Beruflich Dokumente
Kultur Dokumente
Abstract: The effect of axial force on the flexural strength of steel members, not connections, has been extensively researched for nonseismic
loading conditions. To address the latter for seismic applications, four nominally identical beam-column subassemblies with a welded
unreinforced flange-welded web (WUF-W) moment connection were cyclically tested. The specimen design included built-up I-shape beams
(db ¼ 1,118 mm) and built-up I-shape columns (dc ¼ 1,219 mm). Because the member sizes and weights significantly exceeded those permitted
by current standards for use as a prequalified WUF-W connection, all except one specimen had flared beam flanges with the goal of protecting the
beam flange complete-joint-penetration CJP groove welds. A constant axial tension force in the beam (16% of nominal beam yield strength) was
applied to three specimens, whereas one flared specimen did not have axial tension. When tension was present, testing showed that beam local
buckling drastically diminished. A higher flexural strength was developed in the plastic hinge, indicating that the Cpr value in current standards for
capacity design is nonconservative when tension is present. Fracture in the beam web instead of flange CJP welds dominated the failure mode
because of a change in the load transfer mechanism. More stringent beam web welding requirements than those specified in current standards were
shown to improve connection performance. DOI: 10.1061/(ASCE)ST.1943-541X.0001833. © 2017 American Society of Civil Engineers.
Author keywords: Connections; Cyclic tests; Seismic design; Steel; Metal and composite structures.
Introduction (CJP) groove welds. The beam web is first bolted to a shear plate
for erection purposes. The beam web is then attached to the column
Based on the observed failure after the Northridge, California, flange using a CJP weld between weld access holes. The shear plate
earthquake in 1994, a number of field-welded steel moment con- serves as a backing bar for this CJP weld between the beam web
nections such as the reduced beam section (RBS) and connections and the column flange. A special weld access hole (Ricles et al.
with beam flange reinforcements for applications in special mo- 2002; AWS 2009) that is longer than that commonly used in pre-
ment frames (SMFs) have been developed by the SAC Joint Venture Northridge connections and has a special profile is required, where
(FEMA 2000) and adopted into AISC 358 (AISC 2010a). The in- the shear plate is fillet-welded to the column flange and the beam
tent of most of these connections is to move the plastic hinge lo- web. Two beam sizes (W36 × 150 and W24 × 94) were tested.
cation in the beam away from the face of the column, but this is not Therefore, AISC 358 permits the WUF-W connection to be used
the case for the welded unreinforced flange-welded web (WUF-W) for beam sizes up to W36 × 150 and column sizes no deeper than
connection. Although the configuration of this connection is similar 914 mm (or 610 mm for built-up columns). A statistical analysis
to that of the welded flange-bolted web pre-Northridge connection, (Roeder 2000) of the tested WUF-W moment connections sug-
the former uses several design and detailing features to prevent con- gested an expected plastic rotational capacity of 0.041 rad, and this
nection fractures. This is achieved through special detailing require- suggestion is reflected in ASCE 41 (ASCE 2013).
ments associated with the welds joining the beam flanges to the The WUF-W moment connection was chosen for the construction
column flange, the welds joining the beam web to the column of the Transbay Transit Center in downtown San Francisco. The
flange, and the shape and finish of the weld access holes. structural design called for very large sizes of built-up I-shape beams
The WUF-W connection was mainly developed based on two (depth ¼ 1,118 mm) and columns (depth ¼ 1,016 mm), which
research projects (Ricles et al. 2002; Lee et al. 2005a, b). Fig. 1 significantly exceeded the section dimensions and weight limitations
shows the details of a typical WUF-W connection (AISC 2010a), permitted by AISC 358. Furthermore, the unique configuration of the
which is an all-welded connection in that both beam flanges and frame layout created tension in the beams due to gravity loads. In
web are welded directly to the column flange. The beam flanges support of the design and construction for this project, a full-scale
are connected to the column flange using complete-joint-penetration moment connection test program was conducted. The objective
was to (1) evaluate if the WUF-W connection, with some modifica-
1
Assistant Professor, Dept. of Civil and Environmental Engineering, In- tions if needed, could be used for the much larger beam and column
cheon National Univ., Incheon 22012, South Korea. E-mail: hbsim@inu.ac.kr sizes, and more significantly (2) evaluate the effects of beam tension
2
Senior Project Engineer, Thornton Tomasetti, San Francisco, CA on connection performance.
