Sie sind auf Seite 1von 4

Schedule of load preparation is essential and a basic calculation for electrical engineers.

In
this process the proper sizing of conductors, overload protection and conduits are
determined.

While there are different methods doing an electrical design but there is only one thing that
cannot be altered --- code requirements must be followed.

Sample Electrical Plan:

Sample Electrical Plan


 The diagram describe above is simple example of an electrical plan where the actual number of
outlets in lighting and convenience outlet are known.
 This example emphasized the procedure rather than mimicking the actual loads of a residential
unit.
 In this example the voltage drop and short circuit calculation is not included.
 The system voltage of this example is 220 VAC, 60 HZ, Line-Neutral.
Schedule of Loads

Ckt Load Ph Rating No. of VA Volts Amps Wire CB Cond.


Per Outlets
outlet
1 L.O. 1 100 VA 12 1,200 220 5.45 #14 TW 15 AT, 1P ½”
plug-in dia.
2 L.O. 1 100 VA 9 900 220 4.09 #14 TW 15 AT, 1P ½”
plug-in dia.
3 L.O. 1 100 VA 6 600 220 2.73 #14 TW 15 AT, 1P ½”
plug-in dia.
4 C.O 1 180 VA 10 1,800 220 8.18 #12 TW 20 AT, 1P ¾”
plug-in dia.
5 C.O 1 180 VA 12 2,160 220 9.82 #12 TW 30 AT, 1P ¾”
plug-in dia.
6 ACU 1 2.5 HP 1 2331 220 10.60 #10 TW 30 AT, 1P ¾”
plug-in dia.
7 ACU 1 2.5 HP 1 2331 220 10.60 #10 TW 30 AT, 1P ¾”
plug-in dia.
8 ACU 1 2.5 HP 1 2331 220 10.60 #10 TW 30 AT, 1P ¾”
plug-in dia.
9 Range 1 5000 W 1 5000 220 22.71 # 8 TW 80 AT, 1P 1.0”
Load plug-in dia.
Schedule of Loads

Schedule of loads are just a summary of data to easily identify and facilitate the necessary
values and equipment rating to be used in any electrical installation. Any data given in the
schedule of loads were backed by calculation based on a well settled electrical principles
and code requirements.

Computations

Circuit 1:
I = 1,200 VA/ 220 V = 5.45 Ampere
Wire = 5.45 / 80% = 6.82 Amperes , Use 2.0 sqmm TW wire or #14 AWG [1]
Circuit Breaker = Use 15 A plugin type Circuit Breaker
Conduit = Use 1/2" diameter PVC conduit.

Circuit 2:
I = 900 VA/ 220 V = 4.09 Ampere
Wire = 4.09/ 80%= 5.11 Amperes , Use 2.0 sqmm TW wire or #14 AWG
Circuit Breaker = Use 15 A plugin type Circuit Breaker
Conduit = Use 1/2" diameter PVC conduit.

Circuit 3:
I = 600 VA/ 220 V = 2.72 Ampere
Wire = 2.72/ 80%= 3.41 Amperes , Use 2.0 sqmm TW wire or #14 AWG
Circuit Breaker = 6.82 Amperes, Use 15 A plugin type Circuit Breaker
Conduit = Use 1/2" diameter PVC conduit.
Circuit 4:
I = 1,800 VA/ 220 V = 8.18 Ampere
Wire = 8.18/ 80%= 10.23 Amperes , Use 3.5 sqmm TW wire or #12 AWG
Circuit Breaker = 20.45 Amperes, Use 20 A plugin type Circuit Breaker
Conduit = Use 3/4" diameter PVC conduit.

Circuit 5:
I = 2,160 VA/ 220 V = 9.82 Ampere
Wire = 9.82/ 80% = 12.27 Amperes , Use 3.5 sqmm TW wire or #12 AWG
Circuit Breaker = Use 20 A plugin type Circuit Breaker
Conduit = Use 3/4" diameter PVC conduit.

Circuit 6-8:
VA = [ 2.5 HP x ( 746 Watts/ HP ) ] / 0.8 pf (assume 0.8 pf)
VA = 2331 VA

I = 2,331 VA/ 220 V = 10.60 Ampere


Wire = 10.60 x 125% = 13.24 Amperes , Use 3.5 sqmm TW wire or #12 AWG [2]
Circuit Breaker = 5.45 x 250% = 26.5 Amperes, Use 30 A plugin type Circuit Breaker [3]
Conduit = Use 3/4" diameter PVC conduit.

Circuit 9:
VA = 5000 W / 1.0 pf (heating load is a resistive load w/ 100% pf)
VA = 5,000 VA

I = 5, 000 VA/ 220 V = 22.72 Ampere


Wire = 22.71 / 80% = 28.41 Amperes , Use 8.0 sqmm TW wire or #8 AWG
Circuit Breaker = Use 40 A plugin type Circuit Breaker
Conduit = Use 1.0" diameter PVC conduit.

Main Feeder
By inspection:

Continuous loads = 9,963 VA or 45.29 A @ 220V (lighting loads and ACU)


Non- Continuous = 8, 960 VA or 40.72 @ 220V (conv. outlet & range load)
Total Loads = 19, 923 VA

Main Feeder Current = (45.29 x 100% ) + (40.72 x 125%) = 96.19 Amperes [4]

Use 50 sqmm TW cable as main feeder or service entrance wire


Use 100 Ampere MCCB, 1 pole - 10 kAIC*
note: 10 kAIC is just an assumed value, we need short circuit calculation to determine the right
specs of the OCPD to be used in this example

Rules Applied:
1. NEC 210-9a - Maximum to be served by branch circuit must not be less than 80% of the
ampacity of the condutor

2. NEC 430 -22 = The size of the wire supplying motorized load shall not be less than 125%
of the rated full load current of the motor.

3. NEC 430- 52 = The size of the branch circuit protection for motor loads shall not be
greater than 250% of motor full load current for CB and 300% for non-time delay fuses on
full voltage starting.

4. NEC 210-22(C) = Over-Current Protection Device shall be calculated as 100% of non-


continuous load + 125% of the continuous load.

References:
1. National Electrical Code 2011 (Handbook)
2. CESEEPS Red Book, Low Voltage Systems and Applications in the Industries
3. General Electric Circuit Breaker Catalogue

Das könnte Ihnen auch gefallen