Beruflich Dokumente
Kultur Dokumente
Page 34
3.1 Introduction to Switch Gear
A circuit breaker is an automatically operated electrical switch breaker designed to protect an electrical
circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and,
by interrupting continuity, to immediately discontinue electrical flow. Unlike a fuse, which operates once
and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal
operation. Circuit breakers are made in varying sizes, from small devices that protect an individual
household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city.
Switch:- Switch is an electrical component that can break an electrical circuit, interrupting the current or
diverting it from one conductor to another
1. Switches are not automatic as they need to be manually turned on or off while circuit breakers just
trips off on certain conditions
2. Switches allow users to cut off power supply to a certain area or equipment while circuit breakers
are more preventive in nature.
3. Circuit breakers are essentially automatic off switches designed for a very specific purpose, which is
to prevent unnecessary electrical circuit damage.
A circuit breaker is an automatically-operated electrical switch designed to protect an electrical circuit from
damage caused by overload or short circuit. Its basic function is to detect a fault condition and, by
interrupting continuity, to immediately discontinue electrical flow.
The term switchgear, used in association with the electric power system, or grid, refers to the combination of
electrical disconnects, fuses and/or circuit breakers used to isolate electrical equipment. Switchgear is used
both to de-energize equipment to allow work to be done and to clear
faults downstream.
Two contracts called electrode remains closed under normal operating conditions. When fault occurs on any
part of the system, the trip coil of the circuit breaker get energized and contacts are separated.
Arc Phenomenon
An arc is struck when contacts are separated. The current is thus able to continue. Thus the main duty of a
circuit breaker is to distinguish the arc within the shortest possible time.
Degree of ionization
Length of the arc
Cross Section of the arc
Depending upon the arc quenching circuit breakers are classified as follows:
Advantages:
An air blast circuit breaker has the following advantages over an oil circuit breaker:
Disadvantages:
In this breaker, vacuum is being used as the arc quenching medium. Vacuum offers highest insulating
strength, it has far superior arc quenching properties than any other medium.
Used in 11kv panel in control room of grid station.
Advantages
Simple construction and less cost.
SF6 gas is inflammable, non toxic and chemical inert gas.
Same gas is recirculated in the circuit.
Maintenance free Circuit breaker
Ability to interrupt low and high fault current
Excellent Arc extinction
Vacuum circuit breakers are most commonly used and they score over the conventional oil circuit breakers.
Vacuum interrupters have reduced contact movement which imposes reduced mechanism, energy leading to
minimum component wear. Consistent and comparatively reduced arcing time coupled with absence of
arcing media, impart exceptionally high contact life. These benefits of vacuum circuit breakers impart higher
reliability to the system.
General Construction
The design incorporates fully compartmentalized panels having single busbar system and set of interlocks
for safety operation.
A panel consists of a fixed portion which is modular construction having three high voltage chambers,
namely: breaker chamber, busbar chamber and Cable Termination chamber. The panel also houses a moving
portion which comprises of wheel mounted truck fitted with an operating mechanism, vacuum interrupters
and isolating contacts. Motor operated spring closing mechanism keeps the spring charged after every
closing operation making it ready for next closure. Instrument panel is a separate low voltage chamber.
The main breaker chamber is of bolted sheet steel construction which accepts the moving portion at the floor
level. The primary isolating contact comprising of self aligning type spring loaded, silver plated copper
fingers on moving portion engages with silver plated copper flats on the fixed portion of the switchgear
panel. This chamber also includes features like, secondary plug and socket guides for the moving portion,
earthing contact which meets with an earthing strip on the moving portion and the safety shutters.
The moving portion with VCB can be kept either in the ‘SERVICE’ or ‘TEST’ position inside the breaker
chamber.
The instrument and relay chamber is of folded sheet steel construction with a hinged instrument panel door
suitable for flush mounting of instruments in the front. This chamber also accommodates terminal blocks
inside the instrument panel and other internal mounting electrical item viz. fuses, contactor, transducers etc
as per contractual requirements.
