07 MODEL H3
Features
y System Control Valve for Fast Application of
water in Deluge Spray system
y Hydraulically operated, diaphragm-actuated
y Horizontal Globe Configuration
y Ductile Iron ASTM A536 Grade 65-45-12 Valve
Body
y 2" through 8" Valve Sizes
y Neoprene Rubber Diaphragm with Bronze Seat
VALVE OPERATION
The 07 Model H2 Deluge Control Valve is a hydraulically-operated diaphragm-actuated globe valve that is UL
listed for Deluge Service in sizes 2”, 3", 4”, 6" and 8”. The valve has three chambers, separated from each
other by a diaphragm operated clapper and seat seal. When in “set “ position, water pressure is transmitted
through an external bypass check valve and restriction orifice from the system water supply side to the top
chamber so that supply pressure in the top chamber act across the diaphragm operated clapper that holds the
seat against the incoming supply pressure due to differential pressure. On detection of a fire, the top chamber
is vented to atmosphere through the outlet port via opened actuation devices. As the pressure in the top
chamber cannot be maintained through the restricted inlet port, the upward force of the supply pressure lifts the
clapper allowing water to enter the system piping and alarm devices.
TRIM DESCRIPTION
a) Dry Pilot Trim (Pneumatic Release)
The dry pilot operation utilises a pilot line of closed sprinkler detectors that are pressurised with air. It
requires regulated dry air supply with the main supply point through a restricted orifice. The pilot line is
directly connected on the top of the positive drain actuator. The bottom of it is connected to top chamber of
the deluge valve.
When air pressure drops or when any detecting device is released on detection of a fire, the diaphragm of
the positive drain actuator is lifted and allows water to drain. This action reduces the water pressure in the
top chamber of the deluge valve and opens it. The recommended air supply pressure for deluge valves with
a dry pilot trim is 3.5 bar.
Note: A non-return valve must be installed at the air supply connection to the deluge valve trim.
In a dry pilot trim, an actuator (DPA) is provided. As an option, a pneumatic reset device (PRD) can be
provided that acts as a manual reset device in the dry pilot line assembly.
Page 1 of 15
DELUGE CONTROL VALVE
07 MODEL H3
e) Test and Alarm Trim with Sprinkler Alarm
A sprinkler alarm bell is provided for sounding an alarm, with a test valve provided for operation testing of
the bell.
f) Drain and Drip Trim
This consists of the main and system drain valve in addition to the drip valve
TRIM TYPES
The trims have the following designations:
W - Wet Pilot trim. D - Dry Pilot trim
Page 2 of 15
DELUGE CONTROL VALVE
07 MODEL H3
Technical Specification:
Model Specifications
Nominal Sizes 50, 80, 100, 150 and 200 NB
Working Pressure 17.5 bar (250 psi) maximum
Threaded Opening BSPT
Mounting Style Horizontal or Vertical
Factory Hydrostatic Test Pressure 35 bar (500 psi)
Flanged Connection ANSI 150 lbs FF (ANSI 16.5)
50 NB 32 kg
80 NB 35 kg
Net Weight
100 NB 50 kg
(without Trimming)
150 NB 79 kg
200 NB 153 kg
Finish RED (Ral 3000)
Approval UL listed
DV 50NB
DELUGE VALVE M ODEL H3
Nominal Pressure Loss vs Flow
( * flow at 15 feet per second ( 4.57 meter per second)
40
30
20
Nominal Pressure Loss in Pounds per Square Inch (PSI)
10
8 * *
6
5 * *
4
)
CH
IN
3
(8
*
)
NB
CH
)
2
0
IN
CH
20
(6
IN
)
NB
(4
CH
)
NB
0
CH
IN
15
(3
IN
1.0
0
10
NB
(2
0.8
NB
80
50
0.6
0.5
0.4
0.3
0.2
0.1
100 200 300 400 600 800 1000 2000 3000 5000 7000 10000 20000
20
19
18
17
16
15
14
13
12
11
10
6
21
5
Page 4 of 15
DELUGE CONTROL VALVE
07 MODEL H3
PARTLIST TABLE
PART NUMBER DESCRIPTION QUANTITY
NO.
