3.If a refrigerating system extracted 48,800 Btu per hour, the tonnage of the machine would be:
Answer: D
A. 5 tons
B. ½ ton
C. 2 tons
D. 4 tons
4.The purpose of the low pressure cut out switch is to: Answer: D
A. Maintain liquid refrigerant at the suction of the compressor
B. Maintain a present suction pressure to the compressor
C. Cut out the compressor at s set pressure
D. Cut compressor in and out at a present pressure
10.The device used for low – pressure control and high – pressure cutout on a compressor is called a:
Answer: B
A. cutout
B. pressure controller
C. controller switch
D. cutout switch
12.Liquid reaching the compressor through the suction line is called: Answer: A
A. Flooding back
B. superheating
C. overflowing
D. recycling
14.If the cooling water to the condenser should suddenly fail: Answer: C
A. The solenoid valve will close
B. The expansion valve will close
C. The compressor will shut down
D. An alarm will ring to notify the Engineer
15.If the solenoid valve closed by accident, the compressor would be stopped by the: Answer: A
A. Low – pressure cutout
B. High –pressure cutout switch
C. Low – water cutout switch
D. Automatic trip
19.If the compressor short cycles on high pressure cutout, which of the following would you
check?Answer: D
A. Be user system is getting cooler
B. If plenty of cooling water is running through but is not picking up heat, the condenser
tubes need cleaning
C. Check for too much refrigerant in the system
D. All of the above
20.In a refrigerating system the temperature is at its highest between the: Answer: B
A. Condenser and receiver
B. Compressor and condenser
C. Receiver and evaporator
D. Evaporator and compressor
21.A Freon unit will tend to short cycle when operating under: Answer: C
A. Heavy load
B. Normal conditions
C. light loads
D. all of the above
22.Short – cycling means that machine: Answer: B
A. Grounds out frequently
B. Stops and starts frequently
C. Runs too fast
D. Runs too slow
25.A method of reducing capacity without reducing compressor speed is called: Answer: C
A. Low pressure by passing
B. High pressure by passing
C. Hot gas by passing
D. Short - cycling
30.When heavy electrical currents are involved, the thermostat will be operated by a: Answer: D
A. Small circuit breaker
B. Pressure pipe
C. fusetron
D. relay
31.If the compressor runs continually, the cause might be the: Answer: B
A. High – pressure cutout switch is jammed open
B. Low – pressure switch is jammed about
C. Thermal bulb is not operating properly
D. Scale trap is clogged
33.If the compressor had been running satisfactory, for a long period of time but the coil level was
rising slowly, the thing to do would be to: Answer: B
A. Drain out sufficient oil to bring it down to the proper running level
B. Shut down the compressor and check the oil level with the machine stopped
C. Check the dehydrator cartridge
D. Check to see if there is too much refrigerant in the system
34.If the compressor had been running satisfactory for a long period of time but suddenly the
compartment temperature started to rise, the trouble might be: Answer: D
A. The solenoid valve is jammed shut
B. The expansion valve may have water frozen in it
C. A refrigerant leak has developed
D. Any of the above
35.When charging a Freon system, all the valves should be in their normal position except the:
Answer: C
A. Expansion valve
B. Purge valve
C. King valve(liquid)
D. Solenoid valve
36.Abnormal discharge temperatures would be caused by: Answer: D
A. Leaky suction valves
B. Leaky discharge valves
C. Faulty piston rings
D. All of the above
37..A device for holding open the suction valve and drawing gas from the suction manifold and
returning it to the suction line without compressing it is called: Answer: B
A. Discharge line bypass
B. Cylinder unloader
C. Suction line bypass
D. Relief valve
38.As heat is removed open the suction valve and drawing gas from the suction manifold and
returning it to the suction line without compressing it is called: Answer: C
A. Perfect zero
B. Double zero
C. Absolute zero
D. Cold zero
39.The boiling point of water in an open container at sea level is 212°F. If the pressure on the open
container is decreased, such as going up to the top of a mountain, the boiling point will be:
Answer: B
A. increased
B. decreased
C. the same
D. none of the above
41.If the temperature in the icebox is too high, the trouble could be: Answer: C
A. A clogged scale trap
B. Air in the system
C. Automatic controls not functioning properly
D. Insufficient cooling water to the condenser
42.Oil is added to a Freon compressor by: Answer: B
A. Pouring through oil hole in base
B. Pumping in with a hand pump
C. Pumping it with an electric – driven pump
D. Shutting down the machine and pouring in through the crankcase inspection plate
opening
43.If no gaskets are used in the piping joints of a Freon system, the joints must be: Answer: C
A. Finished joints
B. Welded joints
C. Ground joints
D. Soldered joints
44.When adding oil to a Freon system one must be sure that: Answer: A
A. All air removed from the pump and fittings
B. There is too high a suction pressure
C. The discharge pressure is too high
D. The condenser is shut down
46.If the compressor – discharge temperature is higher than the receiver temperature: Answer: B
A. Increase the amount of cooling water to the condenser
B. Decrease the amount of cooling water to the condenser
C. Add more refrigerant to the system
D. Remove some of the refrigeration from the system
48.If the discharge side of the thermal expansion valve is warmer than the inlet side, the: Answer: B
