PIPING LABELS PIPE FITTINGS PLUMBING SPECIALTIES ABBREVIATIONS

DOMESTIC COLD WATER


DOMESTIC HOT WATER SUPPLY FLANGE WATER HAMMER ARRESTER AD ACCESS DOOR G NATURAL GAS S SINK
AFF ABOVE FINISHED FLOOR GA GAUGE SAN SANITARY
(140) DOMESTIC HOT WATER SUPPLY - 140 F UNION FLEXIBLE PIPE CONNECTOR
AFS AUTOMATIC FIRE SPRINKLER GAL GALLON SD STORM DRAINAGE
DOMESTIC HOT WATER RETURN PIPING REDUCER EXPANSION JOINT ALT ALTERNATE GCO GRADE CLEANOUT SF SQUARE FEET
P SH
TEPID WATER (60 F TO 100 F) PIPE SLEEVE PRESSURE GAUGE AP ACCESS PANEL GPF GALLONS PER FLUSH SHOWER
TW
ASSY ASSEMBLY GPM GALLONS PER MINUTE SHT SHEET
NPW NON-POTABLE WATER PIPE ANCHOR
THERMOMETER GWH GAS WATER HEATER SPEC SPECIFICATION
G NATURAL GAS ELBOW INTO PAPER PLANE BG BELOW GRADE SQ SQUARE
AUTOMATIC AIR VENT
G2 NATURAL GAS - 2 PSI ELBOW OUT OF PAPER PLANE BHP BRAKE HORSEPOWER HB HOSE BIBB S/S STAINLESS STEEL
MANUAL AIR VENT BLDG BUILDING HD HUB DRAIN
PG PROPANE GAS TEE OUT OF PAPER PLANE
TEMPERATURE/PRESSURE TEST PORT BS BELOW SLAB HP HORSEPOWER TD TRENCH DRAIN
MV MEDICAL VACUUM TEE INTO PAPER PLANE HZ HERTZ TEMP TEMPERATURE
SENSOR WELL
MA MEDICAL AIR PIPE CAP OR PLUG BTUH BRITISH THERMAL UNITS PER HOUR TOB TOP OF BEAM
HOSE BIBB OR WALL HYDRANT ID INSIDE DIAMETER TOS TOP OF SLAB
O OXYGEN
C COMMON IE INVERT ELEVATION TP TRAP PRIMER
NO NITROUS OXIDE FLOW ARROW IN INCHES TTC TIGHT TO CEILING
POINT OF CONNECTION
WAGD WASTE ANESTHETIC GAS DISPOSAL BREAK IN LINE CAP CAPACITY IW INDIRECT WASTE TYP TYPICAL
PIPE TRAP CB CIRCUIT BREAKER OR CATCH BASIN
A COMPRESSED AIR
FLOOR DRAIN (SQ OR RND) CD CONDENSATE DRAIN KW KILOWATTS UR URINAL
VAC VACUUM CLG CEILING
ROOF OR OVERFLOW DRAIN
FIRE PROTECTION SUPPLY CO CLEANOUT L LENGTH V VENT OR VOLTS
F
PUMP, IN SCHEMATIC REPRESENTATION CONT CONTINUED, OR CONTINUATION LAV LAVATORY VAC VACUUM
RD REFRIGERANT DISCHARGE (HOT GAS) PIPING
CTE CONNECT TO EXISTING LBS POUNDS VIB VALVE IN BOX
WASTE OR SOIL CW COLD WATER VOL VOLUME
WASTE OR SOIL BELOW FLOOR MAX MAXIMUM VTR VENT THRU ROOF
D DRAIN MCA MINIMUM CIRCUIT AMPACITY
VENT
DCW DOMESTIC COLD WATER MEZZ MEZZANINE W WASTE OR WATER OR WATTS
SD STORM DEG DEGREE MFR MANUFACTURER W/ WITH
SD STORM BELOW FLOOR MH MANHOLE W/O WITHOUT
DHW DOMESTIC HOT WATER MIN MINIMUM OR MINUTE WC WATER CLOSET
OD OVERFLOW DRAIN VALVES DHR DOMESTIC HOT WATER RETURN MISC MISCELLANEOUS WCO WALL CLEANOUT
OD OVERFLOW DRAIN BELOW FLOOR DIM DIMENSION MS MOP SINK WH WALL HYDRANT
CD CONDENSATE DRAIN DN DOWN MTD MOUNTED
TWO WAY CONTROL VALVE DS DOWNSPOUT MV MEDICAL VACUUM YH YARD HYDRANT
PC PUMPED CONDENSATE
THREE WAY CONTROL VALVE DWG DRAWING
D EQUIPMENT DRAIN (N) NEW
BALL VALVE
MISCELLANEOUS PROCESS SUPPLY (E) EXISTING NC NORMALLY CLOSED
NAME
GATE VALVE OR GENERAL SHUT OFF VALVE EA EACH NIC NOT IN CONTRACT
(E) NAME EXISTING PIPING
GLOBE VALVE EFF EFFICIENCY NO NORMALLY OPEN, OR NUMBER
(R) NAME EXISTING PIPING TO BE REMOVED ELEV ELEVATION NPT NATIONAL PIPE SIZE
BUTTERFLY VALVE
(R) NAME EXISTING PIPING TO BE REMOVED EQUIP EQUIPMENT NPW NONPOTABLE WATER
NEEDLE VALVE ES EMERGENCY SHOWER NTS NOT TO SCALE
1-1/4" PIPE PIPE WITH SIZE CALLOUT
GAS COCK ET EXPANSION TANK
EWC ELECTRIC WATER COOLER O OXYGEN
CHECK VALVE
EXP EXPANSION OD OUTSIDE DIAMETER, OR OVERFLOW DRAIN
S
SOLENOID VALVE EXT EXTERIOR OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
PRESSURE REDUCING VALVE OFOI OWNER FURNISHED, OWNER INSTALLED
F FAHRENHEIT