Busbar Chamber
The busbar chamber is provided with bolted covers at the top and the back. A pressure release valve
assembly is also provided on top of this chamber. Insulation barriers provide partition between two adjacent
busbar chambers.
The C.T. and cable termination chamber is also of bolted sheet steel construction with an ample space of
cable termination and current transformers of various types. This chamber also houses connections, lugs and
bottom fixed contacts.
Breaker Trolley
The moving portion consists of a truck frame on 4 wheels. Three vacuum interrupters and the operating
mechanism are mounted on the truck frame. The interrupters are mounted between top pole head and bottom
pole head which are supported through epoxy support insulators and are shielded from each other by means
of insulating barriers. Top and bottom insulating contacts are used for current transformer connected to
interrupter through top and bottom pole head. These isolating contacts have parallel spring loaded fingers.
Operating Mechanism
Vacuum Interrupter
Vacuum Interrupter used in circuit breakers to conduct and to interrupt normal current at system voltage and
for making and breaking fault currents.
The operating mechanism is stored energy type. It has 3 helical springs to store energy for closing,
tripping and maintaining desired contact pressure.
Energy is stored in closing spring either by motor charging or manual charging. The tripping and contact’s
pressure springs are automatically charged during closing operation. Part of energy of closing spring is used
to close the breaker and balance energy is transferred to tripping and contact pressure springs after every
closing operation, closing spring automatically gets charged through motor so that mechanism is ready for
next closing operation.
A closed breaker with charged closing spring can perform auto reclose duty, i.e. open-close-open can be
done without any intermediate manual or motor charging. Breaker ON-OFF is indicated by mechanical ON-
OFF indicator and charging or closing spring by mechanical CHARGED-DISCHARGED indicator.
Operating
coil (closing)
Operating coil
(opening)
1. By motor
2. By manual operation.
Closing Operation
After the completion of charging operation of the closing spring, the breaker is ready for closing. If the
breaker is to be closed locally, the spring is released by pressing CLOSE button. In case of remote operation,
the closing coil unlatches the closing spring. As the closing spring is under discharge process, the crankshaft
is turned and the cam disc at the other end of the crankshaft actuates the drive lever with the result that the
mechanism shaft is turned by a lever by the coupling rod. At the same time the levers, fixed on the breaker
shaft operate three insulated couplers and move the bottom contact of breaker poles up. Lever charges the
tripping spring during closing and the breaker is latched in the closed position with pawl roller and by
closing latch.
Opening operation
SALIENT FEATURES
Confirms to IEC62271-100.
Vacuum interrupter and insulating pull rod assembled in an envelope of dry pressurized air to
prevent surface tracking.
Easy to install.
Highly reliable.
Additional structure for mounting CTs/PTs can be provided along with outdoor CTs and PTs.
Outdoor Relay cabinet housing Relays, meters etc. for control of breaker can be provided.
APPLICATIONS
1. Power station and process industry auxilliaries.
2. Distribution duty (width 550 mm).
POLE ASSEMBLY
STORAGE
No. Of poles -3
Class- outdoor
Rated frequency – 50 Hz
ELECTRICAL CHECKS
OPERATING MECHANISM
Charging of closing spring is indep of closing or opening of breaker can be operated
manually or by motor
Closed breaker with charged closing spring can perform auto-reclose duty i.e. -close-open
can be done without any intermediate manual or motor charging. Breaker On-Off indicator
and spring charging/discharging indicator
Components-
1. Gearbox
2. Closing spring
3. Spring charged indicator
4. On-Off indicator
5. Tripping spring
6. Motor cut-off limit switch
7. Mech shaft
8. Dash pot
9. Manual push button (closing)
10. Operating coil (closing)
11. Operating coil (opening)
12. Manual push button
13. Motor
14. Motor
15. Tripping catch
16. Closing catch
17. Crankshaft
18. Comuter coil
Operating mechanism
- Switching operations
- By motor
- Manual operation
Manual charging
Insert the hand crank and turn it clockwise until the indication shows “spring charged”.
