DETAILS ................................................ 13 a fire or suffering an electric shock. This increases the risk of fire or electric shock.
6.1 Wrench torque sheet for installation ........................... 13 • For electrical work, contact the dealer, seller, a qualified • Do not operate the product with wet hands.
6.2 Connecting the cables .............................................. 13 electrician, or an authorized service centre. • Do not place a heater or other appliance near the power
6.3 Pipe length and the elevation ..................................... 14 Do not disassemble or repair the product as doing so will cable.
6.4 Installation for the first time ....................................... 15 increase the risk of fire or electric shock. This increases the risk of fire or electric shock.
6.5 Adding the refrigerant after running • Always ground the product. • Do not allow water to run into electrical parts.
Not doing so increases the risk of starting a fire or suffering an This may cause fire, failure of the product, or electric shock.
the system for many years ........................................ 18
electric shock.
6.6 Re-installation while the indoor unit • Do not store or use flammable gas or combustible
• Install the panel and the control box cover securely. products near the unit.
need to be repaired .................................................. 19
Not doing so increases the risk of starting a fire or suffering an This increases the risk of fire or electric shock.
6.7 Re-installation while the outdoor unit
electric shock.
need to be repaired .................................................. 21 • Do not use the product in an enclosed space for a long
• Always install a dedicated circuit and circuit breaker. time.
7. OPERATION CHARACTERISTICS .................................... 23 Improper wiring or installation may cause a fire or electric Oxygen deficiency may occur.
8. ELECTRONIC FUNCTIONS .............................................. 24 shock.
• If you experience a flammable gas leak, turn off the gas
8.1 Abbreviations ........................................................... 24 • Use the correctly rated fuse or circuit breaker and open a window for ventilation before turning the
8.2 Display function ........................................................ 24 Not doing so increases the risk of starting a fire or suffering an product on.
electric shock. • If strange sounds or smoke comes from product, turn
8.3 Main Protection ........................................................ 25
• Do not modify or extend the power cable. the breaker off or disconnect the power supply cable
8.4 Operation Modes and Functions ................................ 25
Improper wiring or installation may cause a fire or electric immediately.
9. TROUBLESHOOTING ........................................................ 33 shock. Not doing so increases the risk of fire or electric shock.
9.1 Indoor Unit Error Display ............................................ 33 • Do not install, remove, or reinstall the unit by yourself • Close the window and do not operate the unit in
9.2 Diagnosis and Solutions ............................................ 33 (customer). electrical storms or severe winds. If possible, remove
Improper wiring or installation may cause a fire or electric the product from the window before the storm arrives.
shock. Not doing so increases the risk of property damage, failure of
• Be careful when unpacking and installing the product. product or electric shock.
Sharp edges may cause injury. Be especially careful of the • Do not open the inlet grill of the product during
case edges and the fins on the condenser and evaporator. operation. (Do not touch the electrostatic filter, if the
• For installation, always contact the dealer or an unit is so equipped.)
authorized service centre. There is risk of physical injury, electric shock, or product failure.
• Do not install the product on a defective installation • If the unit is soaked, contact an authorized service
stand. centre.
There is an increased risk of fire or electric shock.
2 3
4 5
Model W D H
LNEO26V 790 198 265
LNEO35V 920 223 292
LNEO50V
998 240 322
LNEO65V
L R
Model W D H W1 A B
LNCO26V
760 285 590 823 530 290
LNCO35V
H LNCO50V 845 320 700 908 560 335
LNCO65V 900 315 860 980 590 333
6 7
CHECK VALVE
LIQUID SIDE (Heating Model only)
2-WAY VALVE
CAPILIARY TUBE
HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)
GAS SIDE
LNEO35V
3-WAY VALVE REVERSING VALVE
(Heating Model only)
ACCUMULATOR
COOLING
COMPRESSOR HEATING
8 9
LNEO65V LNCO35V
10 11
LNCO65V The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which is located
on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
12 13
Two-way valve
Close
(Gas side)
Three-way valve
Vacuum
pump
Electronic scale
Procedure: Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the 5. Discharge the refrigerant. Close the valve on the charging 1. Connect the charge hose to the charging cylinder, open the 4. Operate the air conditioner in the cooling mode.
