Sie sind auf Seite 1von 34

500kV Double Circuit Transmission Line From Port Qasim Power Plan

to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

Gantry Port Qasim End Gantry Gantry

1 74.000 334905.000 2742343.000 60.100 74.00 AM#1 39°51'17" R 1 TDD

2 176.070 334921.000 2742447.000 59.730 102.07 132.395 170 AM#2 58°11'30" R 2 TDD

3 338.790 335064.000 2742512.000 59.580 162.72 231.16 233 AM#3 22°10'32" R 3 TDD

4 638.390 335365.000 2742526.000 60.860 299.60 310.41 251 00°40'06" R 4 TDS

5 959.610 336576.000 2742537.000 61.760 321.22 269.05 259 AM#4 01°32'16" R 5 TDS

6 1176.490 335902.000 2742538.000 60.730 216.88 264.265 269 AM#5 01°59'20" L 6 TDS

7 1488.140 336215.000 2742548.000 61.010 311.65 307.995 260 AM#6 00°10'00" L 7 TDS

8 1792.480 336517.000 2742561.000 67.300 304.34 367.56 416 AM#7 00°29'45" R 8 TDD

9 2223.260 336948.000 2742579.000 67.300 430.78 394.195 423 AM#8 00°43'55" L 9 TDA

10 2580.870 337308.000 2742596.000 65.780 357.61 355.67 341 10 TDS

11 2934.600 337659.000 2742614.000 64.130 353.73 326.65 299 AM#9 11 TDS

12 3234.170 337958.000 2742629.000 63.420 299.57 256.23 246 01°07'41" R 12 TDA


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

13 3447.060 338171.000 2742636.000 62.120 212.89 236.315 280 00°36'28" L 13 TDA

14 3706.800 338438.000 2742645.000 61.240 259.74 310.67 307 AM#10 14 TDS

15 4068.400 338801.000 2742660.000 59.380 361.60 349.36 350 15 TDS

16 4405.520 339137.000 2742673.000 58.330 337.12 330.29 332 AM#11 16 TDS

17 4728.980 339460.000 2742685.000 59.340 323.46 330.09 328 17 TDS

18 5065.700 339795.000 2742700.000 58.990 336.72 306.62 308 18 TDS

19 5342.220 340073.000 2742711.000 58.680 276.52 297.21 298 19 TDS

20 5660.120 340392.000 2742725.000 59.650 317.90 336.54 335 20 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

21 6015.300 340746.000 2742737.000 59.010 355.18 330.995 334 AM#12 00°12'55" R 21 TDS

22 6322.110 341052.000 2742749.000 59.280 306.81 280.755 269 22 TDS

23 6576.810 341307.000 2742762.000 59.350 254.70 281.81 345 AM#13 00°03'43" R 23 TDS

24 6885.730 341618.000 2742772.000 58.450 308.92 298.41 392 AM#14 33°19'43" R 24 TDD

25 7173.630 341864.000 2742621.000 59.070 287.90 288.95 350 25 TDS

26 7463.630 342112.000 2742471.000 60.030 290.00 285 280 26 TDS

27 7743.630 342351.000 2742327.000 59.850 280.00 295.18 283 AM#15 27 TDS

28 8053.990 342618.000 2742167.000 58.550 310.36 330 318 29°30'25" L 28 TDD

29 8403.630 342965.000 2742155.000 57.770 349.64 344.82 325 29 TDS

30 8743.630 343303.000 2742144.000 57.740 340.00 346 329 30 TDS

31 9095.630 343655.000 2742133.000 58.660 352.00 350 349 AM#16 31 TDS

32 9443.630 344005.000 2742124.000 58.800 348.00 329 356 32 TDS

33 9753.630 344315.000 2742114.000 57.770 310.00 340 279 33 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

34 10123.630 344683.000 2742101.000 58.390 370.00 348.855 300 34 TDS

35 10451.340 345011.000 2742092.000 58.600 327.71 352.5 344 48°30'50" L 35 TDD

36 10828.630 345252.000 2742350.000 58.050 377.29 356.145 332 36 TDS

37 11163.630 345498.000 2742614.000 69.030 335.00 327.91 379 AM#17 37 TDS

38 11484.450 345719.000 2742845.000 68.860 320.82 340 330 24°53'00" L 38 TDD

39 11843.630 345832.000 2743186.000 70.370 359.18 347.305 369 39 TDS

40 12179.060 345938.000 2743504.000 68.540 335.43 347.715 367 40 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