90017. E-mail: GBallantyne@ThorntonTomasetti.com
3
Associate Principal, Thornton Tomasetti, Los Angeles, CA 90017.
E-mail: AChen@ThorntonTomasetti.com
4
Professor, Dept. of Structural Engineering, Univ. of California, San Test Program
Diego, La Jolla, CA 92093 (corresponding author). E-mail: cmu@ucsd.edu
Note. This manuscript was submitted on June 22, 2015; approved on Test Matrix
February 28, 2017; published online on May 31, 2017. Discussion period
open until October 31, 2017; separate discussions must be submitted for Four full-scale moment connection specimens with the same beam
individual papers. This paper is part of the Journal of Structural Engineer- and column sizes were cyclically tested. Table 1 shows the test ma-
ing, © ASCE, ISSN 0733-9445. trix. Specimen 1 served as the reference specimen, in which no
BACK 25
BEAM WEB
GOUGE 8 .
Table 2. Member Cross Section Dimensions TO COLUMN
DEMAND
Depth Web thickness Flange width Flange CRITICAL 51
Member (mm) (mm) (mm) thickness (mm)
OVERLAP
Beam 1,118 25 610 51
6
Column 1,016 76a 762 51 CONTINUITY
a PLATE
Reduces to 25 mm in Zone A (Fig. 2).
19
30°
16 TYP IN
16 ZONE A 28
610
762
SHEAR TAB
.
22 TO COLUMN
SPECIMEN 2
TAPER WEB PLATE
(a)
R610
@ TRANSITION 152
51 mm CONTINUITY PL
FLANGE 762x51
REMOVE THE (N) RUNOFF TAB &
WEB 914x25
GRIND OFF WELD & SHEAR TAB
TYP
C C
OVERLAP
1118
16
6
CJP
16
127
BUILT UP BEAM
19
30°
(b)
Fig. 3. Beam web CJP details: (a) Specimens 1, 2, and 3; (b) Specimen
Fig. 2. Specimen configuration (unit: millimeter) 4 (unit: millimeter)
2340
AM
BEA
BEAM
M ACING
BRA
BRAC
CING
630
Downloaded from ascelibrary.org by University of California, San Diego on 06/04/17. Copyright ASCE. For personal use only; all rights reserved.
7665
RETE BLOCK
CONCR
STRONGG
FLOOR
478
80
(a)
(b)
Test Results
PLAN
20 1.5 20 1.5
1.0 0.8 Mpn 1.0
(x1000 kN-m)
(x1000 kN-m)
10 10
0.5 0.5
M/Mpn
M/Mpn
0 0.0 0 0.0
-0.5 -0.5
-10 -10
-1.0 -1.0
-20 -1.5 -20 -1.5
-8 -6 -4 -2 0 2 4 6 8 -8 -6 -4 -2 0 2 4 6 8
Story Drift Ratio (%) Story Drift Ratio (%)
(a) (b)
Moment at Column Face
20 1.5 20 1.5
1.0 1.0
(x1000 kN-m)
(x1000 kN-m)
10 10
0.5 0.5
M/Mpn
M/Mpn
0 0.0 0 0.0
-0.5 -0.5
-10 -10
-1.0 -1.0
-20 -1.5 -20 -1.5
-8 -6 -4 -2 0 2 4 6 8 -8 -6 -4 -2 0 2 4 6 8
Story Drift Ratio (%) Story Drift Ratio (%)
(c) (d)
Fig. 6. Comparison of global response: (a) Specimen 1; (b) Specimen 2; (c) Specimen 3; (d) Specimen 4
20 web CJP weld were critical. Although not required by AISC 358,
the weld procedure of Specimen 4 was modified as shown in
(MN-m)
15 Fig. 3(b). Weld runoff tabs were used at both ends of the beam
web CJP weld, and after welding, the runoff tabs were removed.
10
The shear plate as well as the beam web weld at both the top
5 and bottom ends were ground flush to the weld access hole (Sim
and Uang 2012). With this modification, the initiation of the beam
0
1 2 3 4 web weld cracks was delayed, and cyclic performance improved.
(b) Specimen No. Testing was stopped after completing two cycles at 6% drift. A small
crack was observed in the top flange weld access hole. It was specu-
Fig. 7. Comparison of cyclic performance: (a) interstory drift angle; lated that the same fracture mode as in Specimen 3 might have oc-
(b) dissipated energy curred if the testing were to continue to a higher drift level.
