Sie sind auf Seite 1von 16

Section 3.

4
CLOSED RECIRCULATING SYSTEMS

In closed recirculating systems, heat is transferred to the cooling water from the hot process,
and then it is transferred out of the cooling water by conduction in another piece of heat transfer
equipment. No water is evaporated or concentrated. A system is considered “closed” when it is
designed to be filled with water once and then run continuously for long periods of time without
any significant amount of makeup water added. In closed cooling systems, the heat is usually
dissipated by an auxiliary open cooling loop or forced air that passes over tubes containing the
closed system water (as in a fin-fan cooler).

CLOSED SYSTEMS extrusion or molding systems, continuous


casting systems in steel mills, and induction
Figure 3.4.1 illustrates a typical closed recircu-
furnaces.
lating system. The methods employed in a closed
recirculating system for transferring heat to the
Discharge restrictions —A system may be
atmosphere are not as efficient as a cooling
closed to reduce or eliminate discharge due
tower. In some applications, a closed recirculat-
to governmental regulations against chemical
ing system is preferred. The following are some
or thermal pollution, lack of adequate waste
important reasons why a closed system would
treatment facilities, or a variety of other reasons.
be used:
In these cases, air-cooled heat exchangers
(fin-fan coolers) may be used.

Limited water sources—There are limited water


sources or it is more convenient to use forced
air-cooling, as in moving vehicles.

Extended equipment life—Large amounts of


cooling are not required and the easiest method
of extending equipment life is through closing
the system, thereby reducing corrosion. Chiller
systems usually fall into this category.

Restrictions on chemical usage—Because of


the nature of the process, there may be restric-
tions against the use of some chemicals. For
example, the water used in induction furnaces
Figure 3.4.1 - Schematic of a typical closed must have very low conductivity (dissolved
recirculating system solids) due to the electrical current in the
induction heater. Therefore, many cooling
system products cannot be used.
Critical processes—The system requires very
clean heat transfer surfaces and it is believed that
Other types of equipment that do not require
the variability of operating conditions normally
cooling are also treated as closed systems. In
encountered in an open recirculating system
general, a system may be treated as closed if
cannot be tolerated or skin temperatures are too
there is no significant concentration of the solids
high for effective scale control with an open
in the water and it is not directly open to the
system. Examples are primary cooling loops in
atmosphere (not highly oxygenated).
nuclear plants, compressor cooling, plastic

CONFIDENTIAL, For Nalco Employee Use Only 2006 Nalco Company 67


PAC-3 Cooling Water Technical Manual (09-06)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

The following are examples of non-cooling The temperature change in the recirculating
closed systems: fluid generally averages 10-15ºF (5-8ºC) for the
typical system. Occasionally, much greater
• Hot water boilers that are closed to conserve temperature changes are encountered. Maximum
heat but often may be treated economically temperatures can be as high as 350ºF (175ºC)
with closed system products. (e.g., in hot water systems), and minimum
temperatures can be as low as 30ºF (-1ºC)
• Storage tanks or other equipment that are (e.g., in chilled water systems). These systems
filled with water and closed off from the theoretically use very little makeup water,
atmosphere. Emergency stand-by tanks and generally averaging 0.1-0.5% of system capacity
thermal storage tanks are included in this per day. No water bleed-off from closed systems
category. is generally planned, but water losses usually
occur in the average system from leaks around
• Equipment that is tested with water (hydro- expansion tanks, pumps, seals, and valves.
tested) and closed from the atmosphere Conditions during operation are generally
during testing. Engine test stands are an steady; however, some systems are subject to
example of this type of process. frequent on-off conditions.

All closed systems consist of at least an appara- Table 3.4.1 indicates the variety of metals
tus for heating or cooling a recirculating fluid, a typically found in a single closed recirculating
recirculating pump, and a heat exchanger system. In general, if the system is constructed
designed to heat or cool another medium. This of metals within the same group, the chance for
second medium can be air, water, or an industrial galvanic corrosion is reduced. The more widely
process stream. Recirculating velocities gener- separated the coupled metals are (in terms of
ally range from 3-5 ft/s (0.9-1.5 m/s), but can be groups), the greater the galvanic corrosion
as high as 30-40 ft/s (9-12 m/s) for extremely potential. Galvanic corrosion is discussed in
high heat flux applications, such as billet con- more detail in the Corrosion section as follows.
tinuous casters for steel.

