● External structure 20
● Basic features and interrupting operation 22
● Standards and certification 25
● Types and ordering information 26
● Ratings 31
Susol VCB is full line-up new VCB which has the high ● Accessories 34
interrupting capacity, large current(~50kA, ~3000A), and ● Control circuit diagrams 65
maximized compatibility with existing products through ● Dimensions 68
the dual phases and compact sized models. ● Technical data 85
2I
<< Susol VCB Series
I3
Vacuum Circuit Breaker, VCB is installed in the medium voltage distribution
lines to protect life and load equipment. In case of accidents such as over
current, short circuit and ground fault current, VCB works by interrupting the
circuit through the inner Vacuum Interrupter which is acted by signal from the
outside separate relay.
Suitable for use as the main circuit breaker to protect key installations in the
places such as device industry, power plants, high-rise buildings, large ships.
4I
<< Susol VCB Series
I5
4.76/15kV (VL-05/15)
•Rated short-time (to withstand current ): 2sec
•Rated operating sequence: O-0.3s-CO-3min-CO
•Various cradle: P, H type
•CB Compartment for MCSG available
•A variety of control power
- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V
- AC 48V, AC 100~130V, AC 220~250V
•A variety of accessories
- VCB part: Charge switch, UVT, Secondary trip coil, Latch checking
switch, Position switch, Locking magnet, Plug interlock, Key lock,
Button cover, Button padlock, Padlock (H type Door interlock), MOC
- Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck
Operated Cell switch), Temperature sensor, Earthing switch &
accessaries, Door, Door interlock, Door emergency button
- Others: Racking in/out handle,
UVT Time delay controller, CTD
(Condensor Trip Device),
Temperature module
•TEST/CONNECT Automatic Position Indicator
Ur Isc Ir
(kV) (kA) (A)
4.76 40 1200
2000
3000
50 1200
2000
3000
15 40 1200
2000
Ur Isc Ir 3000
(kV) (kA) (A)
50 1200
27 25 1200 2000
2000 3000
VCB
Breaker
Insulation rod
Lower terminal
Shunt
Vacuum interrupter
Upper terminal
Tulip contactor
Fixed
electrode
Fixed
Contacts
seal cup Vacuum Interrupter, VI
Arc shield
The vacuum rate within the VI is very high the contacts are made of special alloy (copper-
Bellows
shield (approximately 5x10-5 Torr) and the spacing chromium) and the interior is completely
Ceramic between fixed contact and movable sealed to prevent loss of vacuum.
contact is about 6~20mm, depending on Therefore the wearing of the contacts can be
Bellows
Movable
the voltage. minimized in the event of short-circuit and the
Movable seal cup
electrode The contacts are in a structure that arc can arc energy by overvoltage or switching can be
easily be extinguished and the surfaces of reduced effectively.
8I
<< Susol VCB Series
Convenience and
Variety
I9
Stego Tulip
Main circuit structure with high reliability
•Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor)
•Strong structure for the temperature rise (Natural cooling system)
Tulip finger
Tulip spring
Plate understar :
Securing freedom of Tulip
Plate star: Supporting Tulip for position maintaing and torsional flow prevention
•Maintaining the connection between breaker and cradle for the optimum current path through securing freedom of Tulip.
•Increasing the heat dissipation area of the contactors and minimizing aging.
10I
<< Susol VCB Series
4.76/15/27kV ...