41 12539.060 346050.000 2743846.000 74.000 360.00 363 282 41 TDS

42 12905.060 346166.000 2744193.000 75.210 366.00 366 330 42 TDS

42-A 13271.060 346282.000 2744540.000 78.640 366.00 363 42-A TDS

42-B 13631.060 346396.000 2744884.000 80.660 360.00 360 42-B TDS

42-C 13991.060 346509.000 2745226.000 81.450 360.00 355.5 42-C TDS

43 14342.060 346619.000 2745557.000 82.630 351.00 338.25 322 22°22'15" R 43 TDD

44 14667.560 346834.000 2745802.000 91.140 325.50 240.565 317 44 TDS

45 14823.190 346934.000 2745922.000 90.170 155.63 273.275 304 AM#18 45 TDS

46 15214.110 347190.000 2746219.000 89.540 390.92 376.71 337 20°27'22" L 46 TDD

47 15576.610 347314.000 2746558.000 90.550 362.50 368.935 326 47 TDS

48 15951.980 347445.000 2746910.000 91.570 375.37 351.245 404 08°45'29" R 48 TDA

49 16279.100 347602.000 2747195.000 93.460 327.12 354.115 303 00°00'00" 49 TDA

50 16660.210 347788.000 2747529.000 95.890 381.11 345.895 371 50 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

51 16970.890 347940.000 2747800.000 97.100 310.68 323.48 355 AM#19 10°08'51" L 51 TDA

52 17307.170 348049.000 2748120.000 98.950 336.28 333.63 303 52 TDS

53 17638.150 348155.000 2748433.000 100.970 330.98 330 349 53 TDS

54 17967.170 348262.000 2748744.000 102.530 329.02 329.51 295 54 TDS

55 18297.170 348369.000 2749056.000 103.940 330.00 311.355 330 55 TDS

56 18589.880 348463.000 2749333.000 105.500 292.71 314.135 332 56 TDS

57 18925.440 348572.000 2749650.000 107.360 335.56 341.57 310 57 TDS

58 19273.020 348687.000 2749977.000 110.470 347.58 353.175 373 58 TDS

59 19631.790 348801.000 2750317.000 113.450 358.77 361.23 336 59 TDS

60 19995.480 348920.000 2750664.000 117.680 363.69 351.33 389 60 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

61 20334.450 349030.000 2750983.000 119.980 338.97 353.41 323 61 TDS

62 20702.300 349149.000 2751330.000 121.920 367.85 349.565 357 AM#20 00°37'45" L 62 TDS

63 21033.580 349252.000 2751644.000 128.210 331.28 340.125 352 63 TDS

64 21382.550 349364.000 2751979.000 128.010 348.97 340.435 336 64 TDS

65 21714.450 349466.000 2752294.000 133.180 331.90 290.725 277 65 TDS

66 21964.000 349546.000 2752529.000 146.070 249.55 292.505 290 66 TDS

67 22299.460 349650.000 2752846.000 142.500 335.46 308.83 268 67 TDS

68 22581.660 349740.000 2753113.000 158.290 282.20 288.175 391 00°00'00" 68 TDA

69 22875.810 349830.000 2753393.000 156.030 294.15 284.005 219 69 TDS

70 23149.670 349920.000 2753664.000 153.270 273.86 296.505 297 70 TDS

71 23468.820 350017.000 2753958.000 169.530 319.15 359.825 409 71 TDS

72 23869.320 350144.000 2754336.000 160.690 400.50 280.75 293 72 TDS

73 24030.320 350227.000 2754591.000 162.630 161.00 279.425 336 73 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

74 24428.170 350320.000 2754868.000 159.550 397.85 355.975 231 74 TDS

75 24742.270 350417.000 2755168.000 170.890 314.10 307.675 306 75 TDS

76 25043.520 350511.000 2755454.000 183.780 301.25 292.09 360 76 TDS

77 25326.450 350600.000 2755721.000 176.320 282.93 353.405 306 77 TDS

78 25750.330 350736.000 2756122.000 187.200 423.88 361.545 408 78 TDS

79 26049.540 350826.000 2756408.000 182.300 299.21 329.665 304 79 TDS

80 26409.660 350940.000 2756748.000 185.320 360.12 347.005 301 80 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

