I/A Series® System

Field Control
Processor 270
(FCP270)
User’s Guide

B0700AR

Rev H
November 30, 2011
Invensys, Foxboro, FoxCom, FoxView, Spec 200, SPECTRUM, I/A Series and the Invensys logo are
trademarks of Invensys plc, its subsidiaries, and affiliates.
All other brand names may be trademarks of their respective owners.

Copyright 2004-2011 Invensys Systems, Inc.


All rights reserved
Contents
Figures................................................................................................................................... vii

Tables..................................................................................................................................... ix

Preface.................................................................................................................................... xi
Who This Book Is For ............................................................................................................. xi
What You Should Know .......................................................................................................... xi
Revision Information ............................................................................................................... xi
Reference Documents ............................................................................................................. xii
Glossary of Terms .................................................................................................................. xiii

1. Introduction ...................................................................................................................... 1
Overview ................................................................................................................................... 1
Features ..................................................................................................................................... 2
Fault-Tolerance ......................................................................................................................... 3
Traditional Redundant Systems ............................................................................................ 4
FCP270 Fault-tolerant Operation ........................................................................................ 4
Self-Hosting and Non-Self-Hosting Modes ............................................................................... 4
Self-Hosting Feature, Available with 200 Series FBMs Only ................................................ 5
On-Line Image Update ............................................................................................................. 5
FCP270 Network Configuration .............................................................................................. 6
Network Path Switching ...................................................................................................... 6
Splitter/Combiner ................................................................................................................ 6
Fieldbus Expansion Module 100 (FEM100) ........................................................................ 8
I/O Communications ................................................................................................................ 8
Dual Baud Functionality ...................................................................................................... 9
Communication to 200 Series Fieldbus Modules ............................................................... 11
Communication to Y-Module (100 Series) Fieldbus Modules ............................................ 14
Communication to Migration Modules .............................................................................. 14
Time Synchronization ............................................................................................................. 14
Overview ............................................................................................................................ 14
Internal Source Time Synchronization .......................................................................... 15
External Source Time Synchronization .......................................................................... 15
FCP270 Sizing Constraints ..................................................................................................... 15
FCP270 Supported Block Processing Cycles ...................................................................... 15

iii
B0700AR – Rev H Contents

2. Installing the Field Control Processor 270 ...................................................................... 17


Overview ................................................................................................................................. 17
System Definition .............................................................................................................. 17
Installing a Single or Primary FCP270 Module ....................................................................... 18
Enabling the FCP270 Self-Hosting Option ........................................................................ 21
Initializing the FCP270 with Self-Hosting Enabled ....................................................... 21
Disabling Self-Hosting .................................................................................................. 21
Verifying Self-Hosting Information Using SMDH ........................................................ 22
Verifying Self-Hosting Information Using Station Block Display .................................. 22
Auto-Checkpoint While Enabling/Disabling Self-Hosting ............................................ 23
Installing a Shadow FCP270 Module ...................................................................................... 24
Cabling a Single (Non-Fault-Tolerant) FCP270 Module ........................................................ 25
Cabling a Fault-Tolerant FCP270 Module Pair ...................................................................... 25
Boot-Up Sequence .................................................................................................................. 29
Case 1 – Rebooting a Commissioned FCP270 ................................................................... 29
Case 2 – Connecting an FCP270 with the Same Letterbug ................................................ 30
Case 3 – Connecting an FCP270 with a New Letterbug .................................................... 30
Case 4 – Connecting a Shadow Module with Same Software Image ................................... 31
Case 5 – Connecting a Shadow Module with Different Software Image ............................. 32
Fault Tolerance Behavior in Self-Hosting FCP270 .................................................................. 33
Cabling Y-Module FBMs to an FCP270 Baseplate ................................................................. 34
Remote Fieldbus Extension, Cable Connections ................................................................ 35
Decommissioning an FCP270 Module ................................................................................... 41

3. Configuration Information.............................................................................................. 43
Overview ................................................................................................................................. 43
System Definition .............................................................................................................. 43
System Definition Procedure .............................................................................................. 43
System Configuration ............................................................................................................. 44
Available I/A Series System Control Blocks ........................................................................ 46
System Configuration with Dual Baud Functionality ......................................................... 47

4. System Management ....................................................................................................... 49


Overview ................................................................................................................................. 49
Operating Status ..................................................................................................................... 49
System Management Displays for the FCP270 ........................................................................ 49
Equipment Information Display for FCP270 ..................................................................... 50
Configuration Information Display for FCP270 ................................................................ 54
Equipment Change Display for FCP270 ............................................................................ 55
Reboot Station Procedure .............................................................................................. 58
Image Update Procedure for a Non-Fault-Tolerant FCP270 ......................................... 58
Image Update Procedure for a Fault-Tolerant FCP270 ................................................. 59
Messages Following Checkpoint Operation in Self-Hosting FCP270 ............................ 59

iv
Contents B0700AR – Rev H

Checkpoint Invalidation in Self-Hosting FCP270 ......................................................... 63


System Management Displays – Primary ECB (FBM0) .......................................................... 65
Equipment Information Display for Primary ECB (FBM0) ............................................... 65
Equipment Change Display for Primary ECB (FBM0) ...................................................... 69
Overview of Fieldbus Switching Mode .......................................................................... 71
Using the Fieldbus Switching Options .......................................................................... 71
Overview of the General Download ............................................................................... 71
Downloading all FBM Images ....................................................................................... 72
On-Line Diagnostics (PIO) Display for Primary ECB (FBM0) .......................................... 72

5. Troubleshooting.............................................................................................................. 75
Overview ................................................................................................................................. 75
LED Indicators, Reset Button, and Infrared Ports ................................................................... 75
Operational Status LED Indicators .................................................................................... 77
FCP270 Troubleshooting ....................................................................................................... 77
Using the Operational Status LEDs .................................................................................... 78
Red off, Green off .......................................................................................................... 78
Red on, Green off .......................................................................................................... 78
Red on, Green on .......................................................................................................... 79
Cycling Red, Red/Green ................................................................................................ 79
Red off, Green on .......................................................................................................... 79
Using the Ethernet Tx and Rx/Link Status LEDs ............................................................... 80
Using the Fieldbus Tx and RX Status LEDs ....................................................................... 80
Fault-Tolerant FCP270 Troubleshooting Addenda ............................................................ 80
Replacing a Failed Module ............................................................................................ 81
Available Memory Error Messages ...................................................................................... 81
Memory Dumps and Last Gasp Messages ............................................................................... 82
Last Gasp Messages ............................................................................................................ 82
Memory Dumps ................................................................................................................. 82
Diagnostics ............................................................................................................................. 84
Start-Up Diagnostics .......................................................................................................... 84
Error Recovery Local Diagnostics ....................................................................................... 84
Error Recovery Cooperative Diagnostics ............................................................................ 84

Appendix A. Upgrade Diagrams .......................................................................................... 85

Appendix B. FEM100 and FBI100 Connection Diagrams .................................................. 95

Index .................................................................................................................................... 99

v
B0700AR – Rev H Contents

vi
Figures
1-1. Typical FCP270 Network Configuration (Simplified) .................................................. 7
1-2. FBI200 Connections to 200 Series and 100 Series FBMs on Mixed 2 Mbps
and 268 Kbps HDLC Module Fieldbus (Conceptual) ................................................. 10
1-3. Example Network with FCP270 with Dual Baud Functionality (Conceptual) ............ 11
1-4. Fieldbus Cable Length Restrictions ............................................................................. 12
1-5. Fieldbus Cable Length Restrictions w/FCM2Fs .......................................................... 12
1-6. Expanded Fieldbus Cable Length Restrictions ............................................................. 13
1-7. Expanded Fieldbus Cable Length Restrictions w/FCM2Fs .......................................... 13
2-1. FCP270 Module Installation (Typical) ....................................................................... 18
2-2. Initializing a Self-Hosting Controller .......................................................................... 21
2-3. Self-Hosting Status via Station Block Display ............................................................. 23
2-4. Cabling the FCP270 Fault-tolerant Controllers (Two-Position Baseplate Example) .... 26
2-5. Cabling the FCP270 Fault-tolerant Controllers (Four-Position Baseplate Example) ... 27
2-6. Cabling Y-Module FBMs to an FCP270 Baseplate (Without FBI200s/FBI100s) ........ 36
2-7. TCA Cable Connection to 268 Kbps Fieldbus Splitter/Terminator
(Without FBI200s/FBI100s) ....................................................................................... 37
2-8. TCA Termination Block Assembly Mounting ............................................................. 37
2-9. TCA Termination Block Removal .............................................................................. 38
2-10. Remote Redundant Fieldbus Cabling (FCP270 End) ................................................. 39
2-11. Example of Extending Fieldbus in Two Directions from FCP270 ............................... 40
3-1. Typical Control Scheme Using an FCP270 and 200 Series FBMs ............................... 45
4-1. Equipment Information Display for FCP270 – Typical (1 of 2) ................................. 50
4-2. Equipment Information Display for FCP270 – Typical (2 of 2) ................................. 51
4-3. Configuration Information Display for FCP270 ......................................................... 55
4-4. Equipment Change Display for FCP270 ..................................................................... 56
4-5. REBOOT STATION Dialogue Box – Fault-Tolerant FCP270 .................................. 58
4-6. Equipment Information Display for Primary ECB (FBM0) – Typical (1 of 2) ............ 66
4-7. Equipment Information Display for Primary ECB (FBM0) – Typical (2 of 2) ............ 66
4-8. Equipment Change Display for Primary ECB (FBM0) ............................................... 69
4-9. On-line Diagnostics Display for Primary ECB (FBM0) .............................................. 73
5-1. FCP270 LED Indicators, Reset Button, and Infrared Port .......................................... 76
A-1. Equipment Replacement Order for CP60-to-FCP270 Conversions ............................ 86
A-2. Converting CP10/30/40 with Local I/O to FCP270s .................................................. 87
A-3. Converting CP60 with DCM10E to FCP270 ............................................................. 88
A-4. Converting CP60 with DCM10Ef to FCP270 ............................................................ 89
A-5. Converting CP60 with DCM10Ef with Fiber Optic Hub to FCP270 ........................ 90
A-6. Converting CP60 with FBI10E and 100 Series FBMs to FCP270s ............................. 91
A-7. Converting CP60 with 200 Series DIN Rail Mounted Equipment to FCP270 ........... 92
A-8. Converting Micro-I/A Station to FCP270 .................................................................. 93
A-9. Converting AW51/AW70 to FCP270s ....................................................................... 94
B-1. Overview for FCP270-to-FEM100 Cabling ................................................................ 96
B-2. Overview for Expanded Fieldbus Cabling (FCP270 to Four FEM100s) ...................... 97
B-3. Overview for Dual Baud Cabling (FCP270 to FEM100 and FBI100) ........................ 98

vii
B0700AR – Rev H Figures

viii
Tables
2-1. Cables for Connecting the FCP270 or Splitter/Combiners to the Ethernet Switches .. 25
2-2. Cables for Connecting the Splitter/Combiners to the FCP270 .................................... 29
4-1. Equipment Information Display Fields for FCP270 .................................................... 51
4-2. Configuration Information Display Fields for FCP270 ............................................... 55
4-3. Equipment Change Display Fields for FCP270 ........................................................... 56
4-4. SMON Log Messages Following Checkpoint Operation ............................................. 60
4-5. Equipment Information Display Fields for Primary ECB (FBM0) .............................. 67
4-6. Equipment Change Display Fields for Primary ECB (FBM0) ..................................... 70
4-7. Equipment Change Display Fields for Primary ECB (FBM0) ..................................... 73
5-1. FCP270 LED Indicators, Reset Button, and Infrared Communication Ports .............. 76
5-2. FCP270 Operational Status LEDs .............................................................................. 77

ix
B0700AR – Rev H Tables

x
Preface
This document describes how to configure and install the Field Control Processor 270 (FCP270)
in an I/A Series® system with The MESH control network. It also describes how the FCP270
functions in The MESH control network. Finally, it describes how to troubleshoot system prob-
lems.

Who This Book Is For


This book is intended for the use of process control engineers and operators, instrument and
maintenance engineers, and other qualified and authorized personnel involved in installing,
configuring and maintaining the FCP270 for operation in the I/A Series MESH control network.

What You Should Know


Prior to using this book, you should be generally familiar with the I/A Series system, and with
DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA). Detailed information relating to the
various I/A Series software and hardware elements is found in the reference documents listed
below.

Revision Information
For this revision of the document (B0700AR-H), the following changes were made:
Global
 Added the FBI200, which replaces the FBI100 and provides additional functionality
over both the 2 Mbps or the 268 Kbps HDLC fieldbus.
Chapter 1 “Introduction”
 Added a note about loading a SaveAll control database from a CP60 or previous
control processor onto an FCP270 to “Overview” on page 1.
 Added Figure 1-2 “FBI200 Connections to 200 Series and 100 Series FBMs on Mixed
2 Mbps and 268 Kbps HDLC Module Fieldbus (Conceptual)” on page 10.
 Updated the cable lengths in “Communication to 200 Series Fieldbus Modules” on
page 11.
Chapter 3 “Configuration Information”
 Added a note about loading a SaveAll control database from a CP60 or previous
control processor onto an FCP270 to “System Definition” on page 43.
Appendix A “Upgrade Diagrams”
 Updated the FCP270-to-the-last-FBM baseplate distance from 20m to 60m in
Figure A-1.
 Updated the FBI200/FBI100 connections in Figure A-2, Figure A-8 and Figure A-9.

xi
B0700AR – Rev H Preface

 Added the new FPS400-24 (P0922YU) power supply input cables - P0927AQ and
P0927AR - to Figure A-2 through Figure A-9.
Appendix B “FEM100 and FBI100 Connection Diagrams”
 Updated the FCP270-to-the-last-FBM baseplate distance from 20m to 60m in
Figure B-1, Figure B-2 and Figure B-3.

Reference Documents
The following documents provide additional and related information.
For information about defining control blocks and compounds, refer to:
 Integrated Control Block Descriptions (B0193AX)
 Integrated Control Software Concepts (B0700AG)
For information about configuring and managing the FCP270, refer to:
 CP 270 On-Line Upgrade (B0700BY)
 System Definition: A Step-by-Step Procedure (B0193WQ)
 Letterbug Configurator User’s Guide (B0700AY)
 Integrated Control Configurator (B0193AV)
 I/A Series Configuration Component (IACC) User’s Guide (B0400BP)
 System Manager (B0750AP)
 Process Operations and Displays (B0700BN)
 System Management Displays (B0193JC)
 Field Control Processor 270 (FCP270) Sizing Guidelines and Excel Workbook
(B0700AV).
For information about associated DIN Fieldbus Modules, the Fieldbus Expansion Module 100,
the FBI200 and the FBI100, refer to:
 DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA).
For information about DIN Fieldbus Modules used to upgrade a 100 Series system and the
FBI200A, refer to:
 100 Series Fieldbus Module Upgrade User's Guide (B0700BQ).
For information about Y-module Fieldbus Modules, refer to:
 I/A Series System Equipment Installation (B0193AC).
For information about system power and earthing (grounding), refer to:
 Power, Earthing (Grounding), EMC and CE Compliance (B0700AU)
For information about supported migration products, refer to:
 SPECTRUM™ Migration Integrator User's Guide (B0193RC)
 SPEC 200™ Control Integrator User's Guide (B0193RD)
 SPEC 200 MICRO™ Control Integrator User's Guide (B0193RR)
 SPEC 200 CCM Control Integrator User's Guide (B0193VU)
 DCS Fieldbus Modules for Westinghouse® WDPF Systems User's Guide (B0400BA).
 DCS Fieldbus Modules for APACS+™ Automation Systems User’s Guide (B0700BK)

xii
Preface B0700AR – Rev H

DCS Fieldbus Modules for Honeywell® TDC 2000 Systems User’s Guide (B0193VL)
 DCS Fieldbus Modules for Honeywell TDC 3000 Systems User’s Guide (B0193YW)
 DCS Fieldbus Modules for Bailey® NET90 and INFI90® Systems User’s Guide
(B0193XG)
 DCS Fieldbus Modules for Fisher PROVOX® Series 10 Systems User’s Guide
(B0193WV)
 DCS Fieldbus Modules for Fisher PROVOX Series 20 Systems User’s Guide (B0193YV)
 DCS Fieldbus Modules for Fisher PROVOX Controller Series Systems User’s Guide
(B0400AR)
For information about The MESH control network, refer to:
 The MESH Control Network Architecture Guide (B0700AZ)
Most of these documents are available on the I/A Series Electronic Documentation CD-ROM
(K0173TQ or K0173WT). The latest revisions of each document are also available through our
IPS Global Client Support at http://support.ips.invensys.com.

Glossary of Terms
The following terminology, used throughout this user’s guide, relates to the FCP270 controller
and associated equipment.

Name Meaning
AI Analog input
APACS+™ Siemens® Process Automation System
AW Application Workstation
BPC Block Processing Cycle
Checkpoint File The Control Database, that resides on the host workstation, which is
downloaded to the FCP270.
CP60 Control Processor 60
CSD Control Strategy Diagram
DIN DIN is a non-governmental organization established to promote the
development of standardization and related activities in Germany.
ECB Equipment Control Block
EEPROM Electrically erasable programmable read-only memory
FBM I/A Series system Fieldbus Module
FCM Fieldbus Communication Module
FCP270 Field Control Processor 270
FCS Foxboro® Control Software (v1-v2.5 of this product was called
InFusion®, v3.0 and later versions of this product are called FCS)
FCS Configuration Foxboro® Control Software Configuration Tools (formerly InFusion
Tools Engineering Environment)
FDSI Foreign Device Systems Integrator

xiii
B0700AR – Rev H Preface

Name Meaning
FEM Fieldbus Expansion Module
Fault Tolerant (FT) A station that is running with two FCP270 controllers.
GMT Greenwich Meridian Time (GMT) is an international time standard
GPS Global positioning system
HART HART Field Communications Protocol is a standard for digitally
enhanced 4 to 20 mA smart instrument communication.
HDLC High-level Data Link Control protocol - Master/Slave Protocol used on
top of several physical layers for FBM communication
I/A Series® Intelligent Automation Series
IACC I/A Series Configuration Component
ICC Integrated Control Configurator
IR Infrared
LC Connector for fiber optic cable connection to the FCP270 or
splitter/combiner
LED Light-emitting diode
Letterbug Alphanumeric string that the user defines to identify a station in an
I/A Series control system.
Letterbug Configurator Handheld device for setting, modifying and reading the controller
letterbug and reading controller status information
Married FT Station Two healthy FCP270 controllers operating as one station.
MMF Multimode fiber cable
MTK Master Timekeeper
MT-RJ Connector for fiber optic cable connection to Ethernet switches
OLUG On-Line Image Upgrade; the procedure that allows a fault tolerant
FCP270 to update to the latest image with minimal I/O down time.
Remarry When a newly booted FCP270 module marries with a FCP270 running
in Single Primary mode.
ROM Read only memory
Rx Receive
Single Primary A FCP270 module that is running as a single module.
SMDH System Management Display Handler, the user interface for equipment
status and change actions
SOE Sequence of Events
Station The virtual controller which runs as one or two CP modules. For exam-
ple, the station may exist on both fault-tolerant modules, but the station
itself is considered a single entity.
STK Slave Timekeeper
SysDEF System Definition
System Configurator Software for configuring your system, such as the FCS Configuration
Tools, IACC, or ICC.

xiv
Preface B0700AR – Rev H

Name Meaning
TDA Transient Data Analyzer
TDR Transient Data Recorder
The MESH The MESH Control Network
Tx Transmit
UTC Universal Coordinated Time

xv
B0700AR – Rev H Preface

xvi
1. Introduction
This chapter describes the main features, fault-tolerant operation, network configuration, and
time synchronization of the Field Control Processor 270.

Overview
The Field Control Processor 270 (FCP270) is an optionally fault-tolerant station that performs
regulatory, logic, timing, and sequential control together with connected Fieldbus Modules
(FBMs) and other process interface devices. It also performs data acquisition (via the FBMs
and/or other devices) and alarm detection and notification.
The FCP270 supports process control via the standard 2 Mbps HDLC fieldbus for the following
products:
 All DIN rail mounted 200 Series FBMs (FBM201, FBM202, and so forth). The
FCP270 supports up to 32 modules itself, and supports up to 128 modules when
used with a Fieldbus Expansion Module 100 (FEM100); based on the loading of
FCP270. Refer to Field Control Processor 270 (FCP270) Sizing Guidelines and Excel
Workbook (B0700AV).
 Field Device Systems Integrator (FDSI) modules (FBM230/231/232/233)
 DCS Fieldbus Modules for APACS+™ Automation Systems
 DCS Fieldbus Modules for Westinghouse® WPDF Systems
The FCP270 also supports process control via the optional 268 Kbps HDLC fieldbus for the fol-
lowing products:
 All Y-module FBMs, also known as 100 Series FBMs (FBM01, FBM02, and so forth)
– up to 64 modules, via an extended fieldbus
 Fieldbus Cluster I/O via FBP10 fieldbus processor module
 Foxboro® Hydrostatic Interface Unit (HIU)
 Foxboro Mass Flowmeter
 Foxboro Panel Display Stations
 SPECTRUM™ Migration Integrators
 SPEC 200™ Control Integrators
 SPEC 200 MICRO™ Control Integrators
 SPEC 200 CCM Control Integrators
 DCS Fieldbus Modules for Honeywell® TDC 2000 and TDC 300 Systems
 DCS Fieldbus Modules for Bailey® Net90 and Infi90 Systems
 DCS Fieldbus Modules for Fisher’s PROVOX® Series 10, Series 20, and Controller
Series Systems.

1
B0700AR – Rev H 1. Introduction

NOTE
The FCP270 can support the 2 Mbps and/or the 268 Kbps HDLC fieldbus, while
the FBI100 is used on the 268 Kbps HDLC fieldbus between the FCP270 and the
100 Series FBMs or competitive migration modules. However, the FBI200 provides
similar functionality as the FBI100 and supports both the 2 Mbps and the 268
Kbps HDLC fieldbus at the same time. For the maximum number of devices sup-
ported by each fieldbus, refer to the device specific Product Specification Sheets.

NOTE
Before loading a SaveAll control database from a CP60 or previous control proces-
sor onto an FCP270, make sure all the ECBs are supported by the FCP270. For
example, ECB110 (for FCM10s) is not supported by the FCP270.
Failing to do this will block ALL the ECBs (invalid and valid) from being loaded
into the new FCP270.

Features
The FCP270 provides the following new features and improvements.
 A direct 100 Mbps Ethernet fiber connection to The MESH control network for high
speed data communication that is immune to electromagnetic interference over the
distance of the fiber cable.
 A fault-tolerant option that delivers improved availability and safety using unique,
dual controller comparison on all outgoing messages.
 Optional self-hosting mode allows the FCP270 to start up and run, executing its con-
figured control scheme using the checkpoint file stored in flash memory. This allows
the FCP270 to boot itself with a valid control database even if its host workstation is
not present.
 On-line image update replaces the executable image (operating system) of a running,
fault-tolerant FCP270 controller with a newer image without having to shut down
the equipment being controlled by the FCP270.
 Hardened, field-mounted control (100 Mbps Ethernet fiber controller, 2 Mbps
fieldbus, 200 Series DIN rail mounted FBMs, Termination Assemblies, and
FPS400-24 power supply). The new configuration eliminates the need for a rack
room (you only need a control room and a field enclosure).
 Supports up to 128 200 Series DIN rail mounted FBMs, or equivalent modules
(depending on the sizing guidelines), when connected to an optional Fieldbus Expan-
sion Module 100 (FEM100) or, depending on the configuration, an FBI200A in a
conversion mounting structure (described in 100 Series Fieldbus Module Upgrade
User's Guide (B0700BQ)).
 Dual baud functionality supports communication with both 200 Series FBMs and
100 Series FBMs and migration products. When installed as specified, the FBI200s or
FBI100s filter the 2 Mbps communications from the FCP270 to ensure the
100 Series FBMs and similar Migration modules only receive the 268 Kbps signals

2
1. Introduction B0700AR – Rev H

intended for them, and extend the 268 kbps Module Fieldbus up to 1830 m
(6000 ft).
 Connection to Ethernet or serial devices via FDSIs which allows for new device
interfaces. The FDSIs include FBM230, FBM231, FBM232, and FBM233.
 Optional global positioning system allows external time synchronization.
 Sequence of Events (SOE) are optionally time stamped at the FBM (200 Series FBMs
only) to 1 ms1 accuracy throughout the system for later analysis of events.
 Optional Transient Data Recorder (TDR) allows 10 ms sampling of analog data for
later analysis of events using Transient Data Analyzer (TDA). TDR data is optionally
time stamped (200 Series FBMs only) to 1 ms1 accuracy.
 Infrared interface to the I/A Series system Letterbug Configurator allows setting and
reading the controller letterbug.
 Memory resident image for fast station reboot. Reboot time is less than 10 seconds.
 Improved controller performance. Block executions/second is 10,000 for the FCP270
compared to 3400 for the CP60.
 Up to 4000 blocks can be configured for the FCP270 (or fault-tolerant FCP270 pair)
 A scalable license lets you start small with a full-featured control system. You can grow
your system over time.
 Alarm enhancements to the function blocks: re-alarming on changes to alarm priority,
re-alarming based on time, alarm suppression based on time.
 Foundation Fieldbus, FoxCom™, HART, Profibus, and Modbus FBMs are
supported.
 Y-module FBMs and DCS migration FBMs are supported.
 For enhanced reliability during maintenance operations, a recessed reset button,
located at the front of the module, allows you to manually reset the module without
removing it from the baseplate.

Fault-Tolerance
Fault-tolerant operation is unique with Foxboro control processors and uses patented technology.
Fault-tolerance is superior to redundancy because outgoing messages from the fault-tolerant
controller must be identical in both modules for a message to transmit successfully.
The following sections describe the difference between redundancy and fault-tolerance from an
applications standpoint and how fault-tolerance is implemented using the FCP270.