(VH-05/15/27)
I 11
CB Compartment
Convenience in building switchgears
4.76/15/27kV 20/25/31.5/40/50kA
•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of operation by Truck
- Drawable in the closed position of the switchgear door
- Racking-in/out positions indicated mechanically
•Equipped with safety devices and accessories
- Control power connected Interlock
- Earthing S/W and interlock, MOC/TOC (ANSI)
•Convenience in building switchgears
- Module assembly with CB compartment
12I
<< Susol VCB Series
LV
Compartment
CB
Compartment
Accessories of CB compartment
(H type cradle)
OC (Mechanism Operated Cell S/W)
■M
OC (Truck Operated Cell S/W)
■T PT
Compartment
hutter Padlock
■S
emperature Sensor
■T
oor Emergency ON/OFF Button
■D
arthing switch & Accessaries
■E
Key lock for Earthing S/W
Locking Magnet for Earthing S/W
Position S/W for Earthing S/W
M (Temperature Monitoring Unit)
■T
I 13
Accessories
A variety of accessories for VL-05/15
Breaker
Motor Key lock CTD (Condenser trip device)
Closing coil Button padlock MOC
Trip coil Button cover Padlock
Counter Position switch Plug Interlock
Auxiliary contact Racking in/out handle
UVT coil UVT Time delay controller
14I
<< Susol VCB Series
Cradle (H type)
TOC (Truck operated cell s/w) Earthing switch & Accessary
MOC (Mechanical operated cell s/w) Key lock for Earthing switch
Temperature sensor Locking Magnet for Earthing switch
Door Position s/w for Earthing switch
Door interlock TM (Temperature monitoring unit)
Shutter padlock Lift Interlock
Emergency ON/OFF button
I 15
Accessories
A variety of accessories for VH-27
Breaker
Motor Auxiliary contact wire D oor Interlock for withdrawable type
AC/DC coil rectifier Key lock Lifting hook
Trip coil/Closing coil B utton cover/Push bar Charge handle
Secondary trip coil Button padlock Racking in/out handle
AC/DC UVT coil rectifier Position switch UVT Time delay controller
UVT coil Locking magnet CTD (Condenser trip device)
Latch checking switch Plug interlock
16I
<< Susol VCB Series
Cradle (H type)
MOC (Mechanism operated cell switch) Earthing switch & Accessaries
TOC (Truck operated cell switch) Key lock for Earthing switch
Shutter padlock Locking magnet for Earthing switch
Temperature sensor Position switch for Earthing switch
Door TM (Temperature monitoring unit)
Emergency ON/OFF button
I 17
Accessories
A variety of accessories for VH-05/15
Breaker
Motor Auxiliary contact wire Door Interlock for withdrawable type
AC/DC coil rectifier Key lock Lifting hook
Trip coil/Closing coil Button cover/Push bar Charge handle
Secondary trip coil Button padlock Racking in/out handle
AC/DC UVT coil rectifier Position switch UVT Time delay controller
UVT coil Locking magnet CTD (Condenser trip device)
Latch checking switch Plug interlock
18I
<< Susol VCB Series
Cradle (H type)
MOC (Mechanism operated cell switch) Earthing switch & Accessaries
TOC (Truck operated cell switch) Key lock for Earthing switch
Shutter padlock Locking magnet for Earthing switch
Temperature sensor Position switch for Earthing switch
Door TM (Temperature monitoring unit)
Emergency ON/OFF button
I 19
External structure of VCB
Back side
20
Breaker ... VH type
❷ ❼ Operation Counter
❹ ❽ TEST/Connect
Position Indicator
❼
❽
Back side
21
Basic functions and interrupting operation
Basic functions
Manual operation
① Manual Charge
a) VL type: operate the charge handle 7-8 times as a fully stroke.
b) VH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more and then
charge will be complete with a click sound.
- When the closing spring is charged fully "CHARGED" is displayed at the charge indicator.
② Manual closing
a) Pressing the ON button the breaker is closed.
b) With the closing of the breaker "ON" is displayed at Close/Trip indicator and "DISCHARGED" at the charge
indicator.
③ Manual trip
a) Pressing the OFF button the breaker is opened.
b) "OFF" is displayed at Close/Trip indicator.
Electric operation
① Electric charge
The breaker is remotely closing with charging of closing spring.
If the breaker trips the closing spring is automatically charged by gear motors.
② Electric closing
Remote closing is operated by the closing coil.
③ Electric trip
Remote trip can be operated by the trip coil or UVT coil.
Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the motor in the
mechanism.
Breaker is closed by closing coil and tripped by trip coil.
These operations are repeated in VCB as shown in the below sequence chart.
Motor
Closing spring
Opening spring
Closing coil
Opening coil
Main contact
Closing time Opening time
22
The interruption of vacuum interrupters
Fixed electrode
Fixed shield
Ceramic
Bellows shield
Bellows
An example of oscillogram obtained through the interrupting test using LC resonant circuit
23
Basic functions and interrupting operation
Arc voltage waveforms and arc image captured during arcing time
24
Standards and certification
Susol VCB has been type tested and obtained certifications according to the latest IEC standard at international testing
laboratory and can be installed and applied at the environment and conditions in accordance with the standard.
● Standard
- IEEE Std C37.09, IEEE Std C37.20.2, ANSI C37.54, ANSI C37.55
25
Types and ordering information
VL-05/15
Breaker
VL 15 H 32 A 20
Basic model name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
UVL Susol VCB 05 4.76 P Fixed 25 25 A 150mm 12 1200A
15 15 H H type drawout (for MESG) 32 31.5 B 210mm 20 2000A
* - In case of 1200A VCB, only 150mm is applicable.
- In case of 2000A VCB, only 210mm is applicable.
