Sie sind auf Seite 1von 4

DISCRIPTION

1, 1000 KVA 11000/415 V ON LOAD DISTRIBUTION TRANSFORMERS

INDOOR TYPE 11 KV VCB PANEL [ ICOG ], INCLUDING SUITABLE SIMENS MAKE VCB,
NUMEICAL 3 O/C + 1E/F RELAY, MASTER TRIP RELAY, TRAFO FAULT RELAY,
2, ANNUNCIATOR WITH INBUILT PUSH BOTTON
600 KVAR APFC PANEL WITH 800 A ON/OFF SWITCH
3,
SRNO DESCRIPTION
1 Specifications reference
2 Rating in kva
3 No load voltage ratio
4 Primary amps
5 Secondary amps
6 No of phase
7 Frequency
8 Method of cooling
9 Vector group
10 Tapping mode
11 Taping range°°

Losses
A, no load loss
12 B, full load loss(copper loss)
13 Impedance (%)
14 Insulation class

Insulation level
A, power frequency test voltage(kVrms)(hv/lv)
15 B, impulse test voltage (kvp)(hv/Lv)
16 Material of winding
Terminal arrangement
17 HV LV
18 Core
19 Maximum temperature rise over an ambient of 45° c

LIST OF STANDARD FITTINGS AND ACCESSORIES


• RTCC Panel with AVR
• Conservator tank with oil filing hole and cap
• Air release plug
• Rating & diagram nameplate
• Detachable Radiators
• Lifting lugs for transformers
• Oil temperature without electric controls
• Lifting lugs for cover
• Silica gel breather
• Thermometer pocket
• Top filter valve with plug
• Plain oil level gauge
• Explosion vent
• Pam connector at LV
• Buchholz Relay
• Aluminum Bus bar for LV side suitable for cable
EXTRA ACCESSORIES
• Oil temperature indicator
• Winding temperature indicator
• Marshaling box
• Magnetic oil level gauge

• PRICE BASE ON
• TAXES
• WARANTEE
•VALIDITY
• DELIVERY
• PAYMENT
• UNLODING
• ERECTION & COMMISSIONING
• INSPECTION
QTY.
1 NO.

1 NO.

1 NO.
PARTICULARS

1000
11000/415
52.5
1391
3
50 HZ
ONAN
Dyn11
OLTC (ON LOAD TAP CHANGER ) WITH RTCC + AVR PANEL
NORMAL + 10% IN STEP OF 1.25% ( 17 NOS )

A - 1.55 KW , B - 13 KW (SUBJECT TO IS TOL)

4.75% (SUBJECT TO IS TOL)


A' CLASS

A - 28 / 3 , B - 95
COPPER
HV WINDING- BARE BUSHING , LV WINDING - CABLE BOX , ORIENTATION - 180° C
CRGO , STAKED
OIL - 50° C ,WINDING - 55°C

YES
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
EPOXY BUSHING AT LV, SO NOT REQUIRED PAM CONNECTOR
YES
YES

YES
YES
YES
YES

Ex--works.
0% Tax against export.
24 MONTHS FROM DATE OF COMMISSIONING BUT ONLY IN INDIA

Das könnte Ihnen auch gefallen