QUALITROL 505ITM Series

QUALITROL 505ITM Series


Intelligent Transformer Monitor


Protocol Manual: DNP V3.00, Modbus & ASCII
Communications
Document ID: IST-105-1 ECN-31022

www.qualitrolcorp.com
Legal

Information in this document is subject to change without notice. This document is provided to purchasers of Qualitrol
products for use in the installation, operation and servicing of such products. No other use, nor any reproduction,
distribution or the making of any derivatives of this document is authorized, without the express prior written permission of
Qualitrol.
Qualitrol endeavors to ensure the accuracy and quality of its published materials; however, no warranty, expressed or
implied, is provided. Qualitrol disclaims any responsibility or liability for any direct or indirect damages resulting from the
use of the information in this manual or products described in it. Mention of any product or brand does not constitute an
endorsement by Qualitrol of that product or brand.
This document was originally composed in English and was subsequently translated into other languages. The fidelity of
subsequent translations cannot be guaranteed. In case of conflict between the English version and another language
version, the English version takes precedence.

©2010 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice.
®

All trademarks are properties of their respective companies, as noted herein. IST-104-1.

www.qualitrolcorp.com
505ITM Protocol Manual

Contents
Hardware Instructions.................................................................................... 1 
OVERVIEW ................................................................................................................ 1 
Communications for the Qualitrol 505ITM Series Transformer Monitor ............................ 1 
General .............................................................................................................................. 1 
About Qualitrol ................................................................................................................... 2 
DNP 3.0 Communications .............................................................................. 3 
Introduction .............................................................................................................. 3 
DNP V3.0 Device Profile ........................................................................................... 3 
DNP V3.0 Implementation Table.............................................................................. 6 
DNP V3.0 Point List ................................................................................................ 14 
Binary Input Points ............................................................................................................. 14 
Binary Output Status Points ............................................................................................ 15 
Counters .......................................................................................................................... 16 
Analog Inputs .................................................................................................................. 16 
Analog Output Status Points ........................................................................................... 18 
Octet Strings .................................................................................................................... 19 
Time and Date .................................................................................................................20 
Modbus Protocol .......................................................................................... 21 
General .................................................................................................................... 21 
Function Codes Supported ................................................................................... 21 
Modbus Register Map ............................................................................................ 21 
Binary Parameters ........................................................................................................... 21 
Binary Parameters ........................................................................................................... 22 
Analog Parameters .......................................................................................................... 22 
Analog Parameters .......................................................................................................... 22 
String Parameters ........................................................................................................... 26 
String Parameters ........................................................................................................... 28 
Analog Parameters .......................................................................................................... 28 
String Parameters ........................................................................................................... 29 
Analog Parameters .......................................................................................................... 29 
ASCII Protocol .............................................................................................. 35 

www.qualitrolcorp.com
505ITM Protocol Manual

General .................................................................................................................... 35 


ASCII Framing......................................................................................................... 35 
Packet Structures ................................................................................................... 35 
Error Checking Calculation ................................................................................... 36 
ASCII Register Map ................................................................................................ 37 
Binary Parameters ........................................................................................................... 37 
Binary Parameters ........................................................................................................... 38 
Analog Parameters .......................................................................................................... 38 
Analog Parameters .......................................................................................................... 38 
String Parameters ........................................................................................................... 42 
String Parameters ........................................................................................................... 44 
Analog Parameters .......................................................................................................... 44 
String Parameters ........................................................................................................... 45 
Analog Parameters .......................................................................................................... 45 
Q ASCII Demo Application........................................................................... 51 

www.qualitrolcorp.com
Hardware Instructions
OVERVIEW
Communications for the Qualitrol 505ITM Series
Transformer Monitor
General
The 505ITM comes equipped with digital communication capabilities through a four-wire RS485 port
on the rear of the device. (See the 505ITM configuration form when ordering for the protocols
option). The hardware wiring and configuring the software for the port is explained in the 505ITM
Hardware/Software Manual IST-104-1.
The 505ITM must be configured for the proper communication protocol using the Qualitrol ITM
Manager Software package supplied with the unit (or downloaded from the Qualitrol Web Site
www.qualitrolcorp.com). Using the software package the user can configure the 505ITM for the
appropriate protocol, baud rates, data bits, etc. for their system requirements (see the communication
window below). Once the correct parameters have been entered and loaded into the 505ITM the unit
must have power cycled before these new values will take affect.

1 www.qualitrolcorp.com
About Qualitrol
Qualitrol has been a leader in supplying pressure, liquid level and temperature controls since 1945.
As an ISO 9001 System-certified company, we are committed to providing quality and reliability, both
in our products and in our service.

2 www.qualitrolcorp.com
DNP 3.0 Communications
Introduction
The purpose of this document is to describe specific configuration and interoperability information for
an implementation of the Distributed Network Protocol (DNP), Version 3.0 using the DNP 3.0 Slave
Source Code Library. This document provides information on how to communicate via the DNP 3.0
protocol.
This implementation of DNP 3.0 is fully compliant with DNP 3.0 Subset Definition Level 3, and
contains significant functionality beyond Subset Level 3.

DNP V3.0 Device Profile


The following table provides a “Device Profile Document” in the standard format defined in the DNP
3.0 Subset Definitions Document. While it is referred to in the DNP 3.0 Subset Definitions as a
“Document,” it is in fact a table, and only a component of a total interoperability guide. The table, in
combination with the Implementation Table provided in Section 0 and the Point List Tables provided
in Section 0 should provide a complete configuration/interoperability guide for communicating with a
device implanting the DNP 3.0 Slave Source Code Library.

DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: Qualitrol
Device Name: 505ITM
Highest DNP Level Supported: Device Function:

For Requests:
For Responses:
Level 3
Level 3
 Master
 Slave

3 www.qualitrolcorp.com
DNP V3.0
DEVICE PROFILE DOCUMENT
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):

For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28 (index) are
supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or 01.

16-bit, 32-bit and Floating Point Analog Change Events with Time may be requested.
Analog Input Deadbands, Object 34, variations 1 through 3, are supported.
Floating Point Analog Output Status and Output Block Objects 40 and 41 are supported.
Sequential file transfer, Object 70, variations 2 through 8, are supported.
Octet String and String Event Objects 110 and 111 are supported.
Virtual Terminal Output and Event Objects 112 and 113 are supported.
Device Attribute Object 0 is supported.
Data Set Objects 85-88 are supported.
Output Event Objects 11, 13, 42 and 43 are supported.
Activate Configuration
Secure Authentication

Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):

Transmitted: 292 Transmitted: Configurable up to 2048


Received 292 Received 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:

 None  None
 Fixed  Configurable
 Configurable from 0 to 65535
Requires Data Link Layer Confirmation:

 Never
 Always
 Sometimes
 Configurable as: Never, Only for multi-frame messages, or Always
Requires Application Layer Confirmation:

 Never
 Always
 When reporting Event Data (Slave devices only)
 When sending multi-fragment responses (Slave devices only)
 Sometimes
 Configurable as: “Only when reporting event data”, or “When reporting event data or
multi-fragment messages.”

4 www.qualitrolcorp.com
DNP V3.0
DEVICE PROFILE DOCUMENT
Timeouts while waiting for:

Data Link Confirm:  None  Fixed at ____  Variable  Configurable.


Complete Appl. Fragment:  None  Fixed at ____  Variable  Configurable
Application Confirm:  None  Fixed at ____  Variable  Configurable.
Complete Appl. Response:  None  Fixed at ____  Variable  Configurable

Others: Transmission Delay, configurable


Select/Operate Arm Timeout, configurable
Need Time Interval, configurable
Application File Timeout, configurable
Unsolicited Notification Delay, configurable
Unsolicited Response Retry Delay, configurable
Unsolicited Offline Interval, configurable
Binary Change Event Scan Period, configurable
Double Bit Change Event Scan Period, configurable
Analog Change Event Scan Period, configurable
Counter Change Event Scan Period, configurable
Frozen Counter Change Event Scan Period, configurable
String Change Event Scan Period, configurable
Virtual Terminal Event Scan Period, configurable

Sends/Executes Control Operations:

WRITE Binary Outputs  Never  Always  Sometimes  Configurable


SELECT/OPERATE  Never  Always  Sometimes  Configurable
DIRECT OPERATE  Never  Always  Sometimes  Configurable
DIRECT OPERATE – NO ACK  Never  Always  Sometimes  Configurable

Count > 1  Never  Always  Sometimes  Configurable


Pulse On  Never  Always  Sometimes  Configurable
Pulse Off  Never  Always  Sometimes  Configurable
Latch On  Never  Always  Sometimes  Configurable
Latch Off  Never  Always  Sometimes  Configurable

Queue  Never  Always  Sometimes  Configurable


Clear Queue  Never  Always  Sometimes  Configurable

Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.


Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events
specific variation requested: when no specific variation requested:

 Never  Never
 Only time-tagged  Binary Input Change With Time
 Only non-time-tagged  Binary Input Change With Relative Time
 Configurable to send one or the  Configurable
other

5 www.qualitrolcorp.com
DNP V3.0
DEVICE PROFILE DOCUMENT
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:

 Never  Never
 Configurable  When Device Restarts


Only certain objects
Sometimes (attach explanation)
 When Status Flags Change
 ENABLE/DISABLE UNSOLICITED No other options are permitted.
Function codes supported
Default Counter Object/Variation: Counters Roll Over at:

 No Counters Reported  No Counters Reported


 Configurable  Configurable (attach explanation)
 Default Object  16 Bits
Default Variation:  32 Bits
 Point-by-point list attached  Other Value: _____
 Point-by-point list attached
Sends Multi-Fragment Responses:
 Yes
 No
 Configurable

Sequential File Transfer Support:

Append File Mode  Yes No


Custom Status Code Strings Yes  No
Permissions Field  Yes No
File Events Assigned to Class  Yes No
File Events Send Immediately  Yes No
Multiple Blocks in a Fragment Yes  No
Max Number of Files Open 1

DNP V3.0 Implementation Table


The following table identifies which object variations, function codes, and qualifiers the DNP 3.0 Slave
Source Code Library supports in both request messages and in response messages. For static (non-
change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with
qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28.
For change-event objects, qualifiers 17 or 28 are always responded.
In the table below, text shaded as 00, 01 (start stop) indicates Subset Level 3 functionality (beyond
Subset Level 2).
In the table below, text shaded as 07, 08 (limited qty) indicates functionality beyond Subset Level 3.

6 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
0 1-253 Device Attribute Specific 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
2 (write) 00, 01 (start-stop)

0 254 Device Attribute - Non-Specific All 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Attributes Request 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
0 255 Device Attribute – List of Attribute 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Variations 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
1 0 Binary Input – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
1 1 Binary Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
1 2 Binary Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
2 0 Binary Input Change – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
2 1 Binary Input Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
2 2 Binary Input Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
2 3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
3 0 Double Bit Input – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
3 1 Double Bit Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 1)
07, 08 (limited qty)
17, 27, 28 (index)
3 2 Double Bit Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
4 0 Double Bit Input Change – Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
4 1 Double Bit Input Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
07, 08 (limited qty) 130 (unsol. resp)
4 2 Double Bit Input Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
07, 08 (limited qty) 130 (unsol. resp)
4 3 Double Bit Input Change with Relative 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
10 0 Binary Output – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)

7 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
10 1 Binary Output 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
1 (write 00, 01 (start-stop)

10 2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
11 0 Binary Output Change – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
11 1 Binary Output Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
(default – 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
11 2 Binary Output Change with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
07, 08 (limited qty) 130 (unsol. resp)
12 0 Control Relay Output Block 22 (assign class) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
12 1 Control Relay Output Block 3 (select) 17, 28 (index) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
12 2 Pattern Control Block 3 (select) 7 (limited quantity) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
12 3 Pattern Mask 3 (select) 00, 01 (start- 129 (response) echo of request
4 (operate) stop)
5 (direct op)
6 (dir. op, noack)
13 0 Binary Output Command Event – Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
13 1 Binary Output Command Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
Time 07, 08 (limited qty) 130 (unsol. resp)
13 2 Binary Output Command Event with 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index )
Time 07, 08 (limited qty) 130 (unsol. resp)
20 0 Binary Counter – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)

7 (freeze) 00, 01 (start-stop)


8 (freeze noack) 06 (no range, or all)
9 (freeze clear) 07, 08 (limited qty)
10 (frz. cl. noack)
20 1 32-Bit Binary Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
20 2 16-Bit Binary Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
20 5 32-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
20 6 16-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)

8 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
21 0 Frozen Counter – Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
21 1 32-Bit Frozen Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
21 2 16-Bit Frozen Counter (with Flag) 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
21 5 32-Bit Frozen Counter with Time Of 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-
Freeze 06 (no range, or all) stop)
07, 08 (limited qty) 17, 28 (index –
17, 27, 28 (index) see note 1)

21 6 16-Bit Frozen Counter with Time Of 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-
Freeze 06 (no range, or all) stop)
07, 08 (limited qty) 17, 28 (index –
17, 27, 28 (index) see note 1)

21 9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
21 10 16-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
22 0 Counter Change Event – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
22 1 32-Bit Counter Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
22 2 16-Bit Counter Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty) 130 (unsol. resp)
22 5 32-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
22 6 16-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
23 0 Frozen Counter Event (Variation 0 is 1 (read) 06 (no range, or all)
used to request default variation) 07, 08 (limited qty)
23 1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17,28 (index)
(default – 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
23 2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17,28 (index)
07, 08 (limited qty) 130 (unsol. resp)
23 5 32-Bit Frozen Counter Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
23 6 16-Bit Frozen Counter Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
30 0 Analog Input - Any Variation 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30 1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)