GENERAL SYMBOLS RELIEF(R), OR SAFETY(S) VALVE FCO


FD
FLOOR CLEANOUT
FLOOR DRAIN
P
PH
PUMP
PHASE
BALANCING VALVE
FDC FIRE DEPARTMENT CONNECTION PIV POST INDICATOR VALVE
AT STRAINER, STRAINER W/BLOWOFF FF FINISH FLOOR POC POINT OF CONNECTION
FLA FULL LOAD AMPS PRV PRESSURE REDUCING VALVE
DIAMETER TEMPERING VALVE FLR FLOOR PSIG POUNDS PER SQUARE INCH GAUGE
HOSE END DRAIN VALVE FPM FEET PER MINUTE
INCHES
FT FEET (R) REMOVE, DEMOLISH
AND VALVE IN RISER RD ROOF DRAIN
(RL) RELOCATE, TO BE RELOCATED
X DEGREES (ANGLE) RM ROOM
KEYED NOTE DESIGNATION RP REDUCED PRESSURE BACKFLOW PREVENTER
RPM REVOLUTIONS PER MINUTE
RWL RAINWATER LEADER
3 OWNER'S EQUIPMENT NUMBER

10
DETAIL OR DETAIL REFERENCE

10 ELEVATION

6 SECTION TAKEN AT

EQUIPMENT TAG

SANITARY DRAINAGE CALCULATION PIPING GENERAL NOTES PIPING INSULATION NOTES


1. COORDINATE PIPING ROUTING WITH WORK OF OTHER TRADES.
FIXTURE EXTENDED ROOM 1. COVER EDGES OF EXPOSED INSULATION WITH FITTING COVERS AND
TRAP ARM
LOCATION QUANTITY DESCRIPTION DRAIN SIZE OCCUPANCY UNITS PER FIXTURE TOTAL ADHESIVE, OR LAGGING COMPOUND. SEAL BUTT JOINTS WITH ADHESIVE.
SIZE 2. PIPING SIZES SHOWN ARE NOMINAL IRON PIPE SIZE (INTERIOR) OR NOMINAL TUBING SIZE FOR
FIXTURE UNITS F.U.
COPPER PIPING.
2. WHERE COLD PIPING IS INSULATED PROVIDE CONTINUOUS VAPOR BARRIER
2 SINK 1-1/2 2 PUBLIC 2 4 -
3. USE FULL 20-FOOT LENGTHS OF PIPING AND TUBING WHERE POSSIBLE. SEALED AT ALL JOINTS. PROVIDE VALVE STEM EXTENSIONS, RIGID INSULATION
BREAK ROOM 117 1 DISHWASHER (FUTURE) 1-1/2 2 PUBLIC 2 2 - INSERTS AT SUPPORTS, AND INSULATION SIZE REDUCERS AND JACKETS AS
ROOM TOTAL 6.0 4. USE SPECIFIED FITTINGS FOR CHANGE IN DIRECTION. BENDING OF PIPING AND TUBING IS NOT NEEDED TO PROVIDE CONTINUOUS VAPOR BARRIER. SEAL JACKET JOINTS
ACCEPTABLE. SADDLE TAPS, PULLED TEES, AND FIELD-FABRICATED FITTINGS ARE NOT WITH SILICONE CAULK.
1 SINK 1-1/2 2 PUBLIC 2 2 -
SICK ROOM 117A ACCEPTABLE EXCEPT WHERE SPECIFIED OR SHOWN.
ROOM TOTAL 2.0 3. INSULATION IN CEILING RETURN PLENUMS SHALL HAVE FLAME SPREAD AND
1 SINK 1-1/2 2 PUBLIC 2 2 - 5. REAM CUT PIPE ENDS TO IPS SIZE AND EXPAND TUBING ENDS TO TUBING INSIDE DIAMETER. SMOKE DEVELOPED RATINGS PER CODE.
MOTHER'S 117B
ROOM TOTAL 2.0
