Beruflich Dokumente
Kultur Dokumente
Given:
For the requirement of Dormitory
Each student = 120 Li/day
No. of Students = 36
Recovery Required :
Where:
q = 500 f ∆T
q = Heat load total (W)
500 = constant rounded off from 8.33 x 60 (Btu - Gal/Hr - min - ºF)
∆T = Water temperature difference (ºF)
f = flow rate of water (gpm)
Given:
f = 500 Li/Hr = 2.2 gal/min
Tcws = 50ºF
Twhs = 150ºF
Solution:
Given :
Boiler Capacity 250 gals
Radiators 455 gals
Air Handling Unit 50 gals
Heat Exchanger 135 gals
Water inside Pipe 170 gals
Solution:
Pf = Static pressure of the fluid in the tank when the system is filled (psig)
H = Distance of the inlet of expansion tank to the top of the system (ft)
Dc = Density of the fluid at its initial temperature (lb/ft³)
Vt = Minimun required tank volume (gals)
Vs = Fluid volume in the system (gals)
TECCENTER EST.
Proj: Andalus University Building
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building
Ground Floor
Total Heating Capacity 31,686 W
Fisrt Floor
Total Heating Capacity 37,714 W
Second Floor
Total Heating Capacity 45,533 W
Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
Tr = Room Temperature (ºC)
To = Ambient Temperature (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)
Solution:
qs = 990li/s x ((20 - (-5)ºC) x 1.2
qs = 29,700 Watts
Total Heat Load of AHU-02 including the load for Stair and Corridor
qt = 29,700 + 3,212 + 790 + 1,466 + 4,384
qt = 39,552 Watts
Where:
Fw = Q / ∆T x p
Fw = Flow of Water (Gpm)
Q. = Heat Load Total (Btu/hr)
∆T = Water Supply and ReturnTemperature difference (ºF)
p = The weight gallon of water (gal/ ºF)
Solution:
Fw = 8.33 gals/ ºF x 20ºF
Fw = 166.6 Gals
Fw = 134,991 Btu/hr
166.6 gals x 60 min /hr
Fw = 13.5 gals/min
Fw = 1.0 l/s
TECCENTER EST.
Proj: Al- Andalus University Project Electro-Mechanical Works
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building
Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)
Solution:
39,552 Watts = 990li/s x ∆T x 1.2
∆T = 39,552 Watts
990 Li/s x 1.2
∆T = 33.ºC
∆T = Ts - To
33 = Ts - To
Ts = 33 + (-5)
Ts = 28ºC
∆T = 35ºC
Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
Tr = Room Temperature (ºC)
To = Ambient Temperature (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)
Solution:
qs = 1,430li/s x ((20 - (-5)ºC) x 1.2
qs = 42,900 Watts
Total Heat Load of AHU-01 including the load for Stair and Hallway
qt = 42,900 + 1,255 + 3,274 + 796
qt = 48,225 Watts
Where:
Fw = Q / ∆T x p
Fw = Flow of Water (Gpm)
Q. = Heat Load Total (Btu/hr)
∆T = Water Supply and ReturnTemperature difference (ºF)
p = The weight gallon of water (gal/ ºF)
Solution:
Fw = 8.33 gals/ ºF x 20ºF
Fw = 166.6 Gals
Fw = 164,592 Btu/hr
166.6 gals x 60 min /hr
Fw = 16.4 gals/min
Fw = 1.24 l/s
TECCENTER EST.
Proj: Al- Andalus University Project Electro-Mechanical Works
Heating Load Calculation
Sizing Summary Description Date: August 03, 05
Dormitory Building
Where:
qs = Q x ∆T x cp x p
qs = Heat Loat Total (Watts)
Q. = Supply air capacity (Li/s)
∆T = Temperature difference (ºC)
cp = specific heat of air (Kj/ (Kg . ºC))
p = density of air at temperature To (Kg/ m³)
Solution:
48,225 Watts = 1,430li/s x ∆T x 1.2
∆T = 48,225 Watts
1,430Li/s x 1.2
∆T = 28ºC
∆T = Ts - To
28 = Ts - To
Ts = 28 + (-5)
Ts = 23ºC
∆T = 35ºC