1.
Time stamping has 1 ms accuracy only when using the optional GPS external time synchronization.
WARNING: ac signals coming into SOE points cannot be synchronized to 1 millisecond in the
same manner as dc based points can. The ac SOE points will have a delay of ~8-20 millisecond due
to the 50 or 60 Hz ac wave form. If 1 millisecond synchronization is critical when time synchroniza-
tion is required, avoid the use of ac inputs.
As well, digital data coming from FBMs with ac driven inputs could be delayed due to the dynamics
of the ac waveform and filtering in the FBM and therefore may not be recorded until the following
10 millisecond sampling period.

3
B0700AR – Rev H 1. Introduction

Traditional Redundant Systems


Traditionally, the goal of improved availability through redundancy has been achieved using a
second, or “backup” controller. Redundant systems that use a secondary controller may have the
following shortcomings:
 Problems with the primary controller are not detected or are only detected after a
number of potentially bad messages have been transmitted to the field.
 Secondary controllers may not use the latest “good” data when they take over from the
primary controller. Configuring the secondary controller correctly can result in
substantial system downtime.
 Secondary controllers may have health problems that are hard to determine after they
have been idle for a long period of time.
To remove these shortcomings from critical systems, the FCP270 uses a patented method of fault-
tolerance.

FCP270 Fault-tolerant Operation


The fault-tolerant version of the FCP270 consists of two modules operating in parallel (primary
and shadow), with redundant connections to both The MESH control network and the HDLC
module fieldbus. The two control processor modules, married together as a fault-tolerant pair,
provide continuous operation of the unit in the event of a single hardware failure occurring within
one module of the pair. When the primary and shadow modules boot up, they join together in a
process which is referred to as “marriage.”
Both modules receive and process information simultaneously, and faults are detected by the
modules themselves. One of the significant methods of fault detection is comparison of
communication messages at the module’s external interface. Upon detection of a fault, the
communication message is aborted, and self-diagnostics are run by both modules to determine
which module is defective. The non-defective module then assumes control without affecting
normal system operations. An aborted control network communication message is then sent by
the non-defective module via the retry mechanisms of the communications protocol. An aborted
fieldbus communication message is retried on the next BPC. For more information, see “Diagnos-
tics” on page 84.

Self-Hosting and Non-Self-Hosting Modes


An FCP270 requires the latest control database to download to its local memory when it boots
up. This database is provided in a checkpoint file, which the controller acquires based on one of
two modes: non-self-hosting mode (the default mode) and the new self-hosting mode introduced
with I/A Series V8.4 software. FCP270 controllers running I/A Series V8.4 or later software
images support the new self-hosting mode.
When the controller boots up in the traditional non-self-hosting mode, it requests the checkpoint
file from its host workstation. When the controller is using the new self-hosting mode of opera-
tion, the checkpoint file is stored locally in the FCP270’s flash memory. Thus, the controller can
boot up in environments where a host workstation is not present. A controller cannot be config-
ured to run in self-hosting mode until after the station boots up the first time in non-self hosting
mode. Non-self-hosting mode is the default for a newly commissioned controller. If a controller
boots up without a valid checkpoint file in flash, it will load the checkpoint file from the host

4
1. Introduction B0700AR – Rev H

workstation. When the database download is complete, the controller issues a checkpoint com-
mand automatically, during which the checkpoint file is written to flash.
The new self-hosting feature provides a mechanism for an FCP270 controller to start up and exe-
cute its configured control scheme in the absence of a host workstation. A host workstation is only
required when you change the control configuration or the controller image.
Controllers running in self-hosting mode require a link to the Ethernet to fully support the self-
hosting functionality, and they must be connected to a fully functional switch. The link is
required for the fault-tolerant network logic to operate. Without this link, the mechanism that is
used to pass the checkpoint file from the primary to the shadow module will not work.
There are certain limitations on the self-hosting mode of an FCP270 controller.
 When you enable self-hosting in a controller, the smallest time interval allowed for the
auto-checkpoint option is two (2) hours.
 If the user attempts to set an auto-checkpoint time of less than two hours, the
FCP270 will force the time to two hours and send a message to the SMON log iden-
tifying the change.
 Flash memory is capable of at least 100,000 write operations. There are two areas of
flash in the controller that are used to save checkpoint files. Flash burns alternate
between the two flash memory areas, providing a total of at least 200,000 checkpoint
file writes. The SMDH display for the primary ECB (FBM0) includes a flash burn
counters for the primary and shadow modules.
For more information, refer to “Enabling the FCP270 Self-Hosting Option” on page 21.

Self-Hosting Feature, Available with 200 Series FBMs Only


The self-hosting feature is recommended only for use in FCP270s which are used with 200 Series
FBMs, or similar modules such as those included in the intrinsically safe I/O subsystem. It is not
recommended for use when the FCP270 is controlling any 100 Series FBMs (Y-module FBMs) or
100 Series FBM based migration cards including Cluster I/O.
All the information that 200 Series FBMs (or similar modules in the intrinsically safe I/O subsys-
tem) need to operate correctly is either burned in the flash of the FCP270 or is included in the
checkpoint file. This means that if a 200 Series FBM (or similar module) needs to reboot and go
on-line after a power cycle, it will be able to do so without the presence of a boot host worksta-
tion. However, 100 Series FBMs have a different behavior. If a 100 Series FBM is power-cycled, it
downloads information it needs to operate correctly from a boot host workstation. If the FCP270
is running in self-hosting mode and the boot host workstation is unavailable, the 100 Series FBM
will not be able to boot or go on-line.
If desired, you can minimize the risk that 100 Series FBMs will need to boot up by making sure
that the 100 Series FBMs are mounted on a rack with a battery back-up or an Uninterruptable
Power Supply (UPS). With this type of configuration, as long as the I/O source does not need to
boot up, the 100 Series FBMs will reconnect when the FCP270 comes back on-line.

On-Line Image Update


For a fault-tolerant FCP270 controller, on-line image update replaces the executable image (oper-
ating system) of a running FCP270 with a newer image without having to shut down the equip-

5
B0700AR – Rev H 1. Introduction

ment being controlled by the FCP270. This feature allows you to take advantage of product
enhancements while interrupting process control for only 1.5 seconds, approximately.

FCP270 Network Configuration


The MESH control network uses redundant communication paths to enhance control reliability.
Figure 1-1 shows a simplified FCP270 network configuration using redundant Ethernet fiber
switches, 100Mbps fiber cables, splitter/combiners, FCP270 controllers (fault-tolerant), and
redundant 2 Mbps fieldbus and redundant 268 Kbps fieldbus. Multiple FCP270s can share the
same redundant switch.
The FCP270 uses 100 Mbps Ethernet fiber connections to communicate with I/A Series
workstations connected to Ethernet switches in The MESH. For information about general
guidelines and specific requirements for designing The MESH above the FCP270 level, including
site planning and network installation guidelines, see The MESH Control Network Architecture
Guide (B0700AZ).
For instructions on installing and cabling the FCP270 in the non-fault-tolerant and fault-tolerant
configurations, see Chapter 2 “Installing the Field Control Processor 270”.

Network Path Switching


The MESH control network provides redundant communications paths. The MESH architecture
and the software in the controller allow it to switch paths when a communications path fails or
when replacing modules.
Each FCP270 has two station MAC addresses and two IP addresses, which are not embedded in
hardware. When you replace the controller, the new controller acquires its station MAC and IP
addresses from the system configuration file based on its assigned letterbug. Software on the
FCP270 then selects the network path that is used to transmit outbound communication.

Splitter/Combiner
Fault-tolerant FCP270s require a pair of splitter/combiners, one to connect to each of The
MESH control network paths (see Figure 1-1). Non-fault-tolerant FCP270s can optionally use
splitter/combiners to provide for a future upgrade to fault-tolerant operation. The splitter/
combiner has three 100 Mbps connections: one to the primary module of a fault-tolerant pair,
one to the shadow module, and one to The MESH. One splitter/combiner in the pair is con-
nected to one Ethernet switch, the other is connected to another Ethernet switch.
The splitter/combiner is connected via fiber optic cables. Inbound traffic from The MESH is split
and sent to each FCP270 controller. Output traffic is sent from the primary module, which can
be either physical module, to The MESH.

6
1. Introduction B0700AR – Rev H

The MESH Control Network


Ethernet Fiber Switch Ethernet Fiber Switch
FAST ETHERNET WORKGROUP SWITCH FAST ETHERNET WORKGROUP SWITCH
RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PWR PWR
RESET
CPU CPU
RESET
COM COM

1 Gbps Ethernet
Fiber Optic Cables

FAST ETHERNET WORKGROUP SWITCH FAST ETHERNET WORKGROUP SWITCH

RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PWR PWR
RESET
CPU RESET
CPU
COM COM

100 Mbps Ethernet


Fiber Optic Cables
(Redundant)
Splitter*

Splitter*

Splitter*
FCP270 Only
Baseplate Splitter*
Splitter*
F F F F
C C C C FCP270 Control Splitter*
P P FCP270 Control P P
Processor Processor
2 2 2 2
7 7 (Fault-Tolerant) 7 7 (Fault-Tolerant) F F
0 0 0 0 C C FCP270 Control
P P Processor
FCP270 Only 2 2
Baseplate 7 7 (Fault-Tolerant)
0 0
2 Mbps HDLC FCP270 Only
Module Fieldbus Baseplate
(Shielded Twisted
Pair Cables)
268 Kbps HDLC
Module Fieldbus
(Shielded Twisted
Pair Cables)

F F F
B B B
M M M Equipment Rack
IPM2

IPM2

FBI

100 SERIES

100 SERIES

100 SERIES

100 SERIES

100 SERIES

100 SERIES

100 SERIES
FBM

FBM

FBM

FBM

FBM

FBM

FBM
FBI
IPM2

IPM2

Up to 8 FBMs per Baseplate Competitive Migration Modules


(See B0400FA) (See “Overview” on page 1)
1x8 FBM Mounting
Structure
DIN Rail Mounted 200 Series FBMs
Up to 32 per FCP270 or FCP270 Pair
(See Note) Y-module FBMs or Migration Modules
Up to 64 Y-module FBMs per FCP270 or
FCP270 Pair
* Splitter/Combiner. (See Note below and “Overview” on page 1)
Note: For additional sizing information, refer to Field Control Processor 270 (FCP270) Sizing
Guidelines (B0700AV).
Figure 1-1. Typical FCP270 Network Configuration (Simplified)

7
B0700AR – Rev H 1. Introduction

Fieldbus Expansion Module 100 (FEM100)


When an FCP270 is connected to a Fieldbus Expansion Module 100 (FEM100), the FEM100
increases the number of 200 Series (or equivalent) FBMs supported up to 128 FBMs. (Refer to
Field Control Processor 270 (FCP270) Sizing Guidelines and Excel Workbook (B0700AV) to deter-
mine actual sizing for your system.)
The FCP270 requires a software level 8.3 or higher to support the FEMs.
The FEM100 generates four single fieldbus ports, or Expanded Fieldbus 1 through 4. Each
Expanded Fieldbus is capable of communicating with up to thirty-two FBMs. The FEM100 and
Expanded Fieldbuses are transparent to the 2 Mbps HDLC Module Fieldbus between the
FCP270 and the 200 Series (or equivalent) FBMs.
A pair of FEM100s provides redundancy for both paths of the redundant 2 Mbps HDLC module
fieldbus network. Both FEM100s are always active. In case of a module’s failure, the other pro-
vides backup coverage until the failed module is returned to service. The failure is reported as an
interruption to one path of the redundant fieldbus network.
Additional information on the FEM100 is provided in the DIN Rail Mounted FBM Subsystem
User’s Guide (B0400FA).

NOTE
The FBI200A, which is installed exclusively in conversion mounting structures, in
the 100 Series Fieldbus Module Upgrade subsystem, can perform a similar function
as the FEM100 when used with an FCP270. A redundant pair of FBI200As in a
mounting adapter support up to thirty-one 200 Series FBMs in a baseplate chain.
However, they can enable their associated FCP270 to support up to one hundred
twenty-four (124) 200 Series FBMs as described in the 100 Series Fieldbus Module
Upgrade User's Guide (B0700BQ).
The FEM100 cannot be used in conjunction with the FBI200A in any CP-to-FBM
configuration. A CP’s subsystem may only have FEM100s or FBI200As.

I/O Communications
The FCP270 contains several I/O communication features and functions:
 Without use in conjunction with the FBI200 or FBI100, support for redundant
HDLC fieldbus at only 2 Mbps or 268 Kbps (depending on whether to connect to
200 Series or 100 Series FBM types and protocols, respectively) for connection to the
FCP270 module
With use in conjunction with the FBI200 or FBI100, support for redundant HDLC
fieldbus to both 2 Mbps or 268 Kbps for connection to the FCP270 module (for con-
nections to both 100 Series and 200 Series FBM types and protocols)
 Simultaneous support of 200 Series FBM types and protocols (HART, Foundation
Fieldbus, Profibus, Modbus, FoxCom, FDSI and standard 200 Series FBMs).
When used with FBI200 or FBI100, simultaneous support of 100 Series FBMs and
100 Series and 200 Series competitive migration modules types and protocols as well.

8
1. Introduction B0700AR – Rev H

 A maximum of 32 DIN railed mounted 200 Series FBMs2 is allowed per 2 Mbps
HDLC fieldbus. The FEM100 provides four Expanded Fieldbuses, which supports
up to 128 200 Series FBMs (or equivalent modules) per FCP270. (See the note above
for the FBI200As.)
 A maximum of 39 Siemens APACS+ DCS migration FBMs2 is allowed on the 2
Mbps HDLC fieldbus. The FEM100 provides two Expanded Fieldbuses, which sup-
ports up to 78 Siemens APACS+ DCS migration FBMs per FCP270.
 A maximum of 36 Westinghouse DCS migration FBMs2 is allowed on the 2 Mbps
HDLC fieldbus. The FEM100 provides two Expanded Fieldbuses, which supports up
to 72 Westinghouse DCS migration FBMs per FCP270.
 A maximum of 64 Y-module (100 Series) FBMs and/or DCS migration FBMs2 is
allowed on the 268 Kbps fieldbus.
I/O communications support the following multiple data streams:
 Real-time I/O
 AI Stream data for the TDR
 Sequence of Events (SOE) data3
 I/O maintenance activity
 Pass-through activity for device configuration, and so forth.

Dual Baud Functionality


The FCP270 supports the dual baud functionality, allowing the FCP270 to communicate with
both 200 Series FBMs and 100 Series FBMs and migration modules when the FBI200 or FBI100
is properly installed between the FCP270 and the 100 Series FBMs. When installed as specified,
the FBI200s or FBI100s filter the 2 Mbps communications from the FCP270 to ensure the
100 Series FBMs and migration modules only receive the 268 Kbps signals intended for them.
The FBI200s/FBI100s also extend the 268 kbps Module Fieldbus between the FBI200s/FBI100s
and the 100 Series FBMs up to 1830 m (6000 ft). See Figure 1-2 and Figure 1-3.
For a typical redundant module Fieldbus configuration, two FBI200s/FBI100s are needed; one
for the A fieldbus and another for the B fieldbus. These FBI200s/FBI100s are installed in their
own special baseplate for high speed communication between the FBM modules and FCP270s.
The process for setting up dual baud functionality for the FCP270 is discussed in DIN Rail
Mounted FBM Subsystem User’s Guide (B0400FA).

2.
Maximums listed are for FCPs connected only to modules of the specified type. Refer to Field Con-
trol Processor 270 (FCP270) Sizing Guidelines and Excel Workbook (B0700AV) for the appropriate
sizing guidelines for the FCP270.
3.
Using the new SOE feature or the original SOE via ECB6. Also see the footnote warning on page 3.

9
B0700AR – Rev H 1. Introduction

Mixed 268 Kbps and 2 Mbps HDLC Module Fieldbus


CP Fieldbus Cable - 60 m (198 ft) Max. To other 200 Series
Baseplates via
Fault-Tolerant 2 Mbps HDLC
FCP270s in FBI200 Pair in Two-Slot Module Fieldbus
Modular Baseplate Vertical Baseplate (P0924RT)*
A
FCP270

FCP270

FBI200

FBI200

FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
B

200 Series FBMs


Twinaxial Termination
Assemblies (P0903VY)

268 Kbps HDLC Module


Fieldbus (Shielded Twinaxial) To other FBIs
Cables - Includes Fieldbus Fieldbus Isolators (FBIs)
A and B - Total length (FBI200
Baseplate to 1x8 Mounting I O I O

1x8 Mounting Structure


Structure) is up to
1830 m (6000 ft)

100 Series FBMs or


Twinaxial Termination Competitive Migration
Assemblies (P0903VY) Modules
(100 Series FBI TCA) To other FBIs

* Communications Mode in FBI200 Baseplate must be set to 268 Kbps mode.


Figure 1-2. FBI200 Connections to 200 Series and 100 Series FBMs on Mixed 2 Mbps
and 268 Kbps HDLC Module Fieldbus (Conceptual)

10
1. Introduction B0700AR – Rev H

Fault-Tolerant HDLC Module Fieldbus


FCP270s in Mix of 268 Kbps and 2 Mbps messages
Modular Baseplate (Shielded Twisted Pair Cables) 2 Mbps Module Fieldbus
Includes Fieldbus A and B (Shielded Twisted Pair Cables)

Termination
A ...
F F
C C B ...
P P
2 2
7 7 F F F F F F
0 0 B B B B B B
M M M M M M

DIN Rail Mounted 200 Series FBMs


And 200 Series-based Migration Modules
Up to 32 per FCP270 or FCP270 Pair (See Note)
F F Other FBIs
B B
FBI100s in I I Mounting Structure or
Two-Slot 100 100 Equipment Rack
Vertical
Baseplate A B
IPM2

IPM2

FBI

100 SERIES

100 SERIES

100 SERIES

100 SERIES

100 SERIES

100 SERIES

100 SERIES
FBM

FBM

FBM

FBM

FBM

FBM

FBM
FBI
IPM2

IPM2

268 Kbps HDLC


Module Fieldbus Only Y-module FBMs or 100 Series based
(Shielded Twisted Migration Modules. Up to 64 Y-module
Pair Cables) FBMs per FCP270 or FCP270 Pair
(See Note below and “Overview” on page 1)
Other FBIs
Note: For additional sizing information, refer to Field Control Processor 270 (FCP270) Sizing
Guidelines (B0700AV).
Figure 1-3. Example Network with FCP270 with Dual Baud Functionality (Conceptual)

Communication to 200 Series Fieldbus Modules


The 200 Series DIN rail mounted FBMs connect to the optionally-fault-tolerant FCP270
through the baseplate. The 2 Mbps HDLC fieldbus is connected to both paths of the redundant
fieldbus network, providing continuous communication in the event one path fails (see
Figure 1-1).
Fieldbus cabling lengths for the FCP270 and 200 Series FBMs are as follows:
 Overall module Fieldbus, shielded twisted-pair (all segments): 60 m (198 ft)
maximum
(For example, this length includes both the 2 Mbps Module Fieldbus for the
200 Series FBMs, and the cable length between the FCP270 and the FBI200s or
FBI100s, if present)
 Module Fieldbus, fiber optic segment (between two baseplates): 10 km (6.2 mi) per
segment maximum, up to 20 km (12.4 mi) total.
 FCP270 Fieldbus without FCM2Fs
The cable length of the Fieldbus cannot exceed 60 m (198 ft) (see Figure 1-4).

11
B0700AR – Rev H 1. Introduction

FCP
FCP FCP Baseplate

First
FBM Baseplate
60 m
(198 ft)

Last
in
FBM Baseplate Chain

Figure 1-4. Fieldbus Cable Length Restrictions

 FCP270 Fieldbus with FCM2Fs


Each FCP/FCM drives a segment of interconnected baseplates of up to 60 m (198 ft).
Up to four pairs of FCM2Fxs can be used in a Fieldbus (see Figure 1-5).

FCP
FCP FCP Baseplate
60 m
(198 ft)

FCM2Fx FCM2Fx
2/4/10 km
(1.24/2.5/6.2 mi)
FCM2Fx FCM2Fx

First
60 m
FBM Baseplate (198 ft)

FCM2Fx FCM2Fx
2/4/10 km
(1.24/2.5/6.2 mi)
FCM2Fx FCM2Fx

Last 60 m
in (198 ft)
FBM Baseplate Chain

Figure 1-5. Fieldbus Cable Length Restrictions w/FCM2Fs

12
1. Introduction B0700AR – Rev H

 FCP270 Fieldbus and Expanded Fieldbuses (1-4) without FCM2Fs


The cable length of the Module Fieldbus (shielded twisted-pair segment) cannot
exceed 60 m (198 ft). See Figure 1-6.

FCP/FEM FCP
FCP FCP Baseplate Baseplate FCP FCP
60 m
FEM (198 ft)
FEM FEM Baseplate FEM FEM

First First
FBM FBM FBM FBM
Base Base Base Base
Plate Plate Plate Plate
60 m 60 m
(198 ft) (198 ft)
Last Last
FBM FBM in FBM FBM in
Base Base Chain Base Base Chain
Plate Plate Plate Plate

Figure 1-6. Expanded Fieldbus Cable Length Restrictions

 FCP270 Fieldbus and Expanded Fieldbuses (1-4) with FCM2Fs


Each FCP/FCM drives a segment of interconnected baseplates of up to 60 m (198 ft).
Up to four pairs of FCM2Fxs can be used in each Expanded Fieldbus. See Figure 1-7.

FCP/FEM FCP
FCP FCP Baseplate Baseplate FCP FCP
60 m
FEM (198 ft)
FEM FEM Baseplate FEM FEM

FCM FCM FCM FCM


2Fx 2Fx * 20 km distance is 2Fx 2Fx
10 km* allowed through 10 km*
(6.2 mi) the use of four (6.2 mi)
FCM FCM pairs of FCM2F10s. FCM FCM
2Fx 2Fx 2Fx 2Fx

First First

FBM Baseplate FBM Baseplate

60 m 60 m
(198 ft) (198 ft)
Last Last
in in
FBM Baseplate Chain FBM Baseplate Chain

Figure 1-7. Expanded Fieldbus Cable Length Restrictions w/FCM2Fs

13
B0700AR – Rev H 1. Introduction

For complete information on DIN Rail mounted devices, see DIN Rail Mounted FBM Subsystem
User’s Guide (B0400FA).

Communication to Y-Module (100 Series) Fieldbus Modules


The Y-module FBMs connect to the optionally-fault-tolerant FCP270 through the baseplate. The
268 Kbps HDLC fieldbus is connected to both paths of the redundant fieldbus network, provid-
ing continuous communication in the event one path fails (see Figure 1-1). The fieldbus connects
to the baseplate via the P0926LC adapter and the P0903VY termination cable assembly (TCA). A
268 Kbps Splitter/Terminator connects the extended fieldbus to 2- position FCP270 only modu-
lar baseplate. This splitter/terminator does not support time strobe signals. The extended fieldbus
can be up to 1 Km (3200 ft) in length.
For complete information on DIN Rail mounted devices, see DIN Rail Mounted FBM Subsystem
User’s Guide (B0400FA).

Communication to Migration Modules


For communication with migration modules, refer to the appropriate migration module docu-
ment. For example:
 For Siemens APACS+ DCS migration FBMs, refer to DCS Fieldbus Modules for Moore
APACS+ Systems User's Guide (B0700BK).
 For Westinghouse DCS migration FBMs, refer to DCS Fieldbus Modules for Westing-
house WDPF Systems User's Guide (B0400BA).
Additional documents are listed in the Preface.

Time Synchronization
The I/A Series system supports time synchronization using either an optional, externally
maintained source of Universal Coordinated Time (UTC) from GPS satellites or an internal
source using proprietary software.
Time synchronization within an I/A Series system synchronizes controllers to provide accurate
timestamps for event and data reporting throughout the system. Time stamping is used for SOE
evaluation, TDA, and alarm messages.

Overview
A Master Timekeeper (MTK), residing in an Application Workstation (AW), maintains the time
source and distributes the system time to all other stations in The MESH control network. A
Slave Timekeeper (STK) receives time information from the MTK and keeps itself synchronized
with the MTK, and thus with all other stations in The MESH. STKs reside in all controllers.
The MTK determines the time for synchronizing all slave stations by using either the AW’s
real-time clock (internal time source) or the optional GPS receiver and time strobe generator
(external time source).
For complete information on time synchronization, refer to Time Synchronization User’s Guide
(B0700AQ).

14
1. Introduction B0700AR – Rev H

Internal Source Time Synchronization


For internal source time synchronization (standard), the MTK station uses time from the internal
clock in the hosting PC. The MTK distributes time as UTC to all stations in The MESH. This
time is displayed as local time.
Date and time is entered using the System Management Set Date and Time display. At run-time,
the time can be changed using the Set Date and Time display or time can continue to run on its
internal clock.
For procedures on how to set the date and time using System Management, refer to System
Management Displays (B0193JC).

External Source Time Synchronization


For external source time synchronization (optional), the MTK station uses an externally
maintained source of Universal Coordinated Time (UTC) from GPS satellites. Equipment to
support this option includes a GPS receiver and time strobe generator.
The MTK uses a hardware connection to the controllers to increase the synchronization accuracy
by providing a time strobe pulse, which is sent continuously by the MTK at a precise time
interval. The controllers have built-in hardware to receive the sync pulses generated by the MTK.
UTC is the international time standard (commonly referred to as Greenwich Meridian Time or
GMT).