M1 C1 T1 SB2 U1 A 14 7
Motor control voltage Trip coil voltage UVT Other accessories Note)
M0 motor none T0 Trip Coil none U0 UVT none A1 Secondary Trip coil
M1 DC 110V T1 DC 110V U1 DC 110V A2 Secondary Trip Coil with TCS Contact
M2 DC200~250V T2 DC200~250V U2 DC200~250V A3 Position s/w (Test: 1a1b,Connect: 2b)
M3 DC 125V T3 DC 125V U3 DC 125V A4 Position s/w (Test: 2a,Connect: 2a)
M4 DC 24V~30V T4 DC 24V~30V U4 DC 24V~30V A5 Position s/w (Test: 1a1b,Connect: 1a1b)
M5 AC 48V~60V T5 AC 48V~60V U5 AC 48V~60V A7 Keylock
M6 AC 48V T6 AC 48V U6 AC 48V A8 Button Padlock
M7 AC 100V~130V T7 AC 100V~130V U7 AC 100V~130V A9 Button cover
M8 AC 200V~250V T8 AC 200V~250V U8 AC 200V~250V AA Lead Wire
AB User Plug(Part)
AC Plug Interlock
Closing coil voltage Connector and wire
AD Padlock(H type)
C0 Without closing coil SA2 A type connector, 4a4b
AE MOC
C1 DC 110V SA4 A type connector, 10a10b
Note) Standard AV T operated coil 1A
C2 DC200~250V SB2 B type connector, 4a4b
1. In the case of selecting accessories such as
A1(Secondary coil), A4(position S/W 2a2a),
AW T operated coil 5A
C3 DC 125V SA4 B type connector, 10a10b
A7(key lock), A147 is type name in the ordering.
2. Unable to select A1(Secondary Trip Coil), C4 DC 24V~30V
U1~U8(UVT) simultaneously.
3. A3(Position S/W 1a3b), A4(Position S/W 2a2b) C5 DC 48V~60V
and A5(Position S/W 2a2b) can not be selected
simultaneously. C6 AC 48V
4. A8(Button Padlock) and A9(Button Cover) can not
be selected simultaneously.
C7 AC 100V~130V
5. When A1(Secondary Trip Coil) is selected the C8 AC 200V~250V
maximum available auxiliary contacts are 9a9b.
6. When A2(Secondary Trip Coil with TCS Contact)
is selected the maximum available auxiliary contacts are 4a3b, 9a8b.
7. The flame retardant wire is applicable to auxiliary contacts 4a4b, not to 10a10b.
8. Locking magnet of breaker use the same control power supply as motor.
9. In case of UL Type, AC(Plug Interlock), AD(Padlock(H type)) and AE(MOC) are
included as standard.
26
Cradle
VCL 15 H 32 A 20 A 14 7
Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A)
Susol VCB 05 4.76 25 25 12 1200A
UVCL
Cradle 15 15 32 31.5 20 2000A
* In case of 1200A VCB, only 150mm is applicable, and position S/W(6a6b)
the phase distance of 2000A VCB is only 210mm.
A5 ES(Earthing Switch) with Keylock
Ha has A, B, M and N type
- A type : 1 50mm phase distance, it is impossible to use A6 ES with Locking magnet: DC110V
busing CT
- M type : 150mm
phase distance, it is possible to use A7 ES with Locking magnet: DC220V
busing CT
- B type : 2 10mm phase distance, it is impossible to use A8 ES with Locking magnet: DC125V
busing CT
- N type : 2 10mm phase distance, it is impossible to use A9 ES with Locking magnet: DC24V
busing CT
Hb has A, B, and N type AA ES with Locking magnet: DC48V
- A type : 1 50mm phase distance, only 1200A VCB has
A type AB ES with Locking magnet: AC48V
- B type : 2 10mm phase distance. Using 3 busing CTs.
It is available in case of 2000A only AC ES with Locking magnet: AC110V
- N type : 2 10mm phase distance. Using 6 busing CTs.
It is available in case of 2000A only AD ES with Locking magnet: AC220V
AE Shutter padlock
AF TOC
AG MOC
AH Door
AJ Door Interlock
Note) 1. Ha type cradle cannot use a door and door options. You can use a door for Hb type cradle only.
2. AJ and AK can not be selected without door(AH). AK Door Emergency Push Button
3. TM(Temperature Monitoring) should be used with AL(Temperature Sensor).
4. H type lead wire(AM, AN) is required for cradle in case of using H type breaker. AM H type¸ Lead Wire 4a4b (Standard)
5. If H type breaker options A8 (Button Padlock) and A9 (Button Cover) are selected the cradle option
AK (Door Emergency Push Button) is not available. AN H type¸ Lead Wire 10a10b (Standard)
6. Earthing Switch (A1) includes Keylock (A5) as standard.
7. H type breaker includes options such as AE (Shutter padlock), AE (TOC, AG (MOC), AH (Door),
AJ (Door Interlock) as standard.