9 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
30 3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
30 4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 5 short floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
30 6 long floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 1)
17, 27, 28 (index)
32 0 Analog Change Event – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
32 1 32-Bit Analog Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1)
32 2 16-Bit Analog Change Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty) 130 (unsol. resp)
32 3 32-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
32 4 16-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
32 5 short floating point Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time 07, 08 (limited qty) 130 (unsol. resp)
32 6 long floating point Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event without Time 07, 08 (limited qty) 130 (unsol. resp)
32 7 short floating point Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited qty) 130 (unsol. resp)
32 8 long floating point Analog Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Event with Time 07, 08 (limited qty) 130 (unsol. resp)
34 0 Analog Input Deadband (Variation 0 is 1 (read) 00, 01 (start-stop)
used to request default variation) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
34 1 16 bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
2 00, 01 (start-stop)
(write) 07, 08 (limited qty)
17, 27, 28 (index)
34 2 32 bit Analog Input Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1) see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
2 00, 01 (start-stop)
(write) 07, 08 (limited qty)
17, 27, 28 (index)
34 3 Short Floating Point Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Deadband 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
2 00, 01 (start-stop)
(write) 07, 08 (limited qty)
17, 27, 28 (index)
40 0 Analog Output Status 1 (read) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)

10 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
40 1 32-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
40 2 16-Bit Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – 06 (no range, or all) 17, 28 (index –
see note 1 see note 2)
07, 08 (limited qty)
17, 27, 28 (index)
40 3 short floating point Analog Output 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Status 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
40 4 long floating point Analog Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index)
41 0 Analog Output Block 22 (assign class) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
41 1 32-Bit Analog Output Block 3 (select) 17, 28 (index) 129 (response) echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 2 16-Bit Analog Output Block 3 (select) 17, 28 (index) 129 (response) echo of request
4 (operate) 27 (index)
5 (direct op)
6 (dir. op, noack)
41 3 short floating point Analog Output Block 3 (select) 17, 27, 28 (index) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
41 4 long floating point Analog Output Block 3 (select) 17, 27, 28 (index) 129 (response) echo of request
4 (operate)
5 (direct op)
6 (dir. op, noack)
42 0 Analog Output Event – Any Variation 1 (read) 06 (no range, or all)
07, 08 (limited qty)
42 1 32-Bit Analog Output Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Time 07, 08 (limited qty) 130 (unsol. resp)
42 2 16-Bit Analog Output Event without 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1
42 3 32-Bit Analog Output Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
42 4 16-Bit Analog Output Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited qty) 130 (unsol. resp)
42 5 short floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
42 6 long floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
42 7 short floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
42 8 long floating point Analog Output Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
43 0 Analog Output Command Event – Any 1 (read) 06 (no range, or all)
Variation 07, 08 (limited qty)
43 1 32-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited qty) 130 (unsol. resp)
43 2 16-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
(default – without Time 07, 08 (limited qty) 130 (unsol. resp)
see note 1
43 3 32-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)

11 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
43 4 16-Bit Analog Output Command Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited qty) 130 (unsol. resp)
43 5 short floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event without Time 07, 08 (limited qty) 130 (unsol. resp)
43 6 long floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event without Time 07, 08 (limited qty) 130 (unsol. resp)
43 7 short floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event with Time 07, 08 (limited qty) 130 (unsol. resp)
43 8 long floating point Analog Output 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Command Event with Time 07, 08 (limited qty) 130 (unsol. resp)
50 0 Time and Date

50 1 Time and Date 1 (read) 07, (limited qty = 1) 129 (response) 07 (limited qty = 1)
(default –
see note 1)

2 (write) 07 (limited qty = 1)

50 3 Time and Date Last Recorded Time 2 07 (limited qty)


(write)

51 1 Time and Date CTO 129 (response) 07 (limited qty)


130 (unsol. resp) (qty = 1)
51 2 Unsynchronized Time and Date CTO 129 (response) 07 (limited qty)
130 (unsol. resp) (qty = 1)

52 1 Time Delay Coarse 129 (response) 07 (limited qty)


(qty = 1)
52 2 Time Delay Fine 129 (response) 07 (limited qty)
(qty = 1)
60 0 Not Defined
60 1 Class 0 Data 1 (read) 06 (no range, or all)
60 2 Class 1 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
20 (enbl. unsol.) 06 (no range, or all)
21 (dab. unsol.)
22 (assign class)
60 3 Class 2 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)

20 (enbl. unsol.) 06 (no range, or all)


21 (dab. unsol.)
22 (assign class)
60 4 Class 3 Data 1 (read) 06 (no range, or all)
07, 08 (limited qty)
20 (enbl. unsol.) 06 (no range, or all)
21 (dab. unsol.)
22 (assign class)
70 0 File Event – Any Variation 1 06 (no range, or all)
(read) 07, 08 (limited qty)
22 (assign class) 06 (no range, or all)

70 2 File Authentication 29 (authenticate) 5b (free-format) 129 (response) 5B (free-format)

70 3 File Command 25 (open) 5b (free-format)


27 (delete)
70 4 File Command Status 26 (close) 5b (free-format) 129 (response) 5B (free-format)
30 (abort) 130 (unsol. resp)
70 5 File Transfer 1 (read) 5b (free-format) 129 (response) 5B (free-format)
2 (write) 130 (unsol. resp)

70 6 File Transfer Status 129 (response) 5B (free-format)


130 (unsol. resp)
70 7 File Descriptor 28 (get file 5b (free-format) 129 (response) 5B (free-format)
info) 130 (unsol. resp)

12 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
70 8 File Specification String 31(activate config) 5b (free-format)
80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01(start-stop)

2 (write) 00 (start-stop)
(see note 3) index=4 or 7
85 0 Data Set Prototype 1 00, 01 (start-stop)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
85 1 Data Set Prototype 1 00, 01 (start-stop) 129 (response) 5B (free-format)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

86 0 Data Set Descriptor 22 (assign class) 00, 01 (start-stop)


06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
86 1 Data Set Descriptor - Contents 1 00, 01 (start-stop) 129 (response) 5B (free-format)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

86 2 Data Set Descriptor – Characteristics 1 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(read) 06 (no range, or all) 17, 28 (index –
07, 08 (limited qty) see note 2)
17, 27, 28 (index
86 3 Data Set Descriptor – Point Index 1 00, 01 (start-stop) 129 (response) 5B (free-format)
Attributes (read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

87 0 Data Set – Present Value 1 00, 01 (start-stop)


(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
87 1 Data Set – Present Value 1 00, 01 (start-stop) 129 (response) 5B (free-format)
(read) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 5b (free-format)

88 0 Data Set Event 1 06 (no range, or all)


(read) 07, 08 (limited qty)

88 1 Data Set Event - Snapshot 1 06 (no range, or all) 129 (response) 5B (free-format)
(read) 07, 08 (limited qty) 130 (unsol. resp)

91 1 Activate Status 129 (response) 07 (limited qty)

110 string Octet String Object 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
length 22 (assign class) 06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index
2 (write) 00, 01 (start-stop)
07, 08 (limited qty)
17, 27, 28 (index)
111 string Octet String Event Object 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
length 07, 08 (limited qty) 130 (unsol. resp)
112 string Virtual Terminal Output Block 2 (write) 00, 01 (start-stop)
length 07, 08 (limited qty)
17, 27, 28 (index)

13 www.qualitrolcorp.com
REQUEST RESPONSE
OBJECT
(Library will parse) (Library will respond with)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
113 string Virtual Terminal Event Data 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
length 07, 08 (limited qty) 130 (unsol. resp)
120 1 Authentication Challenge 32(auth challenge) 5b (free-format) 131 (challenge) 5b (free-format)
132(unsol. challenge
120 2 Authentication Reply 33 (auth reply) 5b (free-format) 129 (response) 5b (free-format)
120 3 Authentication Aggressive Mode 5b (free-format) 131 (challenge) 5b (free-format)
Request 132(unsol. challenge
120 4 Authentication Session Key Status 1 (read) 5b (free-format)
Request
120 5 Authentication Session Key Status 129 (response) 5b (free-format)
120 6 Authentication Session Key Change 129 (response) 5b (free-format)
120 7 Authentication Error 34(auth challenge) 5b (free-format) 129 (response) 5b (free-format)
No Object (function code only) 13 (cold restart)
No Object (function code only) 14 (warm restart)
No Object (function code only) 23 (delay meas.)
No Object (function code only) 24
(record current time)

Note 1: A Default variation refers to the variation responded when variation 0 is requested and/or in
class 0, 1, 2, or 3 scans. Default variations are configurable; however, default settings for the
configuration parameters are indicated in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request
is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00,
01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17
or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 4 or 7 (Need Time IIN1-4 or
Restart IIN1-7)

DNP V3.0 Point List


The tables below identify all the default data points provided by the implementation of the DNP 3.0
Slave Source Code Library.

Binary Input Points


The default binary input event buffer size is set to allow 100 events.

BINARY INPUT; OBJ 1; VAR 0, 1, 2


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1 ENABLED 1 = ENABLED; 0 = DISABLED
1 RELAY 2 ENABLED 1 = ENABLED; 0 = DISABLED
2 RELAY 3 ENABLED 1 = ENABLED; 0 = DISABLED
3 RELAY 4 ENABLED 1 = ENABLED; 0 = DISABLED
8 RELAY 1 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
9 RELAY 2 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
10 RELAY 3 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
11 RELAY 4 ACTUATED 1 = ACTUATED; 0 = NOT ACTUATED
16 SYSTEM STATUS RELAY 1 = ACTUATED; 0 = NOT ACTUATED
17 HEATER STATUS 1 = ENABLED; 0 = DISABLED
18 RELAY 1 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
19 RELAY 2 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED

14 www.qualitrolcorp.com
BINARY INPUT; OBJ 1; VAR 0, 1, 2
POINT POINT VARIABLE DESCRIPTION
20 RELAY 3 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
21 RELAY 4 LATCHING FEATURE 1 = ENABLED; 0 = DISABLED
26 RELAY 1 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
27 RELAY 2 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
28 RELAY 3 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
29 RELAY 4 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
42 INPUT MODULE 1 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
43 INPUT MODULE 2 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
44 INPUT MODULE 3 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
45 INPUT MODULE 4 READ ERROR 1 = ERROR DURING READ; 0 = VALID READ
50 INPUT MODULE 1 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
51 INPUT MODULE 2 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
52 INPUT MODULE 3 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE
53 INPUT MODULE 4 SCALING FEATURE ENABLED 1 = ACTIVE; 0 = NOT ACTIVE

Binary Output Status Points


The following table lists the Binary Output Status Points (Object 10).
While Binary Output Status Points are included here for completeness, they are not often polled by
DNP 3.0 Masters. It is recommended that Binary Output Status points represent the most recent
DNP “commanded” value for the corresponding Control Relay Output Block point. Because many, if
not most, Control Relay Output Block points are controlled through pulse mechanisms, the value of
the output status may in fact be meaningless. Binary Output Status points are not recommended to
be included in class 0 polls.
As an alternative, it is recommended that “actual” status values of Control Relay Output Block points
be looped around and mapped as Binary Inputs. (The “actual” status value, as opposed to the
“commanded” status value, is the value of the actuated control. For example, a DNP control
command may be blocked through hardware or software mechanisms; in this case, the actual status
value would indicate the control failed because of the blocking. Looping Control Relay Output Block
actual status values as Binary Inputs has several advantages:
 it allows actual statuses to be included in class 0 polls,
 it allows change event reporting of the actual statuses, which is a more efficient and time-
accurate method of communicating control values,
 and it allows reporting of time-based information associated with controls, including any delays
before controls are actuated, and any durations if the controls are pulsed.
The default select/control buffer size is large enough to hold 10 of the largest select requests
possible.

BINARY OUTPUT; OBJ 10; VAR 0, 1, 2


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1 ENABLED 1 = ENABLED; 0 = DISABLED
1 RELAY 2 ENABLED 1 = ENABLED; 0 = DISABLED
2 RELAY 3 ENABLED 1 = ENABLED; 0 = DISABLED
3 RELAY 4 ENABLED 1 = ENABLED; 0 = DISABLED
8 INPUT MODULE MAX/MIN RESET PULSE/RESET (1)
9 RELAY 1 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
10 RELAY 2 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC

15 www.qualitrolcorp.com
BINARY OUTPUT; OBJ 10; VAR 0, 1, 2
POINT POINT VARIABLE DESCRIPTION
11 RELAY 3 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
12 RELAY 4 AUTO/MANUAL 1 = MANUAL OPERATION; 0 = AUTOMATIC
19 INPUT MODULE 1 ENABLED 1 = ENABLED; 0 = DISABLED
20 INPUT MODULE 2 ENABLED 1 = ENABLED; 0 = DISABLED
21 INPUT MODULE 3 ENABLED 1 = ENABLED; 0 = DISABLED
22 INPUT MODULE 4 ENABLED 1 = ENABLED; 0 = DISABLED

Counters
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a
freeze function is performed on a Binary Counter point, the frozen value is available in the
corresponding Frozen Counter point. The default Binary Counter and Frozen Counter event buffer
sizes are set to 30.