81 26743.550 351047.000 2757066.000 193.120 333.89 344.04 371 81 TDS

82 27097.740 351157.000 2757412.000 194.000 354.19 359.855 345 82 TDS

83 27463.260 351274.000 2757757.000 203.500 365.52 370.59 382 83 TDS

84 27838.920 351389.000 2758105.000 208.090 375.66 399.94 414 00°00'00" 84 TDA

85 28263.140 351525.000 2758517.000 207.260 424.22 345.34 393 85 TDS

86 28529.600 351611.000 2758769.000 211.170 266.46 327.605 276 86 TDS

87 28918.350 351733.000 2759139.000 220.940 388.75 360.08 348 87 TDS

88 29249.760 351836.000 2759455.000 235.090 331.41 295.44 337 88 TDS

89 29509.230 351918.000 2759701.000 238.880 259.47 270.185 277 89 TDS

90 29790.130 352007.000 2759968.000 239.660 280.90 340.745 339 90 TDS

91 30190.720 352131.000 2760342.000 236.810 400.59 369.15 292 91 TDS

92 30528.430 352239.000 2760668.000 247.780 337.71 343.43 418 92 TDS

93 30877.580 352349.000 2760999.000 257.290 349.15 356.415 406 93 TDS


500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

94 31241.260 352463.000 2761345.000 248.520 363.68 365.24 298 94 TDS

95 31608.060 352580.000 2761693.000 260.850 366.80 355.22 376 95 TDS

96 31951.700 352686.000 2762019.000 256.220 343.64 353.41 316 96 TDS

97 32314.880 352799.000 2762365.000 265.000 363.18 308.98 278 97 TDS

98 32569.660 352878.000 2762612.000 270.650 254.78 281.415 339 98 TDS

99 32877.710 352973.000 2762905.000 269.000 308.05 321.23 340 99 TDS

100 33212.120 353081.000 2763218.000 270.510 334.41 339.605 313 100 TDS
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

101 33556.920 353189.000 2763549.000 275.200 344.80 347.46 399 AM#21 10°49'55" R 101 TDA

102 33907.040 353361.000 2763847.000 271.250 350.12 356.525 382 102 TDS

103 34269.970 353538.000 2764165.000 260.000 362.93 306.53 303 103 TDS

104 34520.100 353659.000 2764382.000 258.860 250.13 258.28 199 104 TDS

105 34786.530 353790.000 2764615.000 260.520 266.43 297.34 388 105 TDS

106 35114.780 353949.000 2764902.000 240.980 328.25 329.625 217 106 TDS

107 35445.780 354110.000 2765199.000 255.560 331.00 343.69 413 107 TDS

108 35802.160 354285.000 2765503.000 243.720 356.38 328.62 271 108 TDS

109 36103.020 354431.000 2765765.000 243.450 300.86 325.93 295 109 TDS

110 36454.020 354602.000 2766070.000 242.000 351.00 413.725 216 00°00'00" 110 TDA

111 36930.470 354831.000 2766491.000 312.930 476.45 401.815 676 00°00'00" 111 TDA

112 37257.650 354990.000 2766779.000 319.030 327.18 327.855 355 112 TDS

113 37586.180 355149.000 2767065.000 317.180 328.53 325.21 313 113 TDS
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

114 37908.070 355305.000 2767346.000 314.000 321.89 315.51 310 114 TDS

115 38217.200 355457.000 2767615.000 312.700 309.13 317.28 318 115 TDS

116 38542.630 355616.000 2767898.000 310.910 325.43 334.79 340 116 TDS

117 38886.780 355784.000 2768198.000 307.270 344.15 353.98 328 117 TDS

118 39250.590 355962.000 2768517.000 309.260 363.81 347.975 350 118 TDS

119 39582.730 356126.000 2768806.000 310.900 332.14 348.315 365 119 TDS

120 39947.220 356303.000 2769123.000 299.420 364.49 463.145 648 00°00'00" 120 TDA
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

121 40509.020 356578.000 2769608.000 247.620 561.80 477.985 299 00°00'00" 121 TDA

122 40903.190 356770.000 2769954.000 248.180 394.17 325.555 319 122 TDS

123 41160.130 356897.000 2770178.000 249.610 256.94 301.695 291 123 TDS

124 41506.580 357066.000 2770481.000 246.130 346.45 375.855 355 00°00'00" 124 TDA

125 41911.840 357263.000 2770835.000 245.570 405.26 352.63 319 125 TDS

126 42211.840 357409.000 2771096.000 245.700 300.00 315 375 126 TDS

127 42541.840 357571.000 2771383.000 244.050 330.00 309.38 267 127 TDS

128 42830.600 357712.000 2771635.000 246.040 288.76 294.46 316 128 TDS

129 43130.760 357859.000 2771896.000 244.250 300.16 345.08 367 129 TDS

130 43520.760 358049.000 2772234.000 247.170 390.00 362.105 357 130 TDS

131 43854.970 358212.000 2772525.000 249.740 334.21 347.42 350 00°28'20" L 131 TDA

132 44215.600 358386.000 2772844.000 252.960 360.63 355.615 355 132 TDS

133 44566.200 358556.000 2773151.000 255.710 350.60 352.46 376 133 TDS
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

