Test Result for:

SUPPLY OF MANPOWER, TOOLS, EQUIPMENT


AND TECHNICAL EXPERTISE FOR THE
INSPECTION AND ELECTRICAL TESTING OF 1-unit
2.5MVA TRANSFORMERS - MABUHAY
INTERFLOUR PROJECT
(Ref. P.O. No.: 19021)

Prepared for:

ENGR. ERNESTO A. NAVARRO


President
SPARKLINE ELECTRICAL
Lakas ng Mahihirap, Sangandaan,
Caloocan, Metro Manila

Prepared by:

ENGR. MARK JORDAN B. AQUINO, REE


Operations Manager
NORTHAMPERE ELECTRICAL SERVICES
035 Tugui Norte, Bani, Pangasinan
(02) 919-4591 / Marikina
0999-9931-405 (Smart)
0917-4625-081 (Globe)
northampere.electrical@gmail.com
salestechnical.northampere@gmail.com

Date: April 23, 2019

1
April 29, 2019

ENGR. ERNESTO A. NAVARRO


President
SPARKLINE ELECTRICAL
Lakas ng Mahihirap, Sangandaan,
Caloocan, Metro Manila

RE : TEST RESULTS – 1 UNIT POWER TRANSFORMER ELECTRICAL TEST –


MABUHAY INTERFLOUR

Dear Engr. Navarro,

We are pleased to submit herewith our final report for the electrical testing of One (1) unit Power
transformer at Mabuhay Interflour Plant and is conducted last April 20, 2019. Please see attached
Test Results for your reference and perusal.

Thank you for the opportunity of being in service to your company.

Very truly yours,

ENGR. MARK JORDAN AQUINO, REE, IRT


Operations Manager

Noted by:

ENGR. FREDERICTO C. AQUINO, PEE


Technical Consultant

2
TEST RESULTS & EVALUATION

3
I. TRANSFORMER - S/N: 1LVN17004044149

NAMEPLATE DATA
Company MABUHAY INTERFLOUR Serial Number 1LVN17004044149
Location Subic Zambales Coolant FR3
Manufacturer ABB Configuration Dyn11
Year Mfg. 2017 Tank Type Hermetically Sealed
Phases 3 Class KNAN
kV 13.8 / 0.400 VA Rating 2.5 MVA
Date 04/20/19 Temp 44°C

A.) TRANSFORMER TURNS RATIO TEST

Np
Detc Np Volt Ltc Cal Ratio 1 Ratio 2 Ratio 3 Min Limit Max Limit Remarks
Volt
4 13,455 3 400 58.2619 58.269 58.267 58.269 57.9705 58.5532 Passed

TEST EQUIPMENT METREL 3280 – DT ANALYSER


ANSI NETA MTS -2013: 7.2.2
REFERENCE:
Measured Turns Ratio must be within ±0.5% of calculated ratio.
REMARKS /
Results are satisfactory.
EVALUATION
RECOMMENDATION Annual Turns Ratio test is recommended to monitor winding conditions.

B.) EXCITING CURRENT TEST

DETC LTC Test kV H1A – H3A H3A – H2A H2A - H1A Remarks
C C 1.24 mA 1.03 mA 1.24 mA Passed

TEST EQUIPMENT METREL 3280 – DT ANALYSER


ANSI NETA MTS -2011: 7.2.2.6, Doble Guidelines, IEEE Std. 62-1995

For the great majority of three phase transformers, the pattern of exciting
REFERENCE:
current is two (2) similar high readings on the outer phases and one lower
reading on the center phase or; two similar low readings on the outer
phases and one high reading on the center phase.
Measured values of exciting current shows the good typical three phase pattern.
REMARKS /
EVALUATION
Results are satisfactory.
Annual trending of exciting current values is recommended to monitor winding
RECOMMENDATION
conditions and contact at the tap changer.

4
C.) INSULATION RESISTANCE TEST

Corrected at 20°C, Correction Factor = 3.95 (44°C)


Connection Volts 1 min (G-ohms) 10 mins (G-ohms) PI Remarks
Hi to Lo/Earth 5,000 4.9375 5.8725 1.1893 Passed
Hi to Earth 5,000 4.819 6.9915 1.4508 Passed
Lo to Earth 1,000 5.095 5.8065 1.1396 Passed

TEST EQUIPMENT METREL MI 3210 TERAOHM XA 10KV


ANSI / NETA MTS-2011: Table 100.5
Minimum insulation resistance for oil immersed transformer having coil rating
REFERENCE
Above 5KV is 5GΩ and 0-600V is 0.1GΩ. Polarization index must be
greater than 1.0.
Results are still within standard acceptable limits and can be considered
EVALUATION
satisfactory.
RECOMMENDATION Annual testing is recommended to monitor insulation deterioration.