BINARY COUNTER; OBJ 20; VAR 0, 1, 2, 3, 4, 5, 6


POINT POINT VARIABLE DESCRIPTION
TRANSLIFE 1; TRANSFORMER LIFE TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE
0 CONSUMPTION 1
3 TOTAL TRANSFORMER OPERATING HOURS CUMULATIVE TRANSFORMER OPERATING HOURS

Analog Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit
variations of Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are
transmitted through DNP as signed numbers.
The “Default Deadband,” and the “Default Change Event Assigned Class” columns are used to
represent the absolute amount by which the point must change before an analog change event will be
generated, and once generated in which class poll (1, 2, 3, or none) will the change event be
reported.
The default analog input event buffer size is set 30.

ANALOG INPUT; OBJ 30; VAR 0, 1, 2, 3, 4, 5, 6


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
1 RELAY 2, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
2 RELAY 3, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
3 RELAY 4, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
8 RELAY 1, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
9 RELAY 2, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
10 RELAY 3, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
11 RELAY 4, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
16 INPUT MODULE 1 PRESENT VALUE OR INPUT MODULE 1 PRESENT WINDING TEMP
17 INPUT MODULE 1 MINIMUM VALUE OR INPUT MODULE 1 MINIMUM WINDING TEMP
18 INPUT MODULE 1 MAXIMUM VALUE OR INPUT MODULE 1 MAXIMUM WINDING TEMP
19 0 OR INPUT MODULE 1 PRESENT CURRENT
20 0 OR INPUT MODULE 1 MAXIMUM CURRENT
21 INPUT MODULE 2 PRESENT VALUE OR INPUT MODULE 2 PRESENT WINDING TEMP

16 www.qualitrolcorp.com
22 INPUT MODULE 2 MINIMUM VALUE OR INPUT MODULE 2 MINIMUM WINDING TEMP
23 INPUT MODULE 2 MAXIMUM VALUE OR INPUT MODULE 2 MAXIMUM WINDING TEMP
24 0 OR INPUT MODULE 2 PRESENT CURRENT
25 0 OR INPUT MODULE 2 MAXIMUM CURRENT
26 INPUT MODULE 3 PRESENT VALUE OR INPUT MODULE 3 PRESENT WINDING TEMP
27 INPUT MODULE 3 MINIMUM VALUE OR INPUT MODULE 3 MINIMUM WINDING TEMP
28 INPUT MODULE 3 MAXIMUM VALUE OR INPUT MODULE 3 MAXIMUM WINDING TEMP
29 0 OR INPUT MODULE 3 PRESENT CURRENT
30 0 OR INPUT MODULE 3 MAXIMUM CURRENT
31 INPUT MODULE 4 PRESENT VALUE OR INPUT MODULE 4 PRESENT WINDING TEMP
32 INPUT MODULE 4 MINIMUM VALUE OR INPUT MODULE 4 MINIMUM WINDING TEMP
33 INPUT MODULE 4 MAXIMUM VALUE OR INPUT MODULE 4 MAXIMUM WINDING TEMP
34 0 OR INPUT MODULE 4 PRESENT CURRENT
35 0 OR INPUT MODULE 4 MAXIMUM CURRENT
69 RELAY 1, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
70 RELAY 2, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
71 RELAY 3, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
72 RELAY 4, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
77 RELAY 1, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
78 RELAY 2, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
79 RELAY 3, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
80 RELAY 4, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
85 RELAY 1, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
86 RELAY 2, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
87 RELAY 3, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
88 RELAY 4, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
93 RELAY 1, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
94 RELAY 2, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
95 RELAY 3, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
96 RELAY 4, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
101 RELAY 1, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
102 RELAY 2, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
103 RELAY 3, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
104 RELAY 4, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
109 RELAY 1, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
110 RELAY 2, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
111 RELAY 3, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
112 RELAY 4, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
117 TRANSLIFE 1 CONSUMED LIFE FOR LAST HOUR CALCULATED CONSUMED LIFE FOR LAST HOUR
118 TRANSLIFE 1 CONSUMED LIFE FOR LAST DAY CALCULATED CONSUMED LIFE FOR LAST DAY
119 TRANSLIFE 1 REMAINING TRANSFORMER LIFE (20 YEARS - CONSUMED LIFE)
120 TL1 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
121 TL1 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
122 TL1 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH
CALCULATED TIME TO 1ST SPT FOR GIVEN
123 TL1 TIME TO CRITICAL SETPOINT 1 CONDITIONS
CALCULATED TIME TO 2ND SPT FOR GIVEN
124 TL1 TIME TO CRITICAL SETPOINT 2 CONDITIONS
CALCULATED TIME TO 3RD SPT FOR GIVEN
125 TL1 TIME TO CRITICAL SETPOINT 3 CONDITIONS

17 www.qualitrolcorp.com
TEMP WHERE CONSUMED LIFE EQUALS OPERATING
306 LIFE CONSUMPTION UNITY TEMPERATURE LIFE
TRANSLIFE 1; TEMPERATURE PROFILE, 1ST
314 RANGE TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 2ND
315 RANGE TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 3RD
316 RANGE TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 4TH
317 RANGE TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 5TH
318 RANGE TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 6TH
319 RANGE TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 7TH
320 RANGE TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 8TH
321 RANGE TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 9TH
322 RANGE TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 10TH
323 RANGE TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 11TH
324 RANGE TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE
TRANSLIFE 1; TEMPERATURE PROFILE, 12TH
325 RANGE TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
433 FIRMWARE REVISION FOR THIS 509ITM UNIT
434 TRANSFORMER LIFE SPAN EXPECTED TOTAL LIFE SPAN OF TRANSFORMER

475 RELAY 1, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 1


476 RELAY 2, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 2
477 RELAY 3, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 3
478 RELAY 4, ACTUATION COUNTS ACTUATION COUNTER FOR RELAY 4
483 RELAY 1, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 1
484 RELAY 2, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 2
485 RELAY 3, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 3
486 RELAY 4, RATE OF CHANGE TIME PERIOD RATE OF CHANGE TIME PERIOD FOR RELAY 4

Analog Output Status Points


The following table lists the Analog Output Status Points (Object 40).
While Analog Output Status Points are included here for completeness, they are not often polled by
DNP 3.0 Masters. It is recommended that Analog Output Status points represent the most recent
DNP “commanded” value for the corresponding Analog Output Control Block point. Analog Output
Status points are not recommended to be included in class 0 polls.
As an alternative, it is recommended that “actual” status values of Analog Output Control Block points
be looped around and mapped as Analog Inputs. (The “actual” status value, as opposed to the
“commanded’ status value, is the value of the actuated control.) For example, a DNP control
command may be blocked through hardware or software mechanisms; in this case, the actual status
value would indicate the control failed because of the blocking. Looping Analog Relay Output Block
actual status values as Analog Inputs has several advantages:
 it allows actual statuses to be included in class 0 polls,
 it allows change event reporting of the actual statuses, which is a more efficient method of
communicating control values,

18 www.qualitrolcorp.com
 and, if analog change events with time variations are supported by the DNP master, it allows
reporting of time-based information associated with controls, including delays before the controls
are actuated.
The default select/control buffer size is large enough to hold 10 of the largest select requests
possible.

ANALOG OUTPUT; OBJ 40; VAR 0, 1, 2, 3, 4


POINT POINT VARIABLE DESCRIPTION
0 RELAY 1, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
1 RELAY 2, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
2 RELAY 3, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
3 RELAY 4, SETPOINT 1 VALUE SETPOINT IN THE 1ST COLUMN OF THE MATRIX
8 RELAY 1, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
9 RELAY 2, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
10 RELAY 3, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
11 RELAY 4, HYSTERESIS 1 VALUE HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
16 RELAY 1, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
17 RELAY 2, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
18 RELAY 3, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
19 RELAY 4, SETPOINT 2 VALUE SETPOINT IN THE 2ND COLUMN OF THE MATRIX
24 RELAY 1, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
25 RELAY 2, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
26 RELAY 3, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
27 RELAY 4, HYSTERESIS 2 VALUE HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
32 RELAY 1, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
33 RELAY 2, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
34 RELAY 3, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
35 RELAY 4, SETPOINT 3 VALUE SETPOINT IN THE 3RD COLUMN OF THE MATRIX
40 RELAY 1, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
41 RELAY 2, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
42 RELAY 3, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
43 RELAY 4, HYSTERESIS 3 VALUE HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
48 RELAY 1, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
49 RELAY 2, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
50 RELAY 3, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
51 RELAY 4, SETPOINT 4 VALUE SETPOINT IN THE 4TH COLUMN OF THE MATRIX
56 RELAY 1, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
57 RELAY 2, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
58 RELAY 3, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
59 RELAY 4, HYSTERESIS 4 VALUE HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
64 TL1 CRITICAL WINDING TEMP SETPOINT 1 1ST CRITICAL SPT TO CALCULATE TIME TO REACH
65 TL1 CRITICAL WINDING TEMP SETPOINT 2 2ND CRITICAL SPT TO CALCULATE TIME TO REACH
66 TL1 CRITICAL WINDING TEMP SETPOINT 3 3RD CRITICAL SPT TO CALCULATE TIME TO REACH

Octet Strings
The default string event buffer size is set to allow 10 events.

OCTET STRING; OBJ 110; VAR STRING LENGTH

19 www.qualitrolcorp.com
POINT POINT VARIABLE DESCRIPTION
0 SERIAL NUMBER UP TO 12 CHARACTERS
1 MANUFACTURE DATE OF THE UNIT UP TO 8 CHARACTERS
2 SUBSTATION NAME UP TO 16 CHARACTERS
3 EQUIPMENT NAME UP TO 16 CHARACTERS

Time and Date


TIME AND DATE; OBJ 50; VAR 0, 1
POINT POINT VARIABLE DESCRIPTION
0 TIME AND DATE

20 www.qualitrolcorp.com
Modbus Protocol
General
Qualitrol supports the Modbus RTU transmission mode in which the message is
placed by the transmitting device into a frame that has a known beginning and
ending point. This allows the 505ITM unit to begin at the start of the message, read
the address portion and determine which device is addressed and to know when the
message is completed. Partial messages can be detected and errors can be set as
a result.
When addressing the 505ITM Modbus register map the registers are one for one
(e.g. to read register 10 request address register 10).
To assist with the development of the Modbus communication for the user, there is a
web site, http://www.win-tech.com/html/demos.htm that offers evaluation software for
most applications.

Function Codes Supported


03 Read Holding Registers
06 Preset Single Register

Modbus Register Map


Binary Parameters
REG # VARIABLE R/W DESCRIPTION
10 RELAY 1 ENABLED READ 1 = ENABLED; 0 = DISABLED
11 RELAY 2 ENABLED READ 1 = ENABLED; 0 = DISABLED
12 RELAY 3 ENABLED READ 1 = ENABLED; 0 = DISABLED
13 RELAY 4 ENABLED READ 1 = ENABLED; 0 = DISABLED
18 RELAY 1 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
19 RELAY 2 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
20 RELAY 3 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
21 RELAY 4 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
26 SYSTEM STATUS RELAY READ 1 = ACTUATED; 0 = NOT ACTUATED
27 HEATER STATUS READ 1 = ENABLED; 0 = DISABLED
28 RELAY 1 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
29 RELAY 2 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED

21 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
30 RELAY 3 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
31 RELAY 4 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED

Binary Parameters
REG # VARIABLE R/W DESCRIPTION
50 RELAY 1 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
51 RELAY 2 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
52 RELAY 3 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
53 RELAY 4 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
58 INPUT MODULE MAX/MIN RESET RD/WR PULSE/RESET (1)
61 RELAY 1 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
62 RELAY 2 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
63 RELAY 3 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
64 RELAY 4 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
69 INPUT MODULE 1 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
70 INPUT MODULE 2 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
71 INPUT MODULE 3 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
72 INPUT MODULE 4 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
77 INPUT MODULE 1 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
78 INPUT MODULE 2 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
79 INPUT MODULE 3 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
80 INPUT MODULE 4 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
85 INPUT MODULE 1 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
86 INPUT MODULE 2 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
87 INPUT MODULE 3 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
88 INPUT MODULE 4 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED

Analog Parameters
Values in registers 100 thru 770 have different formatting depending on the accuracy required.
Those designated by (N) have no multiplier whereas those with 10X or 100X have been multiplied by
10 or 100 allowing for decimal place accuracy in an integer format (e.g. 12.34 would be read as 1234
for 100X).
REG # VARIABLE R/W DESCRIPTION
100 RELAY 1, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
101 RELAY 2, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
102 RELAY 3, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
103 RELAY 4, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
108 RELAY 1, HYSTERESIS 1 VALUE RD/WR (10X)
HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
109 RELAY 2, HYSTERESIS 1 VALUE RD/WR (10X)
HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
110 RELAY 3, HYSTERESIS 1 VALUE RD/WR (10X)
HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX
111 RELAY 4, HYSTERESIS 1 VALUE RD/WR (10X)

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
116 INPUT MODULE 1 PRESENT VALUE READ OR INPUT MODULE 1 PRESENT WINDING TEMP (10X)
117 INPUT MODULE 1 MINIMUM VALUE READ OR INPUT MODULE 1 MINIMUM WINDING TEMP (10X)

