Software writing instruction on Daikin HXHD125A HT indoor unit
1. • This instruction
• Altherma programming cable with “write” extension
(Part nr: 999480P)
• Blue extension cable (part nr: 999485P; drawing nr: 4PW50601-1)
• Following files:
flashsta.exe (programming software)
14004001.mot.mot (software file)
Remark: In case you do not have the above software files available,
please contact DENV Service Department via
fqs.technicalservices@daikineurope.com
2
Software writing instruction on Daikin HXHD125A HT indoor unit
STEP1:
Shut down the main circuit breaker of the unit. It is very
important that there is no power supplied to the indoor
unit.
STEP2:
Open the front plate of the unit to have acces to the switch
box:
Location of
connector X50A
3
Software writing instruction on Daikin HXHD125A HT indoor unit
STEP3:
Install the first end of the programming cable (blue
extension) to X50A connector on the main PCB of the indoor
unit.
STEP4:
Connect serial port end of the cable to the laptop.
4
Software writing instruction on Daikin HXHD125A HT indoor unit
STEP5:
Close the front plate of the indoor unit.
STEP6:
Put power supply to the indoor unit by switching ON the main
circuit breaker.
5
Software writing instruction on Daikin HXHD125A HT indoor unit
6
Software writing instruction on Daikin HXHD125A HT indoor unit
Directory
YP0045V003.mot
14004001.mot
14004001.mot
5. Click on “OK”.
7
Software writing instruction on Daikin HXHD125A HT indoor unit
1 : Click on “Setting”
8
Software writing instruction on Daikin HXHD125A HT indoor unit
9
Software writing instruction on Daikin HXHD125A HT indoor unit
10
Software writing instruction on Daikin HXHD125A HT indoor unit
After clicking on “OK”, the window “M16C Flash start” appears again.
1. Click on “Exit” to finish the programming.
The unit has now been reprogrammed.
STEP9:
Shut down the power supply again with the main circuit breaker
of the unit, to avoid error on hydrobox.
STEP10:
Open the front plate of the indoor unit.
STEP11:
Disconnect the programming cable on the indoor units’ PCB.
11
Software writing instruction on Daikin HXHD125A HT indoor unit
STEP 12:
Add sticker (local supply) with new software version on the indoor
PCB as indicated below:
STEP13:
Close the indoor unit.
STEP14:
Reconnect the power supply and start up the unit again.
12