“closed” position. cylinder and discharge the refrigerant by loosening the flare nut 2-way valve and the 3-way valve. Connect the charge hose 5. Open the valves (Low side) on the charge set and charge the
2. Connect the charge set and a charging cylinder to the service on the 2-way valve approximately 45° until the gauge indicates which you disconnected from the vacuum pump to the valve at system with liquid refrigerant.
port of the 3-way valve. 0.3 to 0.5 Mpa. the bottom of the cylinder. If the refrigerant is R410A, make the
6. When the electronic scale displays the proper weight (refer to
6. Disconnect the charge set and the charging cylinder, and set cylinder bottom-up to ensure the liquid charge.
3. Air purging. Open the valves on the charging cylinder and the the table), disconnect the charge hose from the 3-way valve’s
charge set. Purge the air by loosening the flare nut on the the 2-way and 3-way valves to the “open” position. Be sure to 2. Purge the air from the charge hose. Open the valve at the service port immediately and turn off the air conditioner before
2-way valve approximately 45° for 3 seconds then closing it use a hexagonal wrench to open the valve stems. bottom of the cylinder and press the check valve on the charge disconnecting the hose.
for 1 minute; repeat 3 times. After purging the air, use a torque 7. Mount the valve stems nuts and the service port cap. Be sure set to purge the air (be careful of the liquid refrigerant).
7. Mount the valve stem caps and the service port. Use a torque
wrench to tighten the flare nut on the 2-way valve. to use a torque wrench to tighten the service port cap to a 3. Put the charging cylinder onto the electronic scale and record wrench to tighten the service port cap to a torque of 18Nm. Be
4. Check for gas leakage. Check the flare connections for gas torque of 18Nm. Be sure to check for gas leakage. the weight. sure to check for gas leakage.
leakage.
16 17
Electronic scale
Procedure: Procedure:
1. Connect the charge hose to the 3-way service port, open the 5. Open the valves (Low side) on the charge set and charge the 1. Confirm that both the 2-way and 3-way valves are set to the 4. Set the 2-way valve to the “closed” position.
2-way valve and the 3-way valve. Connect the charge hose system with liquid refrigerant. “open” position 5. Operate the air conditioner on the cooling cycle and stop it
to the valve at the bottom of the cylinder. If the refrigerant is 6. When the electronic scale displays the proper weight (refer to Remove the valve stem caps and confirm that the valve stems when the gauge indicates 0.1MPa.
R410A, make the cylinder bottom-up to ensure liquid charge. the gauge and the pressure of the low side), disconnect the are in the “open” position. 6. Set the 3-way valve to the “closed” position immediately.
2. Purge the air from the charge hose. Open the valve at the charge hose from the 3-way valve’s service port immediately Be sure to use a hexagonal wrench to undo the valve stems. Do this quickly so that the gauge ends up indicating 0.3 to
bottom of the cylinder and press the check valve on the charge and turn off the air conditioner before disconnecting the hose. 0.5Mpa. Disconnect the charge set, and tighten the 2-way and
2. Connect the charge hose with the push pin of handle Lo to the
set to purge the air (be careful of the liquid refrigerant). 7. Mount the valve stem caps and the service port. Use a torque 3-way valve’s stem nuts. Use a torque wrench to tighten the
3-way valve’s gas service port.
3. Put the charging cylinder onto the electronic scale and record wrench to tighten the service port cap to a torque of 18Nm. Be 3-way valves service port cap to a torque of 1.8 kgf.m. Be sure
3. Air purging of the charge hose. Open the handle Lo valve of the
the weight. sure to check for gas leakage. to check for gas leakage.
manifold valve slightly to purge air from the charge hose for 5
4. Operate the air conditioner in the cooling mode. seconds and then close it quickly.
18 19
Procedure: Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the 5. Discharge the refrigerant. Close the valve on the charging 1. Confirm that both the 2-way and 3-way valves are set to the
“closed” position. cylinder and discharge the refrigerant by loosening the flare nut “open” position.
2. Connect the charge set and a charging cylinder to the service on the 2-way valve approximately 45° until the gauge indicates 2. Connect the vacuum pump to 3-way valve’s service port.
port of the 3-way valve. Leave the valve on the charging 0.3 to 0.5 Mpa.