6. INSTALL PIPING CONCEALED AND PARALLEL TO BUILDING STRUCTURE EXCEPT WHERE SHOWN. 4. EXISTING PLUMBING PIPING IS NOT INSULATED. WHERE EXISTING PIPING IS TO
DEMO 1 ISLAND SINK 1-1/2 2 PUBLIC -2 -2 -2.0 REMAIN, INSULATE PER CODE AND AS SPECIFIED.
EXISTING 1 ALL VARIES VARIES VARIES VARIES VARIES 180.0 7. INSTALL RISERS PLUMB.

8. INSTALL HORIZONTAL PIPING SLOPED TO DRAIN. FOR HORIZONTAL DOMESTIC WATER PIPING
NOTES: 1. INTERMITTENT FLOW <7-1/2 GPM
PROVIDE CAPPED BALL VALVE AT EACH LOW POINT AND HIGH POINT.
2. <1.6 GPF
3. <1.0 GPF 9. INSTALL PIPING AND SUPPORTS ARRANGED TO ALLOW FOR EXPANSION AND CONTRACTION
USING OFFSETS, SLIDING SUPPORTS, AND SWING JOINTS. PROVIDE INSERTS AT STUD
4. >1.6 GPF
PENETRATIONS TO PREVENT NOISE DUE TO THERMAL EXPANSION.

TOTAL FIXTURE UNITS 188.0 10. USE REPLACEABLE REDUCERS. CLOSE NIPPLES AND BUSHINGS ARE NOT ACCEPTABLE.

11. FOR IPS PIPING WITH SCREWED JOINTS WITH NPT (TAPERED) THREADS COORDINATE THREAD
MINIMUM WASTE PIPE SIZE IF IN ONE BUILDING DRAIN 4" CUTTING LENGTH/DEPTH WITH PIPE SIZE SO LESS THAN 2 PERCENT OF THREADS ARE EXPOSED
AFTER INSTALLATION.
sancalc 05/12/16
12. WHERE PIPING PENETRATES BUILDING FRAMING DO NOT EXCEED CODE-ALLOWED HOLE SIZES.

13. PIPING SHALL PENETRATE STRUCTURAL MEMBERS INCLUDING STEEL BEAMS, GLULAM BEAMS,
AND SOLID-WEB TRUSSES ONLY WHERE APPROVED BY STRUCTURAL ENGINEER OF RECORD.

14. PIPING INSTALLATION SHALL COMPLY WITH ASME AND IAPMO INSTALLATION STANDARDS.
PLUMBING CONNECTIONS 15. PIPING SIZES AT FIXTURES, VALVES, AND PIPING ACCESSORIES TO MATCH CONNECTION SIZE.
PROVIDE REDUCERS OR INCREASERS IN PIPING TO CHANGE TO RUN-OF-PIPE SIZE SHOWN.
SYMBOL FIXTURE W V CW HW DESIGN BASIS / REMARKS
16. COORDINATE LOCATIONS OF SHUTOFF VALVES MOUNTED ABOVE ACCESSIBLE CEILINGS AND
(120)
ACCESS DOORS WITH CEILING-MOUNTED APPURTENANCES INCLUDING THOSE SHOWN ON
ARCHITECTURAL REFLECTED CEILING PLANS.
COUNTERTOP MOUNT STAINLESS STEEL SINGLE COMPARTMENT SINK, MIN. 20
S1 HAND WASH SINK 2" 1-1/2" 3/4" 3/4" GAUGE, ADA ACCESSIBLE, MIXING FAUCET WITH GOOSENECK SPOUT, 17. PROVIDE UNIONS OR FLANGES AT PIPING CONNECTIONS TO EQUIPMENT TO ALLOW
AERATOR, AND WRISTBLADE HANDLES. DISASSEMBLY FOR MAINTENANCE. ARRANGE PIPING TO ALLOW PULL SPACE FOR EQUIPMENT
REMOVAL.