134 44920.520 358725.000 2773461.000 257.030 354.32 319.595 301 134 TDS

135 45205.390 358863.000 2773711.000 259.700 284.87 276.615 296 135 TDS

136 45473.750 358992.000 2773949.000 259.400 268.36 301.495 295 136 TDS

137 45808.380 359154.000 2774239.000 262.950 334.63 313 336 137 TDS

138 46099.750 359296.000 2774496.000 263.040 291.37 292.005 264 138 TDS

139 46392.390 359437.000 2774751.000 262.450 292.64 290.995 286 139 TDS

140 46681.740 359575.000 2775001.000 262.630 289.35 314.015 359 AM#22 13°45'25" L 140 TDA
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

141 47020.420 359670.000 2775352.000 267.540 338.68 341.255 314 141 TDS

142 47364.250 359761.000 2775684.000 267.260 343.83 316.655 347 142 TDS

143 47653.730 359836.000 2775965.000 267.880 289.48 295.465 256 143 TDS

144 47955.180 359913.000 2776253.000 268.000 301.45 335.545 358 144 TDS

145 48324.820 360011.000 2776611.000 268.630 369.64 348.545 354 145 TDS

146 48652.270 360096.000 2776926.000 269.660 327.45 328.725 325 146 TDS

147 48982.270 360182.000 2777246.000 269.620 330.00 333.04 331 147 TDS

148 49318.350 360269.000 2777571.000 270.310 336.08 336.63 332 148 TDS

149 49655.530 360357.000 2777896.000 269.420 337.18 326.96 327 149 TDS

150 49972.270 360440.000 2778201.000 269.390 316.74 327.12 350 150 TDS

151 50309.770 360528.000 2778526.000 270.180 337.50 261.55 299 AM#23 13°50'14" R 151 TDA

152 50495.370 360619.000 2778690.000 269.700 185.60 265.88 290 43°26'50" L 152 TDD

153 50841.530 360532.000 2779028.000 267.160 346.16 371.825 400 12°34'50" R 153 TDA
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

154 51239.020 360519.000 2779492.000 267.650 397.49 362.745 300 154 TDS

155 51567.020 360509.000 2779817.000 267.420 328.00 327 334 155 TDS

156 51893.020 360500.000 2780073.000 267.250 326.00 348 297 156 TDS

157 52263.020 360488.000 2780442.000 266.040 370.00 372.15 339 32°14'00" L 157 TDD

158 52637.320 360279.000 2780754.000 264.170 374.30 351.65 303 34°38'50" R 158 TDD

159 52966.320 360282.000 2781083.000 264.500 329.00 299.5 326 13°22'30" R 159 TDA

160 53236.320 360364.000 2781413.000 264.800 270.00 341.1 255 160 TDS
500kV Double Circuit Transmission Line From Port Qasim Power Plan
to Interconnect with Existing 500kV Single Circuit Hub-Jamshoro Transmissi

Tower# RD UTM Coordinates Elv. Back Span Wind Span Wt Span Angle# Def.Angle Tower# Tower
(m) East (m) North (m) (m) (m) (m) (degree) Type