22 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
118 INPUT MODULE 1 MAXIMUM VALUE READ OR INPUT MODULE 1 MAXIMUM WINDING TEMP (10X)
119 0 READ OR INPUT MODULE 1 PRESENT CURRENT (10X)
120 0 READ OR INPUT MODULE 1 MAXIMUM CURRENT (10X)
121 INPUT MODULE 2 PRESENT VALUE READ OR INPUT MODULE 2 PRESENT WINDING TEMP (10X)
122 INPUT MODULE 2 MINIMUM VALUE READ OR INPUT MODULE 2 MINIMUM WINDING TEMP (10X)
123 INPUT MODULE 2 MAXIMUM VALUE READ OR INPUT MODULE 2 MAXIMUM WINDING TEMP (10X)
124 0 READ OR INPUT MODULE 2 PRESENT CURRENT (10X)
125 0 READ OR INPUT MODULE 2 MAXIMUM CURRENT (10X)
126 INPUT MODULE 3 PRESENT VALUE READ OR INPUT MODULE 3 PRESENT WINDING TEMP (10X)
127 INPUT MODULE 3 MINIMUM VALUE READ OR INPUT MODULE 3 MINIMUM WINDING TEMP (10X)
128 INPUT MODULE 3 MAXIMUM VALUE READ OR INPUT MODULE 3 MAXIMUM WINDING TEMP (10X)
129 0 READ OR INPUT MODULE 3 PRESENT CURRENT (10X)
130 0 READ OR INPUT MODULE 3 MAXIMUM CURRENT (10X)
131 INPUT MODULE 4 PRESENT VALUE READ OR INPUT MODULE 4 PRESENT WINDING TEMP (10X)
132 INPUT MODULE 4 MINIMUM VALUE READ OR INPUT MODULE 4 MINIMUM WINDING TEMP (10X)
133 INPUT MODULE 4 MAXIMUM VALUE READ OR INPUT MODULE 4 MAXIMUM WINDING TEMP (10X)
134 0 READ OR INPUT MODULE 4 PRESENT CURRENT (10X)
135 0 READ OR INPUT MODULE 4 MAXIMUM CURRENT (10X)
CALCULATED CONSUMED LIFE FOR LAST HOUR
169 TRANSLIFE 1 CONSUMED LIFE FOR LAST HOUR READ (100X)
170 TRANSLIFE 1 CONSUMED LIFE FOR LAST DAY READ CALCULATED CONSUMED LIFE FOR LAST DAY (100X)
171 TRANSLIFE 1 REMAINING TRANSFORMER LIFE READ (20 YEARS - CONSUMED LIFE) (100X)
1ST CRITICAL SPT TO CALCULATE TIME TO REACH
172 TL1 CRITICAL WINDING TEMP SETPOINT 1 RD/WR (10X)
2ND CRITICAL SPT TO CALCULATE TIME TO REACH
173 TL1 CRITICAL WINDING TEMP SETPOINT 2 RD/WR (10X)
3RD CRITICAL SPT TO CALCULATE TIME TO REACH
174 TL1 CRITICAL WINDING TEMP SETPOINT 3 RD/WR (10X)
CALCULATED TIME TO 1ST SPT FOR GIVEN
175 TL1 TIME TO CRITICAL SETPOINT 1 READ CONDITIONS (100X)
CALCULATED TIME TO 2ND SPT FOR GIVEN
176 TL1 TIME TO CRITICAL SETPOINT 2 READ CONDITIONS (100X)
CALCULATED TIME TO 3RD SPT FOR GIVEN
177 TL1 TIME TO CRITICAL SETPOINT 3 READ CONDITIONS (100X)
196 FIRMWARE REVISION FOR THIS 509ITM UNIT READ (100X)

240 RELAY 1 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
241 RELAY 2 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
242 RELAY 3 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
243 RELAY 4 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
248 RELAY 1 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
249 RELAY 2 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
250 RELAY 3 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
251 RELAY 4 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
256 RELAY 1 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
257 RELAY 2 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
258 RELAY 3 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
259 RELAY 4 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
264 RELAY 1 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
265 RELAY 2 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX

23 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
(10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
266 RELAY 3 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
267 RELAY 4 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
272 RELAY 1 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
273 RELAY 2 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
274 RELAY 3 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
275 RELAY 4 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
280 RELAY 1 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
281 RELAY 2 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
282 RELAY 3 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
283 RELAY 4 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)

TEMP WHERE CONSUMED LIFE EQUALS OPERATING


450 LIFE CONSUMPTION UNITY TEMPERATURE READ LIFE (N)
454 INSTALLED DIGITAL SENSORS READ BIT 16 = FIBER MOD 1 INSTALLED; BIT 15 = MOD 2 (N)
455 PRESENT YEAR READ TODAY'S YEAR IN THE 509ITM UNIT (N)
456 PRESENT MONTH READ TODAY'S MONTH IN THE 509ITM UNIT (N)
457 PRESENT DATE READ TODAY'S DAY IN THE 509ITM UNIT (1 - 31) (N)
458 PRESENT HOUR READ PRESENT HOUR (0 - 23) (N)
459 PRESENT MINUTE READ PRESENT MINUTE (0 - 59) (N)
460 PRESENT SECOND READ PRESENT SECOND (0 - 59) (N)
MODULE NUMBER IF THERE IS AN AMBIENT SENSOR
462 AMBIENT TEMPERATURE MODULE NUMBER READ (N)
463 TRANSFORMER LIFE SPAN READ ENTERED TRANSFORMER LIFE SPAN IN YEARS

MINUTES FAN EXERCISER WILL RUN WHEN ACTIVE


465 COOLING EXERCISER RUN TIME READ (N)
DAYS BETWEEN EXERCISER RUN TIME BEING ACTIVE
466 COOLING EXERCISER CYCLE TIME READ (N)
HOUR TO BEGIN FAN EXERCISER IN MILITARY TIME
467 COOLING EXERCISER START TIME READ (N)
468 STARTING MONTH FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 12) (N)
469 STARTING DAY FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 31) (N)
470 ENDING MONTH FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 12) (N)
471 ENDING DAY FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 31) (N)
472 AMBIENT TEMPERATURE FORECAST SETPOINT READ RELAY FEATURE (N)
# OF HOURS TO EXCEED SETPOINT FOR ACTIVE
473 AMBIENT TEMPERATURE THRESHOLD HOURS READ FEATURE (N)
ROLLING PERIOD IN HOURS TO MEASURE
474 AMBIENT TEMPERATURE MEASUREMENT PERIOD READ THRESHOLD TEMP (N)
MODULE NUMBER MEASURING AMBIENT MODULE NUMBER IF THERE IS AN AMBIENT SENSOR
475 TEMPERATURE READ (N)

492 RELAY 1, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 1


493 RELAY 2, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 2
494 RELAY 3, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 3
495 RELAY 4, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 4
500 RELAY 1, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 1
501 RELAY 2, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 2
502 RELAY 3, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 3

24 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
503 RELAY 4, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 4

560 CURRENT LOOP 1 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 1 (10X)
561 CURRENT LOOP 2 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 2 (10X)
MINIMUM SCALING VALUE FOR CURRENT LOOP 1
564 CURRENT LOOP 1 MINIMUM SCALING RANGE READ (10X)
MINIMUM SCALING VALUE FOR CURRENT LOOP 2
565 CURRENT LOOP 2 MINIMUM SCALING RANGE READ (10X)
MAXIMUM SCALING VALUE FOR CURRENT LOOP 1
568 CURRENT LOOP 1 MAXIMUM SCALING RANGE READ (10X)
MAXIMUM SCALING VALUE FOR CURRENT LOOP 2
569 CURRENT LOOP 2 MAXIMUM SCALING RANGE READ (10X)

AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY


600 RELAY 1 AMBIENT SETPOINT VALUE RD/WR 1 (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY
601 RELAY 2 AMBIENT SETPOINT VALUE RD/WR 2 (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY
602 RELAY 3 AMBIENT SETPOINT VALUE RD/WR 3 (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY
603 RELAY 4 AMBIENT SETPOINT VALUE RD/WR 4 (10X)
608 RELAY 1 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
609 RELAY 2 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
610 RELAY 3 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
611 RELAY 4 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)

632 RELAY 1 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
633 RELAY 2 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
634 RELAY 3 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
635 RELAY 4 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
640 RELAY 1 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
641 RELAY 2 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
642 RELAY 3 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
643 RELAY 4 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
648 RELAY 1 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
649 RELAY 2 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
650 RELAY 3 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
651 RELAY 4 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)

691 TRANSLIFE 1 PRESENT CONSUMED LIFE RATE READ INSTANTANEOUS LIFE RATE (100X)

Analog Parameters
For Registers 702 thru 770 the parameters are 32 bits long with the even registers holding the low
word and the high registers holding the high word (e.g. 702 low word; 703 high word).

REG # VARIABLE R/W DESCRIPTION


TRANSLIFE 1; TRANSFORMER LIFE TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 1
702 CONSUMPTION READ (N)
708 TOTAL TRANSFORMER OPERATING HOURS READ CUMULATIVE TRANSFORMER OPERATING HOURS (N)
LIFE 'A' VALUE FOR CALCULATING CONSUMED LIFE
742 TRANSLIFE VARIABLE 'A' VALUE READ (10X)
LIFE 'B' VALUE FOR CALCULATING CONSUMED LIFE
744 TRANSLIFE VARIABLE 'B' VALUE READ (10X)

25 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
TRANSLIFE 1; TEMPERATURE PROFILE, 1ST TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
748 RANGE READ (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 2ND
750 RANGE READ TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 3RD
752 RANGE READ TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 4TH
754 RANGE READ TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 5TH
756 RANGE READ TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 6TH
758 RANGE READ TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 7TH
760 RANGE READ TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 8TH
762 RANGE READ TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 9TH
764 RANGE READ TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 10TH
766 RANGE READ TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 11TH
768 RANGE READ TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 12TH TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
770 RANGE READ (N)

String Parameters
REG # VARIABLE R/W DESCRIPTION
850 SERIAL NUMBER; 12 ASCII CHARACTERS READ SERIAL NUMBER[1] / SERIAL NUMBER[0]
851 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[3] / SERIAL NUMBER [2]
852 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[5] / SERIAL NUMBER [4]
853 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[7] / SERIAL NUMBER [6]
854 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[9] / SERIAL NUMBER [8]
855 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[11] / SERIAL NUMBER [10]
856 MANUFACTURED DATE; 8 ASCII CHARACTERS READ MANUFACTURED DATE[1] / MANUFACTURED DATE [0]
857 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[3] / MANUFACTURED DATE [2]
858 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[5] / MANUFACTURED DATE [4]
859 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[7] / MANUFACTURED DATE [6]
860 SUBSTATION NAME; 16 ASCII CHARACTERS READ SUBSTATION NAME[1] / SUBSTATION NAME[0]
861 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[3] / SUBSTATION NAME[2]
862 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[5] / SUBSTATION NAME[4]
863 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[7] / SUBSTATION NAME[6]
864 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[9] / SUBSTATION NAME[8]
865 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[11] / SUBSTATION NAME[10]
866 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[13] / SUBSTATION NAME[12]
867 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[15] / SUBSTATION NAME[14]
868 EQUIPMENT NAME; 16 ASCII CHARACTERS READ EQUIPMENT NAME[1] / EQUIPMENT NAME[0]
869 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[3] / EQUIPMENT NAME[2]
870 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[5] / EQUIPMENT NAME[4]
871 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[7] / EQUIPMENT NAME[6]
872 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[9] / EQUIPMENT NAME[8]

26 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
873 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[11] / EQUIPMENT NAME[10]
874 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[13] / EQUIPMENT NAME[12]
875 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[15] / EQUIPMENT NAME[14]
876 MODEL NUMBER; 8 ASCII CHARACTERS READ MODEL NUMBER[1] / MODEL NUMBER[0]
877 MODEL NUMBER CONTINUED READ MODEL NUMBER[3] / MODEL NUMBER[2]
878 MODEL NUMBER CONTINUED READ MODEL NUMBER[5] / MODEL NUMBER[4]
879 MODEL NUMBER CONTINUED READ MODEL NUMBER[7] / MODEL NUMBER[6]

Registers 900 thru 903 have the hex codes of the hardware types for the input modules. The types
are explained in the description side of the registers
900 INPUT MODULE 1 HARDWARE TYPE READ 00 = NONE; 01 = 4-20mA; 02 = 0-1mA; 03 = 0-10VDC;
901 INPUT MODULE 2 HARDWARE TYPE READ 04 = 0-100mVDC; 05 = CT, CURRENT; 06 = CT, TEMP;
902 INPUT MODULE 3 HARDWARE TYPE READ 07 = POTENTIOMETER; 08 = 100 OHM RTD; 09 = 10 OHM
903 INPUT MODULE 4 HARDWARE TYPE READ RTD; 0A = DRY SWITCH DETECTION; 0B = POWERED
SWITCH DETECTION; 0C = 100 OHM RTD WINDING
TEMP; 0D = 10 OHM RTD WINDING TEMP; 0E = LTC
RESISTOR BRIDGE; 0F = 0-140VAC; 10 = 0-320VAC;
11 = LTC 0-1mA; 12 = LTC 4-20mA; 13 = FIBER OPTIC
TEMP

Registers 908 thru 967 are packed numbers. For example: reading register 908 gives a decimal
number of 3122. Converting this to hex gives 0C32. Split the bytes in half and it would read 12 hours
and 32 minutes.