18. PIPE ROUTING TO COORDINATE WITH OTHER TRADES AND IS DIAGRAMMATIC IN NATURE AND IS
NOT INTENDED TO SHOW EVERY OFFSET REQUIRED TO MAKE FINAL CONNECTION TO
plumconn 05/17/16 EQUIPMENT. CONTRACTOR SHALL PROVIDE FITTINGS AND OFFSETS AND DETERMINE THE EXACT REVISIONS:
ROUTE OF PIPING TO MAKE THE SIMPLEST AND MOST EFFICIENT POSSIBLE PIPING SYSTEM.

19. PROVIDE DIELECTRIC NIPPLES OR RED BRASS VALVES AT CONNECTIONS OF DISSIMILAR PIPE
MATERIALS.

20. SEE EQUIPMENT SCHEDULES FOR SIZE OF BRANCH PIPING TO INDIVIDUAL FIXTURES.
DOMESTIC WATER SERVICE 21. REFER TO ARCHITECTURAL DETAILS FOR FLASHING OF ROOF-MOUNTED PLUMBING DEVICES

CALCULATION INCLUDING ROOF DRAINS, SANITARY VENTS, AND HOSE BIBBS.

22. PROVIDE ESCUTCHEONS FOR EXPOSED PIPING PENETRATIONS INTO FINISHED ROOMS.
PUBLIC (.75)
NUMBER DESCRIPTION GENERAL TOTAL HOT 23. PROVIDE AIRTIGHT SEAL AROUND PENETRATIONS INTO AIR PLENUMS. PROJECT NO: 15-083
USE UNITS WATER ISSUE DATE: 05-12-2016
24. FOR PIPING INSTALLED ADJACENT TO ELECTRICAL CABLE TRAYS ALLOW MINIMUM ACCESS OF
DOMESTIC DEMAND 12" ABOVE AND 18" TO THE SIDE OF CABLE TRAYS. ACCESS OCCURS EVERY 6 FT. DRAFT DATE: 05-10-16
3 HANDWASH SINK 1.50 4.50 3.38
25. PROVIDE ACCESS DOORS AT PLUMBING ITEMS LOCATED BEHIND WALLS AND REQUIRING DRAWN BY: GB
1 DEMO - ISLAND SINK -1.50 -1.50 -1.13 ADJUSTMENT, REPAIR, OR REPLACEMENT INCLUDING TRAP PRIMERS AND WATER HAMMER CHECKED BY: XX
ARRESTERS.
1 DISHWASHER - FUTURE 1.50 1.50 1.13
1 EXISTING 264.00 264.00 40.00 26. CONTRACTOR SHALL COORDINATE WITH DIVISION 26 AND PROVIDE PIPING AND OFFSETS AS REVISED: -
1 BUILDING ALLOWANCE FOR FUTURE 80.00 80.00 10.00
NEEDED TO MAINTAIN CODE-REQUIRED CLEARANCES AROUND ELECTRICAL PANELS. REVISION NO:
27. TEST PIPING BEFORE INSULATING, COVERING OR BACKFILLING. ISOLATE CONNECTED
EQUIPMENT. D/W/V PIPING FILL WITH WATER FOR STATIC HEAD TEST. MAINTAIN TEST
FIXTURE UNIT SUBTOTAL 348.50 53.38 P[RESSURE FOR 1 HOUR OR AS REQUIRED BY CODE. REPAIR ANY LEAKAGE AND RE-TEST.
FLOW IN GPM 106.99 16.39
28. FIRESTOP PIPING PENETRATIONS THROUGH PROTECTIVE ELEMENTS OF FIRE RATED
TOTAL CW GPM 123.38 ASSEMBLIES. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ASSEMBLIES. AT
EXISTING GPM 120.00 PENETRATIONS OF PIPING THROUGH NON-FIRE-RATED ASSEMBLIES PROVIDE FLEXIBLE
ACOUSTICAL CAULKING.
NET CHANGE (GPM) 3.38
PLUMBING
watercalc 05/12/16 LEGEND,
SYMBOLS &
NOTES

P001 92 95