FCP270 Sizing Constraints


FCP270 has several aspects that consume its capacity, including BPC settings, the number and
type(s) of I/O points, number of blocks, block memory usage, and so forth. Since the FCP270’s
capacity is consumed based on the configuration of these aspects, it is strongly recommended to
review the sizing guidelines described in Field Control Processor 270 (FCP270) Sizing Guidelines
and Excel Workbook (B0700AV) when determining the FCP270 sizing constraints.
In general, the following apply to FCP270:
 The number of 200 Series FBMs hosted by an FCP270 (or fault-tolerant FCP270
pair) is 32 maximum alone, 124 with FBI200As (used only in the 100 Series Fieldbus
Module Upgrade subsystem) or 128 with FEM100s, depending on the selected scan
periods.
 The number of 100 Series FBMs and/or DCS FBMs hosted by an FCP270 (or fault-
tolerant FCP270 pair) is 64 maximum, depending on the selected scan periods, dis-
cussed in “FCP270 Supported Block Processing Cycles” below.
 The maximum number of blocks that can be configured for use with the FCP270 (or
fault-tolerant FCP270 pair) is 4000. The maximum number of blocks used in a given
configuration depends on scan periods and block type selection. These blocks include
all types: control blocks, ECBs, compounds, data blocks, and so forth.

FCP270 Supported Block Processing Cycles


When planning the number of 100 Series FBMs for your FCP270, take into consideration the
length of each Block Processing Cycle (BPC). The FCP270 supports BPC settings with 100 Series
FBMs from 50 ms up to 1 second:

15
B0700AR – Rev H 1. Introduction

 An FCP270 with a BPC of 50 ms can support a maximum of five 100 Series FBMs
that can be a combination of basic input and output types.
 An FCP270 with a BPC of 100 ms can support a maximum of seventeen 100 Series
FBMs that can be a combination of basic input and output types.
FoxCom FBMs are not supported for a 50 or 100 ms BPC, but it is the responsibility of the user
to determine capacity and load.
Due to these speeds, the FCP270 is a viable replacement for high-speed CP30/40 applications.
Note that the slower 2 second BPCs supported by earlier generations of control processors are not
supported by the FCP270.

16
2. Installing the Field Control
Processor 270
This chapter provides installation and cabling information for the Field Control Processor 270.

Overview
The FCP270 is available in two configurations, non-fault-tolerant and fault-tolerant.
Communication between the two modules in the fault-tolerant configuration takes place via a
module connector in the baseplate in which the modules are installed.
The FCP270 can only be plugged into a baseplate connector that specifically supports the
FCP270. This rule is enforced since the FCP270 connectors are located differently from the
connectors of FBMs or FCMs. This prevents accidental installation of a module in the wrong
baseplate location.
 The FCP270 is designed for installation in I/A Series equipment enclosures. For
general information on installing equipment into these enclosures, refer to Enclosures
and Mounting Structures (B0700AS).
 The FCP270 installs on DIN Rail mounted baseplates. For complete information on
these baseplates, refer to DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA).

System Definition
System Definition identifies the I/A Series system components, system software required by each
component, the system component letterbugs, and other system characteristics for correctly
loading system software and identifying the system software objects. The letterbug is an
alphanumeric string that the user defines to identify a station in an I/A Series control system.
System Definition is initially performed prior to installation of the system equipment, and it is
updated with any hardware/software system changes. Reports produced by System Definition
(SysDEF) software define the system network and provide information that can be used in con-
junction with equipment installation.
For a step-by-step procedure for defining an I/A Series system configuration using the System
Definition (SysDEF) software, refer to System Definition: A Step-By-Step Procedure (B0193WQ).
IACC allows you to import system configuration information from an I/A Series system using
SysDEF Export disks created with the System Definition configuration application. For
importing procedures, refer to I/A Series Configuration Component (IACC) User’s Guide
(B0400BP).

17
B0700AR – Rev H 2. Installing the Field Control Processor 270

Installing a Single or Primary FCP270 Module


Figure 2-1 shows how to install a single (non-fault tolerant) or primary (fault-tolerant) FCP270
module on two example FCP270 modular baseplates (P0926HC and P0973CN).

2-Position FCP270 and 2-Position FEM100,


Vertical DIN Rail Mounted Baseplate (P0973CN)

Self-Retaining
Hex Screw
(1 of 2)

FCP270 Module
(P0917YZ)

Position 1 Position 2

FCP270 only, 2-Position Horizontal


DIN Rail Mounted Baseplate (P0926HC)

Figure 2-1. FCP270 Module Installation (Typical)

18
2. Installing the Field Control Processor 270 B0700AR – Rev H

! WARNING
For safety reasons, always consider the possible impact on plant operations before
removing an FCP270 module from a baseplate in an active control system.

NOTE
Be aware of the following when working with FCP270 modules in self-hosting
mode:
1) When replacing a module in a fault-tolerant pair and the other module remains
running as Single Primary, plug in the new module and it will receive the image and
checkpoint file from the Primary module prior to marrying. However, when replac-
ing a module and the station is currently powered down, boot up the module that
was not replaced first before powering on the replacement module. This ensures
that the new module will be given the proper checkpoint file during its marriage.
2) When FCP270 modules are installed for the first time (that is, two fault-tolerant
modules are installed together, or one non-fault-tolerant module is installed, where
none of these modules have generated or received the checkpoint file for their control
scheme) and these modules are intended to run in self-hosting mode, they must be
booted initially in non-self-hosting mode (set by default). This ensures that the
modules download the most recent checkpoint file from the host workstation. To
ensure these modules boot-up in the default mode, change the letterbug to a non-exis-
tent letterbug and then back to desired letterbug. This ensures the FCP270 will load
the checkpoint file from the host workstation.

To install a single (non-fault tolerant) or primary (fault-tolerant) FCP270 on a modular


baseplate:
1. Install the modular baseplate to the DIN rail and connect the dc power cable and the
fieldbus/time strobe cable to the baseplate as described in DIN Rail Mounted
Subsystem User’s Guide (B0400FA). Connection to an external time strobe generator is
optional.

! CAUTION
Observe the signal and power cable separation and segregation guidelines in DIN
Rail Mounted Subsystem User’s Guide (B0400FA).

2. Install the FCP270 module (P0917YZ) by pressing it into position 1 on the


designated modular baseplate.

NOTE
1. The FCP270 can only be plugged into a baseplate connector that specifically
supports the FCP270. These baseplate slots are labeled “FCP270” (see Figure 2-1).
For example, the 4-position P0973CN modular baseplate supports two FCP270
modules and two FEM100 modules, but their connectors are physically different to
prevent a module from being installed in the wrong connector.

19
B0700AR – Rev H 2. Installing the Field Control Processor 270

3. Tighten the two self-retaining hex screws on the module using a hex driver tool
(Foxboro part number X0179AZ).

! CAUTION
1. When using the hex driver tool (Foxboro part number X0179AZ) or other
5/32 hex driver tool, make sure that it does not generate more than 12 inch pound
of torque, or you might strip the threaded inserts out of the baseplate.
2. The FCP270 module must be screwed in place for secure operation. Do not rely
on the signal connectors to hold the module in place.

4. Assign the FCP270 letterbug through the module’s infrared communication port
using the I/A Series system Letterbug Configurator. For procedures to assign
letterbugs to the FCP270, see Letterbug Configurator User’s Guide (B0700AY).

! WARNING
Make sure you assign the FCP270 letterbug before connecting the Ethernet fiber
optic cables to the FCP270. This avoids potential process control safety issues if a
letterbug has previously been assigned to the module. Label space is provided on the
front of the module to record the letterbug.
Also, when replacing a non-fault-tolerant FCP270 set to self-hosting mode, change
the letterbug to a non-configured letterbug and then to its hosted letterbug. This
ensures the correct letterbug is configured and there is no valid checkpoint file in
flash. Without following this order, there is no guarantee what letterbug is configured
for that module.

5. Connect the FCP270 module to Ethernet switches in The MESH:


 To connect a single (non-fault-tolerant) module to Ethernet switches in The
MESH, see “Cabling a Single (Non-Fault-Tolerant) FCP270 Module” on
page 25.
 To connect a fault-tolerant module to Ethernet switches in The MESH, see
“Cabling a Fault-Tolerant FCP270 Module Pair” on page 25.
The module follows one of the following boot-up sequences:
 “Case 2 – Connecting an FCP270 with the Same Letterbug” on page 30
 “Case 3 – Connecting an FCP270 with a New Letterbug” on page 30
6. If replacing an existing non-fault tolerant module, update the FCP270 software image
in the new module with the same image as the module you are replacing. See “Image
Update Procedure for a Non-Fault-Tolerant FCP270” on page 58.
If the FCP270 will run in non-self-hosting mode, the installation procedure is finished. Other-
wise, continue to the next section.

20
2. Installing the Field Control Processor 270 B0700AR – Rev H

Enabling the FCP270 Self-Hosting Option


Modify the CFGOPT parameter in the Station block to enable or disable self-hosting.
To enable self-hosting in an FCP270, use system configurator software to set the self-hosting bit
(Bit 8) of the CFGOPT parameter in the Station block (CFGOPT=0x01XX) and issue a Check-
point command. Refer to Integrated Control Block Descriptions (B0193AX) for additional informa-
tion on the CFGOPT Station block parameter.
For additional details on the operation of an FCP270 with self-hosting enabled, refer to:
 “Initializing the FCP270 with Self-Hosting Enabled” and “Verifying Self-Hosting
Information Using SMDH” below
 “Fault Tolerance Behavior in Self-Hosting FCP270” on page 33
 “Messages Following Checkpoint Operation in Self-Hosting FCP270” on page 59.

Initializing the FCP270 with Self-Hosting Enabled


Be aware that the FCP270’s database cannot be initialized with self-hosting enabled. If you try to
initialize the database on an FCP270 that is configured for self-hosting, you will get the error
message shown below. If the FCP270 is operating in self-hosting mode, you must first disable self-
hosting and perform a checkpoint as indicated in Figure 2-2 before initializing the FCP270.

Figure 2-2. Initializing a Self-Hosting Controller

Disabling Self-Hosting
To disable self-hosting in an FCP270, use system configurator software to reset the self-hosting bit
(Bit 8) of the CFGOPT parameter in the Station block (CFGOPT=0x00XX). Refer to Integrated
Control Block Descriptions (B0193AX) for additional information on the CFGOPT Station block
parameter.
The SMON log indicates the outcome of the Checkpoint command. For example, the SMON
log will contain the following line:
2007-11-03 10:03:20 FP0101 Process = Self Hosting RDHSS 000131 - Self Host-
ing Disabled

21
B0700AR – Rev H 2. Installing the Field Control Processor 270

NOTE
When an FCP270 has self-hosting enabled (CFGOPT=0x01XX) and auto-check-
point is set for 2 hours but configured for 1 hour (CKPOPT=1 and AUTCKP=2),
and self-hosting is then disabled by resetting CFGOPT to 0x00XX without altering
the CKPOPT or AUTCKP values and a checkpoint is performed, the auto-check-
point frequency continues to be 2 hours (instead of the originally configured
1 hour). For ICC only, if the desired auto-checkpoint frequency is 1 hour, place the
cursor at the AUTCKP parameter and press Enter (Return) and DONE without
any modifications and then perform a checkpoint operation for the FCP270. Also
refer to “Auto-Checkpoint While Enabling/Disabling Self-Hosting” on page 23.

Verifying Self-Hosting Information Using SMDH


The status of the FCP270’s self-hosting mode is indicated in the “Equipment Information Dis-
play for Primary ECB (FBM0)” on page 65.
The Primary ECB (FBM 0) display for the FCP270 controllers includes three fields related to
self-hosting.
 The PRIM CHK POINT and SHAD CHK POINT fields are used to display the number of
times the Primary (or Single Primary) and Shadow FCP270 module’s flash memory
has been burned.
 The SELF HOSTING field identifies the status of self-hosting. This field is set to
Enabled when the FCP270 controller is in self-hosting mode (Bit 8 of the CFGOPT
Station block parameter is set to 1), and Not Enabled when the controller is not in
self-hosting mode (Bit 8 of the CFGOPT Station block parameter is set to 0, the
default).

Verifying Self-Hosting Information Using Station Block Display


The status of the FCP270’s self-hosting mode is also indicated in the processor’s Station block dis-
play. Proceed as follows:
1. Open FoxSelect.
2. Select the FCP270’s letterbug.
3. Open the Station block for the FCP270. Refresh if necessary.
The status of self-hosting is shown under Options, as illustrated in Figure 2-3.

22
2. Installing the Field Control Processor 270 B0700AR – Rev H

If self-hosting is disabled, the following is shown:

Figure 2-3. Self-Hosting Status via Station Block Display

Auto-Checkpoint While Enabling/Disabling Self-Hosting


When you enable self-hosting in a controller, the smallest time interval allowed for the auto-
checkpoint option is two (2) hours. This is to ensure that the minimum life of a FCP270’s flash
memory for a module running auto-checkpoint full time is at least 20 years.
If you attempt to set this interval to a smaller amount, the FCP270 will override this command.
The following message may appear in the SMON log:
2008-01-24 14:56:27 FP0101 Process = Checkpoint CIO_DB 000015 - Auto Check-
point Override to 2 Hours
If this occurs, you should do one of the following to ensure the configurator’s work file reflects the
actual AUTCKP value in the FCP270:
 Using system configurator software, modify AUTCKP to reflect 2 hours and issue a
Checkpoint command.
 Perform an “Upload Block/ECB Parameters” operation from system configurator soft-
ware. This will force the FCP270 to upload its current parameter values to the work
file on the workstation.
If either of these steps is not performed when you disable self hosting, the auto-checkpoint inter-
vals will remain at two hours but the value of AUTCKP in the work file will remain unchanged.
To verify the time interval set for auto-checkpoint, view the Station Block Display for the current
FCP270 value.

23
B0700AR – Rev H 2. Installing the Field Control Processor 270

Installing a Shadow FCP270 Module


All FCP270 modules are shipped from the factory with the latest software image (operating
system) stored in flash memory. If the software image of the shadow and primary modules
differ, the shadow module copies the software image from the primary module and burns it to
flash memory before marrying the primary.
If self-hosting is enabled and the checkpoint file of the shadow and primary modules differ, the
shadow module copies checkpoint file from the primary module and burns it to flash memory
before marrying the primary.
If the letterbug of the shadow module differs from the primary module, the shadow copies the
primary’s letterbug to flash memory before marrying the primary.
Also, if the shadow module is to be run in self-hosting mode, refer to the first note on page 19.
To install a shadow (fault-tolerant) FCP270 module on a modular baseplate:
1. While holding the module (P0917YZ) in hand, install the Ethernet fiber optic cables
by connecting them to the shadow module as instructed in “Cabling a Fault-Tolerant
FCP270 Module Pair” on page 25.
2. Install the shadow FCP270 module by pressing it into the position next to the
primary module on the designated modular baseplate.
3. Tighten the two self-retaining hex screws on the module using a hex driver tool
(Foxboro part number X0179AZ).

! CAUTION
1.When using the hex driver tool (Foxboro part number X0179AZ) or other
5/32 hex driver tool, make sure that it does not generate more than 12 inch pound
of torque, or you might strip the threaded inserts out of the baseplate.
2. The FCP270 module must be screwed in place for secure operation. Do not rely
on the signal connectors to hold the module in place.

4. Verify that the shadow module boots up and marries the primary module as described
in one of the following boot-up sequences:
 “Case 4 – Connecting a Shadow Module with Same Software Image” on page 31
 “Case 5 – Connecting a Shadow Module with Different Software Image” on
page 32
5. Verify that the shadow module is married to the primary module using the
Equipment Information display in System Management to confirm the following:
PRIMARY MODE: Married Prim
SHADOW MODE: Married Shad
For more information, see “Equipment Information Display for FCP270” on
page 50.
6. Verify the following using the Equipment Information display for the FCP270 in Sys-
tem Management to confirm the following (see Chapter 4 “System Management”):
 The shadow module is married to the primary module:
PRIMARY MODE: Married Prim

24
2. Installing the Field Control Processor 270 B0700AR – Rev H

SHADOW MODE: Married Shad


 The self-hosting mode:
SELF HOSTING: Disabled (or Enabled)
The installation procedure is finished.

Cabling a Single (Non-Fault-Tolerant) FCP270 Module


! CAUTION
When installing fiber optic cable, do not exceed the minimum bend radius of 5 cm
(2 in).

To connect a single (non-fault-tolerant) FCP270 module to Ethernet switches in The MESH:


1. Remove any rubber fiber optic port dust covers from the module’s Control Network A
and B ports, Ethernet switches ports, and fiber cable connectors. Retain the dust
covers for use on any unused ports.
2. Connect the Control Network A connector on the FCP270 to one Ethernet Fiber
switch (switch 1) in The MESH using 100 Mbps fiber optic cable with LC to MT-RJ
connectors (see Table 2-1).
3. Connect the Control Network B connector on the FCP270 to another Ethernet Fiber
switch (switch 2) in The MESH using 100 Mbps fiber optic cable with LC to MT-RJ
connectors (see Table 2-1).

Table 2-1. Cables for Connecting the FCP270 or Splitter/Combiners to the Ethernet Switches

Part Number Length Material


P0972TR 3 m (9.8 ft) MMF 62.5/125 µm, orange riser. Two ceramic type LC connec-
tors on one end with an MT-RJ connector on the other end.
P0972TS 15 m (49.2 ft) MMF 62.5/125 µm, orange riser. Two ceramic type LC connec-
tors on one end with an MT-RJ connector on the other end.
P0972TT 50 m (164 ft)1 MMF 62.5/125 µm, orange riser. Two ceramic type LC connec-
tors on one end with an MT-RJ connector on the other end.
1.
For fiber optic cable lengths greater than 50 m (164 ft), use a customer-supplied cable up to a max-
imum length of 2 km (6562 ft).

Cabling a Fault-Tolerant FCP270 Module Pair


To cable the fault-tolerant FCP270 module pair, you must first install the splitter/combiners to
split inbound traffic to the modules and combine outbound traffic from the modules. The
splitter/combiners connect the fault-tolerant modules to Ethernet fiber switches in The MESH
using fiber optic cables. The cabling scheme for an FCP270 on a two-position baseplate is shown
in Figure 2-4, while the cabling scheme for an FCP270 on a four-position baseplate is shown in
Figure 2-5.

25
B0700AR – Rev H 2. Installing the Field Control Processor 270

The cable color scheme helps you to properly connect the fiber cables to the splitter/combiners
and modules so that the FCP270 can operate in the fault-tolerant mode. However, you can use
fiber cables of any color to make these connections.

To/From To/From
The MESH Control Network The MESH Control Network
DC Power
Ethernet Fiber Switch 1 Ethernet Fiber Switch 2
Connector

100 Mbps Orange Baseplate Baseplate


MMF Fiber Cables Position 1 Position 2
See Table 2-1
FCP270 Fault-Tolerant
Module Pair
Splitter/Combiner Pair

Port 1 + 2
Port 1
Port 2

100 Mbps Orange Duplex


Fiber Cable (P0972VG) 100 Mbps Gray Duplex
Fiber Cable (P0972UN)
Notes:
1. Port labeled “1 + 2” on the splitter/combiner connects to one Ethernet Fiber switch.
2. Port labeled “1” on the splitter/combiner connects to the FCP270 mounted in baseplate position 1.
3. Port labeled “2” on the splitter/combiner connects to the FCP270 mounted in baseplate position 2.

Figure 2-4. Cabling the FCP270 Fault-tolerant Controllers (Two-Position Baseplate Example)

26
2. Installing the Field Control Processor 270 B0700AR – Rev H

To/From
The MESH Control Network
To/From FCP270 Fault-Tolerant
Ethernet Fiber Switch 2
The MESH Control Network Module Pair
Ethernet Fiber Switch 1 Baseplate Baseplate DC Power
Position 1 Position 2 Connector
100 Mbps Orange
MMF Fiber Cables
See Table 2-1

Optional
Splitter/
Terminator
Splitter/ P0916RB/
Combiner P0926KZ
Pair

To/From
To/From Expanded
Expanded Fieldbuses
Fieldbuses 1-2
3-4

FEM100 FEM100
Module Module
(Bus A) (Bus B)
Notes:
1. Port labeled “1 + 2” on the splitter/combiner connects to one Ethernet Fiber switch.
2. Port labeled “1” on the splitter/combiner connects to the FCP270 mounted in baseplate position 1.
3. Port labeled “2” on the splitter/combiner connects to the FCP270 mounted in baseplate position 2.

Figure 2-5. Cabling the FCP270 Fault-tolerant Controllers (Four-Position Baseplate Example)

27
B0700AR – Rev H 2. Installing the Field Control Processor 270

! CAUTION
1. Failure to properly connect the cables will result in the modules not being able to
operate in a fault-tolerant mode.
2. When installing fiber optic cable, do not exceed the minimum bend radius of
5 cm (2 in).

The splitter/combiners (P0926AH) install in an I/A Series enclosure on the following:


 DIN rail mounted modular baseplate
 DIN rail
 Chassis assembly.
For detailed mounting procedures for the splitter/combiners, refer to DIN Rail Mounted FBM
Subsystem User’s Guide (B0400FA).
To connect the splitter/combiners to The MESH Ethernet switches and fault-tolerant FCP270
modules, see Figure 2-4 and proceed as follows:
1. Remove any rubber fiber optic port dust covers that are installed in the module’s
Control Network A and B ports, splitter/combiner ports, Ethernet switch ports, and
cable connectors. Retain the dust covers for use on any unused ports.
2. Connect the port labeled “1 + 2” on one splitter/combiner to one Ethernet fiber
switch (switch 1) in The MESH using 100 Mbps fiber optic cable with LC to MT-RJ
connectors (P0972TR, P0972TS or P0972TT in Table 2-1, or custom cable up to
2 km (6400 ft) in length).
3. Connect port “1 + 2” on the other splitter/combiner to another Ethernet fiber switch
(switch 2) in The MESH using 100 Mbps fiber optic cable with LC to MT-RJ con-
nectors (P0972TR, P0972TS or P0972TT in Table 2-1, or custom cable up to 2 Km
(6400 ft) in length).
4. Connect port 1 on the splitter/combiner for switch 1 to the Control Network A con-
nector on the FCP270 in baseplate position 1 using orange duplex fiber optic cable
with LC to LC connectors (P0972VG in Table 2-2).
5. Connect port 2 on the splitter/combiner for switch 1 to the Control Network A con-
nector on the FCP270 in baseplate position 2 using orange duplex fiber optic cable
with LC to LC connectors (P0972VG in Table 2-2).
6. Connect port 1 on the splitter/combiner for switch 2 to the Control Network B
connector on the FCP270 in baseplate position 1 using gray duplex fiber optic cable
with LC to LC connectors (P0972UN in Table 2-2).
7. Connect port 2 on the splitter/combiner for switch 2 to the Control Network B
connector on the FCP270 in baseplate position 2 using gray duplex fiber optic cable
with LC to LC connectors (P0972UN in Table 2-2).

28
2. Installing the Field Control Processor 270 B0700AR – Rev H

Table 2-2. Cables for Connecting the Splitter/Combiners to the FCP270

Part Number Length Material


P0972UN 0.5 m (1.6 ft) MMF 62.5/125 µm, gray riser. Ceramic type LC
connectors with clip on each end.
P0972VG 0.5 m (1.6 ft) MMF 62.5/125 µm, orange riser. Ceramic type LC
connectors with clip on each end.

Boot-Up Sequence
The boot up sequence for the FCP270 has the following typical cases:
 Case 1: Rebooting a commissioned FCP270 module.
 Case 2: Connecting a module with the same letterbug to the baseplate with the
Ethernet network cables connected.
 Case 3: Connecting a module with a new letterbug to the baseplate with the Ethernet
network cables connected.
 Case 4: Connecting a shadow module with the same software image to the baseplate,
after the primary module has booted up, loaded the checkpoint file, and initialized
on-control.
 Case 5: Connecting a shadow module with different software image to the baseplate,
after the primary module has booted up, loaded the checkpoint file, and initialized
on-control.
The boot up sequence for above cases are described in the following five sections.

NOTE
For procedures to assign letterbugs to the FCP270, see Letterbug Configurator User’s
Guide (B0700AY).

NOTE
For FCP270s in self-hosting mode, a 14 second delay occurs before the module
attempts to download its checkpoint file from flash memory.

Case 1 – Rebooting a Commissioned FCP270


When a Reboot command is issued to a commissioned FCP270 controller running non-fault-
tolerant, the operational sequence is as follows:
1. The controller lights the red Operational Status LED while running the on-line
diagnostics.
2. If the on-line diagnostics test results are OK, the controller lights the red and green
Operational Status LEDs and performs other internal tests.
3. If the internal test results are OK, the controller lights the green Operational Status
LED and turns off the red LED.

29
B0700AR – Rev H 2. Installing the Field Control Processor 270

4. In non-self-hosting mode, the controller loads the checkpoint file (control database)
from the host server.
In self-hosting mode, the controller either loads the checkpoint file (control database)
from the host server and performs a checkpoint operation if it does not have the
checkpoint file in flash memory, or it loads the checkpoint file from its internal flash
memory if the file is present.
5. The controller initializes on-control as defined by the control database.

Case 2 – Connecting an FCP270 with the Same Letterbug


When connecting to the baseplate an FCP270 module with the same letterbug as the removed
module, with The MESH network cables connected, the operational sequence is the same as for
Case 1.
The controller reboots, loads the checkpoint file from the host, and initializes on-control as
described in Steps 1 through 5 in Case 1.

! WARNING
Make sure you assign the FCP270 letterbug before connecting the Ethernet fiber
optic cables to the FCP270. This avoids potential process control safety issues if a
letterbug has previously been assigned to the module. Label space is provided on the
front of the module to record the letterbug.
Also, when replacing a non-fault-tolerant FCP270 set to self-hosting mode, change
the letterbug to a non-configured letterbug and then to its hosted letterbug. This
ensures the correct letterbug is configured and there is no valid checkpoint file in
flash.
Without following this order, there is no guarantee what letterbug is configured for
that module. The FCP270 may attempt to boot up with an obsolete checkpoint file
that is stored in its flash, which could have an adverse effect on the process running.

Case 3 – Connecting an FCP270 with a New Letterbug


A “new letterbug” is a letterbug for a station which has not been commissioned to date.

NOTE
If the letterbug of a FCP270 is changed, the checkpoint file in flash memory is
invalidated. The next time the FCP270 reboots, it will load the checkpoint file from
the host workstation.

