Beruflich Dokumente
Kultur Dokumente
REPORT
ON
CONDITION MONITORING
OF LIGHTNING ARRESTERS
BY:
NASIM UDDIN
CHIEF ELECTRICAL DISTRIBUTION ENGINEER
NORTH CENTRAL RAILWAY
ALLAHABAD
-1-
INDEX
4. Important Definitions 4
7. Failure Modes of LA 5
13. Conclusion 11
14. References 12
15. Annexure-1 13
-2-
A Report on condition monitoring of Lightning Arresters
1. Introduction
High voltage power systems including traction power supply experience over
voltages, which are generated through occurrence faults, switching operations and
lightning discharges. The duration of the over voltages vary from a few micro
seconds few seconds depending on the type of surges. Similarly, the magnitude of
over voltages varies from 1.5 to 4 times of the normal operating voltages. Under
these severe overvoltage conditions, the insulation of the power
system/equipments undergoes stresses that could lead to catastrophic failure.
Hence it is imperative that the power system equipments are protected from these
over voltages at the time of occurrence. Using a device with variable impedence
with respect to voltages can provide the protection of power equipments from
overvoltages. This kind of overvoltage protection device is connected in parallel
to the system/equipments to be protected. An effective surge Protection device
must satisfy the following conditions:
Usually, metal oxide (Zinc Oxide) type of Lightning Arrester (LA) is used for
protection of system/equipments from overvoltages.
-3-
As shown in Figure 1 that Zinc Oxide elements are made by mixing Zinc Oxide
with small amount of additive materials such as Ba2 O3. The mixture is, then,
granulated, compacted and fired or baked. The equivalent electrical circuit of an
LA is a Parallel Combination of capacitance and variable resistance. The current
flowing through LA is the total leakage current (It) having capacitive leakage
current (Ic) and resistive leakage current (Ir) components. Normal operating
voltages cause ageing of Zinc Oxide elements/blocks whereas
Switching/Lightning overvoltages may cause overloading of all or part of the Zinc
Oxide blocks. Due to various electrical stresses, the granulated layers/barriers
break down causing the conduction. The increase in the voltage stresses on
healthy granulated layers results in the higher resistive leakage current (Ir)
amounting to higher total leakage current in LA.
The non-linear characteristics of these Zinc Oxide blocks is shown in Fig. 2.
-4-
The lower linear part A is temperature dependent, and exhibits a negative
temperature coefficient. The arrester is designed in such a way that the applied
operating voltage gets located around point O. This results in a continuous
resistive current of few micro amps flowing through the resistor elements. Under
overvoltage condition, the voltage increases and shifts operating point
momentarily for overvoltage duration to point near B. This results in a resistive
current of few milli amperes flowing through the resistor elements. As soon as the
overvoltage disappears, the operating point will shift back to O. In the event of
transient switching or lightning overvoltages, the operating point will shift to
portion C.
For the transient of a few micro seconds, it will draw current in the rage of 5/ 10
KAmps. In the event of very high lightning current of the order of 40 to 100
KAmps peak, the operating point will shift to portion D. However, on expiry of
transient of few milliseconds the operating point will come back to point O.
Thus, the operating point of these arresters is normally located at point O called
Maximum Continuous Operating Voltage (MCOV) & the point B of Fig. 2
indicates approximately the rated voltage of arrester. The arrester can stay at point
O, i.e., MCOV, all along its life but it can stay at point B (fault condition), i.e..
Rated Voltage, for only 10 seconds (It is presumed that system breakers will
operate to isolate the fault within 2 seconds). The energy that gets dissipated, i.e.
(1²R) during continuous or overvoltage condition decides the size (dia.) of ZnO
resistor element.
Various types of Zinc Oxide elements typically used in LAs are shown in figure-3
-5-
applications particularly for a 39 KV class lightning arrestors, 12 nos. Zinc Oxide
blocks/elements of 3.25 KV rating each are used.
The energy handling capacity of the commercial ZnO arresters is in the order of
150 Jouls/cm³.
The Energy absorption and dissipation being dependent on this specific energy
handling capacity, the energy discharge of Zinc Oxide Block is basically
dependent on its volume.
The rated voltage of Zinc Oxide element is proportional to the height. The energy
level increases with the increase in area of the Zinc Oxide block.
As long as the heat generated from the ZnO elements due to continuous operating
voltages and surges is less than the thermal power dissipation of the housing, the
elements will remain in an undamaged condition, capable of performing their
protective function.
4. Important Definitions
-6-
4.6 Standard lightning impulse
The wave shape of the standard impulse used is 1.2/50 μA.
4.7 Temporary overvoltage
An oscillatory overvoltage, associated with switching or faults (for example, load
rejection, single-phase faults) and/or nonlinearities (ferroresonance effects,
harmonics), of relatively long duration, which is undamped or slightly damped.
Similarly, rod type gap (ET-1 & ET-2) arresters were provided on 25 KV on the
roof of the electric locomotives in order to protect the Power equipments of the
Locomotives, CLW has now cut in the provision the Zinc Oxide type Lightning
arresters in place of rod-type gap (ET-2).
7. Failures Modes of LA
Approximately 5000 nos. of Zinc Oxide type Lightning Arresters each on 132 KV
and 25 KV side of Traction Sub-Stations are in service. LAs provided on 132 KV
side are identical in design as on 25 KV side except the number of Zinc Oxide
blocks used for different voltage applications. Similarly, about, 500 nos. Zinc
Oxide LAs have been provided on electric locomotives, so far.
Incidentally, the exact rate of failure of LAs on Indian Railways is not accurately
available except the cases of bursting of LAs.
Further, the failure rate of Power equipments such as Transformers etc. are also
not fairly known on account of defective LAs or unprotected circuit in service.