A. Expansion valve is working normally
B. Expansion valve is not working normally
C. When adding refrigerant to the system
D. A and C
49.The oil level in the compressor should be checked: Answer: D
A. While the compressor is in operation.
B. Just before starting the compressor
C. After a long period of operation
D. B and C
53.If the high – pressure switch on the compressor opens and stops the compressor, a possible cause
could be: Answer: D
A. Too much cooling water going through the condenser
B. Not enough refrigerant in the system
C. A leak in the evaporator cells
D. Not enough cooling water going through the condenser
55.Which of the following would not cause high suction pressure: Answer: A
A. Insufficient refrigeration
B. Leaky suction valves
C. Expansion valve stuck open
D. Suction valve not adjusted properly
56.All of the following are alloys of nickel except: Answer: C
A. K - monel
B. Inconel - X
C. Chromium molybdenum steel
D. Nichrome
60.Frost on the outside of the thermal expansion valve may be cause by:: Answer: C
A. King valve and the expansion valve
B. Receiver and the condenser
C. Compressor and the receiver
D. Evaporator coils and the compressor
74.
76.The valve that prevents water from backing out of the boiler in to the feed line is the: Answer: C
A. Bottom – blow valve
B. Skin valve
C. Feed – check valve
D. Feed – stop valve
83.What is the first thing you would check on taking over a watch?Answer: C
A. The bigles
B. The periscope
C. The water level
D. The oil pressure
84.The boiler with its fan(blower) located in the uptake is operating on: Answer: A
A. Induced draft
B. Forced draft
C. Natural draft
D. None of the above
85.A fire room that is completely isolated(closed) operates: Answer: B
A. Induced draft
B. Forced draft
C. natural draft
D. None of the above
86.How many feed water lines are connected to the boiler: Answer: B
A. one
B. two
C. three
D. four
87.If the water in the gage glass has not been blown down for a period of time, the level of the water
in the glass will be: Answer: B
A. The same as that in the steam and the water drum
B. Less than that in the steam and water drum
C. More than that in the steam and water drum
D. None of the above
89.When you are cleaning fuel – oil burner tips, use a: Answer: C
A. Steel scraper
B. Wire brush
C. Brass knife
D. Pocket knife
90.What is the amount of liquid in a tank if you get an ullage sounding of 11’4’’ and the empty ullage
sounding of the tank 32’2’’: Answer: B
A. 20’8’’
B. 20’10’’
C. 21’8’’
D. 21’10’’
95.All fuel – oil service pump steam valves are fitted with: Answer: B
A. Safety locks
B. Automatic controls
C. Reach rods leading to a location outside the fire room
D. Reach rods leading to the engine room
96.Which of the following the fire extinguishers would not be found in the fire room: Answer: D
A. Foam type
B. sand
C. 𝐶𝑂2
D. 𝑆𝑂2+
97.What is the average fuel – oil temperature range of the oil in the discharge line to the burners:
Answer: A
A. 180° - 200°
B. 150° - 180°
C. 200° - 220°
D. 150° - 200°
\
99.The boiler gage glasses should be blown down: Answer: B
A. Once a day
B. At the beginning of every watch
C. Every 12 hours
D. Every 8 hours
100. Gage pressure of 200 lbs per square inch is equivalent to what absolute pressure? Answer: A
A. 215
B. 200
C. 185
D. 300