A. For attending the defect of Line-3 (Bhadravati – DIL Ckt.) panto isolator (4-1389B), first Main Bus-B
of CTU section needs to be completely dead. The steps which need to be followed are mentioned
below.
1. Line-4 Isolator-'B' (4-1289B) open
2. GT-2 Isolator-'B' (4-289B) open
3. ST-2 Isolator-'B' (4-189B) open
B. In next step for transferring of Line-3 on TBC bay for non-interruption of power flow, following steps
need to be followed which are mentioned below.
1. NIT switch of Line-3 in I (Intermediate) mode
2. Line-3 transfer isolator (4-1389T) close
Interlock Permissive for closing of Transfer Bus Isolator:-
C. After completion of the work normalization procedure needs to be followed. The steps are mentioned
below.
1. Line-3 AE earth switch (4-1389AE) open
2. Line-3 Line Isolator (4-1389L1) close
3. Line-3 Isolator-‘A’ (4-1389A) close
4. NIT switch of Line-3 bay in I (Intermediate) mode
5. Line-3 breaker (4-1352) close
Interlock Permissive for closing of circuit breaker in Intermediate mode:-
a)
4-1352 breaker selector switch in remote
b)
86X lockout relay of Line-3 bay not operate
c)
86Y lockout relay of Line-3 bay not operate
d)
86LO lock out relay of Line-3 bay not operate
e)
TC-1 of 4-1352 CB healthy
f)
TC-2 of 4-1352 CB healthy
g)
Bus zone protection relay (A/B) or Transfer zone protection relay (C) of
CTU section not operate
h) Check zone protection relay (CH) of CTU section not operate
i) 4-1389A Isolator or 4-1389B isolator close
j) 4-1489A Isolator or 4-1489B Isolator of TBC bay close
k) 4-1452 breaker of TBC close
l) NIT switch of Line-3 bay in I mode
6. TBC bay breaker (4-1452) open
7. TBC