Beruflich Dokumente
Kultur Dokumente
* Product 30HXC190-PH3
Range 30HXC Phase3 (Standard)
Gross capacity 634 kW
Unit absorbed power 128 kW
Compres. Input power 128 kW
C.O.P. 4.93
No of capacity steps 6
Minimum step 21 %
Refrigerant R134a
Expansion valve EXV
* Evaporator
Fluid Water
Leaving T. 6 °C
Delta T. 5 K
Entering T. 11 °C
Flow rate 30.3 L/s
Evaporator pressure drop 61 kPa
Fouling factor 0.0176 m²-K/kW
Max operating pressure 1000 kPa
* Condenser
Fluid Water
Entering T. 30 °C
Delta T. 4.4 K
Leaving T. 34.4 °C
Flow rate 41 L/s
Pressure drop 72 kPa
Fouling factor 0.044 m²-K/kW
Max operating pressure 1000 kPa
T.H.R. 756 kW
* No of compressors 2
Compressor type screw
Compressor motor speed 49 r/s
Starter type WYE/DELTA
* Volts/Phases/Hertz 400-3-50
Power Factor (at max power) 0.87
Maximum current drawn 344 A (U nom.)
Maximum starting current 442 A
Voltage limits 360/440 V