When connecting an FCP270 module with a new letterbug to the baseplate, with The MESH
network cables connected, the operational sequence is as follows:
1. The controller boots up as described in Steps 1 through 3 in Case 1.
2. The controller loads the network addresses from the host server.
3. The controller reboots, loads the checkpoint file from the host, and initializes on-con-
trol as described in Steps 1 through 5 in Case 1.

30
2. Installing the Field Control Processor 270 B0700AR – Rev H

Case 4 – Connecting a Shadow Module with Same Software


Image
When connecting a shadow module with the same software image as the primary module to the
baseplate – after the primary module has booted up, loaded the checkpoint file, and initialized
on-control – the operational sequence is as follows:
1. The shadow module boots up as described in Steps 1 through 3 in Case 1.
2. If the station is in self-hosting mode and the checkpoint file in flash of the shadow
module differs from the checkpoint file in flash of the primary module or the shadow
module lacks a checkpoint file, the shadow controller lights the red Operational Status
LED while the green LED remains on.
3. The shadow module copies the checkpoint file from the primary module and burns it
to flash memory.
If the checkpoint operation succeeds, messages similar to the following examples are
sent to the SMON log:
2008-01-21 13:53:11 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint update Needed
2008-01-21 13:53:28 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint File Sent
These messages are sent by the primary module and only indicate that the primary has
sent the checkpoint file to the shadow module. The shadow module still has to write
the checkpoint file to its flash. This process could take more than a minute before the
shadow module has completed the write to flash.
If the checkpoint operation fails, messages similar to the following examples are sent
to the SMON log by the primary module:
2008-01-21 13:52:43 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint update Needed
2008-01-21 13:53:00 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint Incomplete - Reboot Shadow
2008-01-21 13:53:00 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint File Sent
Then, one of two scenarios will occur:
 The shadow module will reboot automatically to reinitiate the marriage process.
 The shadow module will remain in the red/green LED state and not reboot. In
this scenario, you must reboot the Shadow module manually to restart the mar-
riage process.
4. The shadow module boots up again as described in Steps 1 through 4 in Case 1.
5. If the letterbug of the shadow module differs from the primary module, the shadow
copies the primary’s letterbug to flash memory.
6. The shadow module marries the primary module, as indicated by the single, simulta-
neous quick flashing of the red Operational Status LED on both modules, then the
modules run fault tolerant.
The marriage should occur within 10 seconds, except for the following conditions
when the station is in self-hosting mode:
 If the primary module (in Single Primary mode) is downloading the checkpoint
file from flash memory, the marriage will be held off until the download is com-

31
B0700AR – Rev H 2. Installing the Field Control Processor 270

plete. The shadow module's LEDs will remain green while it waits for the mar-
riage to occur.
 If the primary module (in Single Primary mode) is performing a checkpoint,
which includes a write to its flash, the marriage will be held off until the check-
point operation is complete. The shadow module's LEDs will remain green while
it waits for the marriage to occur.

Case 5 – Connecting a Shadow Module with Different Software


Image
When connecting a shadow module with a different software image than the primary module to
the baseplate – after the primary module has booted up, loaded the checkpoint file, and initialized
on-control – the operational sequence is as follows:
1. The shadow module boots up as described in Steps 1 through 3 in Case 1.
2. Since the shadow module’s software image differs from the primary module, the
controller lights the red Operational Status LED while the green LED remains on.
3. The shadow module copies the software image from the primary module and burns it
to flash memory.
4. The shadow module boots up again as described in Steps 1 through 3 in Case 1.
5. If the station is in self-hosting mode and the checkpoint file in flash of the shadow
module differs from the checkpoint file in flash of the primary module or the shadow
module lacks a checkpoint file, the shadow controller lights the red Operational Status
LED while the green LED remains on.
6. The shadow module copies the checkpoint file from the primary module and burns it
to flash memory.
If the checkpoint operation succeeds, messages similar to the following examples are
sent to the SMON log:
2008-01-21 13:53:11 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint update Needed
2008-01-21 13:53:28 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint File Sent
These messages are sent by the primary module and only indicate that the primary has
sent the checkpoint file to the shadow module. The shadow module still has to write
the checkpoint file to its flash. This process could take more than a minute before the
shadow module has completed the write to flash.
If the checkpoint operation fails, messages similar to the following examples are sent
to the SMON log by the primary module:
2008-01-21 13:52:43 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint update Needed
2008-01-21 13:53:00 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint Incomplete - Reboot Shadow
2008-01-21 13:53:00 FP0101 Process = Flash Loader RDHSS 000131 -
Shadow Checkpoint File Sent
Then, one of two scenarios will occur:
 The shadow module will reboot automatically to reinitiate the marriage process.

32
2. Installing the Field Control Processor 270 B0700AR – Rev H

 The shadow module will remain in the red/green LED state and not reboot. In
this scenario, you must reboot the Shadow module manually to restart the mar-
riage process.
7. The shadow module boots up again as described in Steps 1 through 3 in Case 1.
8. If the letterbug of the shadow module differs from the primary module, the shadow
copies the primary’s letterbug to flash memory.
9. The shadow module marries the primary module, as indicated by the single, simulta-
neous quick flashing of the red Operational Status LED on both modules. Then the
modules run fault tolerant.
The marriage should occur within 10 seconds, except for the following conditions
when the station is in self-hosting mode:
 If the primary module (in Single Primary mode) is downloading the checkpoint
file from flash memory, the marriage will be held off until the download is com-
plete. The shadow module's LEDs will remain green while it waits for the mar-
riage to occur.
 If the primary module (in Single Primary mode) is performing a checkpoint,
which includes a write to its flash, the marriage will be held off until the check-
point operation is complete. The shadow module's LEDs will remain green while
it waits for the marriage to occur.

NOTE
Since the shadow module assumes the software image and letterbug of the primary
controller, the boot up sequence can be used to identify the shadow controller if its
letterbug and ID are both unknown. When the shadow controller is married, its
letterbug is now known and its Manufacturing ID can be viewed from the
Equipment Information display in System Management, where the ID is the last six
characters of the SHAD ROM ADDRESS in Figure 4-2 on page 51.

Fault Tolerance Behavior in Self-Hosting FCP270


When a fault-tolerant FCP270 station is running in self-hosting mode, the primary module
ensures that its shadow module has a matching version of the checkpoint file in flash before allow-
ing the shadow module to marry with the primary module. To be sure that the files match, the
FCP270s maintain the following behaviors:
 When a fault-tolerant pair of FCP270s are running in self hosting mode, and a check-
point command is issued, the fault-tolerant station sends the checkpoint file to the
host workstation. When the process sending the checkpoint file to the host is com-
plete, the FCP270 station requests that checkpoint file from the host and copies the
file to flash in both the primary and shadow module.
 If two fault-tolerant FCP270 modules, with a newly assigned letterbug, are booted up,
the modules will marry and load the checkpoint file from the host workstation. If self-
hosting is enabled (i.e. the CFGOPT parameter in the checkpoint file has self-hosting
enabled), the FCP270 station will automatically issue a checkpoint command at the
completion of the checkpoint download. As part of the checkpoint process for self-

33
B0700AR – Rev H 2. Installing the Field Control Processor 270

hosting, the checkpoint file is burned into both the primary and shadow modules’
flash memory.
 When a new FCP270 module is booted up, with the intention of marrying with a
FCP270 that is running as Single Primary mode, and the station is configured for self-
hosting mode, the Single Primary module first downloads its checkpoint file to the
shadow module before the shadow module is allowed to marry the Single Primary
module.
If the Single Primary module is downloading the checkpoint file from flash memory
or writing the checkpoint file from the host to flash, the marriage will be held off until
all operations to the Single Primary flash have completed. Normally, a marriage takes
a maximum of 10 seconds to occur when self-hosting is not enabled. However, in this
case the marriage may be held off longer than 10 seconds. Operations should not be
adversely affected.
 If one module of a fault-tolerant pair fails to burn a checkpoint file to flash success-
fully and the other module does succeed, the module that fails to burn to flash will
invalidate the checkpoint file in flash and go off-line. The module that successfully
burns to flash transitions to Single Primary and sends an error message to the SMON
log indicating why the other module went off-line.
 If both modules of a fault-tolerant pair fail to burn the checkpoint file to flash success-
fully, both modules will invalidate the checkpoint file in flash and send an error
message to the SMON log. The station continues to run fault-tolerant and will
attempt to load a new checkpoint file on the next checkpoint command or from their
host when they are rebooted.
 If a non-fault-tolerant module fails to burn a checkpoint file to flash successfully, the
module invalidates the checkpoint file in flash and sends an error message to the
SMON log. The station continues to run as Single Primary and will load a new
checkpoint file on the next checkpoint command or from its host when it is rebooted.

Cabling Y-Module FBMs to an FCP270 Baseplate


Cabling Y-module FBMs to an FCP270 baseplate consists of extending the remote 268 Kbps
fieldbus from the FBM mounting structure (see Figure 2-6). This extension, used between enclo-
sures, involves the use of termination cable assemblies (TCAs) and Fieldbus Isolators (FBIs) to
provide cable connections between primary and extended fieldbus segments, for a maximum
fieldbus length of 1 km (3200 ft).
The FBI200 or FBI100 must be installed between the remote 268 Kbps fieldbus and the FCP270
in order to support the dual baud functionality and/or extend the length of the 268 Kbps field-
bus.
If the fieldbus is non-redundant, only one TCA is connected to the fieldbus splitter/terminator
(P0926LC - shown in Figure 2-7) or to the FBI200 baseplate (P0924RT) or the FBI100 baseplate
(P0923LR). (The connections to these baseplates are also shown in Figure 2-7.) TCA part num-
ber P0903VY includes a strain relief bracket, labels for bus A and B, and a 110 ohm terminating
resistor. You must install one of the labels on the TCA (see Figure 2-6 for label orientation).
You can mount the FCP270 module(s) on either the two-position, vertical DIN rail mounted
baseplate (P0926HW) or the two-position, horizontal DIN rail mounted baseplate (P0926HC).

34
2. Installing the Field Control Processor 270 B0700AR – Rev H

The optional FBI200 or FBI100 modules(s) are only available on a two-position, vertical DIN
rail mounted baseplate (P0924RT for the FBI200, P0923LR for the FBI100).

Remote Fieldbus Extension, Cable Connections


Remote fieldbus extension cable connections are implemented as shown in Figure 2-6 and
Figure 2-10. For cable connections to the Fieldbus Isolator TCA, refer to “Remote Fieldbus
Extension, Cable Connections” in I/A Series System Equipment Installation (B0193AC).
To make the remote fieldbus extension cable connections:
1. Assemble the termination blocks associated with the termination cable assemblies
(P0903VY), snap them onto the mounting rails (DIN rails) in the enclosure (as
shown in Figure 2-8), and connect the ground wires. (For future reference, Figure 2-9
illustrates how to remove the TCA termination blocks.)
If you are not installing the FBI200/FBI100 modules in your configuration, refer to
Figure 2-7 to see how to connect the TCAs directly to the fieldbus splitter/terminator
(P0926LC).
If you are installing the FBI200 or FBI100 modules in your configuration, refer to
“Cabling the FCP270 to the 268 Kbps or 2 Mbps Fieldbus Via the FBI200 or
FBI100” in DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA) for instruc-
tions on how to connect the TCAs directly to the FBI200 or FBI100 baseplate.
2. For configurations without FBI200/FBI100 modules, connect the fieldbus split-
ter/terminator (P0926LC) to the “Fieldbus and Time Strobe” connector on the
FCP270 baseplate (see Figure 2-6). Refer to “Cabling the FCP270 to the 268 Kbps or
2 Mbps Fieldbus (Without FBI100)” in DIN Rail Mounted FBM Subsystem User’s
Guide (B0400FA).
3. For configurations without FBI200/FBI100 modules, make cable connection(s) to
the fieldbus splitter/terminator as shown in Figure 2-7.
For configurations with FBI200/FBI100 modules, make cable connection(s) to the
FBI200 or FBI100 baseplate as shown in Cabling the FCP270 to the 268 Kbps Field-
bus Via the FBI200 or FBI100” in DIN Rail Mounted FBM Subsystem User’s Guide
(B0400FA).
4. Make the fieldbus cable connections between termination cable assemblies (see
Figure 2-10).
5. Add the terminating resistors (supplied with the termination cable assemblies) accord-
ing to the following rules:
 Terminating resistors are used only at the ends of the bus.
 The Fieldbus can be extended in two directions from the FCP270. (Refer to
Figure 2-11.)
6. Connect an insulated 14 AWG green wire between connection point 3 (shield) on the
last Fieldbus Isolator termination cable assembly (or assemblies) and the earth bus in
the enclosure. For I/A Series system earthing requirements, refer to Power, Earthing
(Grounding), EMC and CE Compliance (B0700AU).

35
B0700AR – Rev H 2. Installing the Field Control Processor 270

Customer Installed Label Termination Cable


Assemblies
(P0903VY)
Fieldbus A

Vertical DIN Rail Mounted


Baseplate (P0926HW)
with Fault-Tolerant
FCP270 Modules
Fieldbus B

268 Kbps Fieldbus


Splitter/Terminator
(P0926LC)

No Terminator on
this connector

14 Gauge Twinaxial Cables


1 Km (3200 ft) Maximum
(P0170GF or P0170GG)
~~

Wire Connection to
Enclosure Earth Bus
Fieldbus Isolator
Termination Cable
Assemblies (P0800DC)

1X8 FBM Mounting Structure


with Fieldbus Isolators

Mounting Slots for


Y-Module FBMs

Figure 2-6. Cabling Y-Module FBMs to an FCP270 Baseplate (Without FBI200s/FBI100s)

36
2. Installing the Field Control Processor 270 B0700AR – Rev H

Fieldbus A TCA
Cable Connector

Baseplate (P0926HW)

268 Kbps Fieldbus


Splitter/Terminator
(P0926LC)

Fieldbus B TCA
Cable Connector

Figure 2-7. TCA Cable Connection to 268 Kbps Fieldbus Splitter/Terminator


(Without FBI200s/FBI100s)

Slide strain relief bracket onto TCA Connect ground wire to DIN rail using
1 3
termination block. screw, lock washer and nut (customer
supplied).
Snap assembled termination block
2
onto DIN rail.

TCA Termination Block

Earth (Ground) Wire

Screw

Lock Washer
Strain Relief Bracket
DIN Rail
Ring Lug

Figure 2-8. TCA Termination Block Assembly Mounting

37
B0700AR – Rev H 2. Installing the Field Control Processor 270

1 Disconnect the earth wire from 3 Move the screw drive handle in the
from the DIN rail. direction shown, while lifting the TCA
termination block from the DIN rail.

2 Insert a medium-size flat-head


screw driver as shown.

Lift

Earth (Ground) Wire

Screw
Washer
Move
TCA Termination Block

Figure 2-9. TCA Termination Block Removal

38
2. Installing the Field Control Processor 270 B0700AR – Rev H

Termination Cable Assemblies (2)


(P0903VY)
100 Ohm Twinaxial
Cable P0170GF,
P0170GG, or
Note 1
Equivalent

Note 2
Note 3 Note 3
BK BK
Fieldbus A
W W To Fieldbus
Fieldbus B Isolator TCA
SH SH (See B0193AC)
F F- S F F- S
F F- S Note 5 F F- S

Fieldbus Fieldbus
Note 4 Note 4
B A

B B
BR G/Y BR G/Y
F+ F- SH F+ F- SH

To Splitter/Terminator
(P0926LC)

Notes:
1. For cable strain relief, it is recommended that the Fieldbus cable(s) be routed over the strain
relief bracket and secured using nylon cables ties.
2. TCAs can be daisy chained as indicated by the dashed cable lines, but terminating resistors
(110 ohms) must be installed at the ends of the fieldbus.
3. Wire colors shown (BK and W) are for reference purposes only.
4. Earth (ground) the surge protection network contained within the TCAs by attaching the green
earth wire to a screw on the DIN rail connected to system earth. For more information on earth-
ing, refer to Power, Earthing (Grounding), EMC and CE Compliance (B0700AU).
5. The shield of the twinaxial cable (terminal 3) should be earthed at the farthest end from the
FCP270 baseplate. The fieldbus shield must be earthed at one end only. (See text for
earthing instructions.)

Figure 2-10. Remote Redundant Fieldbus Cabling (FCP270 End)

39
B0700AR – Rev H 2. Installing the Field Control Processor 270

Termination Cable Assembly


(P0903VY)

SH
To Next Fieldbus
Isolator Termination W BK To Next Fieldbus
Cable Assembly Isolator Termination
(See Notes 1, 2 and 4) BK W Cable Assembly
SH (See Notes 1, 2, 3 and 4)

F F- S
F F- S

Fieldbus
A

B
BR G/Y
F+ F- SH
To Splitter/Terminator
(P0926LC)

Notes:
1. Earth the shield (terminal 3) at the termination cable assembly farthest from the FCP270
baseplate.
2. Install terminating resistors at both ends of the extended fieldbus cable. For the last TCA
in the fieldbus, install the termination resistor between terminals 1(F) and 2(F-) and the
earth (ground) wire (14 Gauge) must connect to terminal 3(S) as shown in Figure 2-6.
3. If this TCA is the last TCA in the fieldbus, the cable on this side of the TCA will not be
added.
4. Earth (ground) the surge protection network contained within the TCAs by attaching the
green earth wire to a screw on the DIN rail connected to system earth. For more informa-
tion on earthing, refer to Power, Earthing (Grounding), EMC and CE Compliance
(B0700AU).

Figure 2-11. Example of Extending Fieldbus in Two Directions from FCP270

40
2. Installing the Field Control Processor 270 B0700AR – Rev H

Decommissioning an FCP270 Module


You can decommission an FCP270 module that you no longer plan to use. For example, you want
to remove the FCP270 from the system and place it into storage.
Perform the following procedure to guarantee that when you remove the module for use in
another application, the module will not load a stale checkpoint file out of its flash memory.
Proceed as follows:
1. Plug the module into the system without connecting to The MESH control network.
2. Set the station letterbug to a non-existent value, such as NOSUCH, using the
I/A Series Letterbug Configurator.
3. Allow the module to reboot to accept the new letterbug.
4. Read the module status with the I/A Series Letterbug Configurator. The letterbug
should be the non-configured value, and the IP address should be 255.255.255.255.
The FCP270 module can be removed now.

41
B0700AR – Rev H 2. Installing the Field Control Processor 270

42
3. Configuration Information
This chapter provides system configuration information (System Definition) and control
configuration information.

Overview
In general, “configuration” refers to the act of specifying to the I/A Series system software the
types of hardware and software modules that comprise the system, and the control blocks that will
be used in the control scheme. Prior to performing configuration procedures, you are encouraged
to develop I/O signal lists. You should develop loop control schemes and loop drawings to docu-
ment the control scheme. From the signal lists and loop drawings, you can determine the type and
quantity of equipment required for your control scheme.

System Definition
Your system configurator application is used to identify the I/A Series system components, system
software required by each component, the system component letterbugs, and other system charac-
teristics for correctly loading system software and identifying the system software objects. System
definition with your system configurator produces a Commit disk, which is required for software
installation and, therefore, must be completed before software installation. It is initially performed
prior to installation of the system equipment, and it is updated with any hardware/
software system changes. Reports produced by the system configurator define the network of the
system and provide information that can be used in conjunction with equipment installation. In
the future, if changes are made to the initial hardware layout, the system definition database must
be updated to reflect these changes.
Using the system configurator, you define the type and quantity of FCP270s and associated
FBMs, their letterbugs, and the software (for example, digital input, ladder logic, and so forth) for
the FBMs. Letterbugs are unique, 6-character strings that identify stations, such as FCP270s and
FBMs, to the I/A Series system software.

NOTE
Before loading a SaveAll control database from a CP60 or previous control proces-
sor onto an FCP270, make sure all the ECBs are supported by the FCP270. For
example, ECB110 (for FCM10s) is not supported by the FCP270.
Failing to do this will block ALL the ECBs (invalid and valid) from being loaded
into the new FCP270.

System Definition Procedure


To perform system definition, configure the I/A Series system as described in the corresponding
document provided with your system configurator.
After you have completed system definition, install the system software. Refer to the appropriate
Hardware and Software Specific Instructions for your workstation.

43
B0700AR – Rev H 3. Configuration Information

To use Y-module FBMs (100 Series FBMs) with your FCP270s, use your applicable system con-
figurator to create and configure the required ECBs. Refer to the documentation included with
your system configurator to complete the process.

System Configuration
When you have defined and installed the FCP270, you are ready to configure your control system
and download the control database to the FCP270. System configuration comprises designing
your control strategy loop diagrams and configuring the compounds and control blocks for these
loops. The FCP270 control database consists of configuration data for the compounds and associ-
ated control blocks, including Equipment Control Blocks (ECBs) required for the FBMs and the
FCP270.
As a compound/block editor, the Invensys system configurators provide compound or block
building templates along with a full range of editing functions.
In general, you create a compound in which to locate control blocks for a specific control strategy,
for example, the blocks required to control the outlet temperature of a heat exchanger. Then, you
create the blocks required for implementing the control strategy.
For each FBM, you create a specific ECB which serves as a “holding place” for the FBM data. The
primary ECB for the FCP270 control station is automatically created by the system configurator.
The ECBs provide the software interface between the I/O control blocks and the FBMs. Actual
control of the process is performed by compounds, consisting of control blocks, which you
configure. Figure 3-1 shows a typical application of control blocks.

44
3. Configuration Information B0700AR – Rev H

4-20 MA Remote Setpoint


AIN

4-20 MA Meas.
AIN PID
FBM204 ECB2

4-20 MA Output
AOUT
To/From
Process

Contact
Out Alarm
Status High
COUT
Contact FBM241 ECB5 Alarm
Out Status Low
COUT

Control Compound

Primary
ECB

<Letterbug>_ECB Compound

FCP270 Controller

I/A Series System Enclosure

Notes:
1. For ECB parameters definitions and ECB to FBM assignments, refer to
Integrated Control Block Descriptions (B0193AX).
2. The Primary ECB is automatically assigned to a compound named <Letterbug>_ECB,
for example, if an FCP letterbug is H51FCP, the compound name is H51FCP_ECB.

Figure 3-1. Typical Control Scheme Using an FCP270 and 200 Series FBMs

45
B0700AR – Rev H 3. Configuration Information

Available I/A Series System Control Blocks


The I/A Series system offers a wide range of control blocks, providing solutions for a broad
spectrum of process control applications. For details on the selection and usage of control blocks,
refer to Integrated Control Block Descriptions (B0193AX).
You can use the following control blocks in conjunction with the FCP270:
ACCUM CHARC FFTUNE MEALM PLSOUT STROUT
AIN CIN GDEV MON PLB SWCH
AI CINR IIN MOVLV PTC TIM
AINR CMP IINR MSG RAMP VLV
ALMPRI COUT IND MTR RATIO
AO COUTR IOUT OUTSEL REAL
AOUT DEP LIM PACK REALM
AOUTR DGAP LLAG PAKIN RIN
BIAS DI LOGIC PAKINR RINR
BIN DO LONG PAKOUT ROUT
BINR DPIDA MAI PATALM ROUTR
BLNALM DSI MAIN PATT SIGSEL
BOOL DTIME MATH PID STA
BOUT ECBP MAO PIDA STALM
BOUTR EVENT MCIN PIDE STATE
CALC EXC MCOUT PIDX STRIN
CALCA FBTUNE MDACT PIDXE STRING

46
3. Configuration Information B0700AR – Rev H

System Configuration with Dual Baud Functionality


The FCP270 can communicate with both 200 Series FBMs (over 2 Mbps signals) and 100 Series
FBMs (over 268 Kbps signals) simultaneously and safely when the FBI200 or FBI100 is properly
installed between the FCP270 and 100 Series FBMs. The FBI200 or FBI100 filter out the
2 Mbps signals, allowing only the 268 Kbps signals through.
The process for setting up this hardware configuration with the FBI200 or FBI100 is discussed in
DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA).
The process for setting up this hardware configuration with the FBI200A is discussed in
100 Series Fieldbus Module Upgrade User's Guide (B0700BQ).
However, additional I/O overhead is incurred each BPC cycle for both inputs and outputs when
the FCP270 has to perform baud switching to accommodate the different I/O baud rates
(2 Mbps versus 268 Kbps).
The FCP270 scan order is based on the configuration order of compounds and ECBs for the I/O
input scan cycle and the I/O output scan cycle. For example, during the I/O input scan cycle, first
the ECB compound and all its ECBs are processed, followed by the first compound and all its
ECBs, following by the second compound and all its ECBs, and so forth. This is also the case for
the I/O output scan cycle.
To eliminate unnecessary baud switching and achieve maximum I/O scan efficiency, you must
configure your compounds and ECBs for all 100 Series FBMs, followed by all compounds and
ECBs for all 200 Series FBMs.
When upgrading 100 Series FBMs to 200 Series FBMs in a dual baud configuration, you only
need to change the configuration order if you wish to increase I/O performance. The increase in
200 Series FBMs performance versus 100 Series FBMs will compensate for any efficiency loss due
to baud switching.

47
B0700AR – Rev H 3. Configuration Information

48
4. System Management
This chapter provides general system management information for the Field Control
Processor 270. It also provides references to the manuals that describe the tools you use to
perform in-depth system management tasks.

Overview
The general I/A Series system management philosophy applies to the Field Control Processor 270
in the I/A Series system. Through the System Management Displays, you can receive status infor-
mation on the FCP270 and send change requests to the FCP270.
System management for the FBMs is supported on the following system management tools:
 I/A Series System Manager v2.1 or later (supported on I/A Series system software v8.6
or later) - discussed in I/A Series System Manager (B0750AP)
 SMDH - discussed in System Management Displays (B0193JC)
 FoxView™ - discussed in Process Operations and Displays (B0700BN)
The security of this system is maintained via the standard I/A Series control processor software
and the customer-engineered user interface to the control block database. All access to the I/O
data is through the control blocks. The end user has no direct access to any of the I/O functions
or the data in the FBMs.