MATERIAL 50N 80N 100 150 200
50NB 80NB 100NB 150NB 200NB
SPECIFICATION B B NB NB NB
1 4039 4015 4001 3991 4024 HOUSING DUCTILE IRON 1 1 1 1 1
2 9791 9791 9784 9783 8561 O-RING NEOPRENE 1 1 1 1 1
3 4017 4017 4003 3993 4025 SEAT BRONZE 1 1 1 1 1
4 - - 9112 9112 9151 BOLT STAINLESS STEEL - - 4 4 8
5 4018 4018 4004 3994 4026 RUBBER CLAMP BRONZE 1 1 1 1 1
6 4023 4023 4005 4000 4027 RUBBER SEAT NEOPRENE 1 1 1 1 1
7 4041 4041 4011 3990 4034 CLAPPER DUCTILE IRON* 1 1 1 1 1
8 2786 2786 2786 2427 4035 DIAPHRAGM NEOPRENE 1 1 1 1 1
9 2788 2788 2504 2424 4030 CLAMP RING BRONZE 1 1 1 1 1
10 9187 9187 9151 9151 8806 BOLT STAINLESS STEEL 8 8 8 8 12
11 9986 9986 9986 9986 9986 O-RING NEOPRENE 1 1 1 1 1
12 4020 4020 4007 3996 4029 SPINDLE STAINLESS STEEL 1 1 1 1 1
13 9185 9185 8838 8838 9185 NUT STAINLESS STEEL 1 1 1 1 1
14 9186 9186 9184 9184 9186 LOCK NUT STAINLESS STEEL 1 1 1 1 1
15 2977 2977 2978 2979 2980 SPRING STAINLESS STEEL 1 1 1 1 1
16 3983 3983 4010 3998 4033 ADAPTER BRONZE 1 1 1 1 1
17 4016 4016 4002 3992 4032 COVER DUCTILE IRON 1 1 1 1 1
18 8692 8692 9051 9049 9008 BOLT CARBON STEEL 12 12 12 12 16
19 9982 9982 9982 9982 9982 O-RING NEOPRENE 1 1 1 1 1
20 2514 2514 2514 2514 2514 PLUG STEEL PLATED 1 1 1 1 1
21 - - - - 8843 BOLT (ALLEN) STAINLESS STEEL - - - - 6
* OPTION - BRONZE
DIMENSIONS
VALVE
A B
NOMINAL SIZE
50 NB 320 232
80 NB 372 232
100 NB 412 245
150 NB 462 282
200 NB 552 332
Page 5 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
ETW
OUTLET
TO DETECTION
LINE
**
PS2
PG
PG
SCV DV
RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 1
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
ETD TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
SCV RN-A
OUTLET
**
PS2
PG DPA
PG
OD
SCV DV
RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 2
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
P S2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 6 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
ETWT
**
OUTLET
PS2 TO DETECTION
**
G LINE
SCV
OD
PG
PG
SCV DV
RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 3
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
ETDT TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
SCV RN-A
**
OUTLET
PS2
**
G
SCV
OD PG DPA
PG OD
SCV DV
RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 4
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
PS2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 7 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
ETWD
OUTLET
TO DETECTION
LINE
**
PS2 DR.V
~
PG OD
PG
OD
DV OD
SCV RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 5
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
ETDD TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
RN-A
OUTLET
SCV
**
PS2 DR.V
~
PG OD
PG
OD DPA
OD OD
SCV DV
RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 6
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
PS2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 8 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
NTW TO DETECTION
LINE
OUTLET
PS2**
**
G
DR.V
SCV
OD ~
PG OD
PG
OD
DV
OD
SCV RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 7
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR VERTICAL M OUN TIN G
TO DETECTION
NTD LINE
PG
**
PS1
AIR SUPPLY
OUTLET
SCV RN-A
** **
PS2
G
DR.V
SCV
OD ~
PG OD
PG
OD DPA
DV OD OD
SCV RN
**
SV
OD
~
M
~
INLET
OD
SCHEM ATIC 8
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
PS2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 9 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
TO DETECTION
ETW LINE
**
OD
~
SCV RN SV
M
~
PG OD
PS2 **
DV
INLET OUTLET
PG
SCHEM ATIC 9
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
ETD TO DETECTION