Fracture Area
(a) (b)
Fracture Area
Fracture Area
(c) (d)
Fig. 8. Comparison of failure mode (tension struts removed for specimens with beam tension): (a) Specimen 1; (b) Specimen 2; (c) Specimen 3;
(d) Specimen 4
-2
(a) -4
Downloaded from ascelibrary.org by University of California, San Diego on 06/04/17. Copyright ASCE. For personal use only; all rights reserved.
-2
-4
4
Applied Load (MN)
2
Top Flange Bottom Flange
(c) 0
-4
Fig. 12. Beam cyclic strain hardening ratio up to 6% story drift ratio (Fig. 6) because the lengthening effect mi-
tigated local buckling. Therefore, it is prudent to use a higher Cpr
ratio when beam tension is present.
Kusuda and Thurlimann (1958) developed lower-bound solu-
tions for the reduced plastic moment due to the combined action Weld Fracture Mode
of shear and axial load. Under monotonic loading, testing of three Although the effect of axial force or shear on the flexural strength
W10 × 29 specimens, in which the reduced plastic moment deter- of a member has been extensively researched, research on its cyclic
mined from testing was defined as that when the measured response effect on the member end connection is very limited. This test pro-
started to deviate significantly from the elastic response, showed a gram showed that the presence of a small-to-moderate amount of
good correlation; however, the actual strengths were significantly axial tension in the beam changed not only the buckling mode but
higher than the reduced plastic moments thus defined. Although also the weld fracture pattern, which indicates that the force transfer
this definition is conservative if the objective is to determine the mechanism was also altered.
design strength, it is not conservative from the capacity design Beam webs were instrumented with strain gauges along the
point of view. beam depth. Fig. 13 shows the flexural strain profiles of Section 1
(in Specimen 1) and Section 2 (in Specimen 4) near the column
face. For Specimen 1, the entire section was plastified, with the
Normalized Strain outer fibers experiencing larger strains. The more uniform flexural
-15 -10 -5 0 5 10 15 strain profiles along the beam depth of Specimen 4 indicate that a
600
higher proportion of the beam tension was transmitted to the col-
-1% Drift umn through the beam web; this is consistent with the more uni-
400 -2% Drift
form and longer flaking region of the whitewash in the web shown
-3% Drift
Beam Depth (mm)
200 -4% Drift in Fig. 8(d). When the beam remained in the elastic region, it was
expected that the beam tension would be distributed to the beam
0 flanges and web based on their relative axial stiffnesses (EAi ).
Section 1 As the beam flanges near the column started to yield because of
460 mm flexure, the Young modulus (E) reduced significantly, and therefore
-200 Beam Depth
(+) a larger share of the beam tension was redirected to the beam web.
-400 At the column face, the combined effect of beam flexural yielding
-600
-0.03 -0.02 -0.01 0.0 0.01 0.02 0.03 0.06
(a) 30
Strain (mm/mm)
Normalized Strain 0.04
-15 -10 -5 0 5 10 15 20
600
-1% Drift
Normalized Strain
0.02 10
Strain (mm/mm)
0 76 mm
Section 2 -0.02 -10
560 mm
-200 Specimen 2
Beam Depth
(+) Specimen 3
-0.04 -20
-400 Specimen 4 Location of Strain
Measurement
-600 -0.06 -30
-0.03 -0.02 -0.01 0.0 0.01 0.02 0.03 -4 -3 -2 -1 0 1 2 3 4
(b) Strain (mm/mm) Story Drift Ratio (%)
Fig. 13. Strain profiles along beam depth of flared specimens: (a) at Fig. 14. Effect of beam flange flare on beam top flange strains
Section 1 of Specimen 1; (b) at Section 2 of Specimen 4 (tensioned specimens)
when axial tension was present. That is, flaring the beam flanges study also showed that beam tension, when present, can signif-
appears to play a secondary role in the observed performance of the icantly affect moment connection performance, a factor that is
connections. ignored in AISC 358.
Conclusions
Acknowledgments
Four full-scale steel beam-column subassemblies with WUF-W
moment connections were tested. Beam and column sizes signifi- Funding for this project was provided by the Transbay Joint Power
cantly exceeded those permitted by AISC 358 for use as a WUF-W Authority (TJPA).
connection. All except one specimen had flared beam flanges.