Operating Status
The operating status of the FCP270 is reported by the I/A Series system using on-screen and
printed messages. Refer to the following documents for information on the reporting of equip-
ment operating status and errors:
 I/A Series System Manager (B0750AP)
 I/A Series System Management Displays (B0193JC)
 I/A Series System V8.x System Error Messages (B0700AF)
 I/A Series Process Operations and Displays (B0700BN).

System Management Displays for the FCP270


The I/A Series System Manager and System Management Display Handler (SMDH) allow you to
access:
 Equipment information
 Configuration information
 Equipment change actions.
These displays reflect the system’s current operating status and provide a valuable maintenance aid
by allowing you to observe the current operating status of the various system elements and
intervene in system operations.

49
B0700AR – Rev H 4. System Management

For information on navigating through the System Manager, see I/A Series System Manager
(B0750AP).
For information on navigating through the SMDH screens, see System Management Displays
(B0193JC).

Equipment Information Display for FCP270


The SMDH Equipment Information display pages (Figure 4-1 and Figure 4-2) for the FCP270
contain operational status, equipment change action status, hardware and software information.
Table 4-1 describes the available text fields in the order that they appear on the display pages,
from left column to right column.

Figure 4-1. Equipment Information Display for FCP270 – Typical (1 of 2)

50
4. System Management B0700AR – Rev H

Figure 4-2. Equipment Information Display for FCP270 – Typical (2 of 2)

Table 4-1. Equipment Information Display Fields for FCP270

Field Description
STATION NAME Controller letterbug assigned during definition of system hardware.
RUN MODE On-line or Off-line. This field is initially Off-line. It changes to On-
line when the FCP270 reports to the System Monitor after booting up.
If reporting is disabled, the last known state appears in this field.
RUN MODE and FAIL STATE should be viewed as separate, but
related fields. Although certain Equipment Change options change the
RUN MODE to Off-line, they do not fail the station. However, a
failed station will result in the RUN MODE changing to Off-line.
The field changes to Off-line if any of the following occur:
 Reboot of the station
 EEPROM update
 Power failure
 Any station hardware failure or communication failure that
results in the station no longer being able to send its internal
reports for one minute or more.
For fault-tolerant stations, see the PRIMARY MODE and SHADOW
MODE fields for current RUN MODE of each module of the pair.

51
B0700AR – Rev H 4. System Management

Table 4-1. Equipment Information Display Fields for FCP270 (Continued)

Field Description
FAIL ACK STATE Acknowledged or Not Acknowledged. This field is initially set to
Acknowledged. If the FAIL STATE changes from Not Failed to Failed,
the FAIL ACK STATE field changes to Not Acknowledged to indicate
this transition. Use the ACK key in the top menu bar of the
Equipment Information Display to acknowledge the selected faulted
device or use the ACK ALL key in the top menu bar of the initial
System Management Display to acknowledge all the unacknowledged
devices for which the workstation has responsibility.
FT STATE Fault-Tolerant State is Operational or Non-Operational for fault-
tolerant controllers only. FT STATE indicates Non-Operational if the
shadow module is not installed/configured.
FAIL DEV ACK Acknowledged or Not Acknowledged. This field is initialized to
Acknowledged. If any of the attached devices become unacknowl-
edged, the field changes to Not Acknowledged.
EE UPDATE STATE EE Updating or Not Updating. This field is initially set to Not
Updating. When IMAGE UPDATE is selected under Equipment
Change options, the status changes to EE Updating until the FCP270
image (operating system software) has been burned to flash memory.
For fault-tolerant stations, refer to the PRIMARY MODE and
SHADOW MODE fields for the current EEPROM Updating State.
For more information, see “Image Update Procedure for a Non-Fault-
Tolerant FCP270” on page 58.
SM REPORT STATE Report All or No Reporting. This refers to the type of internal
reporting taking place from the Station Manager to the System
Monitor. The various states are selectable from the Equipment Change
Display ENABLE ALL REPORTS and DISABLE ALL REPORTS.
The default setting is Report All.
TYPE Type of controller defined when the letterbug is assigned during the
site planning and system definition phases. Field Control
Processor 270 has the type Fld Ctl Proc270.

52
4. System Management B0700AR – Rev H

Table 4-1. Equipment Information Display Fields for FCP270 (Continued)

Field Description
FAIL STATE Failed or Not Failed. This field is initially Not Failed. This field
changes to Failed if any of the following occur:
 A hardware problem causes the station to fail for more than two
minutes
 A physical pull/push of the station (requiring more than two
minutes to come back on-line) is performed
 Any station hardware failure or communication failure that
results in the station no longer being able to send its internal
reports for one or more minutes.
Operator-initiated Equipment Change actions (REBOOT, IMAGE
UPDATE) change the RUN MODE to off-line, but do not change the
FAIL STATE to Failed.
For fault-tolerant stations, refer to the PRIMARY MODE and
SHADOW MODE fields for the current FAIL STATE of each
module in the fault-tolerant pair.
ALARMING STATE Enabled or Inhibited. This field indicates whether alarming for system
alarms, not process alarms, is Enabled or Inhibited for the station.
When alarming is Inhibited, the System Monitor continues to indicate
overall system and network health (a green “Sys” bar) while equipment
is failed or off-line. Additionally, when alarming is inhibited, System
Alarm messages are not logged to the system printer, nor the Historian.
FAIL DEV ATT Yes or No. Yes if one or more peripherals attached to the controller are
failed.
DIAG STATE Not Active is always displayed because there are no off-line diagnostics
for the FCP270 station.
DOWNLOAD STATE Downloading or Not Downloading. This field is initially set to Not
Downloading. When the station is rebooted via an operator-initiated
request, the status changes to Downloading until the action is
completed. For fault-tolerant stations, refer to the PRIMARY MODE
and SHADOW MODE fields for the current Downloading State.
CABLE STATE Both Cables Okay or Fault. This field indicates if there is a cable Fault
on either The MESH control network cables A or B, or both.
PRIMARY MODE Single Primary, Married Primary, EE Updating, Downloading or
Failed appears for fault-tolerant controllers.
PRIM ROM ADDRESS A six-octet Media Access Control (MAC) address of the Primary
controller assigned during manufacturing. The Manufacturing ID,
labeled on the left side of the module, is the last six characters of this
address, for example, 220626 in Figure 4-2.
PRIM HARD PART Primary controller hardware part number.
PRIM HARD REV Primary controller hardware revision number. Typically, for an
FCP270 this part number is P0917YZ.
PRIM HARD DATE Primary controller hardware manufacturing date.
PRIM EEPROM REV Primary controller EEPROM revision level.

53
B0700AR – Rev H 4. System Management

Table 4-1. Equipment Information Display Fields for FCP270 (Continued)

Field Description
STATION ADDRESS Six-octet MAC address. This field specifies a unique MAC address that
other stations in the system use to communicate with the FCP270.
SHADOW MODE Married Shadow, EE Updating, Downloading, Failed, or Off-line
appears for fault-tolerant controllers. A non-existent shadow module is
marked as Off-line.
SHD ROM ADDRESS Last known six-octet MAC address of the shadow controller. This is
assigned during manufacturing. The last six characters of this address
are the module hardware ID, which is stamped on a label on the mod-
ule’s left side. For a non-existent shadow module, this field is all zeroes.
SHAD HARD PART Last known shadow controller hardware part number. This field is
blank if the shadow controller does not exist.
SHAD HARD REV Last known shadow controller hardware revision number. This field is
blank if the shadow controller does not exist.
SHAD HARD DATE Last known shadow controller hardware manufacturing date. This
field is blank if the shadow controller does not exist.
SHAD EEPROM REV Last known shadow controller EEPROM revision level. This field is
blank if the shadow controller does not exist.
MT REPORT STATE Indicates the status of UTC time and time strobe from the Master
Timekeeper (MTK), as received by the FCP270.

STATE Description
Pulsed STK FCP270 is receiving UTC time from MTK
and time strobe from both ports A and B.
Sync_A_In_Fail FCP270 is receiving UTC time from MTK
and time strobe only from port B.
Sync_B_In_Fail FCP270 is receiving UTC time from MTK
and time strobe only from port A.
Sync_AB_In_Fail FCP270 is receiving UTC time from MTK,
but lost time strobe from ports A and B.
Sync_not_Cfg FCP270 is not configured as a Sync Pulse
station.

Configuration Information Display for FCP270


The SMDH Configuration Information display (Figure 4-3) for the FCP270 contains system
domain and network configuration information. You can use the information shown in this dis-
play when diagnosing system problems. Table 4-2 describes the available text fields in the order
that they appear on the display, from left column to right column.

54
4. System Management B0700AR – Rev H

Figure 4-3. Configuration Information Display for FCP270

Table 4-2. Configuration Information Display Fields for FCP270

Field Description
STATION NAME Controller letterbug assigned during definition of system hardware.
SMON NAME System monitor name for the selected FCP270.
LI NAME Not applicable (N/A)
IP ADDR Internet Protocol network address. Assigned by system during system
definition phases.
SW CONNECTION Ethernet switches to which the FCP270 is connected, per system
configuration.
TYPE Type of station defined when the letterbug is assigned during site plan-
ning and system definition phases. This should read Fld Ctl Proc270.
SMON AP NAME Name of the application workstation that hosts the controller’s system
monitor.
BOOT HOST Boot image host name for the selected FCP270.

Equipment Change Display for FCP270


You can use the SMDH Equipment Change display (Figure 4-4) for the FCP270 to perform
equipment change actions on the selected controller. Only workstations designated (during Sys-
tem Monitor configuration) to perform secured actions on this FCP270 can access the equipment
change actions. Table 4-3 describes the actions that are available for this display.

55
B0700AR – Rev H 4. System Management

Figure 4-4. Equipment Change Display for FCP270

! CAUTION
Only designated personnel who are aware of the effects of making equipment
changes should initiate equipment changes.

Table 4-3. Equipment Change Display Fields for FCP270

Action Description
CHECKPOINT Saves operator set values and process tuning changes for a controller
COMMAND to the checkpoint file in the host file server. To retain these changes,
you must save them to the host file server checkpoint file before you
reboot (restart) the controller. This checkpoint file contains an
image of the current database. When you reboot (restart) the
controller, the system downloads the current checkpoint file to the
controller to update its database. Checkpointing takes approxi-
mately 5 seconds to 30 seconds depending on the database size.
ENABLE STATION Enables the controller system alarms to be propagated up the equip-
ALARMING ment hierarchy and enables controller system alarm messages. This
action does not affect process alarms.
INHIBIT STATION Prevents the controller system alarms from being propagated up the
ALARMING equipment hierarchy and disables controller system alarm messages.
Does action not affect process alarms.

56
4. System Management B0700AR – Rev H

Table 4-3. Equipment Change Display Fields for FCP270 (Continued)

Action Description
REBOOT STATION Restarts the FCP270 and reloads the checkpoint file, which contains
an image of the controller database, from the host file server if
ENABLE DOWNLOAD is active on the Equipment Change
display.
IMAGE UPDATE Updates the existing FCP270 software image in flash memory with
new software image if ENABLE DOWNLOAD is active on the
Equipment Change display. The update downloads a file and burns
it to flash memory. The system printer logs the update results.

Selecting IMAGE UPDATE for a fault-tolerant FCP270 and select-


ing “Yes” in the dialog box initiates the EEPROM update to both
modules of the fault-tolerant pair. Once initiated, the IMAGE
UPDATE process is entirely automatic. The fault-tolerant FCP270
places the Shadow module off-line and then downloads and burns
the new code in the Primary module. After verification, the Primary
reboots automatically. When the Primary finishes rebooting it sends
the new image to the Shadow. The Shadow reboots and the module
pair marries using the new code. IMAGE UPDATE takes approxi-
mately 1 minute to 5 minutes depending on database size.
ENABLE UPLOAD Enables uploading of the station image to a file on the host file
server if the controller fails.
DISABLE UPLOAD Disables uploading of the station image to a file on the host file
server if the controller fails.
ENABLE DOWNLOAD Enables download of files needed for REBOOT STATION,
IMAGE UPDATE and ON-LINE IMAGE UPDATE actions.
DISABLE DOWNLOAD Disables download of files needed for REBOOT STATION,
IMAGE UPDATE and ON-LINE IMAGE UPDATE actions.
ENABLE ALL REPORTS Enables reporting of all status for the controller and any attached
devices, and reporting of system and peripheral counters to the
System Monitor.
DISABLE ALL REPORTS Disables reporting of all status for the controller and any attached
devices and reporting of system and peripheral counters to the
System Monitor.
ON-LINE IMAGE Allows you to update the software image on a fault-tolerant
UPDATE FCP270, safely and with minimum hold-control time. For more
information, refer to “Image Update Procedure for a Fault-Tolerant
FCP270” on page 59.

The REBOOT STATION, IMAGE UPDATE (EEPROM Update) and ON-LINE IMAGE
UPDATE actions and their procedures are described below.

57
B0700AR – Rev H 4. System Management

NOTE
For more information and procedures for performing equipment change actions,
refer to I/A Series System Management Displays (B0193JC).

Reboot Station Procedure


The REBOOT STATION action restarts the selected FCP270 and reloads its control database
from a file server. While the station is rebooting, it is off-line until the reboot is complete; this
suspends any access to the station database. Rebooting typically is used during system mainte-
nance and upgrades.
To reboot an FCP270 station:
1. Access the Equipment Change Display for the desired FCP270 (refer to I/A Series
System Management Displays (B0193JC).
2. In the Equipment Change Display, ensure that the Enable Download state is active. If
it is not, click ENABLE DOWNLOAD.
To ensure that download is currently enabled, verify that the ENABLE DOWNLOAD but-
ton is back-lighted dark cyan.
3. Click REBOOT STATION.
If this is a fault-tolerant FCP270 station, a dialog box (Figure 4-5) offers choices for
primary module, shadow module, or both. The dialog box displays the MAC address
and status of the primary and shadow modules.

Figure 4-5. REBOOT STATION Dialogue Box – Fault-Tolerant FCP270

The following module operational statuses can be displayed:


M PRIM = married primary, M SHAD = married shadow, S PRIM = single primary
4. Click the module to reboot. The system reboots that module.
If there is an error, the system displays a message on the screen and/or at the system
printer. Refer to I/A Series System V8.x System Error Messages (B0700AF).

Image Update Procedure for a Non-Fault-Tolerant FCP270


The IMAGE UPDATE action updates the existing image (operating system software) in the
selected FCP270’s EEPROM flash memory with a new image. The update downloads a file and
burns a new image to flash memory.

58
4. System Management B0700AR – Rev H

! CAUTION
The IMAGE UPDATE command allows you to upgrade the existing image (operat-
ing system software) in a non-fault-tolerant FCP270, while interrupting process
control for the duration of the image update. IMAGE UPDATE takes approximately
1 minute to 5 minutes depending on database size.

To update the existing image in flash memory for a non-fault-tolerant FCP270 station, refer to
the CP 270 On-Line Upgrade (B0700BY) document.

NOTE
If self-hosting is enabled during an Image Update procedure, the checkpoint files in
flash will be invalidated forcing the checkpoint file to be loaded from the host work-
station. When the procedure is complete and the Database Download is complete, a
checkpoint command will automatically be issued that will result in the checkpoint
file being burned to flash.

Image Update Procedure for a Fault-Tolerant FCP270


The IMAGE UPDATE action updates the existing image (operating system software) in the
selected FCP270’s EEPROM flash memory with a new image. The update downloads a file and
burns a new image to flash memory in both modules of the fault-tolerant FCP270.
The ON-LINE IMAGE UPDATE command allows you to upgrade the existing image (operating
system software) in an on-line, fault-tolerant FCP270, while interrupting process control for only
1.5 seconds, approximately.
To update the existing image in flash memory for a fault-tolerant FCP270 station, refer to the CP
270 On-Line Upgrade (B0700BY) document. While IMAGE UPDATE runs, the system sends
standard EEPROM update progress messages to the system printer. IMAGE UPDATE takes
approximately 1 minute to 5 minutes depending on database size.

NOTE
Selecting IMAGE UPDATE for a fault-tolerant FCP270 automatically updates
both modules of the fault-tolerant pair. Once initiated, the IMAGE UPDATE pro-
cess is entirely automatic.

NOTE
If self-hosting is enabled during an Image Update procedure, the checkpoint files in
flash will be invalidated forcing the checkpoint file to be loaded from the host work-
station. When the procedure is complete and the Database Download is complete, a
checkpoint command will automatically be issued that will result in the checkpoint
file being burned to flash.

Messages Following Checkpoint Operation in Self-Hosting FCP270


The Checkpoint action saves the checkpoint file database on the host workstation, and if the self-
hosting capability of the FCP270 controller is enabled, the checkpoint file is also burned to the

59
B0700AR – Rev H 4. System Management

controller’s flash memory. When a checkpoint command is issued, the FCP270 sends it's control
database to the host workstation and if self-hosting is enabled, the FCP270 will send a request to
the host workstation requesting that checkpoint file to be sent back to the FCP270 to be burned
into flash memory.
When self-hosting is disabled, you will see a message similar to the following after successfully
completing a checkpoint action:
10-31-07 09:58:38 0 SYSMON = SYSMN1 CP0008 Software Manager
SYSMON -00021 Checkpoint Successful
The following is an example of the series of messages (dates are provided as examples in the format
YYYY-MM-DD HH:MM:SS) that are sent to the System Monitor log when performing a check-
point with self-hosting enabled. It is important to note that the checkpoint operation is not com-
plete until the message “Checkpoint installed into flash” appears in the SMON log. When
“Checkpoint installed into flash” appears in the SMON log, the checkpoint file has been sent to
the host workstation and burned into the FCP270 flash memory.
2007-10-17 14:25:51 FP0101 Process = Checkpoint CIO_DB 000015 -
Checkpoint to Flash Requested
2007-10-17 14:25:51 FP0101 Process = Checkpoint CIO_DB 000015 -
Wait For Message 'Checkpoint installed into flash'
2007-10-17 14:26:33 FP0101 Software Manager SYSMON -00021
Checkpoint Successful
2007-10-17 14:26:35 FP0101 Process = Self Hosting RDHSS 000131 -
Checkpoint loading to Flash
2007-10-17 14:27:15 FP0101 Process = Self Hosting RDHSS 000131 -
Backup Checkpoint erased
2007-10-17 14:29:27 FP0101 Process = Self Hosting RDHSS 000131 -
Checkpoint File verified
2007-10-17 14:29:28 FP0101 Process = Self Hosting RDHSS 000131 -
Checkpoint installed into flash
These messages are explained in Table 4-4.

Table 4-4. SMON Log Messages Following Checkpoint Operation

Message Definition Meaning


Checkpoint to This message indicates a check- The checkpoint process has started. The
Flash Requested point command has been checkpoint file has not been written to the
issued and self-hosting is Host or FCP270 flash. If the FCP270 is
enabled. If self-hosting is dis- rebooted after this message, the FCP270
abled, this message will not be will load the checkpoint file out of flash.
sent to the SMON log. The loaded checkpoint file from flash will
not contain any changes that were made
prior to issuing the checkpoint command.

60
4. System Management B0700AR – Rev H

Table 4-4. SMON Log Messages Following Checkpoint Operation (Continued)

Message Definition Meaning


Wait For Mes- This message is a reminder to The checkpoint process has started. The
sage 'Check- the user that the checkpoint checkpoint file has not been written to the
point installed
operation will not be complete Host or FCP270 flash. If the FCP270 is
into flash'
until the message “Checkpoint rebooted after this message, the FCP270
installed into flash” has been will load the checkpoint file out of flash.
sent. If self-hosting is disabled, The loaded checkpoint file from flash will
this message will not be sent to not contain any changes that were made
the SMON log. prior to issuing the checkpoint command.
Checkpoint This message indicates the The checkpoint file has been written to the
Successful checkpoint file was successfully host but not the FCP270 flash. If the
sent to the host workstation FCP270 is rebooted after this message, the
only. It is not an indication FCP270 will load the checkpoint file out
that the complete checkpoint of flash. The checkpoint file will not con-
operation is complete if self- tain any changes that were made prior to
hosting is enabled. This mes- issuing the checkpoint command.
sage is sent to the SMON log if A checkpoint command should be issued
self-hosting is enabled or to synchronize both checkpoint files. Once
disabled. the checkpoint command completes, the
changes will be lost. If you want to
load/use the checkpoint file and contains
the latest changes to the host, the flash in
the FCP270 must be invalidated (that is,
disable self-hosting or reconfigure the let-
terbug) and the FCP270 must be rebooted.
This will force the FCP270 to load the
checkpoint file from the host.

61
B0700AR – Rev H 4. System Management

Table 4-4. SMON Log Messages Following Checkpoint Operation (Continued)

Message Definition Meaning


Checkpoint This message indicates that the The checkpoint file has been written to the
loading to process of downloading the host but not the FCP270 flash. If the
Flash
checkpoint file from the host FCP270 is rebooted after this message, the
to be burned into the FCP270 FCP270 will load the checkpoint file out
flash area has begun. If self- of flash. The loaded checkpoint file from
hosting is disabled, this mes- flash will not contain any changes that
sage will not be sent to the were made prior to issuing the checkpoint
SMON log. command. The checkpoint file on the host
and the checkpoint file in flash of the
FCP270 will not match. A checkpoint
command should be issued to sync up both
checkpoint files.
Once the checkpoint command completes,
the changes will be lost. If you want to
load/use the checkpoint file that contains
the latest changes from the host, the flash
in the FCP270 must be invalidated (that is,
disable self-hosting or reconfigure the let-
terbug) and the FCP270 must be rebooted.
This will force the FCP270 to load the
checkpoint file from the host.
Backup Check- The flash area that is to receive The checkpoint file has not been written to
point erased the new checkpoint file has the FCP270 flash. The area that is to
been erased and is ready for the receive the checkpoint file has been erased
checkpoint file to be burned. If but the previous area still contains a valid
self-hosting is disabled, this checkpoint file. If the FCP270 is rebooted
message will not be sent to the after this message, the FCP270 will load
SMON log. the checkpoint file out of flash. The loaded
checkpoint file from flash will not contain
any changes that were made prior to issu-
ing the checkpoint command. The check-
point file on the host and the checkpoint
file in flash of the FCP270 will not match.
A checkpoint command should be issued
to sync up both checkpoint files.
Once the checkpoint command completes,
the changes will be lost. If you want to
load/use the checkpoint file that contains
the latest changes from the host, the flash
in the FCP270 must be invalidated (that is,
disable self-hosting or reconfigure the let-
terbug) and the FCP270 must be rebooted.
This will force the FCP270 to load the
checkpoint file from the host.

62
4. System Management B0700AR – Rev H

Table 4-4. SMON Log Messages Following Checkpoint Operation (Continued)

Message Definition Meaning


Checkpoint File The checkpoint file has been The checkpoint file has been written to the
verified burned to flash and has been FCP270 flash and marked valid. If the
verified that it is an exact copy FCP270 is rebooted after this message, the
of the checkpoint file on the FCP270 will load the checkpoint file out
host workstation. The check- of flash. The checkpoint file will contain
point file in flash will be all changes that were made prior to issuing
marked as valid. If self-hosting the checkpoint command. The checkpoint
is disabled, this message will file on the Host and the checkpoint file in
not be sent to the SMON log. flash of the FCP270 are identical.
Checkpoint The checkpoint operation is The checkpoint file has been written to the
installed into complete. The checkpoint file FCP270 flash and marked valid. If the
flash
has been sent to the host work- FCP270 is rebooted after this message, the
station and burned into the FCP270 will load the checkpoint file out
FCP270 flash. of flash. The checkpoint file will contain
all changes that were made prior to issuing
the checkpoint command. The checkpoint
file on the Host and the checkpoint file in
flash of the FCP270 are identical.

NOTE
If self-hosting is enabled, the message “Checkpoint Successful” only indicates that
the checkpoint file has been sent to the host workstation. If a station reboot were to
occur prior to the message “Checkpoint installed into flash”, the newest checkpoint
file would not be burned in the FCP270 flash. Always wait for the message “Check-
point installed into flash” to ensure the latest checkpoint file is burned correctly into
the FCP270 flash area.

Checkpoint Invalidation in Self-Hosting FCP270


There are some conditions that exist that will result in the checkpoint in flash to be invalidated.
An invalid checkpoint file in flash results in the FCP270 loading the checkpoint file from the host
workstation on reboots.
The following is a list of conditions that result in the checkpoint file in flash to be invalidated:
 If the letterbug of an FCP270 is changed, the checkpoint file in flash is invalidated.
This ensures the checkpoint file from the host workstation is loaded and not a leftover
checkpoint file in flash.
 If an FCP270 in self-hosting mode fails to load the checkpoint file from flash success-
fully, the checkpoint file in flash is invalidated. The failure of the checkpoint file to
load from flash properly indicates there is some form of corruption on the database.
The station will be rebooted forcing the FCP270 to load the checkpoint file from the
host workstation.
 If an FCP270 with a valid checkpoint file in flash marries into a Single Primary
FCP270 operating with self-hosting disabled, the newly booted module will invalidate
the checkpoint file in flash and reboot to complete the marriage. This prevents that

63
B0700AR – Rev H 4. System Management

module from loading the checkpoint file from flash in the event the station is
rebooted causing that module to come up as the primary module.
 If an On-line Image Update or Image Update operation is performed, the checkpoint
file in flash is invalidated forcing the checkpoint file to be loaded from the host work-
station. Only after the On-line Image Update or Image Update operation is complete
will the checkpoint file be burned to flash.
 If one module of a fault-tolerant pair fails to burn to flash successfully and the other
module successfully burns to flash memory, the module that fails to burn to flash will
invalidate the checkpoint in flash and go off-line. The module that successfully burns
to flash will switch to Single Primary mode and send a message to the SMON log
indicating why the other module went off-line.
 If both modules of a fault-tolerant pair fail to burn to flash successfully, both modules
will invalidate the checkpoint in flash and send a message to the SMON log. The sta-
tion will continue to run fault-tolerant.
 If a Single Primary module fails to burn to flash successfully, the module will invali-
date the checkpoint in flash and send a message to the SMON log. The station will
continue to run single.
 If one side of a fault-tolerant pair goes off-line while running in self-hosting mode, the
off-line modules flash will be invalidated the next time the Single Primary module
performs a checkpoint.
If any of the above conditions occurred and:
 a checkpoint command is issued before the station has been rebooted, there will be an
attempt to burn the checkpoint file to the flash of the FCP270 if self hosting is
enabled.
 the station is rebooted before a checkpoint command is issued, the checkpoint file will
be loaded from the host workstation. In addition, if self hosting is enabled, a check-
point command will be automatically issued after the Database Download is
complete. This will result in the checkpoint file getting burned to flash.
These actions can prevent an incorrect checkpoint file from being loaded.