D.) WINDING RESISTANCE MEASUREMENT

Tap Changer Position – C


Winding Connections Remarks
Winding Resistance in Ω
H1A – H3A 479.2mΩ Passed
H3A – H2A 478.9mΩ Passed
H2A – H1A 478.2mΩ Passed
X1 – X0 0.241mΩ Passed
X2 – X0 0.243mΩ Passed
X3 – X0 0.244m Ω Passed
Measured @ 44°C

TEST EQUIPMENT METREL MICRO OHM 10A


IEEE 62-1995
Interpretation of results is usually based on a comparison of measurements
made separately on each phase in the case of a wye-connected winding or
REFERENCE
between pairs of terminals on a delta-connected winding. Or comparison with
the factory results. Agreement to within 5% for any above comparisons are
considered satisfactory
In the absence of manufacturer’s published data. Comparison of winding
resistance values from phase to phase values are used to evaluate obtained data.
REMARKS /
All phase resistances are within standard deviation.
EVALUATION
Results are satisfactory.
RECOMMENDATION Annual winding resistance test is recommended.

5
E.) DGA AND OIL QUALITY ANALYSIS TEST:

E.1) DGA- DISSOLVED GAS ANALYSIS

CONTENT AS
MEASURED ( ppm ) GAS LIMITS (ppm)
GAS SYMBOL
IEEE C57.104-2008
April 20, 2019
*Hydrogen H2 25.9 112

*Methane CH4 23.5 20


*Ethane C2H6 148.9 232

*Ethylene C2H4 1.9 18

*Acetylene C2H2 0.0 1


*Carbon
CO 54.4 161
Monoxide
Carbon Dioxide CO2 984.0 2500

Nitrogen N2 47,970.6 -
Oxygen O2 565.9 -
TOTAL DISSOLVED
COMBUSTIBLE GASES 254.6 544
( TDCG )
TOTAL GAS CONTENT 49,775.1 -

IEEE Std. C57.155-2008 Key Gas Analysis Guidelines - Natural Esters


REFERENCE The guide uses combinations of individual key gases and total
combustible gas concentration as indicators.
Condition 1 category: TDCG < 544ppm (Total Dissolved Combustible
Gases)

Condition 1: 254.6ppm

Total dissolved combustible gas (TDCG) within this level indicates that
REMARKS / the transformer is operating satisfactorily. However, for Individual
EVALUATION combustible gas; Methane exceeds normal range. This could be due to
a Possible localized overheating within the transformer. Since this is the
first sampling result, this could not be considered conclusive as we must
determine gas generation rate in order to conclude/determine active
fault. Retesting and trending of DGA is necessary to monitor rate of gas
generation.

Results are investigative.

RECOMMENDATION  Retest after 6-months to monitor combustible gas generation


rate and trend results.

6
E.2) OIL QUALITY TEST
CONTENT AS
MEASURED ( ppm ) ASTM/IEC
TEST DESCRIPTION Units LIMITS
METHOD
April 20, 2019

Color Number L0.5/Clear D1500 / D1524 3.5 Max


Interfacial Tension Dynes/cm 32.04 D971 Ref
Acidity Number Mg KOH/g 0.0334 D664 0.3 Max
Dielectric BV KV 88.4 D1816, 2mm 40 Min
Water Content ppm 105.3 D1533 400 Max
Dielectric
Dissipation Factor % 0.00011 IEC 61620 3 Max
@ 25oC

REFERENCE IEEE Standards C57.147 - 2008


Oil Quality result values are within standard acceptable limits
REMARKS /
EVALUATION
Results are satisfactory.
No further actions required as far as Oil Quality is concerned. Continue
RECOMMENDATION
normal operation and retest after one (1) year.

II. VACUUM CIRCUIT BREAKER:

CONTACT RESISTANCE TEST

Test Current: 10A Connection / Description: MVSG AREA


Contact Resistance (mΩ)
Designation
L1 L2 L3
Feeder – MAIN 0.119 0.118 0.119
Feeder – 1 0.110 0.116 0.115
Feeder – 2 0.113 0.112 0.114
Remarks: Passed Passed Passed

TEST EQUIPMENT UNI – T 602B, DLRO


ANSI NETA MTS -2011: 7.6.3.3

Micro or DC millivolt drop vales should not exceed the high levels of the normal
REFERENCE:
range as indicated in the manufacturer’s publish data. If manufacturers data is
not available, investigate values that deviate from adjacent poles or similar
breakers by more that 50percentof the lowest value.
REMARKS /
Results are satisfactory.
EVALUATION
Annual trending of contact resistance values is recommended to monitor circuit
RECOMMENDATION
breaker contact condition.