Table 3.4.1 - Metals used in closed recirculating cooling water systems


Group A Group B Group C Group D
Iron Copper Aluminum Stainless Steel
Steel Admiralty Brass Alclad Aluminum Nickel
Cast Iron Admiralty Brass (Inhibited)
Monel
Red Brass
Muntz Metal
Naval Brass
Cupronickel
Aluminum Brass
Aluminum Bronze

68 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

COMMON OPERATING PROBLEMS recirculating systems require significant makeup


due to loss of water from leaks, overflows
Corrosion, scale, fouling, and microbial growth
through pressure-releasing valves, and unautho-
are considered the four major problems in all
rized use of water for wash-up purposes. Oxygen
types of recirculating water systems. All of these
can enter with this makeup and through air
problems are of importance in closed recirculat-
entrainment at pumps, valves, and air cushion
ing systems because corrosion is significantly
tanks.
affected by fouling and microbial activity.
Scaling interferes with heat transfer of the
Another type of attack is galvanic corrosion.
process and can lead to process-side problems.
This attack results from the potential difference
that exists when two different metals are physi-
Without any provision for the removal of
cally joined. The factors shown in Table 3.4.2
corrosion products in system blowdown,
that accelerate or control galvanic corrosion
the closed system is particularly subject to
serve as a basis for avoiding or minimizing
clogging of small valves and ports, erosive and
corrosion either by design change or by correc-
abrasive attack, and attack beneath deposits as a
tive treatment measures. Galvanic attack is of
result of the increased suspended solids resulting
particular concern in closed recirculating
from corrosion. For this reason, it is imperative
systems because joined dissimilar metals are
to minimize corrosive attack in these systems.
frequently found in such systems.
CORROSION
Table 3.4.2 - Factors affecting galvanic corrosion
The dissolution of a metal in water is essentially
an electrochemical process. Metal dissolves at Accelerates Decelerates
anodes, leaving electrons behind. These elec- Corrosion Corrosion
trons flow through the remaining metal to other Large electrode Small electrode poten-
points called cathodes where reactions that potential difference as tial difference as
evidenced by relative evidenced by relative
consume electrons occur. In this reaction, the position in galvanic position in galvanic
anode is the site of obvious corrosion. Refer to series series
Section 3.10 for more detail on corrosion issues Large ratio of cathodic Large ratio of anodic
and mechanisms. area to anodic area area to cathodic area
High electrolyte Polarization
The two points between which electrons flow content
form a corrosion cell. However, a corrosion cell High velocity Insulation
can be established as a result of a number of
Increased temperature Painting or coating
different mechanisms:
Increased aeration Cathodic protection
1. Oxygen reactions in water Corrosion Inhibitors
2. Dissimilar metal coupling
3. Differential concentration cells The metals that are of most concern when
considering galvanic corrosion are nonferrous-
Oxygen in water reacts with active metal ions type metals that are cathodic to steel in a
and upsets the normal equilibrium conditions at galvanic cell. One example is the use of steel
the metal surface, permitting corrosion to adjacent to copper or copper alloys. In this case,
continue. In a closed system, the oxygen in the the steel, being anodic to copper, corrodes
recirculating stream could be rapidly depleted rapidly. Other couples to avoid are copper-
due to corrosion. Unfortunately, many closed aluminum and steel-aluminum. Copper-alumi-

CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company 69


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

num is an especially bad couple, because the High temperatures such as 200-220ºF (90-105ºC)
copper and aluminum are widely separated in will accelerate corrosion reactions or can lead
the galvanic series, and the corrosion rate of the to surface boiling and solids deposition with
cell is high. subsequent differential cell attack.

Physical deposition of solids is another impor- FOULING


tant factor that can establish a potential differ-
The terms scale and fouling are often used
ence with resulting corrosion. A difference in
interchangeably to include all those materials
electrolyte concentration between two points on
that coat metal surfaces in recirculating systems.
a metal is sufficient to promote corrosion,
With continual development of improved
because this difference is all that is needed to
treatments and better technology, it is more
encourage the flow of electrons. The fact is that
descriptive to restrict the term scale to cover that
such a difference can exist between metal
deposit resulting from the super-saturation of
surfaces in crevices or beneath deposits. Good
otherwise soluble water constituents. Fouling, on
system design should minimize crevice attack,
the other hand, includes a broader range of
and proper water treatment should eliminate the
materials that are generally softer, less adherent
presence of deposits.
and that come from a number of different
sources. Table 3.4.3 lists some typical foulants.
SCALE
Theoretically, under the conditions that exist Table 3.4.3 - Common fouling materials
in a truly closed recirculating system, all of
the common scale-forming constituents in the Foulant
system water (such as calcium carbonate, Corrosion products
calcium sulfate, magnesium salts, and silica) can
Sand
deposit on metal surfaces without any noticeable
Cutting oils
results because such small quantities are in-
volved. However, in the more typical, higher- Joint compounds
makeup closed system, additional scale will Construction debris
precipitate with each new increment of water Process-side contamination
added to the system. In time, this scale will Hydrocarbons
assume significant proportions, plugging water Casting oils
passages, reducing heat transfer, and promoting
corrosion.
Many of these fouling materials are the result of
Another type of deposit, encrustation, can result residue from the construction of new systems,
at leaky flanges or pump seals. Water evaporates contaminants introduced with makeup water, leaks
at these points and leaves behind all of the from process equipment, and most often from
dissolved solids it once carried. This type of incomplete or inadequate corrosion control.
“scale” can cause premature failure due to
concentration cell attack on the metal beneath When these foulants deposit on metal surfaces in
moist deposits. See Section 3.9 for detailed the system, the conditions for concentration cell
discussion on corrosion mechanisms. attack are established. In addition, these foulants
reduce system efficiency by clogging valves,
small orifices, and recirculating lines. Dispers-
ants are often used to help control corrosion
product fouling.