64
4. System Management B0700AR – Rev H

System Management Displays – Primary ECB (FBM0)


The I/A Series System Management Display Handler allows you to access the following displays
for FBM0, which is actually the primary ECB (ECBP), which resides in the FCP270 station.
 Equipment information
 Equipment change actions
 On-line diagnostics (PIO).
These displays reflect the current operating status of the Fieldbus and its attached devices, and
provide a valuable maintenance aid by allowing you to intervene in Fieldbus operations. For infor-
mation on navigating through the SMDH screens, see System Management Displays (B0193JC).

Equipment Information Display for Primary ECB (FBM0)


The SMDH Equipment Information display pages (Figure 4-6 and Figure 4-7) for the Primary
ECB (FBM0) contain operational status, equipment change action status, device status, and
power status fields. The following fields are updated when a status change occurs:

 RUN MODE  DEVICE STATE


 FAIL ACK STATE  ALARMING STATE
 CP POWER 1  ACTIVE PIO BUS
 SWITCHING MODE  CP POWER 2
 DIAG STATUS 1
 PRIM CHK POINT  SHAD CHK POINT
 SELF HOSTING

All other fields are either static, updated when the display is recalled, or unused. Table 4-5
describes the available text fields in the order that they appear on the display pages, from left col-
umn to right column.

65
B0700AR – Rev H 4. System Management

Figure 4-6. Equipment Information Display for Primary ECB (FBM0) – Typical (1 of 2)

Figure 4-7. Equipment Information Display for Primary ECB (FBM0) – Typical (2 of 2)

66
4. System Management B0700AR – Rev H

Table 4-5. Equipment Information Display Fields for Primary ECB (FBM0)

Field Description
NAME The letterbug of the FCP270 in which the primary ECB (FBM 0) is
located.
RUN MODE On-line or Off-line. The primary ECBP is installed as On-line after
it is configured. For the primary ECB (FBM0) located in an
FCP270, changing the FBM0 status to Off-line stops all communi-
cation to the Fieldbus. Subsequently, all attached FBMs fail. As a
result, a number of messages appear at the printer indicating commu-
nication failures and peripheral equipment failures.
Changing an FBM status to Off-line causes communications to that
specific device to stop.
You can change the RUN MODE using the GO ON-LINE and GO
OFF-LINE options in the Equipment Change Display. If station
reporting is disabled, the last known run state appears in this field.
The system updates this field when a status change occurs.
FAIL ACK STATE Displays Acknowledged (default) or Not Acknowledged. If the
DEVICE STATE value changes from Not Failed to Failed, the value
in this field changes to Not Acknowledged.
Click ACK in this display to acknowledge the selected faulted device;
or click ACK ALL in the initial system management display to
acknowledge all unacknowledged devices for which the workstation
is responsible.
The system updates this field when a status change occurs.
Not Acknowledged Status: Check printed/historical log for type of
failure. To clear, click ACK or ACK ALL on the configured applica-
tion workstation (AW).
DOWNLOAD STATE This field does not apply to FBM0. It displays “Not Downloading”.
FAIL DEV ATT This field does not apply to FBM0. It displays “No”.
CP POWER 1 OK or Failed indicates the state of primary power to FCP270.
SWITCHING MODE Displays Enabled (default) or Not Enabled. If Enabled, automatic
switching can occur in the event of a bus fault for the BUS AUTO
SELECT mode.
You can change this field to Not Enabled by selecting SELECT
BUS A ONLY or SELECT BUS B ONLY in the Equipment Change
Display.
DIAG STATUS 2 This field does not apply to FBM0. It displays “0”.
DIAG STATUS 4 This field does not apply to FBM0. It displays “0”.
SOFTWARE TYPE This field does not apply to FBM0. It displays “0”.
PRIM CMD STAT This field does not apply to FBM0. It displays “0”.
FBM STATUS This field does not apply to FBM0. It displays “0”.
HARDWARE REV This field does not apply to FBM0. It displays “00”.
SERIAL NUMBER This field does not apply to FBM0.

67
B0700AR – Rev H 4. System Management

Table 4-5. Equipment Information Display Fields for Primary ECB (FBM0) (Continued)

Field Description
EEPROM REV This field does not apply to FBM0.
TYPE FBM0 represents the primary ECB.
DEVICE STATE The system updates this field when a status change occurs. The possi-
ble mutually exclusive states are:
 Not Failed: The device is healthy.
 On Scan: The device is connected to the control strategy,
though measurements are not guaranteed to be good.
 Comm Failures: No real device information is available.
 Failed: Fatal hardware or other fatal fault reported by the
device. Presupposes that communication has not failed.
 Not Ready: A transition state. The device is healthy and normal
automatic start-up procedures are bringing the device On Scan.
 Out of Service: The device is healthy, but is operating in a mode
incompatible with its normal control functions.
ALARMING STATE Indicates whether alarming is enabled or inhibited for this device.
When alarming is inhibited, the System Monitor continues to indi-
cate overall system and network health while equipment is failed or
off-line, and any system alarm messages are not logged to the system
printer or to the Historian.
The system updates this field when a status change occurs.
Not Responding or Not Acknowledged status: Check the hardware.
DEVICES ATT This field does not apply to FBM0. It displays “No”.
ACTIVE PIO BUS Indicates the current Fieldbus, either BUS A ONLY, BUS B ONLY,
or BUS A & B AUTO. This value is set initially to BUS A ONLY or
to the value saved in the checkpoint file. If SWITCHING MODE is
enabled, this field updates automatically if you switch communica-
tions on the current Fieldbus to the other Fieldbus. BUS A & B
AUTO indicates that both Bus A and Bus B are active, and the
FCP270 determines which bus to use for each transaction.
CP POWER 2 OK or Failed indicates the state of secondary power to FCP270.
DIAG STATUS 1 Indicates CP Power status:
0 = CP Power 1 okay & CP Power 2 okay
1 = CP Power 1 Failed
2 = CP Power 2 Failed
DIAG STATUS 3 This field does not apply to FBM0. It displays “0”.
HARDWARE TYPE This field does not apply to FBM0. It displays “0”.
LOGICAL ADDR This field does not apply to FBM0. It displays “ff ”.
FBM CMD STATUS This field does not apply to FBM0. It displays “0”.
HARDWARE PART NO. This field does not apply to FBM0.
DATE This field does not apply to FBM0.
SOFTWARE REV This field does not apply to FBM0.

68
4. System Management B0700AR – Rev H

Table 4-5. Equipment Information Display Fields for Primary ECB (FBM0) (Continued)

Field Description
PRIM CHK POINT Indicates the number of flash write operations which have occurred
to the primary module’s flash memory.
SHAD CHK POINT Indicates the number of flash write operations which have occurred
to the shadow module’s flash memory.
SELF-HOSTING Indicates the station mode - “Disabled” (default) or “Enabled”.

Equipment Change Display for Primary ECB (FBM0)


You can use the SMDH Equipment Change display (Figure 4-8) for the Primary ECB (FBM0) to
perform equipment change actions on Fieldbus communications and FBMs attached to the Field-
bus. Only workstations designated (during System Monitor configuration) to perform secured
actions on this FCP270 can access the equipment change actions for FBM0. Table 4-6 describes
the actions that are available for this display.
In Figure 4-8, the following fields are not used:

 DOWNLOAD  RESET ATTENTION BIT


 EEPROM UPDATE  SWITCH ROLES

Figure 4-8. Equipment Change Display for Primary ECB (FBM0)

69
B0700AR – Rev H 4. System Management

! CAUTION
Only designated personnel who are aware of the effects of making equipment
changes should initiate equipment changes.

Table 4-6. Equipment Change Display Fields for Primary ECB (FBM0)

Action Description
GO OFF-LINE Stops all communication to the Fieldbus, which causes all attached
FBMs to fail. As a result, a number of messages appear at the
printer indicating communication failures and peripheral equip-
ment failures. It is recommended that you place an FBM0 off-line
for diagnostic purposes only.
GO ON-LINE Starts Fieldbus communication to all attached FBMs. The system
sends a message to the designated printer.
GENERAL DOWNLOAD Downloads FBM images for all off-line/failed FBMs attached to
the selected FCP270. Use GENERAL DOWNLOAD when you
add a new FBM to the FCP270 and the FBM data is not already in
the checkpoint file. Typically, you use GENERAL DOWNLOAD
action to download FBM images after you perform integrated con-
trol configuration on each of the new FBMs.
SELECT BUS A ONLY Designates Fieldbus A as the current bus and deactivates automatic
switching. If the selected bus is not available or is not functioning,
the previous bus selection is maintained. If there is an error, the
system displays a message.
SELECT BUS B ONLY Designates Fieldbus B as the current bus and deactivates automatic
switching. If the selected bus is not available or is not functioning,
the previous bus selection is maintained. If there is an error, the
system displays a message.
BUS AUTO SELECT Automatically switches between Fieldbus A and B. The FCP270
determines which bus to use for each transaction. If the selected
bus is not available or is not functioning, the previous bus selection
is maintained. If there is an error, the system displays a message.
ENABLE DEVICE Enables device alarming from FBMs attached to the Fieldbus. Sys-
ALARMING tem alarm messages are logged to the system printer or Historian.
INHIBIT DEVICE Prohibits device alarming for FBMs attached to the Fieldbus.
ALARMING When you select to prohibit alarming, the system filters alarm con-
ditions so that the System Monitor continues to indicate overall
system and network health while equipment is failed or off-line.
While alarming is prohibited, system alarm messages are not
logged to the system printer or the Historian.

70
4. System Management B0700AR – Rev H

NOTE
For more information and procedures for performing equipment change actions,
refer to I/A Series System Management Displays (B0193JC).

Overview of Fieldbus Switching Mode


The FCP270 records the number of FBM access failures per Fieldbus A and/or B and determines
whether switching occurs. The system checks the other bus (cable) to eliminate switching to a bad
or worse bus.
The following scenarios can occur:
 If the current Fieldbus has a failure(s) and the other bus has fewer or no failures, the
station automatically switches to the better bus if the BUS AUTO SELECT mode is
selected.
 If both buses have an equal number of FBM access failures, the station continues
transmission over the existing bus if the BUS AUTO SELECT mode is selected.
 If SELECT BUS A ONLY or SELECT BUS B ONLY are selected the station
attempts to continue transmission over the selected bus regardless of the failure.

Using the Fieldbus Switching Options


There are three Fieldbus switching options available from the Equipment Change Display.
To automatically switch between Module Fieldbus A and B:
 In the Equipment Change Display, click BUS AUTO SELECT. Both Bus A and Bus B
are active, and the FCP270 determines which bus to use for each transaction. If the
selected bus is not available or is not functioning, the previous bus selection is main-
tained. If there is an error, the system displays a message.
To designate Fieldbus A as the current bus and deactivate automatic switching:
 In the Equipment Change Display, click SELECT BUS A ONLY. The system does not
check the current health of the bus. The system displays a message if an error occurs.
To designate Fieldbus B as the current bus and deactivate automatic switching:
 In the Equipment Change Display, select SELECT BUS B ONLY. The system does not
check the current health of the bus. The system displays a message if an error occurs.
Use the SELECT BUS A ONLY or SELECT BUS B ONLY switching actions for diagnostic purposes,
or when only one bus is available (such as when you are replacing a defective cable or Modular
Baseplate).

Overview of the General Download


The GENERAL DOWNLOAD action downloads FBM images for all off-line/failed FBMs
attached to a selected FCP270. This action is available from the primary FBM (FBM0) for the
FCP270.
Use the GENERAL DOWNLOAD action when you add a new FBM to the FCP270 and the
FBM data is not already in the checkpoint file. Typically, you use the GENERAL DOWNLOAD
action to download FBM images after you perform integrated control configuration on each of
the new FBMs.

71
B0700AR – Rev H 4. System Management

If the file information in the station already includes the selected FBM data (that is, checkpoint-
ing was performed while the FBMs were on-line), downloading occurs automatically, when neces-
sary.

Downloading all FBM Images


You can download FBM images for all off-line, failed FBMs attached to a selected FCP270 from
the Equipment Change display. This option applies to the primary FBM (FBM0) for the
FCP270.
To download FBM images for all off-line/failed FBMs:
1. In the SMDH Equipment Change display, select GENERAL DOWNLOAD. This loads the
FBM images to all off-line/failed FBMs.
Messages indicating the success or failure of the action for each downloaded FBM
appear. If the GENERAL DOWNLOAD action is successful, each FBM goes on-line.
If there is a failure, the system displays a “Not Responding” message.
2. If you use the GENERAL DOWNLOAD action during initial start-up, perform a
checkpoint from the FCP270 after downloading to all the FBMs. This preserves the
on-line state of the FBMs in the checkpoint file. See CHECKPOINT COMMAND
in Table 4-3 on page 56.

On-Line Diagnostics (PIO) Display for Primary ECB (FBM0)


You can use the SMDH On-line Diagnostics (PIO) display (Figure 4-9) for the Primary ECB
(FBM0) to inhibit or enable PIO bus (Fieldbus) cable alarms. Only workstations designated (dur-
ing System Monitor configuration) to perform secured actions on this FCP270 can access the on-
line diagnostics actions for FBM0. Table 4-7 describes the actions that are available for this dis-
play.

72
4. System Management B0700AR – Rev H

Figure 4-9. On-line Diagnostics Display for Primary ECB (FBM0)

! CAUTION
Only designated personnel who are aware of the effects of running on-line diagnos-
tics should initiate diagnostic actions.

Table 4-7. Equipment Change Display Fields for Primary ECB (FBM0)

Action Description
ENABLE PIO BUS Enables PIO Bus A (Fieldbus A) cable alarms to monitor cable faults.
CABLE A ALARMS System alarm messages are logged to the system printer or Historian.
ENABLE PIO BUS Enables PIO Bus B (Fieldbus B) cable alarms to monitor cable faults.
CABLE B ALARMS System alarm messages are logged to the system printer or Historian.
INHIBIT PIO BUS Prohibits PIO Bus A (Fieldbus A) cable alarms. System alarm mes-
CABLE A ALARMS sages are not logged to the system printer or Historian.
INHIBIT PIO BUS Prohibits PIO Bus B (Fieldbus B) cable alarms. System alarm mes-
CABLE B ALARMS sages are not logged to the system printer or Historian.

NOTE
For more information and procedures for performing on-line diagnostic actions,
refer to I/A Series System Management Displays (B0193JC).

73
B0700AR – Rev H 4. System Management

74
5. Troubleshooting
This chapter describes possible FCP270 failure situations and provides diagnostic routines that
allow you to locate and resolve unit failures quickly.

Overview
In most cases, problems occur because the controller is misconfigured or there are faulty network
connections. In the event of a true hardware failure, the I/A Series maintenance approach is
oriented toward module replacement. Any module can be replaced without affecting the
operation of any other module, including the other module of a fault-tolerant pair.
The Station Block displays provide information to help you evaluate FCP270 performance. For
more information, refer to Integrated Control Block Descriptions (B0193AX) and Process Operations
and Displays (B0700BN).

LED Indicators, Reset Button, and Infrared Ports


Light-emitting diodes (LEDs) on the front of the FCP270 module (Figure 5-1) provide visual
indication of the module’s operational status and transmit/receive communications activity of The
MESH control network A and B links. The red Reset button enables you to restart the FCP270.
The infrared communication ports enable you to assign or read the controller letterbug and read
controller status information using the I/A Series system Letterbug Configurator. Table 5-1
describes these LEDs and controls.
The control network path Tx LEDs indicate which controller is primary as well as the network
path it is using; these LEDs are only active on the primary module.

75
B0700AR – Rev H 5. Troubleshooting

Ethernet Switch A Communication


Activity Indicators

Operational Status LEDs

Reset Button (Recessed)


Infrared Communication Active LED

Fieldbus LED Indicators

Infrared Communication Port

Ethernet Switch B Communication


Activity Indicators

Figure 5-1. FCP270 LED Indicators, Reset Button, and Infrared Port

Table 5-1. FCP270 LED Indicators, Reset Button, and Infrared Communication Ports

Item Description
The MESH Control Network A or B LED is on when the primary controller is transmitting
Tx data over control network A or B. LED is active only
on the primary controller.
The MESH Control Network A or B LED is blinking when the controller is receiving data
Rx/Link over control network A or B. The LED is on when the
link is established. If the LED is off for more than 1 s,
the link is broken.
Green and Red Operational Status LEDs indicate the health of the controller. See “Using
LEDs the Operational Status LEDs” on page 78.

76
5. Troubleshooting B0700AR – Rev H

Table 5-1. FCP270 LED Indicators, Reset Button, and Infrared Communication Ports (Continued)

Item Description
Reset Button Resets the controller. The controller’s database is
reloaded from the boot host workstation or from the
primary module.
IR Active LED LED is on when the I/A Series system Letterbug
Configurator is communicating with the controller to
assign, modify or read its letterbug.
Fieldbus A or B Tx LED is on when the primary controller is transmitting
data over fieldbus A or B. LED is active only on the pri-
mary controller.
Fieldbus A or B Rx LED is on when the controller is receiving data over
fieldbus A or B.
Infrared communication port Enables assigning, modifying or reading the controller
letterbug and reading controller status information
using the handheld Letterbug Configurator.

Operational Status LED Indicators


The Operational Status LEDs (red and green) on the front of the FCP270 indicate the module’s
operational status. Table 5-2 describes the operational conditions indicated by these LEDs.

Table 5-2. FCP270 Operational Status LEDs

Red LED Green LED Status


OFF ON Module is on-line and functional. (This is the normal run state.)
OFF OFF No power, or a fault exists in which the green or red LED is not
turned on.
ON ON Start-up, or a fault exists in which the green LED is not turned off.
On power-up, the default condition of both LEDs is on. Once the
system is running, software turns off the red LED.
ON OFF Module is in failed state, or it is running on-line diagnostics during
boot up.

FCP270 Troubleshooting
The following troubleshooting information is intended as a service guide for some of the most
commonly encountered system problems. Problems that surface in many cases are faults associ-
ated with communication paths (cables, connectors, internal data and power buses, and so forth).
At the module (FCP270) level, the quickest way to determine and correct the problem is by
replacement. When spare parts are not available, the following checks may provide a practical
approach.

77
B0700AR – Rev H 5. Troubleshooting

! CAUTION
1. Do not attempt to repair modules in the field!
2. To reboot the FCP270, use System Management displays if possible.

Using the Operational Status LEDs


The Operational Status LEDs (red and green) on the front of the FCP270 (see Figure 5-1) indi-
cate the module’s operational status.

Red off, Green off


When the red and green LEDs are off, this typically indicates loss of dc power. Perform the
following checks. (These checks need not be followed in order.)
1. If other module(s) in the modular baseplate are operating correctly, then:
 Cycle power to the failed FCP270 module off then on by pulling the module
from the baseplate and pushing the module back on the baseplate. Make sure you
unscrew the two self-retaining hex screws on the module before pulling the mod-
ule from the baseplate (see “Replacing a Failed Module” on page 81).
 Replace the failed FCP270 module with a known good module to test that slot in
the baseplate (see “Replacing a Failed Module” on page 81).
 Remove the FCP270 module and check the connector for bent pins. For module
removal procedures, see “Replacing a Failed Module” on page 81).
2. Verify that the operational status LEDs on the front of the Invensys power supply
(FPS400-24) are in the normal state (green LED is on, and red LED is off ).
3. Use a multimeter to verify that the dc voltage at the output connector is within the
range 21.6 to 25.2 V dc. For connector pin assignments, refer to DIN Rail Mounted
Subsystem User’s Guide (B0400FA).
4. Verify that the power cable is firmly connected to the baseplate and power supply.
5. If all modules on the baseplate have failed and the Foxboro power supply is operating
normally, disconnect the power cable from the power supply and baseplate, and use a
multimeter to verify continuity of the cable conductors, or replace the cable. For more
information, refer to DIN Rail Mounted Subsystem User’s Guide (B0400FA).
If none of the above checks resolve the failure, you must replace the module.

Red on, Green off


When the red LED is on and the green LED is off, this indicates that the module was unable to
pass the startup diagnostics. This usually indicates a hardware fault of some kind. Hardware faults
are typically internal to the FCP270 module, but you can try the following tests to correct the
problem:
1. Reboot the FCP270 module using either the module Reset button (see Figure 5-1) or
the System Management displays (see “Reboot Station Procedure” on page 58).
2. Cycle power to the FCP270 module off then on by pulling the module from the
modular baseplate and pushing the module back on the baseplate. Make sure you
unscrew the two self-retaining hex screws on the module before pulling the module
from the baseplate (see “Replacing a Failed Module” on page 81).

78
5. Troubleshooting B0700AR – Rev H

3. If the module is part of a fault-tolerant pair, replace it and verify that the new module
marries successfully.

! WARNING
If the failed FCP270 module is part of a fault-tolerant module pair, disconnecting the
time strobe cable from the baseplate causes the primary FCP270 module on control to
loose time synchronization.

4. Check for insufficient voltage, as shown in Steps 1 through 4 in the previous section.

Red on, Green on


On power-up, the default condition of both LEDs is on. Once the FCP270 module is running,
software turns off the red LED. If this state persists, a processor fault probably exists. Please be
patient with this state – if the module is updating its software, it may stay in the red-green state
for as long as five minutes.
Processor faults can occur for several reasons when fault-tolerant modules are married, but such
faults are unlikely to occur when the module is operating single.
1. Verify that the module is properly configured using System Management.
2. Check the cabling to the splitter/combiner. If married, the module can persist in the
red-green state when the cables are improperly connected, for example, by swapping
MESH control network A and B cables on one module.
If these steps fail to bring the green LED on and the red LED off, you must replace the module.

Cycling Red, Red/Green


When the LEDs cycle between red and red/green being on, this indicates that the probable cause
is a fault on the IOC (fieldbus) side of the FCP270 module. The module passes its main processor
diagnostics, then it tries to load software into the IOC. For whatever reason, this load is either
failing or the cooperative diagnostics between the two processors reaches a bad conclusion. Also,
the fieldbus Tx and Rx/Link LEDs probably flash once.
1. If the module is married to its fault-tolerant partner, make sure that the fieldbus
cabling is properly connected to the baseplate.
2. Cycle power to the FCP270 module off then on by pulling the module from the
baseplate and pushing the module back on the baseplate. Make sure you unscrew the
two self-retaining hex screws on the module before pulling the module from the
baseplate (see “Replacing a Failed Module” on page 81).
If these steps fail to bring the green LED on and the red LED off, you must replace the module.

Red off, Green on


When the red LED is off and the green LED is on, this indicates that the module is on-line and
functional. This is the normal operating state.

79
B0700AR – Rev H 5. Troubleshooting

Using the Ethernet Tx and Rx/Link Status LEDs


The normal idle state of the yellow TX and Rx/Link LEDs on the front of the FCP270 module
(see Figure 5-1) is to have all of the Tx LEDs dark and all of the Rx/Link LEDs lit, which
indicates that the fiber links are established. Every time the module transmits on any Ethernet
cable, the Tx LED for that cable lights up; whenever the module receives a packet of data, the
Rx/Link LED for that cable blinks.
In normal operation, you should see the LEDs start as dark. Then each of the control network
and fieldbus LEDs flash in unison (diagnostics), followed by the LEDs settling into their light
(Rx/Link) and dark (Tx) states. Normal operation quickly causes all of the LEDs on a primary or
single module to start flashing busily. On the shadow module, the Rx/Link LEDs flashes.
If the LEDs on your module are not behaving this way:
1. There is no data being processed. Make sure that some FBMs and workstations
connected to the FCP270 are on-line using System Management.
2. The cabling for that port is disconnected, broken, or otherwise compromised. Check
the cable to the splitter/combiner or Ethernet switch for that port.
3. If the same LEDs are dark on both the primary and shadow modules of a married
fault-tolerant module pair, check the cabling between the Ethernet switch and the
splitter/combiner.
If none of the above issues caused the failure, you must replace the module.

Using the Fieldbus Tx and RX Status LEDs


The yellow Tx and Rx LEDs for Fieldbus A and B only indicate communication activity on their
respective links.
In normal operation, the Tx LED is on when it is transmitting data over fieldbus A or B. The Rx
LED is on when the controller is receiving data over fieldbus A or B. For a fault-tolerant FCP270,
the Tx LEDs are active only on the primary module, but the Rx LEDs are active on both the pri-
mary and shadow modules.
If the LEDs on your module are not behaving this way:
1. There is no data being processed. Make sure that some FBMs and workstations
connected to the FCP270 are on-line using System Management.
2. The fieldbus cabling is disconnected, broken, or otherwise compromised. Check the
fieldbus cabling between baseplates and the termination cable connections between
the baseplate and Termination Assemblies. For more information, refer to DIN Rail
Mounted FBM Subsystem User’s Guide (B0400FA).
If none of the above issues caused the failure, you must replace the module.

Fault-Tolerant FCP270 Troubleshooting Addenda


Fault-tolerance in the FCP270 uses software synchronization to keep the two modules executing
exactly the same software, using exactly the same data. If the software is not synchronized,
synchronization is restored when the primary module transmits its database to the shadow
module in a sequence commonly referred to as a “hot remarry.” The hot remarry is essentially the
same as the initial station marriage.

80
5. Troubleshooting B0700AR – Rev H

NOTE
The fault-tolerant control processor marriage is broken if five hot remarries occur
within one minute. When the marriage is broken, the shadow is placed in off-line
state and the message “Error Escalation Threshold has been exceeded” is printed on
the system printer. You may then use the System Management Displays to reboot
(restart) the shadow module.