REG # VARIABLE R/W DESCRIPTION


908 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
909 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
910 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
911 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
912 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
913 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
914 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
915 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
916 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
917 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
918 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
919 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
932 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
933 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
934 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
935 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
936 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
937 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
938 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
939 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE

27 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
940 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
941 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
942 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
943 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
956 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
957 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
958 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
959 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
960 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
961 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
962 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
963 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
964 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
965 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
966 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
967 DATE READ DAYS BYTE / YEARS BYTE

String Parameters
REG # VARIABLE R/W DESCRIPTION
1200 INPUT MODULE 1 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 1 NAME[1] / INPUT MODULE 1 NAME[0]
1201 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 NAME[3] / INPUT MODULE 1 NAME[2]
1202 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 NAME[5] / INPUT MODULE 1 NAME[4]
1203 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 ZERO / INPUT MODULE 1 NAME[6]
1204 INPUT MODULE 2 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 2 NAME[1] / INPUT MODULE 2 NAME[0]
1205 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 NAME[3] / INPUT MODULE 2 NAME[2]
1206 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 NAME[5] / INPUT MODULE 2 NAME[4]
1207 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 ZERO / INPUT MODULE 2 NAME[6]
1208 INPUT MODULE 3 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 3 NAME[1] / INPUT MODULE 3 NAME[0]
1209 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 NAME[3] / INPUT MODULE 3 NAME[2]
1210 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 NAME[5] / INPUT MODULE 3 NAME[4]
1211 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 ZERO / INPUT MODULE 3 NAME[6]
1212 INPUT MODULE 4 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 4 NAME[1] / INPUT MODULE 4 NAME[0]
1213 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 NAME[3] / INPUT MODULE 4 NAME[2]
1214 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 NAME[5] / INPUT MODULE 4 NAME[4]
1215 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 ZERO / INPUT MODULE 4 NAME[6]

Analog Parameters
Registers 1500 thru 1503; see appropriate scaling (e.g. N, 10X, 100X, 1000X)

REG # VARIABLE R/W DESCRIPTION

28 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1500 INPUT MODULE 1; CT CLAMP-ON RATING VALUE READ (N)
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1501 INPUT MODULE 2; CT CLAMP-ON RATING VALUE READ (N)
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1502 INPUT MODULE 3; CT CLAMP-ON RATING VALUE READ (N)
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1503 INPUT MODULE 4; CT CLAMP-ON RATING VALUE READ (N)

String Parameters
Registers 1508 thru 1515.

REG # VARIABLE R/W DESCRIPTION


INPUT MODULE 1 MEASUREMENT UNITS; 3 ASCII
1508 CHAR READ INPUT MODULE 1; UNITS[1] / UNITS[0]
INPUT MODULE 1 MEASUREMENT UNITS;
1509 CONTINUED READ INPUT MODULE 1; ZERO / UNITS[2]
INPUT MODULE 2 MEASUREMENT UNITS; 3 ASCII
1510 CHAR READ INPUT MODULE 2; UNITS[1] / UNITS[0]
INPUT MODULE 2 MEASUREMENT UNITS;
1511 CONTINUED READ INPUT MODULE 2; ZERO / UNITS[2]
INPUT MODULE 3 MEASUREMENT UNITS; 3 ASCII
1512 CHAR READ INPUT MODULE 3; UNITS[1] / UNITS[0]
INPUT MODULE 3 MEASUREMENT UNITS;
1513 CONTINUED READ INPUT MODULE 3; ZERO / UNITS[2]
INPUT MODULE 4 MEASUREMENT UNITS; 3 ASCII
1514 CHAR READ INPUT MODULE 4; UNITS[1] / UNITS[0]
INPUT MODULE 4 MEASUREMENT UNITS;
1515 CONTINUED READ INPUT MODULE 4; ZERO / UNITS[2]

Analog Parameters
Registers 1524 thru 2299; see appropriate scaling (e.g. N, 10X, 100X, 1000X)
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 1 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1524 POINTER READ MEASUREMENT (N)
INPUT MODULE 2 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1525 POINTER READ MEASUREMENT (N)
INPUT MODULE 3 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1526 POINTER READ MEASUREMENT (N)
INPUT MODULE 4 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1527 POINTER READ MEASUREMENT (N)
1532 INPUT MODULE 1; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1533 INPUT MODULE 1; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1534 INPUT MODULE 1; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1535 INPUT MODULE 2; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1536 INPUT MODULE 2; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1537 INPUT MODULE 2; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1538 INPUT MODULE 3; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1539 INPUT MODULE 3; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1540 INPUT MODULE 3; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1541 INPUT MODULE 4; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1542 INPUT MODULE 4; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1543 INPUT MODULE 4; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)

1600 INPUT MODULE 1; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)

29 www.qualitrolcorp.com
1602 INPUT MODULE 2; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1604 INPUT MODULE 3; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1606 INPUT MODULE 4; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1616 INPUT MODULE 1; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1618 INPUT MODULE 2; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1620 INPUT MODULE 3; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1622 INPUT MODULE 4; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1632 INPUT MODULE 1; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1634 INPUT MODULE 2; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1636 INPUT MODULE 3; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1638 INPUT MODULE 4; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1648 INPUT MODULE 1; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1650 INPUT MODULE 2; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1652 INPUT MODULE 3; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1654 INPUT MODULE 4; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)

For registers 1664 thru 1703 the parameters are 32 bits long with the even registers holding the low
word and the odd registers holding the high word (e.g. 1664 low word; 1665 high word). These
registers are for those applications where the input module values could be greater than 3200
(32,000 with multiplier).
REG # VARIABLE R/W DESCRIPTION
ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
1664 INPUT MODULE 1 PRESENT VALUE READ OR INPUT MODULE 1 PRESENT WINDING TEMP (10X)
1666 INPUT MODULE 1 MINIMUM VALUE READ OR INPUT MODULE 1 MINIMUM WINDING TEMP (10X)
1668 INPUT MODULE 1 MAXIMUM VALUE READ OR INPUT MODULE 1 MAXIMUM WINDING TEMP (10X)
1670 0 READ OR INPUT MODULE 1 PRESENT CURRENT (10X)
1672 0 READ OR INPUT MODULE 1 MAXIMUM CURRENT (10X)
1674 INPUT MODULE 2 PRESENT VALUE READ OR INPUT MODULE 2 PRESENT WINDING TEMP (10X)
1676 INPUT MODULE 2 MINIMUM VALUE READ OR INPUT MODULE 2 MINIMUM WINDING TEMP (10X)
1678 INPUT MODULE 2 MAXIMUM VALUE READ OR INPUT MODULE 2 MAXIMUM WINDING TEMP (10X)
1680 0 READ OR INPUT MODULE 2 PRESENT CURRENT (10X)
1682 0 READ OR INPUT MODULE 2 MAXIMUM CURRENT (10X)
1684 INPUT MODULE 3 PRESENT VALUE READ OR INPUT MODULE 3 PRESENT WINDING TEMP (10X)
1686 INPUT MODULE 3 MINIMUM VALUE READ OR INPUT MODULE 3 MINIMUM WINDING TEMP (10X)
1688 INPUT MODULE 3 MAXIMUM VALUE READ OR INPUT MODULE 3 MAXIMUM WINDING TEMP (10X)
1690 0 READ OR INPUT MODULE 3 PRESENT CURRENT (10X)
1692 0 READ OR INPUT MODULE 3 MAXIMUM CURRENT (10X)
1694 INPUT MODULE 4 PRESENT VALUE READ OR INPUT MODULE 4 PRESENT WINDING TEMP (10X)
1696 INPUT MODULE 4 MINIMUM VALUE READ OR INPUT MODULE 4 MINIMUM WINDING TEMP (10X)
1698 INPUT MODULE 4 MAXIMUM VALUE READ OR INPUT MODULE 4 MAXIMUM WINDING TEMP (10X)
1700 0 READ OR INPUT MODULE 4 PRESENT CURRENT (10X)
1702 0 READ OR INPUT MODULE 4 MAXIMUM CURRENT (10X)

REG # VARIABLE R/W DESCRIPTION


SIMPLE CALCULATION WINDING RISE TEMPERATURE
2100 INPUT MODULE 1; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2101 INPUT MODULE 2; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2102 INPUT MODULE 3; WINDING RISE TEMPERATURE READ (100X)

30 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2103 INPUT MODULE 4; WINDING RISE TEMPERATURE READ (100X)
2108 INPUT MODULE 1; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2109 INPUT MODULE 2; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2110 INPUT MODULE 3; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2111 INPUT MODULE 4; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2116 INPUT MODULE 1; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2117 INPUT MODULE 2; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2118 INPUT MODULE 3; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2119 INPUT MODULE 4; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2124 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2125 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2126 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2127 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2128 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2129 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2130 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2131 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2132 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2133 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2134 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2135 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2136 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2137 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2138 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2139 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2156 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2157 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2158 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2159 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2160 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2161 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2162 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2163 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2164 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2165 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2166 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)

31 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2167 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2168 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2169 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2170 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2171 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2188 INPUT MODULE 1; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2189 INPUT MODULE 1; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2190 INPUT MODULE 1; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2191 INPUT MODULE 1; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2192 INPUT MODULE 2; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2193 INPUT MODULE 2; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2194 INPUT MODULE 2; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2195 INPUT MODULE 2; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2196 INPUT MODULE 3; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2197 INPUT MODULE 3; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2198 INPUT MODULE 3; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2199 INPUT MODULE 3; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2200 INPUT MODULE 4; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2201 INPUT MODULE 4; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2202 INPUT MODULE 4; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2203 INPUT MODULE 4; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2220 INPUT MODULE 1; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2221 INPUT MODULE 1; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2222 INPUT MODULE 1; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2223 INPUT MODULE 1; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2224 INPUT MODULE 2; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2225 INPUT MODULE 2; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2226 INPUT MODULE 2; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2227 INPUT MODULE 2; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2228 INPUT MODULE 3; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2229 INPUT MODULE 3; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2230 INPUT MODULE 3; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2231 INPUT MODULE 3; WINDING RISE TEMP; STAGE 4 READ (100X)
2232 INPUT MODULE 4; WINDING RISE TEMP; STAGE 1 READ COOLING STAGE 1; ADVANCED WINDING RISE TEMP

32 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
(100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2233 INPUT MODULE 4; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2234 INPUT MODULE 4; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2235 INPUT MODULE 4; WINDING RISE TEMP; STAGE 4 READ (100X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2252 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2253 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2254 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2255 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2256 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2257 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2258 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2259 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2260 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2261 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2262 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2263 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2264 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2265 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2266 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2267 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING TIME CONSTANT;
2284 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2285 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2286 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2287 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2288 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2289 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2290 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2291 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2292 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2293 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2294 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2295 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2296 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2297 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)

33 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 4; WINDING TIME CONSTANT;
2298 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2299 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)

34 www.qualitrolcorp.com
ASCII Protocol
General
Qualitrol has developed it’s own ASCII protocol for those applications where the user would prefer to
write their own interface software. The ASCII protocol has a simpler structure than Modbus or DNP
and the flexibility to transmit integers or floating point variables.

ASCII Framing
In the ASCII mode all messages start with ‘the less than’ (<) character (ASCII 3C hex) and end with
‘the greater than’ (>) character (ASCII 3E hex). The allowable characters transmitted for all the other
fields are hexadecimal 0 – 9, A – F and the decimal ‘.’. These would be the ASCII characters of 30-
39, 41-46 and 2E. Networked devices monitor the network bus continuously for the ‘less than’
character. When one is received, each device decodes the address field to find out if it is the
addressed device.

Packet Structures
Send message to read a register (from the computer to the 505ITM):
1 byte Start message character ‘<’
2 bytes Length of message including start and stop message characters and the two Error
Checking bytes
2 bytes Address (from 0 to 255 / 0 to FF) of the 505ITM unit to be read
1 byte Read (0) / Write (1); this is a read so set to (0)
3 bytes Address of register to read or write to; See register map for valid register addresses
2 bytes Error Checking bytes of the message; see the Error Checking section for calculation
description
1 byte Stop message character ‘>’
i.e. To read Register 500 from the 505ITM unit with an address of 03, the message sent would
be: ‘<0C0301F4D5>’

Reply message to read a register (from the 505ITM back to the computer):
1 byte Start message character ‘<’
2 bytes Length of message including start and stop message characters and the two Error
Checking bytes
2 bytes Address (from 0 to 255 / 0 to FF) of the 505ITM unit that was read

35 www.qualitrolcorp.com
1 byte If the message was okay returns a (1), returning anything else means an error
occurred
3 bytes Address of register to read or write to; See register map for valid register addresses
N bytes Returned value; integer, hex number or floating point number (floating point numbers
may include a decimal point)
2 bytes Error Checking bytes of the message; see the Error Checking section for calculation
description
1 byte Stop message character ‘>’
i.e. The return message from the 505ITM, address 03 for reading register 500 and returning a
value of 75.0 would be: ‘<100311F475.01C>’

Send message to write to a register (from the computer to the 505ITM):


1 byte Start message character ‘<’
2 bytes Length of message including start and stop message characters and the two Error
Checking bytes
2 bytes Address (from 0 to 255 / 0 to FF) of the 505ITM unit that will be written to
1 byte Read (0) / Write (1); this is a write message so set to (1)
3 bytes Address of register to read or write to; See register map for valid register addresses
N bytes Sending value; integer or floating point number (floating point numbers may include a
decimal point)
2 bytes Error Checking bytes of the message; see the Error Checking section for calculation
description
1 byte Stop message character ‘>’
i.e. To write a value of 75.0 to Register 500 to the 505ITM unit with an address of 03, the
message sent would be: ‘<100311F475.01C>’
Reply message to write to a register (from the 505ITM back to the computer):
1 byte Start message character ‘<’
2 bytes Length of message including start and stop message characters and the two Error
Checking bytes
2 bytes Address (from 0 to 255 / 0 to FF) of the 505ITM unit that was read
1 byte If the message was correct will return a (1), returning anything else means an error
occurred
3 bytes Address of register to read or write to; See register map for valid register addresses
2 bytes Error Checking bytes of the message; see the Error Checking section for calculation
description
1 byte Stop message character ‘>’
i.e. The return message from the 505ITM, address 03 for writing register 500 with a value of 75.0
would be: ‘<0C0311F4D4>’

