SELECTION OF WATER COOLED SCREW CHILLER – 180 TR

Chiller selection Software


Version 4.37 (21-AOUT-2007) - Copyright © 2000-2007, Carrier Corp.

* Project Bio Zeen


Date 11/18/2008 12:13:05 PM
Location Bangalore
Company name Aerience
Contact name
CARRIER reference 30HXC

* Product 30HXC190-PH3
Range 30HXC Phase3 (Standard)
Gross capacity 634 kW
Unit absorbed power 128 kW
Compres. Input power 128 kW
C.O.P. 4.93
No of capacity steps 6
Minimum step 21 %
Refrigerant R134a
Expansion valve EXV

* Evaporator
Fluid Water
Leaving T. 6 °C
Delta T. 5 K
Entering T. 11 °C
Flow rate 30.3 L/s
Evaporator pressure drop 61 kPa
Fouling factor 0.0176 m²-K/kW
Max operating pressure 1000 kPa

* Condenser
Fluid Water
Entering T. 30 °C
Delta T. 4.4 K
Leaving T. 34.4 °C
Flow rate 41 L/s
Pressure drop 72 kPa
Fouling factor 0.044 m²-K/kW
Max operating pressure 1000 kPa

T.H.R. 756 kW

* No of compressors 2
Compressor type screw
Compressor motor speed 49 r/s
Starter type WYE/DELTA

* Volts/Phases/Hertz 400-3-50
Power Factor (at max power) 0.87
Maximum current drawn 344 A (U nom.)
Maximum starting current 442 A
Voltage limits 360/440 V

* Operating weight 3179.0 kg


Refrigerant charge 140 kg
Length/Width/Height 3275 mm
980 mm
1940.5 mm