3. Evacuate for approximately one hour. Confirm that the
cylinder closed. 6. Disconnect the charge set and the charging cylinder, and set compound meter indicates -0.1Mpa.
3. Air purging. Open the valves on the charging cylinder and the the 2-way and 3-way valves to the “open” position. Be sure to
4. Close the valve (Low side) on the charge set, turn off the
charge set. Purge the air by loosening the flare nut on the use a hexagonal wrench to operate the valve stems.
vacuum pump, and confirm that the gauge needle does not
2-way valve approximately 45° for 3 seconds then closing it 7. Mount the valve stems nuts and the service port cap. move (approximately 5 minutes after turning off the vacuum
for 1 minute; repeat 3 times. After purging the air, use a torque Be sure to use a torque wrench to tighten the service port cap pump).
wrench to tighten the flare nut on the 2-way valve. to a torque 18Nm. 5. Disconnect the charge hose from the vacuum pump.
4. Check for gas leakage. Check the flare connections for gas Be sure to check for gas leakage.
leakage.
20 21
CAUTION
1. If the air conditioner is used outside the above conditions,
certain safety protection features may come into operation
and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the
air conditioner operates above this figure, the surface of
the air conditioner may attract condensation. Please set the
vertical air flow louvre to its maximum angle (vertically to the
floor), and set fan mode to HIGH.
3. Optimum performance will be achieved whilst operating
within this temperature zone.
Electronic scale
Procedure:
1. Connect the charge hose to the charging cylinder, open the 4. Open the valves (Low side) on the charge set and charge the
2-way valve and the 3-way valve. Connect the charge hose system with liquid refrigerant. If the system cannot be charged
which you disconnected from the vacuum pump to the valve at with the specified amount of refrigerant, it can be charged a
the bottom of the cylinder. If the refrigerant is R410A, make the little at a time (approximately 150g each time), operating the
cylinder bottom-up to ensure liquid charge. air conditioner in the cooling cycle. However, one time is not
2. Purge the air from the charge hose. sufficient. Wait approximately 1 minute and then repeat the
procedure.
Open the valve at the bottom of the cylinder and press the
check valve on the charge set to purge the air (be careful of the 5. When the electronic scale displays the proper weight,
liquid refrigerant). disconnect the charge hose from the 3-way valve’s service
port immediately. If the system has been charged with liquid
3. Put the charging cylinder onto the electronic scale and record
refrigerant while operating the air conditioner, turn off the air
the weight.
conditioner before disconnecting the hose.
6. Mount the valve stem caps and the service port. Use a torque
wrench to tighten the service port cap to a torque of 18Nm. Be
sure to check for gas leakage.
22 23
High
8.3.4 Fan Speed is out of control
27
When Indoor Fan Speed remains too low (300RPM) for a certain
Medium
time, the unit will stop and the LED will display the failure. 25.5
25
8.3.5 Inverter Module Protection
The Inverter module has a protection function related to current, Low
voltage and temperature. If one of these protection functions
occur, the corresponding code will display on the indoor unit and
the unit will stop working.
8.4.2 Cooling Mode
8.3.6 Indoor fan delayed 10 seconds open function 8.4.2.1 Compressor running guidelines
Run Indication Lamp: This lamp lights up when the air When the unit starts up, the louvre will be active immediately The maximum operating frequency of the compressor after
run conditioner is in operation. and the indoor fan will open 10 seconds later. If the unit runs in starting is specified in the diagram below:
heating mode, the indoor fan will be also controlled by the anti-
cold wind function.
Auto Indication Lamp: Lights up during the Auto operation Fmax=F4
8.3.7 Compressor pre-heating functions 45
Pre-heating permitting condition:
43
Ion Indication Lamp: Lights up when Ionizer/Plasma If T4 (outdoor ambient temperature) < 3° and the machine has
ion function is activated. just been turned on or if T4 < 3° and compressor has been 40 Fmax=F7
switched off for over 3 hours, the compressor heating cable will
38
work.
