Annexure I - Vendor Data Sheet

Item: Chilled Water Unit

A) General

1 Make :
2 Model :
3 Type of Unit :
4 Quantity Nos :
5 Capacity, Nominal & Actual, TR :
6 Chilled water Temperatures - Inlet /Outlet :
7 Cooling Water Temperatures - Inlet / Outlet :
8 Operating & shipping Wt. (Kgs.) :
9 Noise Level at 1mtr. Distance. :
10 Overall Dimensions (L x W x H ) mm :
11 Minimum Clearance Reqd. ( L x W x H ) mm
12 Refrigerant :
13 Main Incomer Rating :

B) Compressor (Rotary Screw )

1 Manufacture/ Model :
2 Type ( Semi hermetic, twin screw ) :
3 Quantity (Nos) per chiller :
4 Type of Drive :
5 Type of Lubricant :
6 Saturated suction pressure (Kg./cm2) :
7 Saturated Discharge pressure(Kg/cm 2) :
8 Type of Bearing :
9 Economiser Cycle :
10 Speed. Rpm. :
11 IKW consumed at 100%, 75%,50%, & 25% capacity :
12 Lowest turn down capacity, TR :
13 Type of Control :
14 Type of Oil Seperator :
15 Lubrication Pump (Capacity) :
16 Minimum continous operating load and power consumption :

C) Motor

1 Manufacture- Model :
2 Type :
3 Service (duty) :
4 Quantity (Nos) per chiller :
5 Type of power supply :
6 Type of enclosure :
7 Degree of protection :
8 Efficiency :
9 Ambient design temperature ( C ) :
10 Maximum design temperature ( C ) :
11 Type of starter :
12 Type of control (microprocessor based) :
13 Type of bearings :
14 Speed (rpm.) :
15 Frame size (mm) :
16 Electrical continous power (KW) :
17 Starting current (A) :
18 Continous current (A) :
19 Operating weight (Kgs.) :

D) Chiller

1 Manufacture - Model :
2 Type (DX or Flooded ) :
3 Quantity (Nos.) per chiller :
4 Capacity (Nominal / Actual) TR :
5 Shell outlet diameter (mm) x length :
6 Number of tubes ( Nos ) :
7 Tube OD X Thickness mm
8 Number of refrigerant circuit ( Nos ) :
9 Design Chilled Water Water Temp. C inlet/outlet :
10 Pressure Drop (mm Wg) :
11 Water Flow Rate :
12 Face area of tubes for Heat transfer (cm ) :
13 Design fouling factor :
14 Shell Material :
15 TubeMaterial: :
16 Insulation Material :
17 Thickness of Insulation :
18 Insulation cladding :

E) Condensor (Water Cooled)

1 Manufacture-Model :
2 Type :
3 Quantity (nos.) per chiller :
4 Capacity Nominal / Actual, TR :
5 Number of passes (Nos) :
6 Shell outer diameter x length (mm) :
7 Cooling water Temp C inlet/outlet :
8 Water flow rate (m3/hr.) :
9 Fouling factor :
10 Tubes OD x thichness :
11 Pressure drop (mm Wg) :
12 Shell Material :
13 Tube Material :
Carrier
30HXC - 355TR
Water cooled Screw Chiller
One
375 TR & 355 TR
11 / 6 Deg. C
32 / 37 Deg. C
5258 & 5721 Kgs.
85 dBA
4533 x 1015 x 2112
5200 x 1200 x 600
R 134a
Shall be furnished later

Carrier / 06N
Semi hermetic, twin screw
4
Gear Drive
Shall be furnished later
To suit the duty conditions
To suit the duty conditions
Heavy duty roller bearing
NA
2950 (Motor)
0.77, 0.79, 0.77, 0.76
35.5 TR
Pilot operated solenoid valve
Proprietary Information
Proprietary Information
44 TR / 49.2 KW

Carrier
Induction
Continous
4
400 V - 3 Ph - 50 Hz
Shall be furnished later
IP 44
Shall be furnished later
Shall be furnished later
Shall be furnished later
Wye Delta
microprocessor based
Heavy duty bearings
2950 RPM
NA
276 KW (input power)
920
460
Included in unit weight

Carrier
Flooded
One
375 TR / 355 TR
Proprietary Information
Proprietary Information
19 mm x 0.635 mm
Two
11 / 6 Deg. C
6500 mm Wg
216 m3 / hr
Proprietary Information
0.0001 FPS
Steel
Copper
Closed Cell
19 mm
NA

Carrier
Shell & Tube
One
430 TR
Two
Proprietary Information
32 / 37 Deg. C
259.2 m3 / hr
0.00025 FPS
19 mm x 0.635 mm
7400 mm Wg
Steel
Copper