27
Types and ordering information
VH-27
Breaker
VH 27 H 25 E 12
Basic model name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
VH Susol VCB 27 27 H type drawout 25 25 E 300mm 12 1200A
H
(for MCSG)
VH-06H50B32 M1 C1 T1 SB2 U1 A 14 7
28
Cradle
VCL 27 H 25 E 12 A 14 7
Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A)
Susol VCB 27 27 25 25 12 1200A
VCL
Cradle
29
Types and ordering information
VH-05/15
Breaker
VH 15 H 50 C 30
Basic model name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
VH Susol VCB 05 4.76 H MCSG type drawout 40 40 C 254mm 12 1200A
15 15 50 50 20 2000A
Note) 4.76kV is for 50kA 30 3000A
VH-15H50C30 M3 C3 T3 SC1 U0 N 12 3 4 5
Cradle
VCL 15 H 50 C 30 N 12 3 4 5
Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A)
Susol VCB 05 4.76 40 40 12 1200A
VCL
Cradle 15 15 50 50 20 2000A
Note) 4.76kV is for 50kA 30 3000A
30
Ratings - 4.76/15kV 25/31.5kA 1200/2000A
VL-05/15
Rated current Ir (A) 1200 2000 1200 2000 1200 2000 1200 2000
Pole distance (mm) 150 210 150 210 150 210 150 210
Weight(H, Cradle) (kg) 430 510 430 510 430 510 430 510
Weight(H, Circuit Cradle) (kg) 115 140 115 140 115 140 115 140
Rated interrupting capacity (MVA) 207 260 207 260 650 820 650 820
Rated Closing Control voltage (V) DC 24~30V, DC 48~60V, DC110V, DC125V, DC220V, AC 48V, AC100~130V, AC220~250V
Rated Trip Control voltage (V) DC 24~30V, DC 48~60V, DC110V, DC125V, DC220V, AC 48V, AC100~130V, AC220~250V
Draw-out H Type
Applicable standard IEEE Std C37.09, IEEE Std C37.20.2, ANSI C37.54, ANSI C37.55
31
Ratings - 27kV 25kA 1200/2000A
VH-27
Class Class 1
32
Ratings - 4.76/15kV 40/50kA 1200/2000/3000A
VH-05/15
Rated normal current Ir (A) 1200 2000 3300 1200 2000 3000
Weight Breaker (MESG, MCSG) (kg) 230 230 265 230 230 265
Cradle (MESG, MCSG) (kg) 248 248 286 248 248 286
33
Accessory
Mounting Supplied as
Type Accessory Remarks page
Position VL VH
A3 Position S/W(Test: 1a1b, Connect: 2b) Option Option Attached at the factory 43
A4 Position S/W(Test: 2a, Connect: 2a) Option Option Attached at the factory 43
A5 Position S/W(Test: 1a1b, Connect: 1a1b) Option Option Attached at the factory 43
AA Lead Wire: A/B type connector Option Option Attached at the factory 48
* ●: Basic Installation
34
Mounting Supplied as
Type Accessory Remarks page
Position VL VH
ES(Earthing Switch)
A2 Option Option Attached at the factory 57
with Position Switch(2a2b)
ES(Earthing Switch)
A4 Option Option Attached at the factory 57
with Position Switch(6a6b)
ES(Earthing Switch)
A5 Option Option Attached at the factory 58
with Keylock
ES(Earthing Switch)
A6 Option Option Attached at the factory 58
with Locking magnet: DC110V
ES(Earthing Switch)
A7 Option Option Attached at the factory 58
with Locking magnet: DC220V
ES(Earthing Switch)
A8 Option Option Attached at the factory 58
with Locking magnet: DC125V
ES(Earthing Switch)
A9 Option Option Attached at the factory 58
with Locking magnet: DC24V
ES(Earthing Switch)
AA Option Option Attached at the factory 58
with Locking magnet: DC48V
ES(Earthing Switch)
AB Option Option Attached at the factory 58
Cradle with Locking magnet: AC48V
ES(Earthing Switch)
AC Option Option Attached at the factory 58
with Locking magnet: AC110V
ES(Earthing Switch)
AD Option Option Attached at the factory 58
with Locking magnet: AC220V
AM Type H Lead Wire 4a4b (Normal cable) Option Option Attached at the factory 63
35
Accessory
VL type Motor
Charge completion
contact
Motor
VL type
DC 24~
DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Load current (A) ≤5 ≤3 ≤1 ≤ 1 ≤ 0.5 ≤ 3 ≤ 1 ≤ 0.5
Starting current (A) 5 times of load current
Charge time Within 5 sec.