70 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

MICROBIAL GROWTH
It may seem that because the average closed
system sees little sunlight and has low oxygen
content and few nutrients, there is no problem
with microbial growth. In reality, microbial
growth can be severe for the following reasons:

• Higher makeup rates introduce more oxy-


gen, debris, and nutrients and serve to
inoculate the system.

• Process leaks can also provide excessive


high amounts of food. Figure 3.4.2 - Cooper sheets plated on steel as
a result of acid reuse
• Many closed systems use tanks that are open
to the atmosphere or have entrainment of air
at seals, so oxygen levels can be at or close Another type of very distinctive metal attack,
to saturation. caused by vibration, occurs more frequently than
supposed in closed systems. Vibration causes
• Some corrosion inhibitors can become food physical breakdown or cavitation of the metal by
for bugs. water. This results in a honeycombed appearance
of the metal. (See Figure 3.4.3.) The pieces of
All of these factors point to microbial problems metal torn free can, like corrosion products,
in many systems, and experience has proved this deposit elsewhere in the system to set up gal-
to be the case. Microbial problems contribute to vanic or differential cell attack. They can also
fouling, corrosion, and loss of heat transfer. In clog small control parts, or, in being carried by
fact, biofilms are among the most insulating the water stream, cause abrasive attack on other
deposits encountered on heat transfer surfaces. metal or seal surfaces.

OTHER PROBLEMS
Closed recirculating systems are also subject to
the deposition of metallic ions that have been
removed from parent metal elsewhere in the
system. For example, copper ions corroded from
heat exchange tubes can be reduced to pure
copper on other metals with a resulting bimetal-
lic couple. (See Figure 3.4.2.) Severe pitting
corrosion will result. Acid used initially to clean
copper alloy heat exchangers and subsequently
used to clean other metals can cause copper
plating. The dissolved copper ions in the acid
can coat the steel or other more active metals,
resulting in bimetallic couples and severe Figure 3.4.3 -Result of vibration attack on
corrosion. engine cylinder

CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company 71


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

CORROSION CONTROL draining and flushing can all help reduce corro-
sion or indicate those points where system
At this point, it is desirable to decide just what
modifications may be necessary to maximize
is meant by practical corrosion control in closed
corrosion protection.
recirculating systems. In some systems, this term
can be defined by corrosion rates less than a
Ion exchange softened water, demineralized
certain value on a specific type of metal. For
water, and even steam condensate have been
example, a general etch attack on mild steel of
used as makeup water for closed systems.
less than 3 mpy (<75 µm/y) is usually considered
Softened water reduces the chances of scaling,
satisfactory protection in open recirculating
but increases the corrosivity of water by unbal-
systems.
ancing the calcium/alkalinity relationship.
Subsequent chemical treatment of the recirculat-
On the other hand, practical corrosion control
ing water can compensate for this increased
can also be defined in terms of maintenance
corrosivity. However, it is generally not neces-
costs or system operating efficiency. Most
sary to use softened water for closed system
frequently, in closed recirculating systems,
makeup, particularly if the amount of makeup
control is considered to be satisfactory as long as
water is low, except in high heat flux applica-
the system continues to operate efficiently with
tions or high temperature systems, which must at
a minimal amount of necessary maintenance.
least have softened water makeup. The type of
suspended solids-free water usually available
Because of the characteristics of closed systems
from a municipal or well water source is almost
and the more than usual problems that corrosion
always satisfactory unless considerable makeup
products cause, it is important to minimize
is required.
corrosion from the start of system operation.
Finally, corrosion resistance of a system
NON-CHEMICAL TECHNIQUES
can be maximized through the selection
A number of non-chemical steps can be taken of corrosion-resistant metals. Economics gener-
to minimize corrosion in a closed recirculating ally is the deciding factor in materials selection.
system. The basic objective is to design and Ideally, a single metal should be specified
operate the system efficiently by effectively throughout a system to avoid dissimilar metal
eliminating or minimizing water losses and corrosion. Minimizing the number of different
eliminating bimetallic couples. metals to reduce galvanic corrosion problems
will greatly improve corrosion control. Occa-
Probably the most important step involves taking sionally, coatings have been applied to metal
actions that eliminate or minimize loss of water. surfaces in a closed system to reduce corrosion.
Thus, less fresh makeup water is required and
treatment residuals are more easily maintained. CHEMICAL TREATMENT
Water added to a system brings oxygen and
SYSTEM PREPARATION
other dissolved gases that renew or intensify the
corrosion in the system. In addition, system When considering chemical treatment tech-
makeup water can carry suspended solids that niques, it is important to provide corrosion
can also promote corrosion. protection from the very start in a new system
or in a system from which deposits are to be
Tightening up connections within a system, removed prior to startup.
periodically checking all possible water take-off
points, and eliminating or minimizing system

