Sie sind auf Seite 1von 5

MODEL : ECCLP 360A25 /46

30 ton scroll process chillers


specs,installation manual and service manuals
MODEL T.R. A B C REFRIGERANT VOLTAJE WEIGHT (LBS)

ECCLA360A46E 30 72'' 88.5'' 40.5'' R-410 A 460 / 3 / 60 1240

* Restrictions apply
* Tables and load data information aireyork.net, american chillers sa de cv & ecochillers
not be held responsible for errors of calculation, see your counselor.

PRODUCT DRAWING Project Name:


Location:
Sold To:
Cust Purch Order##:
Date: MAY2011
Rev. 2.0
AIR-COOLED SCROLL CHILLER SYSTEM Engineer: Contract##: Form: 190.54-E1S
MODEL ECCLA300A25E / A46E Contractor: UNIT Dwg. Lev.: 08//04
NOT FOR CONSTRUCTION For: TAG: Dwg. Scale : NTS
PIPE IN/OUT
MODEL T.R. PUMP TANK LTS WEIGHT (LBS)
WATER

ECCLP300A46E 30 3 HP 300 LTS 2 '' 8326

MINIMUM CLEARANCES
CLEARANCE DESCIPTION DISTANCE IN INCHES

OVERHEAD (TOP) 120''

FRONT 36''

REAR 36''

LEFT SIDE 30''

RIGHT SIDE 30''


BOTTOM 0
* Restrictions apply
1. In all installations where now accumulates and winter
Operations is expected, additional height must be privided * Tables and load data information aireyork.net, american chillers sa de cv & ecochillers
To insure normal condenser airflow.
not be held responsible for errors of calculation, see your counselor.

PRODUCT DRAWING Project Name:


Location:
Sold To:
Cust Purch Order##:
Date: MAY2011
Rev. 2.0
AIR-COOLED SCROLL CHILLER SYSTEM Engineer: Contract##: Form: 190.54-E1S
MODEL ECCLP300A25E / A46E Contractor: UNIT Dwg. Lev.: 08//04
NOT FOR CONSTRUCTION For: TAG: Dwg. Scale : NTS
AIR COOLED SCROLL CHILLER
PERFOMANCE SERIES A, B

Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant

ECCLP360A46 1 ECCLP360A46 30 460/3/60 R410


Pin No: ECCLP360A46

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 9.0 / 2.6
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13 / 3.8
Design Flow Rate
(gpm) 72 Water 100% Physical Data
Pressure Drop (psig) 9.98 Rigging Wt. (lbs.) 1240
Fluid Water Operating Wt. (lbs.) 1392
Fouling Factor 0.00010
Water Volume. (gal) 2.58

Electrical Data
Circuit 1 2 3 4
Compressor RLA 2/26.9
Compressor Start Current (LRA) 179
Fan QTY/FLA (each) 2/3.3

Single Point
Min. Circuit Ampacity 67.1
Min. Non-Fused Disconnect 90
(Amps)
Min. Dual Element Fuse Size 90
(Amps)
Max. Dual Element Fuse Size 90
(Amps)
Min. Circuit Breaker (Amps) 90
Max. Circuit Breaker (Amps) 90
Wire Lugs Per Phase* 6
Wire Range (Lug Size) (6)
Total Amps 60.4 Operating Condition Electrical
Data
Compressor kW 33
Starter Type Across the Line Total Fan kW 2.23
Total kW 35.23

RATED IN ACCORDANCE WITH ARI STANDARD 550/590.


* Use Copper Conductors only
CALCS do not include pump motors, all the information is subject to change whit out notice,
Notes: If you need specific calcs, please call a representative or email to chillers@aireyork.com
Note: The Power calculations do not include recirculating water pumps

Project Name: Sold To:


Location: Customer Purchase Order No.:
Engineer: Contract No.:
Contractor: Date: December 2011 Revision: 2.1
Performance
Page 1 of 2
AIR COOLED SCROLL CHILLER
PERFOMANCE SERIES A, B

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency*
100.0 95.0 30 33 10.3 / 3.0
75 86.3 22.5 24.75 12.2 / 3.6
50 80.6 15 16.5 13.2 / 3.9
25 66.9 7.5 8.25 15.8 / 4.6

SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz
ECCLA360A46 ( Equipped with Low Sound Fans )
Load % Ambient 63 125 250 500 1K 2K 4K 8K LWA
(°F)
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0
77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0
67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0
44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0
22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


ECCLA360A46 ( Equipped with Low Sound Fans )
Load % Ambient 63 125 250 500 1K 2K 4K 8K dBA
(°F)
100.0 95.0 75.0 71.0 68.0 69.0 64.0 63.0 58.0 54.0 71.0
77.7 86.3 74.0 71.0 68.0 69.0 64.0 62.0 58.0 54.0 70.0
67.0 80.6 74.0 71.0 68.0 68.0 64.0 62.0 57.0 53.0 70.0
44.7 66.9 72.0 69.0 66.0 66.0 62.0 60.0 55.0 51.0 68.0
22.3 55.0 68.0 65.0 62.0 62.0 58.0 57.0 51.0 47.0 64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)
• *Chillers capacity and performance may vary according to specifications releases

Project Name: Sold To:


Location: Customer Purchase Order No.:
Engineer: Contract No.:
Contractor: Date: December 2011 Revision: 2.1
Performance
Page 2 of 2