Error Checking Calculation


The Error Checking for the ASCII string being sent or received is a running addition of the ASCII
characters, truncated to two bytes and then taking the twos compliment of the result. This includes all

36 www.qualitrolcorp.com
the characters of the string (start and stop characters and the message) except for the Error
Checking bytes, which we are in the process of calculating.
For example: We want to read register 100, from a 505ITM with an address of 7. We have a starting
character ‘<’ which is an ASCII 3C. The length of the message is next with one byte for start, two
bytes for length, two bytes for the address, one byte for read, three bytes for the register, two bytes
for the error checking and one byte for the stop character, which totals twelve or 0C in hex. This
converts to two ASCII characters of 30 and 43. The address of the 505ITM comes next and it is a 07,
which converts to 30 and 37. The read byte (0) translates to a 30 ASCII. Next is the register
address, which is 100 or 064 in hex. This converts to 30, 36 and 34 in ASCII. We skip the error
checking bytes so that leaves just the stop message character ‘>’ which is 3E ASCII.
3C Start byte
30 Length of message (two characters)
43
30 Address of the 505ITM unit (two characters)
37
30 The read byte
30 The register address (three characters)
36
34
(In a message this is where the two Error Checking bytes will go)
3E Stop byte
__+_________
21E
This is truncated to just 1E. We then take the twos complement and get an E2. This converts to an
ASCII 45, 32. So the completed message is:
3C, 30, 43, 30, 37, 30, 30, 36, 34, 45, 32, 3E
This is displayed in the sent window of the Qualitrol ASCII Test Program as:
<0C070064E2>

ASCII Register Map


Binary Parameters
REG # VARIABLE R/W DESCRIPTION
10 RELAY 1 ENABLED READ 1 = ENABLED; 0 = DISABLED
11 RELAY 2 ENABLED READ 1 = ENABLED; 0 = DISABLED
12 RELAY 3 ENABLED READ 1 = ENABLED; 0 = DISABLED
13 RELAY 4 ENABLED READ 1 = ENABLED; 0 = DISABLED
18 RELAY 1 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
19 RELAY 2 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
20 RELAY 3 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
21 RELAY 4 ACTUATED READ 1 = ACTUATED; 0 = NOT ACTUATED
26 SYSTEM STATUS RELAY READ 1 = ACTUATED; 0 = NOT ACTUATED

37 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
27 HEATER STATUS READ 1 = ENABLED; 0 = DISABLED
28 RELAY 1 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
29 RELAY 2 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
30 RELAY 3 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED
31 RELAY 4 LATCHING FEATURE READ 1 = ENABLED; 0 = DISABLED

Binary Parameters
REG # VARIABLE R/W DESCRIPTION
50 RELAY 1 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
51 RELAY 2 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
52 RELAY 3 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
53 RELAY 4 ENABLED RD/WR 1 = ENABLED; 0 = DISABLED
58 INPUT MODULE MAX/MIN RESET RD/WR PULSE/RESET (1)
61 RELAY 1 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
62 RELAY 2 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
63 RELAY 3 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
64 RELAY 4 AUTO/MANUAL RD/WR 1 = MANUAL OPERATION; 0 = AUTOMATIC
69 INPUT MODULE 1 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
70 INPUT MODULE 2 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
71 INPUT MODULE 3 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
72 INPUT MODULE 4 ENABLED/DISABLED RD/WR 1 = ENABLED; 0 = DISABLED
77 INPUT MODULE 1 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
78 INPUT MODULE 2 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
79 INPUT MODULE 3 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
80 INPUT MODULE 4 READ ERROR READ 1 = READ ERROR; 0 = VALID READ
85 INPUT MODULE 1 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
86 INPUT MODULE 2 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
87 INPUT MODULE 3 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED
88 INPUT MODULE 4 SCALING ENABLED READ 1 = SCALING ENABLED; 0 = DISABLED

Analog Parameters
Values in Registers 100 thru 770 have different formatting depending on the accuracy required.
Those designated by (N) have no multiplier whereas those with 10X or 100X have been multiplied by
10 or 100 allowing for decimal place accuracy in an integer format (e.g. 12.34 would be read as 1234
for 100X).
REG # VARIABLE R/W DESCRIPTION
100 RELAY 1, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
101 RELAY 2, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
102 RELAY 3, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
103 RELAY 4, SETPOINT 1 VALUE RD/WR SETPOINT IN THE 1ST COLUMN OF THE MATRIX (10X)
108 RELAY 1, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
109 RELAY 2, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
110 RELAY 3, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)
111 RELAY 4, HYSTERESIS 1 VALUE RD/WR HYSTERESIS IN THE 1ST COLUMN OF THE MATRIX (10X)

ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE

38 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
116 INPUT MODULE 1 PRESENT VALUE READ OR INPUT MODULE 1 PRESENT WINDING TEMP (10X)
117 INPUT MODULE 1 MINIMUM VALUE READ OR INPUT MODULE 1 MINIMUM WINDING TEMP (10X)
118 INPUT MODULE 1 MAXIMUM VALUE READ OR INPUT MODULE 1 MAXIMUM WINDING TEMP (10X)
119 0 READ OR INPUT MODULE 1 PRESENT CURRENT (10X)
120 0 READ OR INPUT MODULE 1 MAXIMUM CURRENT (10X)
121 INPUT MODULE 2 PRESENT VALUE READ OR INPUT MODULE 2 PRESENT WINDING TEMP (10X)
122 INPUT MODULE 2 MINIMUM VALUE READ OR INPUT MODULE 2 MINIMUM WINDING TEMP (10X)
123 INPUT MODULE 2 MAXIMUM VALUE READ OR INPUT MODULE 2 MAXIMUM WINDING TEMP (10X)
124 0 READ OR INPUT MODULE 2 PRESENT CURRENT (10X)
125 0 READ OR INPUT MODULE 2 MAXIMUM CURRENT (10X)
126 INPUT MODULE 3 PRESENT VALUE READ OR INPUT MODULE 3 PRESENT WINDING TEMP (10X)
127 INPUT MODULE 3 MINIMUM VALUE READ OR INPUT MODULE 3 MINIMUM WINDING TEMP (10X)
128 INPUT MODULE 3 MAXIMUM VALUE READ OR INPUT MODULE 3 MAXIMUM WINDING TEMP (10X)
129 0 READ OR INPUT MODULE 3 PRESENT CURRENT (10X)
130 0 READ OR INPUT MODULE 3 MAXIMUM CURRENT (10X)
131 INPUT MODULE 4 PRESENT VALUE READ OR INPUT MODULE 4 PRESENT WINDING TEMP (10X)
132 INPUT MODULE 4 MINIMUM VALUE READ OR INPUT MODULE 4 MINIMUM WINDING TEMP (10X)
133 INPUT MODULE 4 MAXIMUM VALUE READ OR INPUT MODULE 4 MAXIMUM WINDING TEMP (10X)
134 0 READ OR INPUT MODULE 4 PRESENT CURRENT (10X)
135 0 READ OR INPUT MODULE 4 MAXIMUM CURRENT (10X)
169 TRANSLIFE 1 CONSUMED LIFE FOR LAST HOUR READ CALCULATED CONSUMED LIFE FOR LAST HOUR (100X)
170 TRANSLIFE 1 CONSUMED LIFE FOR LAST DAY READ CALCULATED CONSUMED LIFE FOR LAST DAY (100X)
171 TRANSLIFE 1 REMAINING TRANSFORMER LIFE READ (20 YEARS - CONSUMED LIFE) (100X)
1ST CRITICAL SPT TO CALCULATE TIME TO REACH
172 TL1 CRITICAL WINDING TEMP SETPOINT 1 RD/WR (10X)
2ND CRITICAL SPT TO CALCULATE TIME TO REACH
173 TL1 CRITICAL WINDING TEMP SETPOINT 2 RD/WR (10X)
3RD CRITICAL SPT TO CALCULATE TIME TO REACH
174 TL1 CRITICAL WINDING TEMP SETPOINT 3 RD/WR (10X)
CALCULATED TIME TO 1ST SPT FOR GIVEN
175 TL1 TIME TO CRITICAL SETPOINT 1 READ CONDITIONS (100X)
CALCULATED TIME TO 2ND SPT FOR GIVEN
176 TL1 TIME TO CRITICAL SETPOINT 2 READ CONDITIONS (100X)
CALCULATED TIME TO 3RD SPT FOR GIVEN
177 TL1 TIME TO CRITICAL SETPOINT 3 READ CONDITIONS (100X)
196 FIRMWARE REVISION FOR THIS 509ITM UNIT READ (100X)

240 RELAY 1 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
241 RELAY 2 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
242 RELAY 3 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
243 RELAY 4 SETPOINT, 2nd COLUMN OF MATRIX RD/WR SETPOINT IN THE 2ND COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
248 RELAY 1 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
249 RELAY 2 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
250 RELAY 3 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 2ND COLUMN OF THE MATRIX
251 RELAY 4 HYSTERESIS, 2nd COLUMN OF MATRIX RD/WR (10X)
256 RELAY 1 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
257 RELAY 2 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
258 RELAY 3 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)
259 RELAY 4 SETPOINT, 3rd COLUMN OF MATRIX RD/WR SETPOINT IN THE 3RD COLUMN OF THE MATRIX (10X)

39 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
264 RELAY 1 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
265 RELAY 2 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
266 RELAY 3 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 3RD COLUMN OF THE MATRIX
267 RELAY 4 HYSTERESIS, 3rd COLUMN OF MATRIX RD/WR (10X)
272 RELAY 1 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
273 RELAY 2 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
274 RELAY 3 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
275 RELAY 4 SETPOINT, 4th COLUMN OF MATRIX RD/WR SETPOINT IN THE 4TH COLUMN OF THE MATRIX (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
280 RELAY 1 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
281 RELAY 2 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
282 RELAY 3 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)
HYSTERESIS IN THE 4TH COLUMN OF THE MATRIX
283 RELAY 4 HYSTERESIS, 4th COLUMN OF MATRIX RD/WR (10X)

TEMP WHERE CONSUMED LIFE EQUALS OPERATING


450 LIFE CONSUMPTION UNITY TEMPERATURE READ LIFE (N)
454 INSTALLED DIGITAL SENSORS READ BIT 16 = FIBER MOD 1 INSTALLED; BIT 15 = MOD 2 (N)
455 PRESENT YEAR READ TODAY'S YEAR IN THE 509ITM UNIT (N)
456 PRESENT MONTH READ TODAY'S MONTH IN THE 509ITM UNIT (N)
457 PRESENT DATE READ TODAY'S DAY IN THE 509ITM UNIT (1 - 31) (N)
458 PRESENT HOUR READ PRESENT HOUR (0 - 23) (N)
459 PRESENT MINUTE READ PRESENT MINUTE (0 - 59) (N)
460 PRESENT SECOND READ PRESENT SECOND (0 - 59) (N)
MODULE NUMBER IF THERE IS AN AMBIENT SENSOR
462 AMBIENT TEMPERATURE MODULE NUMBER READ (N)
463 TRANSFORMER LIFE SPAN READ ENTERED TRANSFORMER LIFE SPAN IN YEARS

465 COOLING EXERCISER RUN TIME READ MINUTES FAN EXERCISER WILL RUN WHEN ACTIVE (N)
DAYS BETWEEN EXERCISER RUN TIME BEING ACTIVE
466 COOLING EXERCISER CYCLE TIME READ (N)
467 COOLING EXERCISER START TIME READ HOUR TO BEGIN FAN EXERCISER IN MILITARY TIME (N)
468 STARTING MONTH FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 12) (N)
469 STARTING DAY FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 31) (N)
470 ENDING MONTH FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 12) (N)
471 ENDING DAY FOR SEASONAL SETPOINT READ RELAY FEATURE (1 - 31) (N)
472 AMBIENT TEMPERATURE FORECAST SETPOINT READ RELAY FEATURE (N)
# OF HOURS TO EXCEED SETPOINT FOR ACTIVE
473 AMBIENT TEMPERATURE THRESHOLD HOURS READ FEATURE (N)
ROLLING PERIOD IN HOURS TO MEASURE THRESHOLD
474 AMBIENT TEMPERATURE MEASUREMENT PERIOD READ TEMP (N)
MODULE NUMBER MEASURING AMBIENT MODULE NUMBER IF THERE IS AN AMBIENT SENSOR
475 TEMPERATURE READ (N)

492 RELAY 1, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 1


493 RELAY 2, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 2
494 RELAY 3, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 3
495 RELAY 4, ACTUATION COUNTS READ ACTUATION COUNTER FOR RELAY 4
500 RELAY 1, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 1
501 RELAY 2, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 2

40 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
502 RELAY 3, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 3
503 RELAY 4, RATE OF CHANGE TIME PERIOD READ RATE OF CHANGE TIME PERIOD FOR RELAY 4