72 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

Previous discussion has shown that suspended Therefore, it is most desirable in new and acid-
solids in a closed recirculating system are the cleaned equipment not only to remove deposits
cause of problems such as corrosion beneath of every kind before starting up the system but
deposits, erosion of metal surfaces, clogging of also to minimize the time between system
lines and ports, and damage to mechanical seal cleaning and the addition of treatment. Chemical
surfaces. Therefore, for the most effective formulations are available today to perform all
corrosion protection of either a new or dirty three functions (cleaning, passivating, and film-
system, the system must be cleaned. In new forming) in one application. Figure 3.4.4 illus-
systems, materials to be removed include mill trates the type of performance that can be
scale, pipe dope, dirt, grease, and sand. In a expected from these materials.
system that as been in operation or has been
standing idle, the same materials may be found,
as well as corrosion products.

A three-step program is generally recommended


to put a new system into condition for effective
corrosion control.

1. The system must be cleaned with wetting


agents, an iron clean-up program, or inhibited
acids (in the case of heavy deposits). A B
2. The metal surface must be prepared for the Figure 3.4.4 - (A) Heat exchanger channel
acceptance of a protective film. showing corrosion resulting from hydrotesting
(B) Heat exchanger channel after pretreatment
3. Metal surfaces must be passivated by laying
down a corrosion-resistant film.

To a large extent, the practice today is to start CHEMICAL TREATMENT TECHNIQUES


operating a new system without any prior Various types of chemicals are capable of
treatment. Occasionally, the system is flushed protecting closed system metals effectively and
with untreated water, a practice that may initiate very economically. The most widely used types
corrosion. By the time treatment is started, some today are various boron-nitrite formulations,
damage has been done. After acid cleaning and molybdate blends, all-organic programs, and
neutralization, it is not unusual to observe the dispersible oils. (Environmental concerns have
formation of a thin film of corrosion products on placed restrictions on the use of chromate-based
metal surfaces. This is due to the reaction of the treatments, which were commonly used in the
very active surface of the acid-cleaned metal past. Their use is already low and expected to
with the oxygen of the air. These corrosion decline further.) Occasionally, sodium silicate
products will resist formation of a protective formulations, chelating agents, special filming
film once inhibitor is added and will contribute agents, and oxygen scavenging materials have
to the suspended solids concentration in the been used for specific applications.
recirculating water.

CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company 73


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

These chemicals protect system metals against occur in the system with plugging and possible
corrosion by forming extremely thin, highly failure of the metal components? The reasonable
corrosion-resistant films on metal surfaces. In answer is to fix or modify the weakest link in the
many cases, these films are the result of an system (the pump seal) rather than to permit the
interaction between the chemical inhibitor and entire system to fail.
the reactive metal surface. In other cases, purely
physical films of the inhibitor are laid down. To The goal of corrosion control in closed systems
maintain these films, a certain minimum level of is to establish as close to 100% protection as
inhibitor must be maintained. Below these possible of all metals. Effective treatments, when
minimum levels, a previously established film properly controlled and maintained, approach
will be removed from the metal, and corrosion this goal.
will take place. Because temperature will affect
corrosion rates, higher levels of treatment will Chromate-Based Treatment—Treatment with
be required at higher temperatures. buffered chromate or dichromate salts of sodium
has been used historically in closed recirculating
In closed recirculating systems, maximum systems and has provided extremely low corro-
corrosion prevention involves the use of high sion rates of 0.01 mpy (0.25 µm/y) or less on
inhibitor levels that are definitely more eco- steel. Chromate treatments are used at pH levels
nomical than they would be in open recirculating of 7.0-9.5, depending upon the system character-
systems. High inhibitor levels are required to istics. The most commonly recommended chro-
assure the practical elimination of corrosion mate levels are in the range of 600-1500 mg/L
resulting from the coupling of dissimilar metals. CrO4. The lower end of this range is generally
They also provide back-up protection should an recommended for low-temperature systems,
unexpected water loss lower treatment levels. such as chilled water loops. Higher chromate
This insurance is particularly important in closed levels, in excess of 1500 mg/L, are sometimes
recirculating systems, because the start of recommended to provide the greatest possible
corrosion will introduce insoluble corrosion protection against galvanic corrosion resulting
products with their attendant problems. from dissimilar metals. These higher levels have
proved to be extremely effective in preventing
In the past, exceptionally high levels of galvanic attack, although it is very difficult, if
chromates had been thought to be responsible not impossible, to eliminate this type of attack
for failure of mechanical seals in closed recircu- completely when widely different metals are
lating systems. This failure was theoretically the joined. Finally, maintaining higher levels of
result of an actual chemical attack on the seal chromate in a closed system appears to offer a
surfaces. Data have shown that chemical corro- degree of protection against erosive attack due to
sion-inhibiting treatments, including chromates, high water velocities or high-suspended solids.
are no more responsible for these problems than
are other dissolved and suspended solids usually Because chromate is an anodic inhibitor, it is
found in recirculating water. Equally important essential that a continuous chromate film be
is the proper installation of pump seals. maintained at all times. At chromate levels
below 200 mg/L, an inhibiting film can develop
A question often arises when pump seal failures inconsistencies. All attack will be concentrated
occur: Should the inhibitor be eliminated to at individual points, causing severe pitting.
protect the pump seals, allowing corrosion to

74 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

Three limitations apply to the use of chromates small, especially if sufficient nitrite is present
in closed recirculating systems: and passivation occurs quickly. If nitrite con-
sumption is high, it is indicative of a number of
1. Chromate is a priority pollutant and faces problems, primarily microbial oxidation of
severe environmental restrictions. Relatively nitrite to nitrate, but it can also indicate repeated
few locations continue to use chromate today. corrosion and re-passivation of the metal.

2. The chromate ion will react with ethylene Boron-nitrite inhibitors are compatible with
glycol and common antifreeze alcohols. The ethylene glycol and alcohol antifreeze mixtures.
reaction results in inactivation of the chro- The effectiveness of boron-nitrite formulations
mate as a corrosion inhibitor and the forma- is illustrated in Table 3.4.4.
tion of a precipitate. In those cases where it is
necessary to use antifreeze in a closed system, Nitrite is an oxidizing, anodic corrosion inhibi-
other inhibitors, such as nitrite and molyb- tor for mild steel and requires a minimum nitrite
date, should be selected. concentration within the water to maintain the
passive metal film and good corrosion control. If
3. Chromate in the hexavalent form (which is the the nitrite concentration repeatedly drops below
inhibiting form) is subject to reduction to the the minimum critical concentration, mild steel
trivalent form (non-inhibiting and sludging corrosion will increase. The typical mode of
form) by a number of chemicals, such as corrosion when dropping below the critical
hydrogen sulfide, stack gases, nitrites, and concentration of nitrite is pitting corrosion. High
many organics. Chromate cannot be used in chloride and sulfate levels will increase the
systems containing such compounds. demand for inhibitor because of increased
corrosiveness of the water and potential break-
Boron-Nitrite-Based Treatment—Blended down of the oxide film. The critical nitrite
formulations containing sodium nitrite (NaNO2) concentration is system specific and depends on
are perhaps the most common treatment pro- water chemistry, temperature, metallurgy, and
grams used today in closed loop systems, both operating conditions. Maintaining the minimum
hot and cold. The formulations typically contain nitrite concentration is critical to successful
borate to buffer the system pH between 8 and application of a nitrite treatment program.
10.5 and azoles for copper alloy corrosion Dosages of boron-nitrite inhibitors generally
protection. Additional components might include range from 500-2000 mg/L active nitrite.
nitrate or silicate for aluminum corrosion
protection, polymers for suspended solids Besides the initial nitrite loss due to system
dispersion, and scale inhibitors. Nitrite works passivation and on-going corrosion control,
well in reducing environments. Nitrite oxidizes nitrite loss can be due to several other mecha-
mild steel surfaces to form an extremely thin and nisms. It is important to understand and be able
highly tenacious corrosion product layer. When to identify these mechanisms so that corrective
mild steel corrodes, the nitrite will oxidize the action can be taken to prevent nitrite loss and
ferrous iron (Fe+2) released by the metal to iron maintain the minimum nitrite concentration.
oxides. The nitrite is reduced to ammonia in this Several mechanisms that can lead to nitrite loss
reaction. This passivation process will consume in closed loop systems are discussed as follows.
nitrite, but the amount of nitrite lost is generally

CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company 75


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

Table 3.4.4 - Corrosion control in closed polymetallic cooling systems

Corrosion Rates, MPY* (Coupled)


Commercial Antifreeze No. 1 Commercial Antifreeze No. 2
Metal Uninhibited 0.75 oz/gal Uninhibited 0.75 oz/gal
Boron Nitrite Boron Nitrite
Cast Iron 6.3 0.2 3.5 0.2
Aluminum 11.4 0.7 66.7 2.4
Solder .07 1.0 0.5 0.7
Copper 1.1 0.5 0.6 0.2
Brass .07 0.2 0.5 0.1
(Insulated)
Cast Iron 4.3 0.3 9.6 0.3
Aluminum 13.8 0.5 17.6 0.6
Copper 2.1 0.5 1.9 0.5
Brass 0.8 0.3 1.5 0.2
* 7 days at 189°F (87°C)

WATER LOSS often be detected by measuring the water


Obviously, if water loss occurs in a closed loop conductivity and comparing the nitrite and
system, the treatment products will be lost too. nitrate concentrations. If nitrifying bacteria are
Water losses are common in many closed loop an issue, the nitrite residual will decrease while
systems, and this is a common cause of low the nitrate concentration will increase. The water
treatment residual. Performing a Diagnostic conductivity will remain relatively unchanged,
TRASAR® procedure is an excellent method to but the water pH can drop due to the formation
determine if water losses are occurring, as well of nitric acid. If the water conductivity decreases
as to measure the system volume accurately. along with the nitrite residual, then water loss is
Note that sealing gland losses from the recircula- likely responsible and should be investigated.
tion pumps can represent a significant water loss
from a closed loop system. Denitrifying bacteria can also be a problem
in closed loop systems. Denitrifying bacteria
Water loss from a closed loop system can often convert nitrite and nitrate to nitrogen gas or
be confirmed with conductivity testing. If both ammonia, which can increase corrosion of
the treatment residual and the water conductivity copper alloys. Denitrifying bacteria may be
decrease, water loss is likely. If only the treat- simply Pseudomonas. Keep in mind that
ment residual decreases, then another cause for Pseudomonas bacteria will convert nitrite in
nitrite loss should be investigated. areas of the system that are low in oxygen. They
prefer to use oxygen, but in its absence, they
BIOLOGICAL ACTIVITY will use nitrite. Another area to consider is
slime masses or biofilm. Although bulk bacteria
A common biological problem in closed loop counts may look good, if there is any slime
systems treated with nitrite is nitrifying bacteria, build-up in the system, nitrite could be reduced
which oxidize nitrite to nitrate. This problem can without showing any denitrifiers in a bulk water

76 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

sample. If denitrifying bacteria are suspected, bial counts very low. Once biological activity
the nitrite and ammonia concentrations should was established, the nitrite was rapidly converted
be tracked. to nitrate. The major problem with nitrite in open
systems is biological, not oxidation by oxygen.
Differential Microbiological Analysis (DMA) Nitrite can either be oxidized to nitrate or
can be used on both water samples and surface reduced to nitrogen by bacteria.
swabs, but nitrifying and denitrifying bacteria
are difficult to culture and detect. Bulk water In the absence of the enzymes provided by the
DMA results only indicate a presence or absence microbial activity, nitrite does not react readily
of denitrifying or nitrifying bacteria in the bulk with oxygen at typical cooling water pH. How-
water sample taken. A swab DMA result is more ever, it is still good practice to minimize aeration
useful because these bacteria tend to be in in closed loop systems. Oxygen ingress to a
biofilm rather than in bulk water. For these closed system might increase corrosion, particu-
bacteria, other monitoring methods are often larly if the nitrite level is lower than the optimal
more reliable. Typically, when nitrite loss is recommended (500-2000 mg/L). The increased
believed to be due to biological activity, nitrite, corrosion will increase nitrite consumption to re-
nitrate, and ammonia concentrations should be passivate the metal surface, but again, this loss
tracked for confirmation. should be low, unless the nitrite level is below
500 mg/L initially, and corrosion continues to
OXIDATION occur. The source of the oxygen ingress should
be found and mechanical methods used to
The standard Redox tables show the reaction of
eliminate the oxygen. Methods might include
nitrite and oxygen to form nitrate to be thermo-
replacing pump packing with mechanical seals,
dynamically unfavored at high pH but favored at
replacing air with an inert gas in the suction
low pH. If the nitrite program is buffered to
tank, and using an expansion tank with a bladder
produce a system pH greater than 8.5, the
to prevent air contact with the closed loop water.
oxidation of nitrite by air is not a real concern.
Water returning to a tank should be directed
However, it is possible in a closed loop system
below the water surface to prevent unnecessary
for oxygen to promote corrosion, and the nitrite
turbulence and aeration.
can then be consumed repassivating the metal as
discussed above.
Any ingress of oxidants will tend to oxidize the
nitrite to nitrate. Therefore, oxidants should not
Lab work and field experience with nitrite
be used for biocontrol. If the closed loop system
in open recirculating systems show that nitrite is
can be contaminated by another system, such as
not readily oxidized by air in alkaline water
a cooling tower system containing an oxidant,
systems. Nitrite does not oxidize appreciably to
additional monitoring should be implemented to
nitrate from contact with the air in the cooling
detect and correct the contamination.
tower. However, nitrite does react quickly to
form nitrate on contact with an oxidizing
HIGH TEMPERATURE
biocide. Therefore, oxidizing biocides should not
be used with nitrite in closed loop systems. The Merck Index reports the decomposition
temperature for sodium nitrite as 320°F
In a Pilot Cooling Tower (PCT) study, nitrite was (160°C). Additionally, a number of water
maintained in an open recirculating water treatment people have reported problems main-
system. However, it required the use of nonoxi- taining nitrite residual in high temperature
dizing biocides to keep the tower water micro- applications. Based on this information, nitrite

CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company 77


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

should not be used in applications over about the conductivity of the water might help. If stray
300°F (150°C). If nitrite is needed in high currents are indeed involved, there may also be
temperature applications, extra monitoring damage by stray current corrosion. The system
should be implemented to assure adequate nitrite may have strict conductivity limits set by the
residual. The extra monitoring should include manufacturer of critical equipment, such as
nitrate and ammonia, which are potential induction furnaces and welding arms.
decomposition products.
Molybdate-Based Treatment—Molybdate
ELECTROLYSIS inhibits general and localized corrosion on
ferrous and non-ferrous metals by forming a
If part of the closed loop system is under volt-
passivating film. It is generally accepted that the
age, nitrite loss may be related to stray currents
corrosion inhibition of iron is achieved by
in the system. Equation 1 is one of the possible
adsorption of molybdate onto the porous oxide
Redox reactions that may be involved. As can be
surface. The adsorption produces a layer imper-
seen, this reaction would be more favorable at
meable to other anions, particularly chlorides
elevated pH, such as generally experienced in
and sulfates. Molybdate blends are designed to
closed loop systems.
buffer the pH to the 8.5-10.5 range. One advan-
tage of molybdate over nitrite is that it is not a
NO2 − + 2OH − → NO3− + H 2O + 2e − (1)
nutrient for bacteria.
In a temperature control loop for a fluoride
The typical dosage range for molybdate, when
electrolysis cell, stray electrical current caused
used alone or in a blend, is 200-1000 mg/L as
nearly complete conversion of nitrite to nitrate in
MoO4. Initial passivation dosages should be at
both cold and hot water at 194°F (90°C) that was
the upper end of the typical operating range.
alternated through the cell. Reversion was quick
and complete. In the hot water, one would not
Nitrite-Molybdate Blends — Nitrite-molybdate
expect bacteria to be a problem. A simple
blends inhibit corrosion in the same way as
laboratory test confirmed that nitrite can be
described for the individual components. The
converted to nitrate by passing a 10 mA current
nitrite increases the effectiveness of the molybdate,
through a solution at a positive overvoltage of
producing enhanced passivation and improving an
4 Volts DC. Half of the 300 mg/L nitrite in a
otherwise unacceptable cost imbalance. One
200 mL volume was converted to nitrate.
advantage of nitrite-molybdate blends is that if
the nitrite is consumed by bacteria, the molybdate
Stray currents may not be so obvious in a closed
still offers some corrosion protection. The nitrite-
loop system as in an electrolysis cell. However,
molybdate blend is designed to buffer the pH in the
if the system contains welding equipment or
range of 8.5-10.5.
electrical furnaces or if system grounding is
defective, stray currents and associated nitrite
A variety of nitrite-molybdate blends are avail-
conversion are possible.
able, and their ratios vary. Typical dosages range
from 500-1500 mg/L nitrite and 75-200 mg/L
If stray currents are the root cause, flushing of
molybdate. Dosage depends heavily on the
the system, increasing the biocide dosage, or
temperature of the system.
iron clean-up programs will not give the desired
effect. Improved electrical insulation or reducing