LINE
PG
PS1 **
AIR SUPPLY
RN-A SCV
DPA
OD
** OD
~
RN M SV
~
PG OD
PS2 **
INLET DV OUTLET
PG
SCHEM ATIC 1 0
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
PS2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 10 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
ETWT
TO DETECTION
LINE
**
OD
~
SCV RN SV
M
~
PG OD
**
PS2
** G
~
OD
SCV
DV
INLET OUTLET
PG
SCHEM ATIC 1 1
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
ETDT TO DETECTION
LINE
PG
PS1**
AIR SUPPLY
RN-A SCV
DPA
OD ** OD
~
RN M SV
~
PG OD
**
PS2
** G
~
OD
DV
INLET OUTLET
PG
SCHEM ATIC 1 2
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
PS2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 11 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
ETWD TO DETECTION
LINE
**
OD
~
SCV RN SV
M
~
PG OD
PS2 **
DV
INLET OUTLET
PG
DR.V ~
OD
~
OD
OD
SCHEM ATIC 1 3
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
TO DETECTION
ETDD LINE
PG
PS1 **
AIR SUPPLY
RN-A SCV
DPA
OD
** OD
~
RN M SV
~
PG OD
**
PS2
DV
INLET OUTLET
PG
DR.V
~
OD
~
OD
OD
SCHEM ATIC 1 4
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
P S2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 12 of 15
DELUGE CONTROL VALVE
07 MODEL H3
SCHEM ATIC FOR W ET PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
NTW TO DETECTION
LINE
**
OD
~
SCV RN SV
M
~
PG OD
**
PS2
** G
~
OD
SCV
DV
INLET OUTLET
PG
DR.V ~
OD
~
OD
OD
SCHEM ATIC 1 5
SCHEM ATIC FOR DRY PILOT BASIC TRIM FOR DELUGE VALVE
M ODEL - H3 FOR HORIZON TAL M OUN TIN G
NTD TO DETECTION
LINE
PG
**
PS1
AIR SUPPLY
RN-A SCV
DPA
OD **
SV
OD
~
RN M
~
PG OD
**
PS2
** G
~
OD
DV
INLET OUTLET
PG
DR.V
~
OD
~
~ OD
SCHEM ATIC 1 6
DV – DELUGE VALVE G – SPRINKLER ALARM (WMG) – SWING CHECK VALVE M – EMERGENCY RELEASE STATION
OD – OPEN DRAIN – VALVE RN – RESTRICTION NOZZLE (PRIMING LINE) DPA – DRY PILOT ACTUATOR
– STRAINER SV – SOLENOID VALVE – ANGLE VALVE PG – PRESSURE GAUGE
DR.V – DRIP VALVE – BY USER PS1 – LOW AIR ALARM PRESSURE SWITCH – OPTIONAL
PS2 – WATER FLOW PRESSURE ALARM SWITCH RN-A – RESTRICTION NOZZLE (AIR LINE)
**
Page 13 of 15
DELUGE CONTROL VALVE
07 MODEL H3
DV 2 0 0 N B DV 1 5 0 N B
KG/SQCM KG/SQCM
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
220. 240
65 70
220. ET
FE
ET T
180 FE 55 200
F EE 60
25 T 0
EE 50 25 55
160 F
180
ET
0 FE
25 45 160 5 00 50
140 E T
FE 40 45
METERS
METERS
0 140
120 50 40
35
120
100 35
30
100 30
80 25
80 25
20
60 20
15 60
40 15
10 40
10
20 5 20 5
0
20 50 100 150 200 250 0
20 50 100 150 200 250
SYSTEM SUPPLY PRESSURE - PSI SYSTEM SUPPLY PRESSURE - PSI
EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120 EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120
DV 200NB DV 150NB
DV 1 0 0 N B DV 8 0 N B
KG/SQCM KG/SQCM
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
240 220.
70 65
220. 200
MAXIMUM PILOT LINE HEIGHT - FEET
65 60
MAXIMUM PILOT LINE HEIGHT - FEET
ET
200 T 60 180 FE 55
FEE 25
25 55 50
180 160 ET
ET FE
FE 50 2 50 45
160 0 140
25
45 T 40
METERS
140 EE
T EE
METERS
F 120 0F 35
5 00 40 50
120 35 100 30
100 30 80 25
80 25 20
60
20 15
60 40
15 10
40 20
10 5
20 5 0
20 50 100 150 200 250
0
20 50 100 150 200 250 SYSTEM SUPPLY PRESSURE - PSI
SYSTEM SUPPLY PRESSURE - PSI EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120
EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120
DV 80NB
DV 100NB
Page 14 of 15
DELUGE CONTROL VALVE
07 MODEL H3
DV - 5 0 N B
KG/SQCM
2 4 6 8 10 12 14 16 18
220.
65
MAXIMUM PILOT LINE HEIGHT - FEET
200 60
T 55
180 E
FE
25 50
160 ET
F E
50 45
140 2
40
ET METERS
120 0 FE
50 35
100 30
80 25
20
60
15
40
10
20 5
0
20 50 100 150 200 250
SYSTEM SUPPLY PRESSURE - PSI
EQUIVALENT LENGTH BASED ON 1/2" SCHEDULE 40 PIPE WITH C = 120
Page 15 of 15