1. Closing operation
2. After closing of spring -> breaker ready to get closed -> spring is released by pressing closed button
-> the crankshaft is turned -> disc at its other end actuates the driver lever -> at the same time, via
drive rod. -> Movement is transferred to interphase shaft -> moves 3 insulated rods -> closing of
breaker
Opening operation
If breaker is to be tripped locally, the spring is released by pressing the open button -> the tripping
solenoid unlatches the tripping spring -> the tripping spring turns the mechanical shaft -> the
sequence is similar but motion is reversed to that of closing.
Hold the handle -> press it downwards until contacts touch -> pressure is higher as it compresses the spring
until the trip panel catches with trip lever roller and the mech is latched in closed position.
MAINTAINENCE
Interval at which maintainence is done depends upon:
1. No. Of short circuit interruptions
2. Switching frequency
3. Actual service time
INTRODUCTION
Control and relay panels (CRP’s) include
1. GRP
Used in power plants.
Depends on the amount of power being produced and amount of protection needed.
They have relays in them.
Receives voltage and current signals.
Using algorithms, identifies the fault and operates accordingly.
It has 2 relays :
a) Protection relays
- Numerical variety
b) Auxiliary relays
- Electromechanical relays
- Help the main protection relays
- By multiplying the contacts and sending tripping signal.
1. Relay panel
- Protects from important faults
- In case of line circuits also tells the distance of the fault (distance protection)
- If transformer ratio is not maintained in transformer circuit, differential fault is observed and
protection relays are used.
2. Control panel
Contains instruments to measure current, voltage, power etc., signals (both audio and visual),
LEDs, lamps, alarm initiators etc.
PRODUCT RANGE:
Generator protection is a complex and elaborate task due to the following reasons:
a) Generator is a large machine with associated components like transformers and other
auxiliary equipment.
b) Generator consists of subsystems like excitation system, prime mover, voltage regulator,
governor, cooling system, etc.
c) Generator is a costly and important equipment. As far as possible, it should be in service. The
protection system should provide sufficient advance information so that the corrective action
can be initiated well in advance.
d) Generator should not be tripped for the faults which are external to the generator and which
external equipment can clear
SCR is in the field of design, manufacture and supply of Control and Protection Panels for 33kV
to 400kV Switchyard. These cover the following main circuits:
a) Transmission Lines.
b) Generator Transformers.
c) Inter Connecting Transformers.
d) Feeder Transformers.
e) Reactors.
f) Tie / Transfer Bus Coupler.
g) Bus Coupler.
h) Bus bars.
Switchyard Control & Protection Panels are designed for all types of Bus Configurations which
include the following:
Manufacturing set up should be equipped with all modern facilities necessary for
manufacturing of C/R Panels:
Latest CNC Turret Punch and Bending Machines for fabrication of Panels.
Full fledged Chemical pre treatment process line and Powder Coating Plant.
Dust Free enclosure for assembly and wiring of Control Panels.
Latest CMC256 Automatic Relay Test kits of Omicron make.
1) The standard Sheet steel cubicle is 2230 mm (height) & 800 mm (depth) resting on 50 mm high
plinth & 15mm thick anti-vibration pad. The width of the panels is suitable to accommodate all the
fitments. The fitments are comfortably mounted to provide easy accessibility for maintenance. No
relays or fitments are mounted below 300 mm level. Hand reset type tripping relays and main
protection relays requiring programming are mounted at normal reach.
5) Terminal blocks are clip-on to channel, screw driver operated stud type. Disconnecting type
(CATDM4 of Elmex or equivalent make) for CT & PT circuits and non-disconnecting type
(CATM3 of Elmex or Equivalent make) for rest of the circuits.
6) Panel wiring: PVC insulated, 1100V grade FRLS & stranded copper conductor wire (ISI
mark) with conductor cross section as under:
7) Color of wires:-
Earth : Green
A phase: Red
B phase: Yellow
C phase: Blue
Neutral: Black
8) For identification of wires, numbered ferrules with black letter / digit over white surface at
both ends of wire are provided.
9) At least 20% spare terminal blocks are provided on each terminal strip.