Timer Indication Lamp: Lights up during Timer operation Pre-heating mode: 30 Fmax=F8
timer
If the current flow through the wiring terminal of the compressor is
too low, the compressor can get heated even if it is not operating. 28
Defrost Indication Lamp: This indicator lights up when the
air conditioner starts defrosting automatically or when the Pre-heating release condition: 22 Fmax=F6
def. anti-cold wind function is activated in heating operation. If T4 > 5° or the compressor starts running, the pre-heating
function will stop. 20
C 34 Off
2.0 33
D 20 28
1.5 Fmax=F2
27
1.0
E Low
25 Fmax=F3
F 24
0.5
22
21 Fmax=F4
-0.5
G
-1.0 8.4.2.3 Indoor fan running rules 19
18 Fmax=F5
H In cooling mode, the indoor fan runs continuously and the speed
can be selected as high, medium, low and auto. Auto fan in 17
Fmax=F6
cooling mode acts as follow: 16
Temp. zone A B C D E F G 15
Fmax=F7
Frequency F8 F8 F7 F6 F5 F3 F1 14
12
Fmax=F8
11
Note:
When T1-Ts remains in the same temperature zone for 3 minutes, the compressor will run according to the following: 4 6
5 Fmax=F9
A~E: Increase the frequency to the higher level until reaches F8.
High
3 Fmax=F10
F: Maintain the current frequency.
Medium
G: Decrease the frequency to the lower level until it reaches F1.
1.5
H: Run at F1 for 1 hour (if T1-Ts < -2°, the compressor will stop) If users switch on the unit by remote control, the compressor will
1 run at the Fmax frequency for 7 minutes according to outdoor
Meanwhile, the compressor running frequency is limited by the current. ambient temperature. During the 7 minutes, the frequency
Low limitation is active.
Resume
8.4.2.5 Evaporator temperature protection
• T2 < 0°, the compressor will stop and restart when T2 ≥ 5°.
• 0° ≤ T2 < 4°, the compressor frequency will be limited and
Off: Compressor stops. reduced to the lower level
Decrease: Decrease the running frequency to the lower level. Note: When unit is in the “hold” zone for 3 minutes, the • 4° ≤ T2 ≤ 7°, the compressor will maintain the current
Hold: Maintain the current frequency. compressor frequency will rise to the higher level. (The maximum frequency.
Resume: No limitation for frequency. amount frequency will increase is 200%) • T2 > 7°, the compressor frequency will not be limited.
26 27
Condition of defrosting:
H T4 > 0°C,
When the unit is running, if the following two conditions are met,
H the unit starts defrosting:
+5.0
+4.5 Low • The unit runs with T3 < 3°C for 40 minutes and T3 keeps lower
17 than TCDI°C for more than 3 minutes.
G
+3.5
• The unit runs with T3 < 3°C for 80 minutes and T3 keeps lower
than TCDI + 2°C for more than 3 minutes and TCDI = – 6°C.
+3.0 F
15
T4 < 0°C,
+2.5 E
High If the 1st and 2nd conditions are met, then the program
+2.0 D determines if T2 has decreased by more than 5°C. When T2
has decreased by more than 5°C, it will automatically enter the
C defrosting mode.
+1.5
No matter what value T4 is, if the machine runs with T3 < 3°C for
+1.0 B 8.4.3.3 Indoor fan running rules more than 120 minutes and T3 remains lower than TCDI + 4°C for
+0.5
If the compressor stops due to the room temperature rising, the more than 3 minutes, the machine will enter the defrosting mode
A
indoor fan will be forced to run for 127 seconds with breeze. no matter if T2 drops by more than 5°C or not.
During this period, the anti-cold-wind is disabled.
If the machine runs in rating capacity test mode, the indoor fan Condition of ending defrosting:
will run with rating speed and the anti-cold-wind function is If any one of the following conditions are met, the defrosting will
disabled. finish and the machine will return to normal heating mode.
Temp. zone A B C D E F G Indoor fan speed can be set as high, medium, low or auto fan and • T3 rises to be higher than TCDE1°C.
Frequency F10 F9 F8 F7 F5 F3 F1 the anti-cold-wind function is optional. • T3 remains higher than TCDE2°C for 80 seconds.
▲T = 0°C as default. Auto fan action in heating mode: • The machine has run for 10 minutes in defrosting mode.