If either module in a fault-tolerant pair fails, the failed module’s red LED turns on. If this occurs,
proceed with the following checks. (These checks need not be followed in order.)
1. Make sure that the FCP270’s Ethernet network fiber cables are correctly connected.
2. Check for error messages at the system printer.
3. Replace the module if all else fails.

Replacing a Failed Module


To replace a failed module in an FCP270 fault-tolerant pair:
1. Disconnect the fiber optic cables from the Control Network A and B connectors on
the front of the failed module. To release the LC connector latch, push on the latch
with your finger until the connector springs apart slightly to an unlatched position.
Then, grasp the LC connector by hand and pull it to disconnect it from the
module.

NOTE
If you grasp the connector and squeeze to unlatch it, the spring-apart action may be
defeated.

2. Loosen the module base mounting screws completely using a 5/32 hex driver tool
(Foxboro P/N X0179AZ).
3. Using both hands, pull on the module to remove it from the baseplate.
4. Install the new module using the appropriate procedure.
See “Installing a Shadow FCP270 Module” on page 24.
After the new module (shadow) is installed, it automatically boots up, acquires its letterbug, image
and control database from the primary module, and marries the primary module.

Available Memory Error Messages


The following error messages indicate any issues that arise with regards to the available memory in
the FCP270. The available memory in a FCP270 is required not to go below 500Kb and these
messages are sent to SMON when various memory thresholds (below 500Kb) are passed. They
may precede various failures induced by CPs operating with reduced available memory, such as
communications slow-downs, loss of connections and potential serious issues when the memory
drops below 100Kb. The error messages and their thresholds are as follows:
 Available Memory is below recommended limits - indicates that there are less
than 400Kb available
 Available Memory far below recommended limits - indicates that there are
less than 200Kb available

81
B0700AR – Rev H 5. Troubleshooting

 Available Memory is critically low - indicates that there are less than 100Kb
available

Memory Dumps and Last Gasp Messages


The following sections describe memory dumps and last gasp messages.

Last Gasp Messages


Last gasp messages are a way of sending information about a failure before the FCP270 restarts.
Last gasp messages contain the controller ID and error code.
In the case of a failed module within a fault-tolerant pair, the failed controller passes the last gasp
message to the primary controller. The primary controller then transmits the message to a work-
station. Last gasp messages from a non-fault-tolerant controller are transmitted directly.

Memory Dumps
There are two kinds of memory dumps. If the module experiences a SW error while running
(such as WDT time-out or a memory violation), it saves a memory image of the FCP270 so that
a thorough failure analysis can be performed. To preserve the information about this event, the
controller quickly compares its code image to the code image in flash memory. Any differences are
burned into the flash memory for later analysis. The failed controller also compresses and burns
the entire data space into flash memory for later analysis. The controller will reboot immediately
after writing the memory dump into the flash memory (elapsed time approximately 30 seconds).
Upon reboot, the module sends a message to the error log indicating that it experienced a mem-
ory violation or WDT time-out.
The other kind of memory dump is when a “Forced” dump is initiated, whereby the current con-
tents of memory are compressed and saved into flash. Forced dump analysis IS NOT useful to
analyze hardware failures of RED only or RED/GREEN modules. Forced dumps erase any previ-
ous memory violation information stored in flash, so should only be initiated at the express
request of Invensys development.
The memory dump information can be extracted from the controller in one of two ways.
1. The controller is replaced by another controller and its dump information extracted
off-line.
2. The controller can be uploaded on-line while still running all normal control
functions.

! WARNING
For safety reasons, always consider the possible impact on plant operations before
placing the primary FCP270 module off-line or rebooting it after the shadow
module has failed.

a. If the module was married at the time of the violation, only the information from
the primary can be uploaded (the shadow module will be placed off-line during
the dump upload). If the violation was in the shadow module, it must become the
primary to upload the memory dump. To make the shadow module become pri-

82
5. Troubleshooting B0700AR – Rev H

mary, push the Reset button on the front of the current primary module or use the
SMDH Equipment Change display to reboot the primary module.
b. To initiate the dump upload from the command line prompt, execute the
iaboot_upld <letterbug> command from directory opt/fox/bin/tools.
The module sends its entire flash memory contents to a 16 MB file in directory
usr/fox/sp/files with the title <letterbug>_dumpX where X is a sequential number
with the current dump having the greatest number.
The entire upload process takes approximately 3 minutes and its status is
indicated by messages at the system printer.
Syntax
iaboot_upld <letterbug> action
where:
 <letterbug> = 6-character letterbug of the controller
 action = U to upload existing dump image from single/primary module. This
is the command that should always be used to extract memory violation
information.
 action = F to create a new dump image and restart single/shadow module

NOTE
The “F” option forces a dump of the current module state and WILL ERASE any
information from a previous memory violation. ONLY USE the “F” option when
directed by Invensys Development personnel.

After successful launch of the program it issues a double-check message as follows.


If action = F:
“Create a new dump image and restart single/shadow module - enter Y/N:”
If action = U:
“Set controller to run single and upload existing dump image - enter Y/N:”
If Y (or y) is entered, a final message is issued
“Create new dump image initiated.”
or
“Upload dump initiated”
c. If the original fault occurred while the modules were married, you can now restart
the off-line module, which remarries its partner. To restart the module, use the
“Reboot Station Procedure” on page 58.

NOTE
Non-fault-tolerant controllers can transmit their memory dump at any time.

83
B0700AR – Rev H 5. Troubleshooting

Diagnostics
The FCP270 diagnostic routines are broken down into four areas as follows:
 Start-up
 Error Recovery Local
 Error Recovery Cooperative

NOTE
There are no user scheduled diagnostics required for the FCP270.

Start-Up Diagnostics
Start-up diagnostics run every time the module is powered up or restarted. Start-up diagnostics
test the basic core functionality of the module prior to running control or attempting marriage.
They consist of boot flash checksum, code flash checksum, main and I/O shared memory tests,
Interrupt controller tests, and other low level functionality. The start-up diagnostics complete in
approximately five seconds. A failure is indicated by the Operational Status LEDs (red LED
remains on and green LED remains off ).

Error Recovery Local Diagnostics


Error recovery local diagnostics run at initial installation and whenever a fault is detected by the
run-time mechanisms (output miscompare, sync time-out, and so forth). These diagnostics
attempt to identify any faults that can be isolated to a particular controller. Examples are Ethernet
port loopback tests, state sequencer tests, interrupt controller tests, shared memory tests, and I/O
interface tests. A failure is indicated by the Operational Status LEDs (red LED is on and green
LED is off ) and by messages at the system printer.

Error Recovery Cooperative Diagnostics


Error recovery cooperative diagnostics run when a fault is detected by the run-time mechanisms
(output miscompare, sync time-out, and so forth). These diagnostics tests work cooperatively to
identify any faults that inhibit normal fault-tolerant operations.
If a failure is localized to a particular controller, that controller is sent to the failed state. An
example of this type of failure is a detected compare logic failure. In this case, logic is that
controllers A and B perform cooperative loopback tests with comparison logic enabled;
controller B passes all tests and controller A fails due to a miscompare.
If a fault is detected in the mechanisms but it cannot be isolated to a particular controller, the
shadow controller is sent to the off-line state. An example of this is inter-link exchange failure.
If no fault is detected then a PASSED indication is returned which results in a Hot-Remarry
where all variable data from the primary controller are copied into the shadow controller.
A failure is indicated by the Operational Status LEDs (red LED is on and green LED is off ) and
by messages at the system printer.

84
Appendix A. Upgrade Diagrams
This Appendix contains cabling diagrams for upgrading various Control Processors to the
FCP270.
Multiple options are available for upgrading (converting) systems containing various control pro-
cessors to the FCP270 in an I/A Series network. The figures in this Appendix illustrate how to
perform these upgrades (conversions) to the FCP270, including their parts and cables necessary to
interconnect the various modules. The illustrations are as follows:
 Figure A-2 “Converting CP10/30/40 with Local I/O to FCP270s” on page 87
 Figure A-3 “Converting CP60 with DCM10E to FCP270” on page 88
 Figure A-4 “Converting CP60 with DCM10Ef to FCP270” on page 89
 Figure A-5 “Converting CP60 with DCM10Ef with Fiber Optic Hub to FCP270” on
page 90
 Figure A-6 “Converting CP60 with FBI10E and 100 Series FBMs to FCP270s” on
page 91
 Figure A-7 “Converting CP60 with 200 Series DIN Rail Mounted Equipment to
FCP270” on page 92
 Figure A-8 “Converting Micro-I/A Station to FCP270” on page 93
 Figure A-9 “Converting AW51/AW70 to FCP270s” on page 94

NOTE
Systems with combinations of FCM10- and DCM10-type modules will not be
supported until a later I/A Series software release.

The order in which to replace equipment when upgrading (converting) systems with the Control
Processor 60 to the FCP270 is illustrated in Figure A-1 “Equipment Replacement Order for
CP60-to-FCP270 Conversions” on page 86.

85
B0700AR – Rev H Appendix A. Upgrade Diagrams

CP60
CONFIGURATION

200 SERIES 200 SERIES 100 SERIES


or
100 SERIES

FCM10E FCM10E FCM10Ef DCM10E DCM10E DCM10Ef


or DCM10Ef or
FCM10Ef FBI10E

FBI10E
• Remove CP60 • Remove CP60 • Remove CP60 • Remove CP60
• Remove Coax Cable • Remove Coax Cable • Remove Coax Cable • Remove Coax Cable
• Remove CP60
• Remove Cox ‘Tees’ • Remove Cox ‘Tees’ • Remove Cox ‘Tees’ • Remove Cox ‘Tees’
• Remove Coax Cable
• Remove Terminators • Remove Terminators • Remove Terminators • Remove Terminators
• Remove Cox ‘Tees’
• Remove any fiber extension • Remove Fiber Equip. • Remove any fiber extension • Remove Fiber Equip.
• Remove Terminators
equipment • Re-use Fiber Cable equipment • Leave Fiber Cable
• Remove FCM10E modules • Remove any fiber extension
• Remove FBM01Ef modules • Remove DCM10E modules
equipment
• Replace FBI10e modules with
Fieldbus Isolator modules
• Connect Fieldbus Terminal
Assemblies
<60 m <60 m >60 m
or
>60 m
<975 m >975 to 1830 m <975 m
<975 m <975 m
or or
>975 m >975 m

>975 to
One FBM baseplate connection: One FBM baseplate connection:
2000 m
• FBM modules can be installed • Install FCM2f modules in FCM
in FCM locations locations
• Install FCP270, baseplate • Install FCP270, baseplate &
& supplies supplies
• Connect FCP270 baseplate to • Install FCM2f*, baseplate &
200 Series baseplates with an supplies near FCP270s
HDLC cable • Connect FCP270 baseplate
• Install FCP270 modules, • Install FCP270 modules, • Install FCP270 modules,
• Terminate the HDLC cables to FCM2f* baseplate with an
baseplate & supplies baseplate & supplies baseplate & supplies
HDLC cable
OR • Connect terminal assemblies • Install FBI200/100 modules, • Connect terminal assembly
• Connect FCM2f* modules with
to FCP270 baseplate baseplate & supplies near to FCP270 baseplate
More than one FBM baseplate fiber cables
• Connect FCP270 terminal the FCP270 modules • Install fiber optic modems,
connection: • Terminate the HDLC cables
assemblies to 100 Series • Connect FBI200/100 baseplate & supplies near
• FBM modules can be installed
OR terminal assemblies with baseplate to FCP270 the FCP270 modules
in FCM locations
More than one FBM baseplate Twinaxial cables baseplate with an HDLC • Connect fiber modems to
• Install FCP270, baseplate &
connection: • Terminate the HDLC cables cable FCP270 terminal
supplies
• Connect FBI200/100 assemblies using
• Install FEM100 modules, • FBM modules can be installed
baseplate to Fieldbus Twinaxial cables
baseplates & supplies near in FCM locations
Isolator terminal assemblies • Install fiber optic modems,
FBMs • Install FCP270, baseplate &
with Twinaxial cables baseplate & supplies
• Connect FEM100 baseplate to supplies
• Terminate the HDLC cables near the 100 Series
200 Series baseplate with • Install FCM2f*, baseplate &
supplies near FCP270s nest
HDLC cables
• Connect FCP270 baseplate • Connect the remote fiber
• Connect FEM100 baseplate to
to the FCM2f* baseplate with modems to FBI terminal
FCP270 baseplate with an
an HDLC cable assembly using
HDLC cable
• Install FEM100 modules, Twinaxial cables
• Terminate the HDLC cables
baseplates & supplies near • Connect the fiber modems
FBMs near the FCP270 modules
• Connect FEM100 baseplate to to the fiber modems near
the 200 Series baseplate with the 100 Series nest using
an HDLC cable the existing fiber cables
• Install FCM2f*, baseplate & • Terminate the HDLC cables
supplies near FEM100s
• Connect FEM100 baseplate to
the FCM2f* baseplate with an
HDLC cable
• Connect FCM2f* modules with
fiber cables
• Terminate the HDLC cables

Transfer the control scheme to the FCP270

Figure A-1. Equipment Replacement Order for CP60-to-FCP270 Conversions

86
Appendix A. Upgrade Diagrams B0700AR – Rev H

P0926CM = 33"
P0927AQ = 72”
P0927AR = 96”

FBI200/100

FBI200/100

Figure A-2. Converting CP10/30/40 with Local I/O to FCP270s

87
B0700AR – Rev H Appendix A. Upgrade Diagrams

FBI200/100
P0926CM = 33"
P0927AQ = 72”
P0927AR = 96”

FBI200/100

Figure A-3. Converting CP60 with DCM10E to FCP270

88
Overview Cabling Diagram For Converting CP60 w/DCM10Ef To FCP270s
FIBER CABLE GROUP A FPS400 POWER CABLES FIBER CABLE GROUP C FPS400 LINE CORDS
MMF with MT-RJ/LC GROUP B MMF w/MTRJ CABLES GROUP D EXISTING CP60/DCM10Ef EQUIPMENT
CABLES P0926KK = 16" P0972KV = 3 m P0926CN = 11"
P0972TR = 3 m P0926KL = 36" P0972KW = 10 m P0923DA = 15" REMOVE EQUIPMENT HIGHLIGHTED IN YELLOW
P0972TS = 15 m P0926KM = 48" P0972KX = 50 m P0926CM = 33"
P0972TT = 50 m P0926KN = 60" CUSTOMER 10Base-2 COAX
P0927AQ = 72”
CUSTOMER SUPPLIED = P0926KP = 72" SUPPLIED = >50m, < 2 km 185 m /607 ft (max) END-OF-LINE
P0927AR = 96”
>50m, < 2 km P0926KQ = 84" NOTE: OTHER WELL TERMINATOR
FILTERED 24 TO 39 Vdc
TO OTHER MESH TO OPTIONAL ADDITIONAL
POWER SOURCES MAY BE
COMPONENTS BNC to FIBER 1 x 8 STRUCTURES
SUBSTITUTED FOR THE
MESH CONVERTER
P0904AU PDU.
CABLE GROUP C
NETWORK OPTIONAL 1 GBit UPLINK. ST/ST MMF FIBER
REQUIRES UPLINK CARDS 2 km (max) CABLE

P0972YC (EXAMPLE) P0972WP (EXAMPLE) TWINAXIAL CABLE 1 x 8 STRUCTURE


Appendix A. Upgrade Diagrams

24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-TX SWITCH


DCM 6000 ft (max)
W/MTRJ CONNECTORS W/RJ-45 CONNECTORS
10Ef

10Base-2 COAX
SWITCH GROUP A SWITCH GROUP A
FBI

IPM2
IPM2

TO OTHER MESH PDU


P0904AU
FBM
FBM

FBM
FBM
FBM

FBM
FBM

COMPONENTS
100 SERIES
100 SERIES

100 SERIES
100 SERIES
100 SERIES

100 SERIES
100 SERIES

FBI

IPM2
IPM2

P0972WP (EXAMPLE) TWINAXIAL CABLE


24-PORT, 100Base-TX SWITCH
6000 ft (max)
P0972YC (EXAMPLE) W/RJ-45 CONNECTORS
NODEBUS DCM
24-PORT, 100Base-FX SWITCH SWITCH GROUP B
W/MTRJ CONNECTORS CP60 10Ef
ST/ST MMF FIBER 2 km (max)
SWITCH GROUP B CABLE
CONNECTION TO EXISTING TO OPTIONAL ADDITIONAL
NODEBUS BNC to FIBER 1 x 8 STRUCTURES
CONVERTER
END-OF-LINE
TERMINATOR

10Base-2 COAX
POWER
MODULE 185 m/607 ft (max)
FIBER OPTIC
FPS400-24
CABLE GROUP A
P0917LY/
FBI TERMINAL ASSEMBLY
P0922YU UPGRADED EQUIPMENT P0800DC
ADD EQUIPMENT HIGHLIGHTED IN GREEN
1 x 8 STRUCTURE
P0973EE
CABLE P0904AT TWINAX
P0973ED
FAULT TOLERANT PAIR
GROUP D
EXISTING
ST/ST MMF FIBER
FBI

IPM2
IPM2

OR FIBER CABLE FIBER PDU


PRI PWR CABLE GROUP B
OPTIC OPTIC P0904AU
FBM
FBM
FBM
FBM
FBM
FBM
FBM

BASEPLATE TERMINAL MODEM 2 km (max) MODEM


100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES

FBI

ASSEMBLY KIT
A A
IPM2
IPM2

P0903QF P0903QF
OR OR

OPTICAL
SPLITTER
EXISTING TWINAXIAL CABLE
P0903VY FBI TERMINAL ASSEMBLY
3200 ft/975 m (Max - all segments)
P0800DC

FCP270
FCP270

P0917YZ
P0917YZ
ADAPTER
P0926LC TERMINATOR
B B (USE AT END OF LINE)
SEC PWR TO OTHER
TWINAX

REMOTE
P0904AT I/O

Figure A-4. Converting CP60 with DCM10Ef to FCP270


P0972UN (GRAY, 50 cm) OPTIONAL 2nd

OPTICAL
SPLITTER
P0972VG (ORANGE, 50 cm) BASEPLATE TERMINAL 1 x 8 STRUCTURE
EXISTING TWINAXIAL CABLE
P0973BU (GRAY, 25 cm) ASSEMBLY KIT

SOCKET

FIELDBUS &
P0926AH P0972ZQ (ORANGE, 25 cm) 3200 ft/975 m (Max - all segments)

TIME STROBE
FBI

IPM2
IPM2

OR OR
EXISTING
BASEPLATE
FBM
FBM
FBM
FBM
FBM
FBM
FBM

P0903VY FIBER ST/ST MMF FIBER


FIBER
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES

HORIZONTAL = P0926HC
FBI

CABLE
OPTIC OPTIC
EXISTING
IPM2
IPM2

VERTICAL = P0926HW POWER CABLE GROUP B


MODEM 2 km (max) MODEM
MODULE OR
TWINAXIAL CABLE

FPS400-24 P0973ED TERMINATOR


P0903QF P0903QF (USE AT END OF LINE)
P0917LY/ TO OTHER
CYAN P0922YU REMOTE
COPPER (ie, Cu) ETHERNET CABLE P0973EE
I/O
MAGENTA FIBER (ie, FO) ETHERNET CABLE

CABLE GROUP D
B0700AR – Rev H

89
90
Overview Cabling Diagram For Converting CP60 w/DCM10Ef To FCP270s
FIBER CABLE GROUP A FPS400 POWER CABLES FIBER CABLE GROUP C FPS400 LINE CORDS
MMF with MT-RJ/LC GROUP B MMF w/MTRJ CABLES GROUP D EXISTING CP60/DCM10Ef EQUIPMENT
CABLES P0926KK = 16" P0972KV = 3 m P0926CN = 11"
P0972TR = 3 m P0926KL = 36" P0972KW = 10 m P0923DA = 15" REMOVE EQUIPMENT HIGHLIGHTED IN YELLOW
B0700AR – Rev H

P0972TS = 15 m P0926KM = 48" P0972KX = 50 m P0926CM = 33" 10Base-2 COAX FIBER OPTIC HUB
P0972TT = 50 m P0926KN = 60" CUSTOMER P0927AQ = 72” P0922KS END-OF-LINE
TERMINATOR
CUSTOMER SUPPLIED = P0926KP = 72" SUPPLIED = >50m, < 2 km P0927AR = 96” NOTE: OTHER WELL
>50m, < 2 km P0926KQ = 84" FILTERED 24 TO 39 Vdc TO OPTIONAL ADDITIONAL
ST CONNECTORS ST/ST MMF FIBER CABLE 1 x 8 STRUCTURES
POWER SOURCES MAY BE 2 km/6562 ft (max)
TO OTHER MESH
COMPONENTS SUBSTITUTED FOR THE
MESH P0904AU PDU.
TWINAXIAL CABLE
CABLE GROUP C
NETWORK 6000 ft (max)
OPTIONAL 1 GBit UPLINK. DCM
REQUIRES UPLINK CARDS 10Ef
1 x 8 STRUCTURE
P0972YC (EXAMPLE) P0972WP (EXAMPLE) PDU
24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-TX SWITCH P0904AU
W/MTRJ CONNECTORS W/RJ-45 CONNECTORS
FBI

IPM2
IPM2

POWER

10Base-2 COAX
SWITCH GROUP A SWITCH GROUP A
CABLES
FBM
FBM
FBM

FBM
FBM
FBM
FBM

TO OTHER MESH
100 SERIES
100 SERIES
100 SERIES

100 SERIES
100 SERIES
100 SERIES
100 SERIES

FBI

COMPONENTS
IPM2
IPM2

P0972WP (EXAMPLE)
24-PORT, 100Base-TX SWITCH DCM
10Ef TWINAXIAL CABLE
P0972YC (EXAMPLE) W/RJ-45 CONNECTORS
NODEBUS 6000 ft (max)
24-PORT, 100Base-FX SWITCH SWITCH GROUP B
W/MTRJ CONNECTORS CP60 ST/ST MMF FIBER
CABLE
TO OPTIONAL ADDITIONAL
SWITCH GROUP B 2 km/6562 ft (max)
CONNECTION TO EXISTING ST CONNECTORS 1 x 8 STRUCTURES
NODEBUS FIBER OPTIC HUB END-OF-LINE
P0922KS TERMINATOR

POWER TWINAX FBI


MODULE TERMINAL ASSEMBLY
FIBER OPTIC
FPS400-24 UPGRADED EQUIPMENT P0800DC
CABLE GROUP A
P0917LY/
P0922YU
ADD EQUIPMENT HIGHLIGHTED IN GREEN
1 x 8 STRUCTURE
P0973EE
PDU
P0973ED P0904AU
EXISTING
CABLE ST/ST MMF FIBER
FBI

P0904AT
IPM2
IPM2

GROUP D OR FIBER CABLE FIBER


FAULT TOLERANT PAIR
CABLE GROUP B OPTIC OPTIC
FBM
FBM
FBM
FBM
FBM
FBM
FBM

MODEM 2 km/6562 ft (max) MODEM


100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES

FBI

PRI PWR
IPM2
IPM2

OR P0903QF P0903QF OR
A A EXISTING TWINAXIAL CABLE FBI
TWINAX

P0903VY 3200 ft/975 m (Max - all segments) TERMINAL ASSEMBLY


ADAPTER P0800DC

OPTICAL
SPLITTER
P0926LC EXISTING TWINAXIAL CABLE
P0903VY
3200 ft/975 m (Max - all segments) TERMINATOR
TWINAX (USE AT END OF LINE)
OR

FCP270
FCP270
OR

P0917YZ
P0917YZ
EXISTING
FIBER ST/ST MMF FIBER FIBER OPTIONAL 2nd
BASEPLATE CABLE
B B SEC PWR
TERMINAL ASSEMBLY OPTIC OPTIC P0904AT 1 x 8 STRUCTURE
KIT x 2 MODEM 2 km/6562 ft (max) MODEM

P0972UN (GRAY, 50 cm) P0903QF P0903QF

OPTICAL
SPLITTER
FBI

P0972VG (ORANGE, 50 cm)


IPM2
IPM2

P0973BU (GRAY, 25 cm)

SOCKET
TWINAX
TWINAX

OR

FIELDBUS &
P0972ZQ (ORANGE, 25 cm)
FBM
FBM
FBM
FBM
FBM
FBM
FBM

P0926AH

TIME STROBE
D
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES

FBI

BASEPLATE CABLE GROUP B


73E
IPM2
IPM2

HORIZONTAL = P0926HC
P09
E

VERTICAL = P0926HW POWER


73E

MODULE
P09

FPS400-24 TERMINATOR

Figure A-5. Converting CP60 with DCM10Ef with Fiber Optic Hub to FCP270
P0917LY/ (USE AT END OF LINE)
CYAN P0922YU
COPPER (ie, TP) ETHERNET CABLE TO OTHER REMOTE I/O

MAGENTA FIBER (ie, FO) ETHERNET CABLE

CABLE GROUP D
Appendix A. Upgrade Diagrams
Appendix A. Upgrade Diagrams B0700AR – Rev H

P0926CM = 33"
P0927AQ = 72”
P0927AR = 96”

Figure A-6. Converting CP60 with FBI10E and 100 Series FBMs to FCP270s

91
92
Overview Cabling Diagram For Converting CP60-200 Series To FCP270s
FIBER CABLE GROUP A FPS400 POWER CABLES FIBER CABLE GROUP C FPS400 LINE CORDS
MMF with MT-RJ/LC GROUP B MMF w/MTRJ CABLES GROUP D EXISTING CP60-200 SERIES EQUIPMENT
CABLES P0926KK = 16" P0972KV = 3 m P0926CN = 11"
P0972TR = 3 m P0926KL = 36" P0972KW = 10 m P0923DA = 15" REMOVE EQUIPMENT HIGHLIGHTED IN YELLOW
P0972TS = 15 m P0926KM = 48" P0972KX = 50 m P0926CM = 33"
REDUNDANT FCMs Cable Group B
P0972TT = 50 m P0926KN = 60" CUSTOMER P0927AQ = 72” Fiber Extension
B0700AR – Rev H