560 CURRENT LOOP 1 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 1 (10X)
561 CURRENT LOOP 2 CONTROL SIGNAL READ VALUE OF SIGNAL CONTROLLING LOOP 2 (10X)
564 CURRENT LOOP 1 MINIMUM SCALING RANGE READ MINIMUM SCALING VALUE FOR CURRENT LOOP 1 (10X)
565 CURRENT LOOP 2 MINIMUM SCALING RANGE READ MINIMUM SCALING VALUE FOR CURRENT LOOP 2 (10X)
568 CURRENT LOOP 1 MAXIMUM SCALING RANGE READ MAXIMUM SCALING VALUE FOR CURRENT LOOP 1 (10X)
569 CURRENT LOOP 2 MAXIMUM SCALING RANGE READ MAXIMUM SCALING VALUE FOR CURRENT LOOP 2 (10X)

AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 1


600 RELAY 1 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 2
601 RELAY 2 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 3
602 RELAY 3 AMBIENT SETPOINT VALUE RD/WR (10X)
AMBIENT LOOKBACK FEATURE SETPOINT FOR RELAY 4
603 RELAY 4 AMBIENT SETPOINT VALUE RD/WR (10X)
608 RELAY 1 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
609 RELAY 2 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
610 RELAY 3 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)
611 RELAY 4 SEASONAL SETPOINT VALUE RD/WR SEASONAL SETPOINT VALUE (10X)

632 RELAY 1 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
633 RELAY 2 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
634 RELAY 3 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
635 RELAY 4 ACTUATION DELAY - HOURS VALUE RD/WR ACTUATION DELAY - HOURS (N)
640 RELAY 1 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
641 RELAY 2 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
642 RELAY 3 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
643 RELAY 4 ACTUATION DELAY - MINUTES VALUE RD/WR ACTUATION DELAY - MINUTES (N)
648 RELAY 1 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
649 RELAY 2 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
650 RELAY 3 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)
651 RELAY 4 ACTUATION DELAY - SECONDS VALUE RD/WR ACTUATION DELAY - SECONDS (N)

691 TRANSLIFE 1 PRESENT CONSUMED LIFE RATE READ INSTANTANEOUS LIFE RATE (100X)

Analog Parameters
For Registers 702 thru 772 the parameters are 32 bits long with the even registers holding the low
word and the high registers holding the high word (e.g. 702 low word; 703 high word).

REG # VARIABLE R/W DESCRIPTION


TRANSLIFE 1; TRANSFORMER LIFE TOTAL LIFE CONSUMPTION CALCULATED; TRANSLIFE 1
702 CONSUMPTION READ (N)
708 TOTAL TRANSFORMER OPERATING HOURS READ CUMULATIVE TRANSFORMER OPERATING HOURS (N)
LIFE 'A' VALUE FOR CALCULATING CONSUMED LIFE
742 TRANSLIFE VARIABLE 'A' VALUE READ (10X)
LIFE 'B' VALUE FOR CALCULATING CONSUMED LIFE
744 TRANSLIFE VARIABLE 'B' VALUE READ (10X)

41 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
TRANSLIFE 1; TEMPERATURE PROFILE, 1ST TOTAL WINDING TEMP TIME IN LOWEST TEMP RANGE
748 RANGE READ (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 2ND
750 RANGE READ TOTAL WINDING TEMP TIME IN 2ND TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 3RD
752 RANGE READ TOTAL WINDING TEMP TIME IN 3RD TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 4TH
754 RANGE READ TOTAL WINDING TEMP TIME IN 4TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 5TH
756 RANGE READ TOTAL WINDING TEMP TIME IN 5TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 6TH
758 RANGE READ TOTAL WINDING TEMP TIME IN 6TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 7TH
760 RANGE READ TOTAL WINDING TEMP TIME IN 7TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 8TH
762 RANGE READ TOTAL WINDING TEMP TIME IN 8TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 9TH
764 RANGE READ TOTAL WINDING TEMP TIME IN 9TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 10TH
766 RANGE READ TOTAL WINDING TEMP TIME IN 10TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 11TH
768 RANGE READ TOTAL WINDING TEMP TIME IN 11TH TEMP RANGE (N)
TRANSLIFE 1; TEMPERATURE PROFILE, 12TH TOTAL WINDING TEMP TIME IN HIGHEST TEMP RANGE
770 RANGE READ (N)

String Parameters
REG # VARIABLE R/W DESCRIPTION
850 SERIAL NUMBER; 12 ASCII CHARACTERS READ SERIAL NUMBER[1] / SERIAL NUMBER[0]
851 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[3] / SERIAL NUMBER [2]
852 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[5] / SERIAL NUMBER [4]
853 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[7] / SERIAL NUMBER [6]
854 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[9] / SERIAL NUMBER [8]
855 SERIAL NUMBER CONTINUED READ SERIAL NUMBER[11] / SERIAL NUMBER [10]
856 MANUFACTURED DATE; 8 ASCII CHARACTERS READ MANUFACTURED DATE[1] / MANUFACTURED DATE [0]
857 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[3] / MANUFACTURED DATE [2]
858 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[5] / MANUFACTURED DATE [4]
859 MANUFACTURED DATE CONTINUED READ MANUFACTURED DATE[7] / MANUFACTURED DATE [6]
860 SUBSTATION NAME; 16 ASCII CHARACTERS READ SUBSTATION NAME[1] / SUBSTATION NAME[0]
861 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[3] / SUBSTATION NAME[2]
862 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[5] / SUBSTATION NAME[4]
863 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[7] / SUBSTATION NAME[6]
864 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[9] / SUBSTATION NAME[8]
865 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[11] / SUBSTATION NAME[10]
866 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[13] / SUBSTATION NAME[12]
867 SUBSTATION NAME CONTINUED READ SUBSTATION NAME[15] / SUBSTATION NAME[14]
868 EQUIPMENT NAME; 16 ASCII CHARACTERS READ EQUIPMENT NAME[1] / EQUIPMENT NAME[0]
869 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[3] / EQUIPMENT NAME[2]
870 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[5] / EQUIPMENT NAME[4]
871 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[7] / EQUIPMENT NAME[6]
872 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[9] / EQUIPMENT NAME[8]

42 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
873 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[11] / EQUIPMENT NAME[10]
874 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[13] / EQUIPMENT NAME[12]
875 EQUIPMENT NAME CONTINUED READ EQUIPMENT NAME[15] / EQUIPMENT NAME[14]
876 MODEL NUMBER; 8 ASCII CHARACTERS READ MODEL NUMBER[1] / MODEL NUMBER[0]
877 MODEL NUMBER CONTINUED READ MODEL NUMBER[3] / MODEL NUMBER[2]
878 MODEL NUMBER CONTINUED READ MODEL NUMBER[5] / MODEL NUMBER[4]
879 MODEL NUMBER CONTINUED READ MODEL NUMBER[7] / MODEL NUMBER[6]

Registers 900 thru 903 have the hex codes of the hardware types for the input modules. The types
are explained in the description side of the registers
900 INPUT MODULE 1 HARDWARE TYPE READ 00 = NONE; 01 = 4-20mA; 02 = 0-1mA; 03 = 0-10VDC;
901 INPUT MODULE 2 HARDWARE TYPE READ 04 = 0-100mVDC; 05 = CT, CURRENT; 06 = CT, TEMP;
902 INPUT MODULE 3 HARDWARE TYPE READ 07 = POTENTIOMETER; 08 = 100 OHM RTD; 09 = 10 OHM
903 INPUT MODULE 4 HARDWARE TYPE READ RTD; 0A = DRY SWITCH DETECTION; 0B = POWERED
SWITCH DETECTION; 0C = 100 OHM RTD WINDING
TEMP; 0D = 10 OHM RTD WINDING TEMP; 0E = LTC
RESISTOR BRIDGE; 0F = 0-140VAC; 10 = 0-320VAC;
11 = LTC 0-1mA; 12 = LTC 4-20mA; 13 = FIBER OPTIC
TEMP

Registers 908 thru 967 are packed numbers. For example: reading register 908 gives a decimal
number of 3122. Converting this to hex gives 0C32. Split the bytes in half and it would read 12
hours and 32 minutes.

REG # VARIABLE R/W DESCRIPTION


908 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
909 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
910 INPUT MODULE 1 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
911 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
912 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
913 INPUT MODULE 2 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
914 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
915 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
916 INPUT MODULE 3 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
917 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
918 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
919 INPUT MODULE 4 MAXIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
932 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
933 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
934 INPUT MODULE 1 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
935 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
936 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
937 INPUT MODULE 2 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
938 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
939 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE

43 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
940 INPUT MODULE 3 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
941 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ HOURS BYTE / MINUTES BYTE
942 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ SECONDS BYTE / MONTHS BYTE
943 INPUT MODULE 4 MINIMUM VALUE TIME & DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
956 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
957 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 1 MAXIMUM CURRENT TIME &
958 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
959 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
960 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 2 MAXIMUM CURRENT TIME &
961 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
962 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
963 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 3 MAXIMUM CURRENT TIME &
964 DATE READ DAYS BYTE / YEARS BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
965 DATE READ HOURS BYTE / MINUTES BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
966 DATE READ SECONDS BYTE / MONTHS BYTE
INPUT MODULE 4 MAXIMUM CURRENT TIME &
967 DATE READ DAYS BYTE / YEARS BYTE

String Parameters
REG # VARIABLE R/W DESCRIPTION
1200 INPUT MODULE 1 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 1 NAME[1] / INPUT MODULE 1 NAME[0]
1201 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 NAME[3] / INPUT MODULE 1 NAME[2]
1202 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 NAME[5] / INPUT MODULE 1 NAME[4]
1203 INPUT MODULE 1 NAME; CONTINUED READ INPUT MODULE 1 ZERO / INPUT MODULE 1 NAME[6]
1204 INPUT MODULE 2 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 2 NAME[1] / INPUT MODULE 2 NAME[0]
1205 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 NAME[3] / INPUT MODULE 2 NAME[2]
1206 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 NAME[5] / INPUT MODULE 2 NAME[4]
1207 INPUT MODULE 2 NAME; CONTINUED READ INPUT MODULE 2 ZERO / INPUT MODULE 2 NAME[6]
1208 INPUT MODULE 3 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 3 NAME[1] / INPUT MODULE 3 NAME[0]
1209 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 NAME[3] / INPUT MODULE 3 NAME[2]
1210 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 NAME[5] / INPUT MODULE 3 NAME[4]
1211 INPUT MODULE 3 NAME; CONTINUED READ INPUT MODULE 3 ZERO / INPUT MODULE 3 NAME[6]
1212 INPUT MODULE 4 NAME; 7 ASCII CHARACTERS READ INPUT MODULE 4 NAME[1] / INPUT MODULE 4 NAME[0]
1213 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 NAME[3] / INPUT MODULE 4 NAME[2]
1214 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 NAME[5] / INPUT MODULE 4 NAME[4]
1215 INPUT MODULE 4 NAME; CONTINUED READ INPUT MODULE 4 ZERO / INPUT MODULE 4 NAME[6]

Analog Parameters
Registers 1500 thru 1503, see appropriate scaling (e.g. N, 10X, 100X, 1000X)

REG # VARIABLE R/W DESCRIPTION

44 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1500 INPUT MODULE 1; CT CLAMP-ON RATING VALUE READ (N)
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1501 INPUT MODULE 2; CT CLAMP-ON RATING VALUE READ (N)
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1502 INPUT MODULE 3; CT CLAMP-ON RATING VALUE READ (N)
IF INPUT MODULE A CT TYPE; HOLDS SENSOR VALUE
1503 INPUT MODULE 4; CT CLAMP-ON RATING VALUE READ (N)

String Parameters
Registers 1508 thru 1515.
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 1 MEASUREMENT UNITS; 3 ASCII
1508 CHAR READ INPUT MODULE 1; UNITS[1] / UNITS[0]
INPUT MODULE 1 MEASUREMENT UNITS;
1509 CONTINUED READ INPUT MODULE 1; ZERO / UNITS[2]
INPUT MODULE 2 MEASUREMENT UNITS; 3 ASCII
1510 CHAR READ INPUT MODULE 2; UNITS[1] / UNITS[0]
INPUT MODULE 2 MEASUREMENT UNITS;
1511 CONTINUED READ INPUT MODULE 2; ZERO / UNITS[2]
INPUT MODULE 3 MEASUREMENT UNITS; 3 ASCII
1512 CHAR READ INPUT MODULE 3; UNITS[1] / UNITS[0]
INPUT MODULE 3 MEASUREMENT UNITS;
1513 CONTINUED READ INPUT MODULE 3; ZERO / UNITS[2]
INPUT MODULE 4 MEASUREMENT UNITS; 3 ASCII
1514 CHAR READ INPUT MODULE 4; UNITS[1] / UNITS[0]
INPUT MODULE 4 MEASUREMENT UNITS;
1515 CONTINUED READ INPUT MODULE 4; ZERO / UNITS[2]

Analog Parameters
Registers 1524 thru 2299; see appropriate scaling (e.g. N, 10X, 100X, 1000X)
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 1 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1524 POINTER READ MEASUREMENT (N)
INPUT MODULE 2 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1525 POINTER READ MEASUREMENT (N)
INPUT MODULE 3 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1526 POINTER READ MEASUREMENT (N)
INPUT MODULE 4 OIL TEMPERATURE ADDER IF CT INPUT MODULE; POINTER TO OIL TEMP
1527 POINTER READ MEASUREMENT (N)
1532 INPUT MODULE 1; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1533 INPUT MODULE 1; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1534 INPUT MODULE 1; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1535 INPUT MODULE 2; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1536 INPUT MODULE 2; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1537 INPUT MODULE 2; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1538 INPUT MODULE 3; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1539 INPUT MODULE 3; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1540 INPUT MODULE 3; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1541 INPUT MODULE 4; COOLING STAGE 2 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1542 INPUT MODULE 4; COOLING STAGE 3 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)
1543 INPUT MODULE 4; COOLING STAGE 4 RELAY # READ IF CT ADVANCED CALCULATION; RELAY NUMBER (N)