-7-
However, as per the field survey of power utilities and cases reported by Central
Railway for bursting cases of dc Lightning Arrester on dc EMUs, a general
pattern of porcelain housed LA failures have been identified which is summarised
in Figure-4.
100
90
90 Ingress of moisture
%age of total failures
80
70
60
50
40 Premature ageing
of ZnO blocks
30
20
10
10
0
1 2
Causes of failures
Figure - 4
-8-
accurate monitoring the health of an LA. Therefore, practically no real time
system for monitoring the health of LAs exists on Indian Railways. Even, if the
measurement of total leakage current is monitored, then also a database is
required to be built up by the Railways in order to prescribe a threshold limit for
various make of Lightning Arrestors for taking the decision of replacing the LA.
-9-
However, by using arrester system data and measuring the ambient temperatures
and operating voltage at the same time as the condition monitoring is performed,
it is possible to recalculate the leakage current data to a common reference. The
resistive leakage current values will then be approximately the same independent
of the test conditions. In other words – by taking account of the ambient
temperature and operating voltage, measurements performed under different
conditions can be directly compared and the measured values will be a reliable
indicator of the arrester conditions.
The resistive current consists of fundamental, third harmonic, fifth harmonic and
seventh harmonic components. The harmonic contents depend on the magnitude
of the resistive current and on the degree of non-linearity of the voltage current
characteristics of zinc oxide blocks. Further, the harmonic contents also are the
function of temperature of LA. The third harmonic is the largest harmonic
contents of the resistive current and most commonly used for monitoring
purposes.
In addition to the above, the harmonic contents in operating voltage also increase
the harmonic contents in the leakage current. The system harmonics will interfere
with the harmonics generated by the arrestor itself. This implies that with the
presence of harmonics contents in the system voltage, if any, cannot be ignored
for the purpose of evaluation of the resistive leakage current. In other words – if
the harmonic contents of the system voltage are ignored, then it will not be known
if an apparent increase in the third harmonic resistive leakage current (Ir) is really
due to ageing phenomena of the arrester or it is a ‘false’ increase due to varying
harmonic contents with time.
- 10 -
10. Proposed method for measurement of leakage current
As already explained in the previous Para that only third harmonic resistive
leakage current is important for evaluation of the performance of LA in service.
Depending on the value and trend in rise of third harmonic resistive leakage
current, a decision can be taken either for close monitoring or for replacement of
an LA. Various kinds of instruments are now available in the market, which can
be used for measurement of third harmonic resistive leakage current flowing
through an LA under normal working conditions. A schematic diagram for the
measurement of third harmonic leakage current by using such instruments is
shown in figure –5.
Figure –5.
- 11 -
11. Case study of Lightning Arrester failure:
For the above observations, the following conclusions were drawn to explain the
failure of the above Lightning Arresters:
Flash over and short circuit of the metal blocks took place due to ingress of
moisture, which was confirmed by looking at the rusted parts of the Lightning
Arresters.
The ingress of moisture was due to improper fitment of the gasket between the
porcelain housing and the top cover.
Hence, from the above observations, it was confirmed that the above Lightning
Arrester failed on account of ingress of moisture due to improper fitment of
rubber gasket between porcelain housing and the top cover. A few photographs
taken for the failed Lightning Arresters are reproduced and placed at Annexure-1.
i) Quality of the neoprene rubber gaskets and the dimensions including the
concentricity are to be ensured before the fitment on the Lightning
Arresters.
ii) Use of stainless steel fasteners in order to prevent the rusting/corrosion.
iii) Use of ‘O’ ring in place of gasket between porcelain housing and the top
cover for better sealing.
- 12 -
System Range of THRC* Range of THRC* Remarks
voltage Make A Make B
Normal range Abnormal Normal range Abnormal
range range
400 kV 10-100 μA 150-400 30-150 μA 300-500 μA Five surge
μA arresters
were
showing
upto 2100
μA
220 kV 20-40 μA 200-400 20-40 μA 200-400 μA Three Surge
μA arresters
were
showing
upto 1000
μA
The value of the third harmonic resistive leakage current was recorded generally
in the range of 10-15 micro amperes for new LAs whereas for 12 to 15 years old
LAs, the value was in the range of 200-300 micro ampere.
13. Conclusion
As explained earlier, LA is one of the most vital devices used to protect the power
equipments such as transformers etc. against over voltages including lightning
surges. Therefore, it is quite imperative that the health/condition of the LAs
provided on electrical rolling stock and Traction Sub-Stations is to be monitored
at a regular interval by measuring third harmonic resistive leakage current with
the help of measuring instruments. Further, a database for the third harmonic
resistive leakage current for all the LAs (make wise) is to be developed and
analysed. A threshold/critical value of third harmonic resistive leakage current is
then to be specified based on the database developed over a period of time.
As discussed earlier, the following major reasons have been identified for LA
failures:
- 13 -
In order to avoid the ingress of moisture into the porcelain housing of LAs
through the sealing system, the LAs with polymeric housing have been developed
and about 150 such LAs have already been put into the service on the electric
locomotives built by CLW a few years ago. No failures of these LAs with
polymeric housing have been reported so far. However, a close monitoring is
required for these kind of LAs in order to establish their efficacy against the
ingress of moisture etc.
In the light of the foregoing discussions, the following practices for maintenance
and condition monitoring of LAs in service are suggested:
14. References
[3] Surge Arrester Monitorintg and Failure Investigations; Ravindra Kumar Tyagi,
S.Victor, Narendra Singh Sodha; PGCIL, Gurgaon.
- 14 -
ANNEXURE-1
- 15 -
- 16 -
- 17 -
- 18 -
- 19 -
- 20 -