Breeze
Off
I3HEAT 17
Decrease Off
I2HEAT
I1HEAT Hold
Resume
While TEH2 = 53°C for LNIV2610 and LNIV3510 8.4.7 Timer function
TEH2 = 55°C for LINV5010 and LNIV6510 8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. The machine will turn on automatically when
8.4.4 Auto mode reaching the set time.
This mode can be chosen with the remote control and the setting 8.4.7.3 Timer off. The machine will turn off automatically when
temperature can be changed between 17–30°C. In auto mode, reaching the set time.
the machine will choose cooling, heating or fan-only mode 8.4.7.4 Timer on/off. The machine will turn on automatically when
according to ▲T (▲T =T1-Ts). reaching the set “on” time, and then turn off automatically when
reaching the set “off” time.
▲T = T1 - Ts Running mode
8.4.7.5 Timer off/on. The machine will turn off automatically when
▲T > 1°C Cooling
reaching the set “off” time, and then turn on automatically when
-1 < ▲T ≤ 1°C Fan-only reaching the set “on” time.
▲T ≤ -1°C Heating 8.4.7.6 The timer function will not change the unit’s current
Indoor fan will run on auto in the relevant mode. operation mode. If the unit is off, it will not start up after setting
the “timer off” function. When reaching the set time, the timer LED
For other models: The louvre operates same as in relevant mode.
will be off and the unit running mode will not be changed.
If the machine switches modes between heating and cooling, the
8.4.7.7 The set time is relative to the actual time.
compressor will keep stopping for 15 minutes and then choose
the relevant mode according to T1-Ts. If the temperature setting is
8.4.8 Sleep function mode
modified, the machine will choose running function again.
8.4.8.1 Operation time in sleep mode is 7 hours. After 7 hours the
8.4.5 Drying mode units leaves this mode and turns off.
8.4.5.1 Indoor fan speed is fixed at breeze and can’t be changed. 8.4.8.2 Operation process in sleep mode is as follows:
The louvre angle is the same as in cooling mode. When cooling, the set temperature rises 1°C (be lower than 30°C)
8.4.5.2 Compressor running rules every one hour. 2 hours later the setting temperature stops rising
and indoor fan is fixed at low speed.
8.4.5.3 Low indoor room temperature protection
When heating, the set temperature decreases 1°C (be higher than
In drying mode, if room temperature is lower than 10°C, the
17°C) every one hour. 2 hours later the set temperature stops
compressor will stop and not resume until room temperature
rising and indoor fan is fixed at low speed.
exceeds 12°C.
8.4.8.3 Timer setting is available
8.4.5.4 Evaporator anti-freezing protection, condenser high
temperature protection and outdoor unit frequency limit are active 8.4.8.4 When user uses timer off function in sleep mode (or sleep
and the same as that in cooling mode. function in timer off mode) and the set time is less than 7 hours,
sleep function will be cancelled when reaching the set time. If the
8.4.5.5 The outdoor fan operates the same as in cooling mode.
set time is more than 7 hours, the machine will not stop until it
reaches the set time in sleep mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
When the machine is off, pressing the touch button will change
the setting to forced auto mode. Pressing the button again within
Model FD FD1
5 seconds will change the setting to forced cooling mode. In
LNIV3510 60 70 forced auto, forced cooling or any other operation mode, pressing
LNIV5010 the touch button will turn off the machine.
90 100
LNIV6510 8.4.6.2 In forced operation mode, all general protections and
remote control are available.
30 31
Yes
32 33
Turn off the power supply. After 1 minute, re-start Turn off the power supply and turn
the unit using the remote control it back on 5 secs later
The unit does not work normally The unit does not work normally
Yes
Are the LED4 (red) and LED1 (yellow) lights Is the fan motor connector and
Replace indoor PCB
blinking on the outdoor PCB? connection good?
No
Replace the PCB
Yes
Yes
Replace the sensor and check if the error
Replace the outdoor PCB
re-occurs.
34 35
Yes Yes
Yes
No
No Is the refrigerant circulation Is the protector OK? Replace it
Check whether the IPM is affixed to volume normal?
Fasten the IPM to the radiator
the radiator tightly.
Yes
No, Charge refrigerant
No
Is the power supply good? Make sure the power supply is normal
Replace the outdoor e-box Are the connections to the compressor good? No
Is the wiring sequence correct? Is the voltage Re-connect and test again.
supply within the correct range?
Yes
No
Replace the outdoor PCB Replace the inverter compressor
36 37