MINIMUM CLEARANCES
CLEARANCE DESCIPTION DISTANCE IN INCHES
FRONT 36''
REAR 36''
Unit Tag IDENT Qty Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
Electrical Data
Circuit 1 2 3 4
Compressor RLA 2/26.9
Compressor Start Current (LRA) 179
Fan QTY/FLA (each) 2/3.3
Single Point
Min. Circuit Ampacity 67.1
Min. Non-Fused Disconnect 90
(Amps)
Min. Dual Element Fuse Size 90
(Amps)
Max. Dual Element Fuse Size 90
(Amps)
Min. Circuit Breaker (Amps) 90
Max. Circuit Breaker (Amps) 90
Wire Lugs Per Phase* 6
Wire Range (Lug Size) (6)
Total Amps 60.4 Operating Condition Electrical
Data
Compressor kW 33
Starter Type Across the Line Total Fan kW 2.23
Total kW 35.23
SOUND POWER LEVELS (In Accordance with ARI 370) – Octave Band Center Frequency, Hz
ECCLA360A46 ( Equipped with Low Sound Fans )
Load % Ambient 63 125 250 500 1K 2K 4K 8K LWA
(°F)
100.0 95.0 102.0 98.0 95.0 96.0 91.0 90.0 85.0 81.0 98.0
77.7 86.3 101.0 98.0 95.0 96.0 91.0 89.0 85.0 81.0 97.0
67.0 80.6 101.0 98.0 95.0 95.0 91.0 89.0 84.0 80.0 97.0
44.7 66.9 99.0 96.0 93.0 93.0 89.0 87.0 82.0 78.0 95.0
22.3 55.0 95.0 92.0 89.0 89.0 85.0 84.0 78.0 74.0 91.0