Sie sind auf Seite 1von 4

Gas Chlorination of Swimming Pools

General
In all swimming pools, there are Average air temperature
problems of contamination caused by The following are general guidelines
substances introduced by the for chlorination equipment sizing.
swimmers and the environment. 1. Indoor pools
Eliminating the contamination to One (1) pound of chlorine feed
create a safe, pleasant and capability per day for each 5,000
comfortable place in which persons gallon capacity (20 g/h/20 m3)
can enjoy swimming and bathing, is
the objective of all owners, operators 2. Outdoor pools
and regulatory agencies. a. Cool temperatures - One (1) pound
per 5,000 gallons (20 g/h/20 m3) is obtained by using a small booster
The primary methods used to control
b. Moderate temperatures - One (1) pump or utilizing an existing
contamination are filtration and
pound per 4,000 gallons (20 g/h/16 circulating pump.
disinfection. This bulletin will discuss
disinfection only and the most widely m3) At swimming pools, the following type
accepted disinfectant, chlorine. c. Warm temperatures - One (1) of filtration equipment may be used
pound per 3,000 gallons (20 g/h/12 so chlorination may be installed in
Sizing different ways, as follows:
m3)
In chlorinating swimming pool water, 1. Pressure filter systems
These figures contain sufficient
factors to be considered in sizing the a. use a booster pump to operate the
excess capacity to cover most
chlorination equipment are: ejector (Figure 1).
installation needs even in times of
Pool volume and surface area overload (e.g. holidays, exceptionally b. There may be occasions where
Pool turnover rate - standard pool hot days, etc.) such that chlorine feed sufficient pressure drop is available
design generally provides for an 8- will average 1/3 of the rated for ejector operation. Use of this
hour turnover equipment capacity. Table I provides technique requires a complete
Location of pool - indoors or outdoors chlorinator capacity versus pool understanding of the hydraulics and
Configuration - a deep-diving pool volume based upon average air feed rate required since the pressure
exposing a small surface area has a temperature. drop across the filter increases as the
lower chlorine demand than a shallow System Operation filter is used (Figure 2).
pool of the same volume exposing a 2. Vacuum filter system
Chlorine feed from a gas chlorinator
very large surface areas. Factory requires sufficient vacuum to be Either use a separate booster pump
consultation is suggested in unusual created in a venturi for operation of to operate or take the discharge from
pool configurations. the chlorinator. Vacuum is created the filter pump to operate the ejector
using a differential in water pressure and feed the chlorine solution into the
to operate an ejector. The differential filter tank (Figure 3).

Table I - Gas Chlorinator Capacity

Chlorinator Pool Volume


Capacity
Cool Temperature 1
M oderate Temperature 1 Warm Temperature 1
PPD g/h Gal. (1,000) m3 Gal. (1,000) m3 Gal. (1,000) m3
4 75 to 20 to 76 to 16 to 60 to 12 to 45
10 200 20 to 50 76 to 190 16 to 40 60 to 150 12 to 30 45 to 115
25 500 50 to 125 190 to 475 40 to 100 150 to 380 30 to 75 115 to 285
50 900 125 to 250 475 to 950 100 to 200 380 to 760 75 to 150 285 to 570
75 1,400 250 to 375 950 to 1,420 200 to 300 760 to 1,135 150 to 225 570 to 850
100 2,000 375 to 500 1,420 to 1,895 300 to 400 1,135 to 1,515 225 to 300 850 to 1,135
200 4,000 500 to 1,000 1,895 to 3,785 400 to 800 1,515 to 3,030 300 to 600 1,135 to 2,270

1. The reference to location by temperature is an aid to choosing chlorinator capacity. Temperatures refer to average
temperature for outdoor pools. 75°F (24°C) is considered cool, 80°F (27°F) is moderate, and 85°F (30°C) warm. Indoor
pools should use cool temperatures as a guide.
-1- 010.4012.0
Figure 1 - Pressure Filter System With Booster Bump

Figure 2 - Pressure Filter System Without Booster Pump

010.4012.0 -2-
Figure 3 - Vacuum Filter System

Anti-Siphon Ejector
A swimming pool filtering system that
is located above pool water surface
may drain back into the pool when the
filtering system is turned off. An anti-
siphon ejector should be used.
In Figure 4, the anti-siphon ejector
check valve assembly “D” is
mechanically locked in a closed
position by the push pin rods “C”
(attached to diaphragm assembly
“B”), in the absence of water pressure
in the ejector nozzle. Application of
water pressure to the nozzle will fill
cavity “E” through the nozzle bleed
hole compressing spring “A” by the
action of diaphragm assembly “B”.
Push pin rods “C” are pulled away
and the anti-siphon ejector check
valve assembly “D” is free to open
upon the creation of a vacuum by the
nozzle. The anti-siphon ejector/check
valve assembly maintains tight
closure of 30" of mercury vacuum.

Figure 4 - Anti-Siphon Ejector

-3- 010.4012.0
Summary
1. Use of Table I sizes the chlorinator. depending upon local requirement. 4. An analyzer may be used to
Automatic switchover systems may Generally, 1.3 pounds of soda ash continuously monitor chlorine
be desired for 100% standby. are required for each pound of residual.
2. The addition of gas chlorine to pool chlorine feed. 5. A free available chlorine residual of
water also affects pH. Corrective 3. The presence of foreign materials 0.5 ppm (mg/l) is suggested for
action with the addition of soda ash or (e.g. hair) can affect the ejector optimum bather comfort and safety.
similar material is required to keep vacuum. Care should be taken to
the pH at a level of 7.5 to 8.0, prevent any plugging by the use of
strainers and by cleaning the nozzle
and diffuser.

Design improvements may be made without notice.


Represented by:

3000 Advance Lane Colmar, PA 18915


Tel: 215-997-4000 • Fax: 215-997-4062
Web: www.capitalcontrols.com
E-mail: marketing@capitalcontrols.com

UNITED KINGDOM • UNITED STATES • HONG KONG


INDIA • ITALY • MALAYSIA

10/00 Copyright 2000 Capital Controls


010.4012.0 -4-

Das könnte Ihnen auch gefallen