OTHER TECHNICAL DATA

EN

CROSS-SECTIONS OF CABLES TO BE USED


In some cases, the air to be drawn by the engine may be taken from outside as the room is not suitable.
Following points shall be considered in such cases.
Stand By power power power power power power power power
(kVA) max. cable cable cable cable cable cable cable cable
A 1 pc. / 2 pcs. / 3 pcs. / 4 pcs. / 5 pcs. / 6 pcs. / 7 pcs. / 8 pcs. /
min. max
phase phase phase phase phase phase phase phase
10 25 36 4 mm2 - - - - - - -
25 33 47 6 mm2 - - - - - - -
33 45 65 10 mm2 - - - - - - -
45 60 87 16 mm2 - - - - - - -
60 80 115 25 mm2 - - - - - - -
80 99 143 35 mm2 - - - - - - -
99 123 178 50 mm2 - - - - - - -
123 152 220 70 mm2 - - - - - - -
152 184 265 95 mm2 - - - - - - -
184 215 310 120 mm2 - - - - - - -
215 246 355 150 mm2 50 mm2 - - - - - -
246 281 405 185 mm2 70 mm2 - - - - - -
281 333 480 240 mm2 95 mm2 - - - - - -
333 430 620 - 120 mm2 70 mm2 - - - - -
430 457 660 - 150 mm2 70 mm2 - - - - -
457 551 795 - 185 mm2 95 mm2 - - - - -
551 610 880 - 240 mm2 120 mm2 70 mm2 - - - -
610 735 1060 - - 150 mm2 95 mm2 70 mm2 - - -
735 842 1215 - - 185 mm2 120 mm2 95 mm2 70 mm2 - -
842 984 1420 - - 240 mm2 150 mm2 120 mm2 95 mm2 70 mm2 -
984 1123 1620 - - - 185 mm2 150 mm2 120 mm2 95 mm2 70 mm2
1123 1331 1920 - - - 240 mm2 185 mm2 150 mm2 120 mm2 95 mm2
1331 1663 2400 - - - - 240 mm2 185 mm2 150 mm2 120 mm2
1663 1965 2835 - - - - - 240 mm2 185 mm2 150 mm2
1965 2245 3240 - - - - - - 240 mm2 185 mm2
2245 2661 3840 - - - - - - - 240 mm2