Sie sind auf Seite 1von 3

Star-Delta Timer

DIN size W48×H48mm Star-Delta Timer


(A)
▣Features Counter

lThis is upgraded model from AT8SD series.


l Wide range of setting time and switching time.
(B)
U T1(Setting time) : Selectable 5, 10, 50, 100sec Timer

U T2(Switching time) : Selectable 0.05, 0.1, 0.2, 0.3, 0.4, 0.5sec


lEasy to set the setting time and switching time on front panel.
lLED indicators show status of Start and Delta output. (C)
Temp.
lPower supply : 100-240VAC 50/60Hz / 24-240VDC controlle

12VDC(Option)
lApplication : Starting large capacity motors (D)
Power
controlle
Please read "Caution for your safety" in operation
! manual before using.

(E)
▣Ordering information Panel
meter

AT 8 SDN
(F)
Tacho/
SDN Star Delta New Type Speed/
Pulse
meter
8 8pin plug Type

AT Analog Timer (G)


Display
unit
▣Specifications
Model AT8SDN
(H)
Function Star-Delta TIMER Sensor
controlle
Control time setting range 0.5sec~100sec(Max. time)
Power supply 100-240VAC 50/60Hz / 24-240VDC , 12VDC(Option)
Allowable voltage range 90 ~ 110% of rated voltage (I)
Proximit
Power consumption Approx. 4VA(240VAC 60Hz), Approx. 1.3W(240VDC), Approx. 0.5W(12VDC) sensor
Return time Max. 100ms
Control Contact type contact : SPST(1a), contact : SPST(1a)
(J)
output Contact capacity 250VAC 3A resistive load Photo
Mechanical Min.10,000,000 times electri c
Relay sensor
life cycle Electrical Min. 100,000 times(250VAC 3A resistive load)
Repeat error Max. ±0.3%
(K)
Setting error Max. ±5% ±0.05sec. Pressur
Voltage error Max. ±0.5% sensor

Temperature error Max. ±2%


Switching time error ±25%
(L)
Insulation resistance 100MΩ(at 500VDC) Rotary
encoder
Dielectric strength 2000VAC 50/60Hz for 1 minute
Noise strength ±2kV the square wave noise(pulse width:1㎲) by the noise simulator
(M)
Mechanical 0.75mm amplitude at frequency of 10 ~ 55Hz in each of X, Y, Z directions for 1 hours 5-Phase
Vibration stepping
Malfunction 0.5mm amplitude at frequency of 10 ~ 55Hz in each of X, Y, Z directions for 10 minutes motor &
Driver &
Mechanical 300m/s²(Approx. 30G) in X, Y, Z directions 3 times Controlle
Shock
Malfunction 100m/s²(Approx. 10G) in X, Y, Z directions 3 times
Ambient temperature -10 ~ 55℃(at non-freezing status)
Storage temperature -25 ~ 65℃(at non-freezing status)
Ambient humidity 35 ~ 85%RH
Approval
Weight Approx. 100g

B-46
AT8SDN
▣Connections
CONTACT :
250VAC 3A RESISTIVE LOAD
4 5
3 6

2 7
1 8

- SOURCE + !

▣Dimensions
lPanel cut-out
80
lBracket 48 Min. 53
15 50 15

45 +0
-0
.5

Min. 62
45 +- 0.5
0

1 0se c

AT8SDN CHA NGE


TIME

71

Panel Socket : PG-08

Unit:mm

▣Front panel identification

(STAR) LED (DELTA) LED

Time range display Switching time(T2) display


A : 50ms
F : 100ms
Time range(T1) selector F1 : 200ms
AT8SDN CH A NG E

C : 300ms
T IME

D : 400ms
Switching time range(T2) selector
I : 500ms

B-47
Star-Delta Timer
▣Time specification
(A)
1. T1(Setting time) Counter

Time range Time unit Time setting range


0.5 0.5 ~ 5sec
1.0 1 ~ 10sec (B)
×10sec Timer
5 5 ~ 50sec
10 10 ~ 100sec
Switching time (C)
2. T2(Switching time) (Unit:ms) AT8SDN CH ANG E
TIM E
display Temp.
controlle

Display A F F1 C D I
Time ragne Switching time
T2 switching selector(T1)
50 100 200 300 400 500 selector(T2) (D)
time
Power
controlle

▣Operation
(E)
When power is applied, contact will be ON. When reaching to T1 setting time, contact will be OFF Panel
meter
and after T2 switching time, contact will be ON.
It the power is OFF, contact will be OFF.
(F)
Tacho/
Power(2-7) Speed/
Pulse
meter
contact(5-8)
T1
(G)
T2
Display
unit

contact(6-8)

LED (H)
Sensor
controlle
LED

※ T1 : Set ting time ( contact operation time)


※ T2 : Switching time ( contact and contact are OFF simult aneously at power ON) (I)
Proximit
sensor

▣Proper usage
(J)
1. Please supply power quickly at once with using 5. Do not change Timer range, setting time, switching Photo
electri c
switch or Relay contact. Otherwise it may cause time while time oprating. When changing setting, sensor
time error or power reset failure. plese power off.
2. Connect power line without concerning polarity
6. Environment (K)
for ATN series AC power type. Pressur
Please avoid the following places:
But please aware power connection for DC power sensor
lWhere this product may be damaged by strong
type.
impact or vibration.
3. Please use like (Fig. 2) in order not to flow leakage
lWhere there are corrosive gas or flammable (L)
current into Timer. Rotary
gas, water, oil and dust. encoder
4. Please use it like (Fig. 2) in order not to flow
lWhere magnetic and electrical noise occurs.
leakage current into timer.
lWhere there are High temperature and humidity (M)
(Fig. 1) (Fig. 2) 5-Phase
beyond rated specification. stepping
motor &
lWhere there are strong alkalis and acids. Driver &
Leakage current R Controlle
lWhere there are direct rays of sun.
R C C
T T

B-48