161 53648.520 360448.000 2781411.000 264.710 412.20 297.43 343 15°47'05" L 161 TDA

162 53831.180 360443.000 2781927.000 264.300 182.66 340.91 346 AM#24 14°41'30" R 162 TDA

163 54330.340 360554.000 2782415.000 263.600 499.16 356.395 344 00°00'00" 163 TDA

164 54543.970 360601.000 2782620.000 264.100 213.63 241.44 304 AM#25 43°01'25" L 164 TDD

164-A 54813.220 360554.000 2782886.000 263.650 269.25 269.825 23°09'53" L 164-A DHJ

164-B 55083.620 360399.000 2782800.000 262.720 270.40 214.605 61°43'50" L 164-B DHJ

164-C 55242.430 360470.000 2783022.000 262.910 158.81 150.355 21°41'40" L 164-C DHJ

164-D 55384.330 360324.000 2782923.000 262.250 141.90 235.87 16°52'37" R 164-D DHJ

165 55714.170 360437.000 2782910.000 262.930 329.84 164.92 165 DHJ


wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

32.00

24.00 0 8

19.75 0 4 wall

29.75 6 8 check post

27.75 6 6 check post, manhole

27.75 6 6 Temporary hotel, culvert

27.75 6 6 Stagnant water, nala

27.75 6 6 k.track, water pipe

29.75 6 8 2 k.track, manholes

27.75 6 6 manholes

27.75 6 6 pond, manhole

21.75 0 6

29.75 6 8 Road, manhole


wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

29.75 6 8 11kV ht=10.0m

23.75 0 8 2 w.c

23.75 0 8 culvert

21.75 0 6 nala, culvert

21.75 0 6 nala, culvert

23.75 0 8 manholes

21.75 0 6 manholes

21.75 0 6
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

23.75 0 8 manholes

21.75 0 6 manholes

25.75 6 4 manholes

20.00 0 4 Road, manhole

17.75 0 2 nala

17.75 0 2

19.75 0 4

19.75 0 4

21.75 0 6

19.75 0 4 fence

19.75 0 4 pond

19.75 0 4 pond

19.75 0 4
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

19.75 0 4

22.00 0 6

21.75 0 6

21.75 0 6

24.00 0 8

21.75 0 6

23.75 0 8
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

21.75 0 6

21.75 0 6

21.75 0 6

21.75 0 6

21.75 0 6

24.00 0 8 wall, k.track, 11kV ht=10.1m

29.75 6 8 Highway (N-5),132kV ht=19.43m

29.75 6 8 road

24.00 0 8

19.75 0 4

30.00 6 8 Railway Track, w.c, road, room

24.00 0 8

29.75 6 8 132kV ht=15.58m, k. track


wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

30.00 6 8

23.75 0 8 Road, w.c, room, 11kV ht=7m

21.75 0 6

19.75 0 4

23.75 0 8 Gas line, road

23.75 0 8

19.75 0 4 11kV ht=8m

21.75 0 6

23.75 0 8

23.75 0 8 k. track
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

19.75 0 4

23.75 0 8 k. track

21.75 0 6 k. track

23.75 0 8 nala

21.75 0 6

19.75 0 4

23.75 0 8

22.00 0 6

17.75 0 2

29.75 6 8

19.75 0 4 k. track

27.75 6 6

29.75 6 8
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

25.75 6 4

21.75 0 6

19.75 0 4

23.75 0 8

19.75 0 4

21.75 0 6

19.75 0 4 road
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

23.75 0 8

23.75 0 8 fence

19.75 0 4

24.00 0 8 k. track

29.75 6 8

23.75 0 8

23.75 0 8

19.75 0 4

17.75 0 2

19.75 0 4

23.75 0 8

29.75 6 8 inspan cutting

23.75 0 8
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

27.75 6 6

17.75 0 2 k. track

21.75 0 6 nala

17.75 0 2

21.75 0 6 k. track

21.75 0 6

19.75 0 4 fence
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

24.00 0 8

23.75 0 8 2 k.track, inspan cutting

27.75 6 6

17.75 0 2

17.75 0 2

27.75 6 6

17.75 0 2

23.75 0 8

19.75 0 4 fence

30.00 6 8

30.00 6 8

19.75 0 4

19.75 0 4
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

21.75 0 6

19.75 0 4

19.75 0 4

19.75 0 4

19.75 0 4

21.75 0 6 k. track

30.00 6 8 fence
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

28.00 6 6

21.75 0 6

19.75 0 4

30.00 6 8

23.75 0 8 k. track, 11kV ht=10.6m

21.75 0 6

17.75 0 2

19.75 0 4 k.track

23.75 0 8 nala

23.75 0 8 k. track

22.00 0 6 2 k.tracks

21.75 0 6 2 k.tracks

21.75 0 6 nala, tracks


wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

19.75 0 4 k.track

23.75 0 8 Digging area

23.75 0 8 Digging area

23.75 0 8

17.75 0 2

17.75 0 2 k. track

24.00 0 8 k. track
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

21.75 0 6 k.track

21.75 0 6

17.75 0 2

21.75 0 6 k. track

21.75 0 6

21.75 0 6

19.75 0 4

19.75 0 4 Digging area, k. track, k.road

23.75 0 8

21.75 0 6 fence

22.00 0 6 132kV ht=11m, 2 11kV ht= 8 & 9m, road

24.00 0 8 road, 11kV ht=9m

30.00 6 8
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

21.75 0 6

17.75 0 2

17.75 0 2

23.75 0 8 road

23.75 0 8

19.75 0 4

21.75 0 6
wer Plant
ansmission Line

Cond. Attachment Body Ext. Leg Ext. In span Crossings


ht (m) (m) (m)

30.00 6 8 220kV ht=23.2m

30.00 6 8

28.00 6 6 132kV ht=20.1m

28.00 6 6

31.50 9 6

31.50 9 6

27.10 4.5 6

27.10 4.5 6

18.10 0 1.5 500kV TL