1600 INPUT MODULE 1; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1602 INPUT MODULE 2; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)

45 www.qualitrolcorp.com
1604 INPUT MODULE 3; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1606 INPUT MODULE 4; CT RATIO PRIMARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1616 INPUT MODULE 1; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1618 INPUT MODULE 2; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1620 INPUT MODULE 3; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1622 INPUT MODULE 4; CT RATIO SECONDARY # READ IF CT MODULE TYPE; HOLDS CT RATIO # (1000X)
1632 INPUT MODULE 1; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1634 INPUT MODULE 2; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1636 INPUT MODULE 3; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1638 INPUT MODULE 4; SCALING OFFSET VALUE READ SCALING OFFSET CALIBRATION VALUE (1000X)
1648 INPUT MODULE 1; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1650 INPUT MODULE 2; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1652 INPUT MODULE 3; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
1654 INPUT MODULE 4; SCALING GAIN VALUE READ SCALING GAIN CALIBRATION VALUE (1000X)
For registers 1664 thru 1702 the parameters are 32 bits long with the even registers holding the low
word and the odd registers holding the high word (e.g. 1664 low word; 1665 high word). These
registers are for those applications where the input module values could be greater than 3200
(32,000 with multiplier).
REG # VARIABLE R/W DESCRIPTION
ALL MODULES BUT CT, WINDING TEMPERATURE IF THE MODULE IS A CT, WINDING TEMPERATURE
1664 INPUT MODULE 1 PRESENT VALUE READ OR INPUT MODULE 1 PRESENT WINDING TEMP (10X)
1666 INPUT MODULE 1 MINIMUM VALUE READ OR INPUT MODULE 1 MINIMUM WINDING TEMP (10X)
1668 INPUT MODULE 1 MAXIMUM VALUE READ OR INPUT MODULE 1 MAXIMUM WINDING TEMP (10X)
1670 0 READ OR INPUT MODULE 1 PRESENT CURRENT (10X)
1672 0 READ OR INPUT MODULE 1 MAXIMUM CURRENT (10X)
1674 INPUT MODULE 2 PRESENT VALUE READ OR INPUT MODULE 2 PRESENT WINDING TEMP (10X)
1676 INPUT MODULE 2 MINIMUM VALUE READ OR INPUT MODULE 2 MINIMUM WINDING TEMP (10X)
1678 INPUT MODULE 2 MAXIMUM VALUE READ OR INPUT MODULE 2 MAXIMUM WINDING TEMP (10X)
1680 0 READ OR INPUT MODULE 2 PRESENT CURRENT (10X)
1682 0 READ OR INPUT MODULE 2 MAXIMUM CURRENT (10X)
1684 INPUT MODULE 3 PRESENT VALUE READ OR INPUT MODULE 3 PRESENT WINDING TEMP (10X)
1686 INPUT MODULE 3 MINIMUM VALUE READ OR INPUT MODULE 3 MINIMUM WINDING TEMP (10X)
1688 INPUT MODULE 3 MAXIMUM VALUE READ OR INPUT MODULE 3 MAXIMUM WINDING TEMP (10X)
1690 0 READ OR INPUT MODULE 3 PRESENT CURRENT (10X)
1692 0 READ OR INPUT MODULE 3 MAXIMUM CURRENT (10X)
1694 INPUT MODULE 4 PRESENT VALUE READ OR INPUT MODULE 4 PRESENT WINDING TEMP (10X)
1696 INPUT MODULE 4 MINIMUM VALUE READ OR INPUT MODULE 4 MINIMUM WINDING TEMP (10X)
1698 INPUT MODULE 4 MAXIMUM VALUE READ OR INPUT MODULE 4 MAXIMUM WINDING TEMP (10X)
1700 0 READ OR INPUT MODULE 4 PRESENT CURRENT (10X)
1702 0 READ OR INPUT MODULE 4 MAXIMUM CURRENT (10X)

SIMPLE CALCULATION WINDING RISE TEMPERATURE


2100 INPUT MODULE 1; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2101 INPUT MODULE 2; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2102 INPUT MODULE 3; WINDING RISE TEMPERATURE READ (100X)
SIMPLE CALCULATION WINDING RISE TEMPERATURE
2103 INPUT MODULE 4; WINDING RISE TEMPERATURE READ (100X)
2108 INPUT MODULE 1; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2109 INPUT MODULE 2; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)

46 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
2110 INPUT MODULE 3; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2111 INPUT MODULE 4; CURRENT FACTOR READ SIMPLE CALCULATION CURRENT FACTOR (100X)
2116 INPUT MODULE 1; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2117 INPUT MODULE 2; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2118 INPUT MODULE 3; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
2119 INPUT MODULE 4; WINDING TIME CONSTANT READ SIMPLE CALCULATION WINDING TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2124 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2125 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2126 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TEMPERATURE;
2127 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2128 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2129 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2130 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 2; OIL RISE TEMPERATURE;
2131 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2132 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2133 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2134 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 3; OIL RISE TEMPERATURE;
2135 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2136 STAGE 1 READ COOLING STAGE 1 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2137 STAGE 2 READ COOLING STAGE 2 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2138 STAGE 3 READ COOLING STAGE 3 OIL RISE TEMPERATURE (100X)
INPUT MODULE 4; OIL RISE TEMPERATURE;
2139 STAGE 4 READ COOLING STAGE 4 OIL RISE TEMPERATURE (100X)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2156 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2157 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2158 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 1; OIL RISE TIME CONSTANT;
2159 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2160 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2161 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2162 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 2; OIL RISE TIME CONSTANT;
2163 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2164 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2165 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2166 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 3; OIL RISE TIME CONSTANT;
2167 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2168 STAGE 1 READ COOLING STAGE 1 OIL RISE TIME CONSTANT (N)

47 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2169 STAGE 2 READ COOLING STAGE 2 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2170 STAGE 3 READ COOLING STAGE 3 OIL RISE TIME CONSTANT (N)
INPUT MODULE 4; OIL RISE TIME CONSTANT;
2171 STAGE 4 READ COOLING STAGE 4 OIL RISE TIME CONSTANT (N)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2188 INPUT MODULE 1; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2189 INPUT MODULE 1; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2190 INPUT MODULE 1; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2191 INPUT MODULE 1; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2192 INPUT MODULE 2; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2193 INPUT MODULE 2; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2194 INPUT MODULE 2; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2195 INPUT MODULE 2; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2196 INPUT MODULE 3; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2197 INPUT MODULE 3; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2198 INPUT MODULE 3; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2199 INPUT MODULE 3; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1 ADVANCED CURRENT FACTOR
2200 INPUT MODULE 4; CURRENT FACTOR; STAGE 1 READ (100X)
COOLING STAGE 2 ADVANCED CURRENT FACTOR
2201 INPUT MODULE 4; CURRENT FACTOR; STAGE 2 READ (100X)
COOLING STAGE 3 ADVANCED CURRENT FACTOR
2202 INPUT MODULE 4; CURRENT FACTOR; STAGE 3 READ (100X)
COOLING STAGE 4 ADVANCED CURRENT FACTOR
2203 INPUT MODULE 4; CURRENT FACTOR; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2220 INPUT MODULE 1; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2221 INPUT MODULE 1; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2222 INPUT MODULE 1; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2223 INPUT MODULE 1; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2224 INPUT MODULE 2; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2225 INPUT MODULE 2; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2226 INPUT MODULE 2; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2227 INPUT MODULE 2; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2228 INPUT MODULE 3; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2229 INPUT MODULE 3; WINDING RISE TEMP; STAGE 2 READ (100X)
COOLING STAGE 3; ADVANCED WINDING RISE TEMP
2230 INPUT MODULE 3; WINDING RISE TEMP; STAGE 3 READ (100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2231 INPUT MODULE 3; WINDING RISE TEMP; STAGE 4 READ (100X)
COOLING STAGE 1; ADVANCED WINDING RISE TEMP
2232 INPUT MODULE 4; WINDING RISE TEMP; STAGE 1 READ (100X)
COOLING STAGE 2; ADVANCED WINDING RISE TEMP
2233 INPUT MODULE 4; WINDING RISE TEMP; STAGE 2 READ (100X)
2234 INPUT MODULE 4; WINDING RISE TEMP; STAGE 3 READ COOLING STAGE 3; ADVANCED WINDING RISE TEMP

48 www.qualitrolcorp.com
REG # VARIABLE R/W DESCRIPTION
(100X)
COOLING STAGE 4; ADVANCED WINDING RISE TEMP
2235 INPUT MODULE 4; WINDING RISE TEMP; STAGE 4 READ (100X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2252 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2253 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2254 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING CALC EXPONENT;
2255 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2256 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2257 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2258 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 2; WINDING CALC EXPONENT;
2259 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2260 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2261 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2262 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 3; WINDING CALC EXPONENT;
2263 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2264 STAGE 1 READ COOLING STAGE 1; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2265 STAGE 2 READ COOLING STAGE 2; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2266 STAGE 3 READ COOLING STAGE 3; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 4; WINDING CALC EXPONENT;
2267 STAGE 4 READ COOLING STAGE 4; ADVANCED CALC EXPONENT (10X)
INPUT MODULE 1; WINDING TIME CONSTANT;
2284 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2285 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2286 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 1; WINDING TIME CONSTANT;
2287 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2288 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2289 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2290 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 2; WINDING TIME CONSTANT;
2291 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2292 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2293 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2294 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 3; WINDING TIME CONSTANT;
2295 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2296 STAGE 1 READ COOLING STAGE 1; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2297 STAGE 2 READ COOLING STAGE 2; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2298 STAGE 3 READ COOLING STAGE 3; WINDING TIME CONSTANT (N)
INPUT MODULE 4; WINDING TIME CONSTANT;
2299 STAGE 4 READ COOLING STAGE 4; WINDING TIME CONSTANT (N)

49 www.qualitrolcorp.com
50 www.qualitrolcorp.com
Q ASCII Demo Application
Qualitrol has developed a program to assist the user with the development of an ASCII based software to
communicate with the 505ITM. This software allows the user to communicate with the 505ITM while showing
the actual ‘Sent’ and ‘Reply’ packets that are used to send the data. The Q ASCII demonstration program
runs on Windows NT, 95, 98 and 2000 and is named ‘qascii.exe’. The software can be copied onto the hard
drive or run directly from the floppy disk. Before using the program though, the 505ITM must be set to
communicate ASCII through the RS485 port at the rear of the unit. This is done by running the Qualitrol
Remote Software package and entering the communications section under the ‘Customer-Setup’. See the
Qualitrol 505ITM Manual (IST-104-1) for detailed instructions. Set the protocol to QASCII and take note of
the baud rate and address (change these values if so desired). Now exit out of the Remote program.
Momentarily remove power from the 505ITM. NOTE: Only upon powering up the 505ITM are new
communication values applied to the system.
Shown below is the Communications Configuration window in the Qualitrol Remotes Software. This is where
the 505ITM protocol type is set to communicate ASCII out the RS485 port.

51 www.qualitrolcorp.com
Now connect your computer to the RS485 connection on the 505ITM and start the qascii.exe
program. Upon starting the program the following window should appear on your computer.

52 www.qualitrolcorp.com
Set the communications port to match the connection on your computer and set the baud rate and
address to match what was entered in the Remote Software. Now click on the ‘Connect’ button. If a
communication error occurs, check your hardware connection and step through setting the protocol
again making sure the values match.

Comm Selects the communication port you are connected to.

Baud Indicates the baud rate that will be communicated at.

Address Indicates the address that the 505ITM is programmed for.

Connect Pressing this button will attempt to establish communications with the
505ITM.

Register This box holds the register address that you wish to read or write to.
Check the ASCII Register Map shown earlier in this manual for variable
locations.

Value This window will hold the return value on a read or will accept the value to
be written to the selected address.

Read/Write These radio buttons select whether you want to read a value from the
505ITM or write a value to the 505ITM.

Read/Write Clicking on this button specifies whether a read or write is performed.

Packets-Sent This shows the actual packet structure sent to the 505ITM.

Packets-Reply This shows the actual structure of the packet received from the 505ITM.

Exit Clicking on the exit button will remove the user from the program.

53 www.qualitrolcorp.com
QUALITROL® Field Services
QUALITROL® provides on-site commissioning/ start-up and comprehensive maintenance contracts to all customers
worldwide. To further improve reliability, an extended warranty is available on selected products commissioned by
QUALITROL®.
QUALITROL® Educational Services
®
QUALITROL professional training (designed to achieve hands-on performance based objectives) prepares operations,
maintenance, and engineering personnel to install, test, configure, operate and maintain QUALITROL® products.
QUALITROL® Accelerated Delivery
®
QUALITROL provides accelerated delivery on many products and services including replacements, spare parts and
repairs.

About Qualitrol:
Qualitrol manufactures substation and transformer monitoring and protection devices used by electric utilities and
manufacturing companies. It is the global leader in sales and installations of transformer asset protection equipment, fault
recorders and fault locators. Established in 1945, Qualitrol produces thousands of different types of products on demand,
each customized to customers' unique requirements.
©2008 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice.
®

All trademarks are properties of their respective companies, as noted herein. IST-099-1.

54 www.qualitrolcorp.com