Product data sheet RM17UAS15

Characteristics voltage control relay RM17-U - range 65..260 V


AC

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Zelio Control
Product or component type Modular measurement and control relays
Relay type Voltage control relay
Product specific application For single-phase and DC supply
Relay name RM17UAS
Relay monitored parameters Self-powered
Overvoltage or undervoltage detection
Time delay type Adjustable 0.1...10 s, 0 + 10 % on crossing the threshold
Switching capacity in VA 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Power consumption in VA 0...3 VA AC
Measurement range 65...260 V voltage AC 50/60 Hz
65...260 V voltage DC
Utilisation category AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1

Complementary
Reset time 1500 ms for time delay
Maximum switching voltage 250 V AC/DC
[Us] rated supply voltage 110...240 V AC/DC, 50/60 Hz +/- 10 %
Supply voltage limits 50...270 V AC/DC
Power consumption in W <= 1 W DC
Immunity to microbreaks 20 ms
Control circuit frequency 50...60 Hz +/- 10 %
Jul 22, 2018
1
Output contacts 1 C/O
Nominal output current 5A
Measuring cycle <= 150 ms measurement cycle as true rms value
Hysteresis 5...20 % of threshold setting
Run-up delay at power-up <= 100 ms DC
<= 500 ms AC
Measurement accuracy +/- 10 % of the full scale value
Repeat accuracy +/- 0.5 % for input and measurement circuit
+/- 1 % for time delay
Measurement error < 1 % over the whole range with voltage variation
0.2 %/°C with temperature variation
Polarity Non reversible polarity on DC supply
Quality labels CE
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage 250 V conforming to IEC 60664-1
400 V conforming to IEC 60664-1
Operating position Any position without derating
Connections - terminals Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without cable end
Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without cable end
Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with cable end
Screw terminals 1 x 0.2...2 x 2.5 mm² - AWG 24...AWG 12, flexible cable with cable end
Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Local signalling LED green for power ON
LED yellow for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability 100000 cycles
Mechanical durability <= 30000000 cycles
Operating rate <= 360 operations/hour under full load
Width 17.5 mm
Product weight 0.08 kg

Environment
Electromagnetic compatibility Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC
61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards EN/IEC 60255-6
Product certifications CSA
C-Tick
GL
UL
GOST
Directives 89/336/EEC - electromagnetic compatibility
73/23/EEC - low voltage directive
Ambient air temperature for storage -40...70 °C
Ambient air temperature for operation -20...50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance 0.35 mm (f = 5...57.6 Hz) conforming to IEC 60068-2-6
1 gn (f = 57.6...150 Hz) conforming to IEC 60255-21-1
Shock resistance 5 gn conforming to IEC 60068-2-27
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2 kV AC 50 Hz, 1 min conforming to IEC 60255-5
2 kV AC 50 Hz, 1 min conforming to IEC 60664-1
Non-dissipating shock wave 4 kV conforming to IEC 60255-5

2
4 kV conforming to IEC 60664-1
4 kV conforming to IEC 61000-4-5

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0701  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available
End of life manual

Contractual warranty
Warranty period 18 months