11) All internal wiring to be connected to external equipment are terminated on vertically
mounted terminal blocks on each side of the cubicle.
12) Cable gland plate: Cable entry is from bottom. Un drilled cable gland plate with proper
gasket is provided. Cable gland plate is earthed (connected to earth bar) using copper braided
flexible cable. Thickness of gland plate is 3 mm.
13) Lifting Arrangement: Lifting eye bolts are provided at the 4 top corners of cubicle. Suitable
plugs are provided for blanking eye bolts after erection.
14) Panel Lock: Concealed handle with built-in lock & shooting bolts with 3 point latching at
top, middle & bottom.
15) Suitable stiffeners are provided at the back of front panel to avoid buckling & waviness after
cutouts are made and fitments are mounted.
16) Door: Lift off type doors are provided in the panel. Doors are provided with ventilating
louvers having fine suitable washable filter for dust proofing. EPDM rubber gasket & door
pocket is provided. Each door of cubicle is connected to earth bar using flexible copper braided
cable.
17) All ferrous components like internal mounting plates, C channels, fuse panels, brackets etc.
are painted, same as interior finish, to prevent any kind of rusting or corrosion.
18) Earth Bar : 3 mm * 25 mm cross section tin plated copper bar is provided at the bottom of
the panel across the width and one depth of the cubicle.
1 No. Door switch operated CFL 18W rated for 240V, 50Hz.
1 No. 5 pin, 240V, 50Hz AC socket with switch suitable for 5/15A
1 No. thermostatically controlled space heater of suitable wattage and rated for 240V AC,50Hz.
Versatility:
Three-pole design for neutral application at 350A, 500A and 600A ratings for three-phase wye-
connected windings.
Three-pole fully insulated design, at 350A, 500A and 600A ratings for the three-phase delta or auto
connected windings.
Single-pole designs at 350A, 500A, 600A, 800A, 1200A, 1500A and 1800A ratings for auto
connected windings or single-phase transformers.
Available with ±9, ±11, ±13, ±15, ±17 steps.
Insulation to ground and tap selector size can be selected independently of one another.
Convenient for bell-type tank installation.
Additional devices for potential tie-in of tap winding during change-over operation of the change-
over selector (tie-in resistors, tie-in contact).
Compactness:
High speed transition resistor type diverter switch with arc extension at the first current zero.
Diverter switch uses snap-action mechanics by energy accumulator mounted directly on the diverter
switch.
Minimum possible tap selector dimensions because four available sizes ensure matched impulse
voltage with standability.
Radial dimensions of the tap selector are reduced by special shaping of all parts of parts on high
potential distances between tap selector bars determined by actual voltage stress.
Robustness-long life:
Rapid tap change operation, low thermal stress on the transition resistors.
Diverter switch arcing contacts made of tungsten-copper alloy at 500A and above.
Simple tap selector design, effective contact cooling, high short-circuit withstandability.
Tap selector gear with steady torque during the tap changer operation.
Oil immersed installation of the entire tap changer in the transformer main tank.
Simple to connect.
Drive shaft and pipe connections easy to orientate.
Straight forward coupling to motor drive unit
Reduced maintenance:
This unit comprises of the spring operated energy accumulator, the diverter switch itself and the transition
resistors. For inspection, the unit has to be withdrawn from the oil compartment through the head.
The tap selector comprises of the gearing, the column with take-off rings, the insulating bar cage with
connecting terminals, the contact bridges with corresponding drive tubes and segments, and the upper and
lower cage rings. The tap selector may also include a change-over selector.
Type V
Type M
BHEL Bhopal is a vast service centre. The headquarters of the services of BHEL is in Bhopal. It was a great
experience for me to interact with the engineers and learn about the working of such a huge organisation of
the stature of BHEL. The Switchgear department is one of the largest of its kind in India today. This is the
only place in India to manufacture Gas Insulated Switch Gear with a clean room facility. BHEL Bhopal
houses Asia’s largest Ultra High Voltage Lab ( UHV Lab ) operating at voltages as high as 3 million
volts !!!!