CUSTOMER SUPPLIED = P0926KP = 72" SUPPLIED = >50m, < 2 km P0927AR = 96” Equipment
>50m, < 2 km P0926KQ = 84" (Optional)

TO OTHER MESH
COMPONENTS FBM FBM
MESH
CABLE GROUP C FCM FCM POWER
NETWORK OPTIONAL 1 GBit UPLINK. I/A Series I/A Series I/A Series I/A Series MODULE
REQUIRES UPLINK CARDS
FPS400-24

P0972YC (EXAMPLE) P0972WP (EXAMPLE) P0922YU/


24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-TX SWITCH P0917LY
Up to 4 Baseplace each with 30 FBMs
W/MTRJ CONNECTORS W/RJ-45 CONNECTORS
SWITCH GROUP A SWITCH GROUP A

TO OTHER MESH
COMPONENTS
FBM FBM
POWER
P0972WP (EXAMPLE) FCM FCM MODULE
I/A Series I/A Series I/A Series I/A Series
24-PORT, 100Base-TX SWITCH FPS400-24
P0972YC (EXAMPLE) W/RJ-45 CONNECTORS
P0922YU/
24-PORT, 100Base-FX SWITCH SWITCH GROUP B
NODEBUS
DNBT CP60 CP60 P0917LY
W/MTRJ CONNECTORS OR REDUNDANT FCMs
SWITCH GROUP B CONNECTION TO EXISTING
NODEBUS P0916RB
Terminator Cable Group D

POWER MODULE NOTES:


POWER
FIBER OPTIC P0922YC available with
MODULE UPGRADED EQUIPMENT
CABLE GROUP A 24 Vdc INPUT
FPS400-24 ADD EQUIPMENT HIGHLIGHTED IN GREEN P0922YU and P0917LY =
P0917LY/ 85-240 Vac INPUT
P0922YU P0916RB or 125 Vdc INPUT
Terminator
CABLE GROUP D Cable Group B
CABLE GROUP B
Up to 20 meters, total lenght
FAULT TOLERANT PAIR

PRI PWR RX RX
FBM FBM
TX TX
FCM FCM
A A 2f2/4/10 2f2/4/10 POWER
I/A Series I/A Series I/A Series I/A Series MODULE
FPS400-24

OPTICAL
SPLITTER
OR
P0922YU/
RX RX
P0917LY
Up to 4 Baseplace each; with 30 FBMs Total
Up to 10Km

FCP270
FCP270
TX TX Cable Group C

P0917YZ
P0917YZ
P0916RB

SOCKETS
FCM FCM

FIELDBUS &
Terminator 2f2/4/10 2f2/4/10

TIME STROBE
I/A Series I/A Series
B B

P0972UN (GRAY, 50 cm) RX RX


FBM FBM

OPTICAL
SPLITTER
TX TX
P0972VG (ORANGE, 50 cm) POWER
P0973BU (GRAY, 25 cm) To another FCM FCM
SEC PWR FCP270 Controller 2f2/4/10 2f2/4/10 MODULE
P0926AH P0972ZQ (ORANGE, 25 cm) I/A Series I/A Series I/A Series I/A Series
FPS400-24
BASEPLATE CABLE GROUP B P0922YU/
HORIZONTAL = P0926HC P0917LY
VERTICAL = P0926HW POWER
MODULE
FPS400-24
CABLE GROUP D
P0917LY/
CYAN P0922YU
COPPER (ie, TP) ETHERNET CABLE
MAGENTA FIBER (ie, FO) ETHERNET CABLE

Figure A-7. Converting CP60 with 200 Series DIN Rail Mounted Equipment to FCP270
Appendix A. Upgrade Diagrams
Appendix A. Upgrade Diagrams B0700AR – Rev H

FBI200/100

FBI200/100
P0927AQ = 72”
P0927AR = 96”

Figure A-8. Converting Micro-I/A Station to FCP270

93
B0700AR – Rev H Appendix A. Upgrade Diagrams

FBI200/100

FBI200/100
P0927AQ = 72”
P0927AR = 96”

Figure A-9. Converting AW51/AW70 to FCP270s

94
Appendix B. FEM100 and FBI100
Connection Diagrams
This Appendix contains cabling diagrams for connecting the FEM100 and FBI100 modules to
the FCP270.
The figures in this Appendix illustrate typical configurations for connecting the FEM100 and
FBI100 modules to the FCP270, including their parts and cables necessary to interconnect the
various modules. The illustrations are as follows:
 Figure B-1 “Overview for FCP270-to-FEM100 Cabling” on page 96
 Figure B-2 “Overview for Expanded Fieldbus Cabling (FCP270 to Four FEM100s)”
on page 97
 Figure B-3 “Overview for Dual Baud Cabling (FCP270 to FEM100 and FBI100)” on
page 98

95
96
FIBER CABLE GROUP A FIBER CABLE GROUP C HDLC CABLES
MMF with MT-RJ/LC MMF w/MTRJ CABLES GROUP E Overview Cabling Diagram For FEM100s
CABLES P0972KV = 3 m P0916ND = 0.25 m
P0972TR = 3 m P0972KW = 10 m P0917JJ = 0.5 m
P0972TS = 15 m P0972KX = 50 m P0916MZ = 1.0 m
FCP270 INSTALLATION WITH 32 FBM LIMIT
HDLC CABLES: LAST OF BASEPLATES HOLDING UP TO 32 FBMs
P0972TT = 50 m CUSTOMER P0916NC = 3.0 m PRI PWR CABLE GROUP E
CUSTOMER SUPPLIED = SUPPLIED = >50m, < 2 km P0916NB = 5.0 m FIBER OPTIC
>50m, < 2 km P0916NA = 10 m CABLE GROUP A
A A
B0700AR – Rev H

FPS400 LINE CORDS P0916UH = 20 m


FPS400 POWER CABLES GROUP D P0916UJ = 30 m FBM FBM
GROUP B

OPTICAL
SPLITTER
P0926CN = 11" BASE- BASE-

FBM
FBM
FBM
FBM

P0916UK = 60 m
P0926KK = 16"

SOCKET
P0923DA = 15" PLATE PLATE

200 Series
200 Series
200 Series
200 Series

FIELDBUS &
P0926KL = 36" TO OTHER MESH

TIME STROBE
P0926CM = 33" I/A Series I/A Series I/A Series I/A Series
COMPONENTS TERMINATOR

FCP270
FCP270
P0926KM = 48"

P0917YZ
P0917YZ
P0916RB
P0926KN = 60" CABLE GROUP C See Note 2
P0926KP = 72" OPTIONAL 1 GBit UPLINK. TERMINATOR
B B
P0926KQ = 84" REQUIRES UPLINK CARDS P0916RB

SOCKET
Notes:

FIELDBUS &
TIME STROBE
P0972YC (EXAMPLE) P0972YC (EXAMPLE) P0972UN (GRAY, 50 cm) 1. The number of FBMs supported is subject to

OPTICAL
SPLITTER
24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-FX SWITCH P0972VG (ORANGE, 50 cm)
P0973BU (GRAY, 25 cm)
FCP270 sizing restraints.
W/MTRJ CONNECTORS W/MTRJ CONNECTORS P0972ZQ (ORANGE, 25 cm)
P0926AH SEC PWR
SWITCH GROUP A SWITCH GROUP A 2. The total cable length of the Module Fieldbus (shielded
BASEPLATE twisted-pair segment) cannot exceed 60 m (198 ft)
HORIZONTAL = P0926HC
VERTICAL = P0926HW
between the FCP, FEM100 or FCM2F2/4/10 and the
end of the baseplate chain.
P0972YC (EXAMPLE) P0972YC (EXAMPLE) FCP270 INSTALLATION WITH 4-SLOT FEM100 BASEPLATE (See Note 1)
24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-FX SWITCH
3. The cable length between the FCP and FEMs
W/MTRJ CONNECTORS W/MTRJ CONNECTORS TO PRI POWER SUPPLY
cannot exceed 60 m (198 ft). See “FCP270 Product
SWITCH GROUP B SWITCH GROUP B Sizing” in B0400FA for the list of cabling restrictions.
A A TERMINATOR
P0916RB

P0926KZ
MESH OPTIONAL

FCP270
FCP270

P0917YZ
P0917YZ
TIME STROBE

OPTICAL
OPTICAL
NETWORK

SPLITTER
SPLITTER
B B ADAPTER/TERMINATOR
FBM
FBM
FBM
FBM

See Note 2
200 Series
200 Series
200 Series
200 Series

TERMINATOR
I/A Series I/A Series I/A Series I/A Series
P0916RB
FIBER OPTIC POWER FIELDBUS 3 FIELDBUS 1 FBM FBM
CABLE GROUP A MODULE 3 1 BASE- BASE- LAST OF BASEPLATES HOLDING UP TO 32 FBMs
FPS400-24 PLATE PLATE
P0926KW
P0926KW

FEM100
FEM100

P0973CA
P0973CA
P0917LY/ FIELDBUS 2
P0922YU 2
I/A Series I/A Series HDLC CABLES:
FIELDBUS 4 CABLE GROUP E
4-SLOT FEM100 BASEPLATE
FBM
FBM
FBM
FBM

TERMINATOR
200 Series
200 Series
200 Series
200 Series

FAULT TOLERANT PAIR BASEPLATE: P0973CN


FIELDBUS "A" CABLE FBM FBM P0916RB
I/A Series I/A Series I/A Series I/A Series

PRI PWR
BASE- BASE-

CABLE GROUP B
FIELDBUS "B" CABLE PLATE PLATE

A A

OPTICAL
SPLITTER
FCP270 INSTALLATION WITH 2-SLOT FEM100 BASEPLATE UPGRADE (See Note 1)

CA

SOCKET
BL
CABLE GROUP E

FIELDBUS &
TIME STROBE
EG

FCP270
FCP270
PRI PWR

RO

P0917YZ
P0917YZ
FIELDBUS 4 FBM FBM

UP
E
4
FBM
FBM
FBM
FBM

BASE- BASE-
TERMINATOR PLATE PLATE TERMINATOR
200 Series
200 Series
200 Series
200 Series

B B HDLC
P0916RB P0916RB

SOCKET
I/A Series I/A Series I/A Series I/A Series
FIELDBUS 3

FIELDBUS &

Figure B-1. Overview for FCP270-to-FEM100 Cabling


TIME STROBE
3
P0972UN (GRAY, 50 cm) SEC PWR ADDED EQUIPMENT

OPTICAL
SPLITTER
P0972VG (ORANGE, 50 cm) LAST OF BASEPLATES HOLDING UP TO 32 FBMs
FEM100
FEM100

P0973BU (GRAY, 25 cm)


P0973CA
P0973CA

FIELDBUS 2 HDLC CABLES:


P0926AH P0972ZQ (ORANGE, 25 cm) SEC PWR 2
TERMINATOR CABLE GROUP E
I/A Series I/A Series
P0916RB
BASEPLATE FBM FBM
HORIZONTAL = P0926HC BASEPLATE 2-SLOT 1 BASE- BASE-
VERTICAL = P0926HW POWER P0973CG FEM100 BASEPLATE PLATE PLATE
FBM
FBM
FBM
FBM

MODULE TERMINATOR
200 Series
200 Series
200 Series
200 Series

CABLE GROUP B
FPS400-24 P0916RB
I/A Series I/A Series I/A Series I/A Series
P0917LY/ See Note 3 See Note 2
P0922YU

CABLE GROUP D
Appendix B. FEM100 and FBI100 Connection Diagrams
Overview Cabling Diagram For Connecting FCP270s with FEM100
FIBER CABLE GROUP A FPS400 POWER CABLES FIBER CABLE GROUP C FPS400 LINE CORDS
MMF with MT-RJ/LC GROUP B MMF w/MTRJ CABLES GROUP D Up to 4 Baseplates each; 128 FBM modules total
Adjust power supply loading accordingly CABLE GROUP C
CABLES P0926KK = 16" P0972KV = 3 m P0926CN = 11"
P0972TR = 3 m P0926KL = 36" P0972KW = 10 m P0923DA = 15"
P0972TS = 15 m P0926KM = 48" P0972KX = 50 m P0926CM = 33" HDLC CABLES
P0972TT = 50 m P0926KN = 60" CUSTOMER GROUP E
CUSTOMER SUPPLIED = P0926KP = 72" SUPPLIED = >50m, < 2 km P0916ND = 0.25 m
>50m, < 2 km P0926KQ = 84" P0917JJ = 0.5 m
P0916MZ = 1.0 m POWER
TO OTHER MESH P0916NC = 3.0 m MODULE

FBM
FBM
FBM
FBM
COMPONENTS

I/A Series
I/A Series
I/A Series
I/A Series

MESH P0916NB = 5.0 m FPS400-24


CABLE GROUP C P0916NA = 10 m P0922YU /
NETWORK OPTIONAL 1 GBit UPLINK. P0916UH = 20 m P0917LY
REQUIRES UPLINK CARDS P0916UJ = 30 m
P0916UK = 60 m
P0972YC (EXAMPLE) P0972WP (EXAMPLE)

FBM
FBM
FBM
FBM

I/A Series
I/A Series
I/A Series
I/A Series

24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-TX SWITCH


W/MTRJ CONNECTORS W/RJ-45 CONNECTORS
SWITCH GROUP A SWITCH GROUP A POWER
MODULE

FBM
FBM
FBM
FBM

TO OTHER MESH FPS400-24

I/A Series
I/A Series
I/A Series
I/A Series

COMPONENTS P0922YU /
P0917LY

P0972WP (EXAMPLE)

FBM
FBM
FBM
FBM

I/A Series
I/A Series
I/A Series
I/A Series

24-PORT, 100Base-TX SWITCH


P0972YC (EXAMPLE) W/RJ-45 CONNECTORS
24-PORT, 100Base-FX SWITCH SWITCH GROUP B CABLE GROUP D
W/MTRJ CONNECTORS P0916RB
SWITCH GROUP B Terminator
POWER MODULE NOTES:
See Note 1., Note 2. and P0922YC available with
Appendix B. FEM100 and FBI100 Connection Diagrams

cable group E.
24 Vdc INPUT
P0922YU and P0917LY =
85-240 Vac INPUT
or 125 Vdc INPUT

Extension
Extension
Extension
Extension

FIELDBUS 4
Equipment
FIELDBUS 3
Equipment
FIELDBUS 2
Equipment
FIELDBUS 1
Equipment

POWER
FIBER OPTIC
MODULE

2Mbit HDLC Fiber


2Mbit HDLC Fiber
2Mbit HDLC Fiber
2Mbit HDLC Fiber

CABLE GROUP A
FPS400-24
P0922YU /
P0917LY
CABLE GROUP D
CABLE GROUP B

FAULT TOLERANT PAIR CABLE GROUP E


See Note 2
PRI PWR BASEPLATE: P0973CG
BASEPLATE: P0926KH BASEPLATE: P0926KH
or P0926KE or P0926KE
PRI PWR
4

A A 2Mbit HDLC Fiber


Extension Equipment P0916RB

OPTICAL
Cable group E Terminator

SPLITTER
3

RX RX RX RX
FEM100
FEM100

TX TX TX TX
P0973CA
P0973CA

Cable group E

FCP270
FCP270
2

P0917YZ
P0917YZ
P0916RB FCM FCM FCM FCM

SOCKETS
2f2/4/10 2f2/4/10 2f2/4/10 2f2/4/10 I/A Series I/A Series

FIELDBUS &
Terminator I/A Series I/A Series I/A Series I/A Series

TIME STROBE
B B
1

SEC PWR 2-SLOT


Up to 10Km FEM100 BASEPLATE
P0972UN (GRAY, 50 cm) See Note 2

OPTICAL
SPLITTER
P0972VG (ORANGE, 50 cm)
P0973BU (GRAY, 25 cm)
P0972ZQ (ORANGE, 25 cm) SEC PWR
P0926AH

BASEPLATE CABLE GROUP B NOTES:


HORIZONTAL = P0926HC 1. Remote HDLC cable can be eliminated if remote FBM2F* modules are
mouted on the 200 Series baseplates.
VERTICAL = P0926HW POWER
2. The total cable length of the Module Fieldbus (shielded twisted-pair segment) cannot exceed 60 m (198 ft) between the FCP, FEM100 or FCM2F2/4/10 and the end of the baseplate chain.
MODULE 3. The cable length between the FCP and FEMs cannot exceed 60 m (198 ft). See “FCP270 Product Sizing” in B0400FA for the list of cabling restrictions.
FPS400-24

Figure B-2. Overview for Expanded Fieldbus Cabling (FCP270 to Four FEM100s)
CABLE GROUP D P0922YU /
CYAN P0917LY
COPPER (ie, TP) ETHERNET CABLE

MAGENTA FIBER (ie, FO) ETHERNET CABLE


B0700AR – Rev H

97
98
Overview Cabling Diagram For FEM100s w/FBI100s
For Dual-Baud Systems
B0700AR – Rev H

FIBER OPTIC FIBER CABLE GROUP A FIBER CABLE GROUP C HDLC CABLES
TO OTHER MESH
CABLE GROUP A MMF with MT-RJ/LC CABLES MMF w/MTRJ CABLES GROUP E
COMPONENTS
P0972TR = 3 m P0972KV = 3 m P0916ND = 0.25 m
CABLE GROUP C P0972TS = 15 m P0972KW = 10 m P0917JJ = 0.5 m
OPTIONAL 1 GBit UPLINK.
TO OTHER MESH P0972TT = 50 m P0972KX = 50 m P0916MZ = 1.0 m
REQUIRES UPLINK CARDS
DEVICES CUSTOMER SUPPLIED = CUSTOMER P0916NC = 3.0 m
MESH P0972YC (EXAMPLE) P0972YC (EXAMPLE) >50m, < 2 km SUPPLIED = >50m, < 2 km P0916NB = 5.0 m
24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-FX SWITCH P0916NA = 10 m
NETWORK FPS400 LINE CORDS P0916UH = 20 m
W/MTRJ CONNECTORS W/MTRJ CONNECTORS FPS400 POWER CABLES GROUP D P0916UJ = 30 m
SWITCH GROUP A SWITCH GROUP A GROUP B P0926CN = 11" P0916UK = 60 m
P0926KK = 16" P0923DA = 15"
P0926KL = 36" P0926CM = 33"
P0926KM = 48"
P0926KN = 60"
P0972YC (EXAMPLE) P0972YC (EXAMPLE) P0926KP = 72"
24-PORT, 100Base-FX SWITCH 24-PORT, 100Base-FX SWITCH P0926KQ = 84"
W/MTRJ CONNECTORS W/MTRJ CONNECTORS
SWITCH GROUP B SWITCH GROUP B

AN EXPANDED FIELDBUS SEGMENT


HDLC CABLES:
CABLE GROUP E
See Note 1

FBM
FIBER OPTIC

FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM

BASE-
CABLE GROUP A PLATE TERMINATOR

200 Series
200 Series
200 Series
200 Series
200 Series
200 Series
200 Series
200 Series

P0916RB
I/A Series I/A Series I/A Series I/A Series I/A Series I/A Series I/A Series I/A Series

POWER
MODULE LAST BASEPLATE
HDLC CABLES:
FPS400-24 CABLE GROUP E
P0917LY/ See Note 1
P0922YU
CABLE FBM
GROUP D BASE-
PLATE

FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM

TERMINATOR

CABLE
200 Series
200 Series
200 Series
200 Series
200 Series
200 Series
200 Series
200 Series

GROUP B
FCP270 FBM EXPANSION SYSTEM P0916RB
I/A Series I/A Series I/A Series I/A Series I/A Series I/A Series I/A Series I/A Series

A A
CP FIELDBUS

CABLE GROUP E AN EXPANDED FIELDBUS SEGMENT FBI TERMINAL ASSEMBLIES


P0800DC

FCP270
FCP270

P0917YZ
P0917YZ

OPTICAL
OPTICAL
TWINAX (P/N P0170GF/GG )

SPLITTER
SPLITTER
FBI TERMINAL ASSEMBLIES
B B TERMINATOR (P0916RB) 6000 FT (MAX) [ALL SEGMENTS, END TO END]
OR OPTIONAL
P0800DC 110 O TERMINATOR
FBI100 SYSTEM (USE AT END OF FIELDBUS)
TIME STROBE ADAPTER TO OTHER REMOTE I/O
BASEPLATE TERMINAL
(P0916KZ)
ASSEMBLY KITS
FIELDBUS 1 P0903VY x 2 1 x 8 STRUCTURE 1 x 8 STRUCTURE
3 1

FEM100
FEM100

P0973CA
P0973CA
FBI
FBI

FIELDBUS 2
4 2

FBI100
FBI100

I/A Series I/A Series CABLE GROUP E


P0923LN
P0923LN
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM
FBM

See Note 1
P0400VE
P0400VE

I/A Series I/A Series


100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES
100 SERIES

4-SLOT FEM100 BASEPLATE


FBI
FBI

FBI100 BASEPLATE = P0923LR 110 O TERMINATORS


BASEPLATE: P0973CN (USE AT END OF FIELDBUS)
FBI = P0903ZE or
FBI = P0903ZE or

FIELDBUS 4
TERMINATOR
FIELDBUS 3 P0916RB TO OTHER REMOTE I/O 110 O TERMINATOR
POWER FBI TERMINAL ASSEMBLIES (USE AT END OF FIELDBUS)
MODULE P0800DC TWINAX (P/N P0170GF/GG )

Figure B-3. Overview for Dual Baud Cabling (FCP270 to FEM100 and FBI100)
6000 FT (MAX) [ALL SEGMENTS, END TO END]
FPS400-24
CABLE FBI TERMINAL ASSEMBLIES
P0917LY/
P0922YU GROUP B P0800DC
NOTE 1:
TThe total cable length of the Module Fieldbus (shielded twisted-pair segment) cannot exceed 60 m (198 ft) between the FCP, FEM100 or FCM2F2/4/10 and the end of the baseplate chain.
NOTE 2:
CABLE GROUP D The cable length between the FCP and FEMs cannot exceed 60 m (198 ft). See “FCP270 Product Sizing” in B0400FA for the list of cabling restrictions.
Appendix B. FEM100 and FBI100 Connection Diagrams
Index
A
Addresses
IP 6
MAC 6

B
Baseplates for FCP270 mounting 17
Block, defining 44
Boot-up sequence 29
commissioned FCP270 29
FCP270 module with a new letterbug 30
FCP270 module with the same letterbug 30
shadow module with the same letterbug and software image 31
shadow module with the same letterbug but different software image 32

C
Cables, installing 25
Cabling
remote fieldbus extension 35
Y-module FBMs 34
Communication to Series 200 FBMs 11, 14
Configuration Information display, FCP270 54
Control block, defining 44
Control Configuration 44
Control scheme, typical 45

D
Data stream types 9
Defining blocks 44
Diagnostics
error recovery cooperative diagnostics 84
error recovery local diagnostics 84
start-up 84
Dual baud 9
cabling 98
dual baud functionality 9, 34, 47

E
EEPROM Update procedure 58
Equipment Change display
FCP270 55
Primary ECB (FBM0) 69

99
B0700AR – Rev H Index

Equipment Information display


FCP270 50
Primary ECB (FBM0) 65
Error recovery cooperative diagnostics 84
Error recovery local diagnostics 84
External timing 15
Extracting memory dump information 82

F
Failure messages 82
Fault-tolerant operation 4
hot remarry 80
FBI200A 8, 15
FBM
general download for off-line or failed 71
FBMs
supported modules 1
Y-module 14
FBMs, supported 1
FCP270
fault-tolerant operation 4
infrared communication ports 75
installing 18
installing cables 25
installing secondary module 24
installing single or primary module 19
LED indicators 75
letterbug installation 20
network configuration 6
overview 1
replacing a failed module 81
reset button 75
sizing constraints 15
Fiber optic cables, installing 25
Field Control Processor 270, overview 1
Fieldbus Expansion Module 100 (FEM100) 1, 8

H
Hosted FBMs and blocks 15
Hot remarry 80

I
I/O communications 8
image 59
Image Update procedure 59
Infrared communication ports 75
Installing
cables 25

100
Index B0700AR – Rev H

FCP270 18
secondary FCP270 module 24
single or primary FCP270 module 19
Internal timing 15
IP addresses 6
IPS Global Client Support xiii

L
Last gasp messages 82
LED diagnostic indicators 75
Letterbug installation 20

M
MAC addresses 6
Master TimeKeeper 14
Memory dumps 82
extracting 82

N
Network configuration, FCP270 6
Network path switching 6

O
On-line Diagnostics display, Primary ECB (FBM0) 72
On-Line Image Update
Update 59
Operational Status LEDs, troubleshooting 77, 78

R
Reboot Station procedure 58
Reference documents xii
Remote fieldbus extension 34
cable connections 35
Replacing a failed FCP270 module 81
Reset button 75
Reset button, location and operation 3
Revision information xi

S
self-hosting 4
checkpoint invalidation 63
enabling or disabling 21
installation 19
messages 59
order of powering on 19
with fault-tolerance 33

101
B0700AR – Rev H Index

Slave TimeKeeper 14
Software installation 43
Splitter/combiner 6
Start-up diagnostics 84
Supported products 1
Switching network paths 6
System Definition 43
System Management displays
FBM0 65
FCP270 49

T
Time synchronization 14
Timing
external 15
internal 15
Troubleshooting
failure messages 82
fault-tolerant FCP270 failure 80
hot remarry 80
last gasp messages 82
memory dumps 82
Operational Status LEDs 77, 78

Y
Y-module FBMs, cabling 34

102
Index B0700AR – Rev H

103
Invensys Operations Management
5601 Granite Parkway Suite 1000
Plano, TX 75024
United States of America
http://www.iom.invensys.com

Global Customer Support


Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424 or contact your
local Invensys representative.
Website: http://support.ips.invensys.com

Das könnte Ihnen auch gefallen