78 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

Dispersible Oil Treatment —A third class of Avoid treating high heat flux systems with hard
closed system inhibitors is the dispersible oils, water with silicate-based programs. This combi-
so called because they are blends of organics nation could cause magnesium silicate scale to
that are dispersible in water. These materials also form. If aluminum is present in a high-heat flux
form a corrosion-resistant film on metal surfaces system and silicate is desired, soft water makeup
and are usually as effective as the boron-nitrite should be used.
inhibitors on all metals. The very high level of
dispersibility of these materials assures thorough SPECIAL CLOSED SYSTEMS
film formation in all parts of a system. However,
High-Temperature Systems—Pressurized hot
as the dispersible oils free deposits, they have a
water heating systems with temperatures in
tendency to open leaks in a system that may
excess of 300°F (150°C), can sometimes be
have experienced extensive corrosion in the past.
treated with oxygen scavengers and organic
Generally, dispersible oils require higher dosage
dispersants, much the same as low-pressure
levels than boron-nitrite inhibitors to assure
boilers. Standard treatments, such as boron-
protection. In addition, because the dispersible
nitrite and molybdate inhibitors, can also be
oils lay down a purely physical film, it is neces-
effective in high-temperature systems. Nitrite-
sary to maintain inhibitor levels and circulation
based treatments have an upper temperature
to assure film maintenance. Off-On operation
limit of about 300°F (150°C) before nitrite
can degrade the performance of dispersible oils.
decomposition significantly affects performance.
When switching from a nitrite or molybdate
program to an oil program or vice versa, specific
Continuous Casting Mold Water Systems—
system cleaning is required.
In the primary metals industry, straight nitrite
programs controlled at 300-500 mg/L nitrite
Dosage typically ranges from 5000-10000 mg/L
work well in continuous casting mold water
of product in the treated water. The pH should be
systems. These closed systems have heat transfer
kept between 8.4 and 8.8. Also, these products
surfaces exceeding 500000 Btu/ft2•h (1.4 million
usually do not contain any scale inhibitors and
kcal/m2•h). Total hardness must be maintained
should be used primarily in soft water applica-
below 1 mg/L as CaCO3 to avoid scaling.
tions. Before using an oil-based treatment
This type of treatment program is necessary
program, it is important that local regulations
because water losses can be as much as 1-5 gpm
regarding oil and grease discharge be checked.
(0.2-1 m3/h), and a conventional blended closed
system treatment program would be cost pro-
Silicate Blends—Silicate serves as an anodic
hibitive. For further information on these critical
inhibitor and is often blended with nitrite formula-
and specialized systems, contact a member of
tions to provide corrosion inhibition for systems
the Primary Metals business unit.
containing aluminum. The inhibiting properties of
silicates increase with temperature and pH and are
Low Conductivity Systems—These are specialized
most successfully applied to soft, alkaline waters.
applications where the cooling water in the closed
Silicates do not perform as well in systems where
system must maintain the water conductivity
the pH is below 7.0. Film formation for silicates is
below a specified set point, such as 500 or 1000
slow and takes several days or weeks to form.
micromhos (microsiemens). The conductivity limit
Dosage ranges from 20-50 mg/L above the
is imposed due to the nature of the equipment
inorganic silica content in the water.
being cooled. Typically, these systems cool

CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company 79


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

equipment using high voltage or current applica- molybdate programs, modified all-organic pro-
tions where elevated water conductivity can lead to grams, and even oxygen scavenger and passivation
stray currents and short-circuiting of the electrical programs that are more commonly used in boiler
equipment. Using a conventional nitrite or molyb- feedwater applications. The keys to successful
date treatment program with the standard plant treatment in these systems are extensive monitor-
water supply as makeup will usually exceed the ing to detect problems early and rapid response to
conductivity limit. Therefore, these systems all problems. Pre-cleaning, passivation, and
generally must be treated using demineralized sidestream filtration are musts in these systems to
water as makeup and a modified treatment pro- maintain clean metal surfaces and minimize
gram to accommodate the low conductivity limit. fouling issues.
Some success has been achieved using low-level

80 CONFIDENTIAL, For Nalco Employee Use Only 2005 Nalco Company


PAC-3 Cooling Water Technical Manual (01-05)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

For your notes:

This page has been intentionally left blank.

CONFIDENTIAL, For Nalco Employee Use Only 2006 Nalco Company 81


PAC-3 Cooling Water Technical Manual (09-06)
Section 3.4
CLOSED RECIRCULATING SYSTEMS

For your notes:

This page has been intentionally left blank.

82 CONFIDENTIAL, For Nalco Employee Use Only 2006 Nalco Company


PAC-3 Cooling Water Technical Manual (09-06)

Das könnte Ihnen auch gefallen