A constant axial tension force in the beam (16% of nominal beam
yield strength) was applied to three specimens. Based on the test References
results, the following conclusions can be made:
AISC. (2010a). “Prequalified connections for special and intermediate steel
1. The presence of beam tension significantly altered the local
moment frames for seismic applications.” AISC 358-10, Chicago.
buckling mode of the beam in the plastic hinge region. Whereas AISC. (2010b). “Seismic provisions for structural steel buildings.” AISC
Specimen 1 without beam tension showed a typical local buck- 341-10, Chicago.
ling mode, such buckling diminished in the other three ten- ASCE. (2013). “Seismic rehabilitation of existing buildings.” ASCE/SEI
sioned specimens (Fig. 8). 41-13, Reston, VA.
2. Conventional plastic analysis theory predicts that the presence AWS (American Welding Society). (2009). “Structural welding code–
of an axial force would reduce the plastic moment capacity. For seismic supplement.” AWS D1.8/D1.8M, Miami.
the level of axial force applied, all four specimens were able to FEMA. (2000). “Recommended seismic design criteria for new steel
reach and exceed the unreduced plastic moment, computed moment-frame buildings.” FEMA 350, Washington, DC.
based on the actual yield stresses, owing to cyclic strain hard- Joint Committee of the Welding Research Council and ASCE. (1971).
“Plastic design in steel: a guide and commentary.” Manual of Practice
ening. Because the flexural strength of three tensioned speci-
No. 41, New York.
mens was not degraded by local buckling, the maximum Kasai, K., and Popov, E. P. (1986). “General behavior of WF steel shear
flexural strengths of the tensioned specimens were higher. link beams.” J. Struct. Eng., 10.1061/(ASCE)0733-9445(1986)112:
The measured Cpr value from Specimen 1 was consistent with 2(362), 362–382.
that specified in AISC 358 (1.4), whereas the measured Cpr va- Kusuda, T., and Thurlimann, B. (1958). “Strength of wide-flange beams
lues for the tensioned specimens were higher than 1.4 (Fig. 12). under combined influence of moment, shear, and axial force.” Rep.
It is prudent to use a higher Cpr value for capacity design when No. 248.1, Fritz Engineering Laboratory, Lehigh Univ., Bethlehem, PA.
beam tension is present. Lee, D., Cotton, S. C., Hajjar, J., Dexter, R. J., and Ye, Y. (2005a). “Cyclic
3. Conventional plastic analysis theory addresses the effects of ax- behavior of steel moment-resisting connections reinforced by alterna-
ial load on the strength of members, but not connections. With tive column stiffener details. I: Connection performance and continuity
plate detailing.” Eng. J., 42(4), 189–213.
no tension force applied, it is expected that the beam flange CJP
Lee, D., Cotton, S. C., Hajjar, J., Dexter, R. J., and Ye, Y. (2005b). “Cyclic
groove welded joints are more vulnerable to fracture than that of behavior of steel moment-resisting connections reinforced by alterna-
the beam web. Testing showed the opposite trend when beam tive column stiffener details. II: Panel zone behavior and doubler plate
tension was present (Fig. 8). In the elastic range, the beam ten- detailing.” Eng. J., 42(4), 215–238.
sion was distributed to the flanges and web based on their re- Ricles, J. M., Mao, C., Lu, L. W., and Fisher, J. W. (2002). “Inelastic cyclic
lative areas. Once flanges yielded because of flexure, a much testing of welded unreinforced moment connections.” J. Struct. Eng.,
higher percentage of the beam tension was transmitted to the 10.1061/(ASCE)0733-9445(2002)128:4(429), 429–440.
column through the beam web because it was stiffer. The com- Roeder, C. W. (2000). “State of the art report on connection performance.”
bined effect of beam flexural yielding and higher normal stres- FEMA Rep. No. 355D, Federal Emergency Management Agency,
ses from beam tension tended to overload and fracture the beam Washington, DC.
Sim, H. B., and Uang, C. M. (2012). “Cyclic testing of welded steel mo-
web CJP weld, especially at the top and bottom ends. Improved
ment connections in support of design for Transbay Transit Center in
welding requirements beyond that specified in AISC 358 for San Francisco.” Rep. No. TR-12/01, Dept. of Structural Engineering,
the beam web CJP weld, such as the use of weld runoff tabs and Univ. of California, San Diego.
grinding smooth at weld ends as implemented in Specimen 4, Tomás, J., Nseir, J., Camotim, D., and Boissonnade, N. (2013). “Stability,
were useful to enhance the cyclic performance of the failure and design of I-section steel beams subjected to tension.” Proc.,
connection. Annual Stability Conf., SSRC, St. Louis, MO, 669–695.