Note) Rated operation and control voltage range, see page 40.
VH type
Motor
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Load current (A) ≤6 ≤3 ≤3 ≤ 2.6 ≤6 ≤3 ≤ 2.6
Starting current (A) ≤ 30 ≤ 20 ≤ 20 ≤ 17 ≤ 30 ≤ 20 ≤ 17
Charge time Within 12 sec.
Note) Rated operation and control voltage range, see page 40.
36
Closing Coil: C Installed inside of a breaker as standard
VL type
ᆞIt is a control device which closes a circuit
breaker, when applying voltage continuously or
instantaneously over 200ms to the coil control
terminals.
Closing coil
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) ≤5
Note) Rated operation and control voltage range, see page 40.
VH type
ᆞIt is a control device which closes a circuit
breaker, when applying voltage continuously
about 45ms to the coil control terminals.
Electrical pumping preventing circuit is built in.
Closing coil
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤ 3 ≤ 3 ≤ 2.5 ≤8 ≤ 3 ≤ 2.5
Note) Rated operation and control voltage range, see page 40.
37
Accessory
VL type
ᆞIt is a control device which trips a circuit breaker
from remote place, when applying voltage
continuously or instantaneously over 35ms to
coil control terminals.
ᆞWhen UVT coil is installed, its location is
changed.
Trip coil
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) ≤5
Note) Rated operation and control voltage range, see page 40.
VH type
ᆞIt is a control device which trips a circuit
breaker, when applying voltage continuously or
instantaneausly over 35ms to the coil control
terminals.
Trip coil
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤3 ≤3 ≤ 2.5 ≤8 ≤3 ≤ 2.5
Note) Rated operation and control voltage range, see page 40 .
38
Secondary Trip Coil: A1 Installed inside of a breaker as an option
VL type
ᆞIt is a control device which trips a circuit breaker
doubly from the outside. If the trip coil (T ) fails,
it can trip a circuit breaker safely.
ᆞTrip coil: Install it at existing location.
ᆞSecondary trip coil: Install it on the right side of
the trip coil.
ᆞIt is not available with UVT coil when installing
secondary trip coil.
Secondary
Trip coil
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
Power consumption (inrush, W) 200
Power consumption (steady, W) ≤5
VH type
ᆞIt is a control device which trips a circuit breaker
doubly from the outside. If the trip coil (T) fails, it
can trip a circuit breaker safely.
ᆞIt is not available with UVT coil when installing
secondary trip coil.
Secondary
Trip coil
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤ 3 ≤ 3 ≤ 2.5 ≤8 ≤ 3 ≤ 2.5
39
Accessory
Susol VCB
Item Remarks
VL: 7.2kV 8/12.5kA VL: 20/25kA VH
AC 85~110% 85~110% 85~110%
Motor
DC 75~110% 85~110% 85~110%
AC 85~110% 85~110% 85~110%
Closing
DC 75~125% 85~110% 85~110%
AC 60~125% 85~110% 85~110%
Trip
DC 60~125% 70~110% 70~110%
IEC62271-100 (2008)
Applied standards IEC62271-100 (2008) IEC62271-100 (2008)
KSC4611
VL type : AV, AW
Current Trip Coil
ᆞThis trip coil uses the output of the CT as its
control power source and is used with over
current relay in combination. Two current trip
coils are supplied.
ᆞCoil impedance(Z) is like below
- 1A: 160Ω or less, Operating current AC 1A (AV)
- 5A: 6Ω or less, Operating current is AC 5A (AW)
ᆞCT must be installed at load side.
If it is installed at bus side there is the danger of
malfunction or damage to CT.
ᆞDon’t disconnect the control power connector on
main power is live condition at connect position.
Otherwise there is the danger of malfunction or
damage to CT.
* CT is recommended to use 15VA 5P10 and more.
40
Auxiliary Contact: SA Installed inside of a breaker as an option
VL type
Auxiliary contact
ᆞIt is a contact used to monitor ON/OFF status of
a breaker from remote place.
ᆞThe auxiliary contacts supplied as standard
configuration is 4a4b. 10a10b is also available
on request.
ᆞFor 7.2kV 8/12.5kA VCB standard configuration
is 2a2b. 4a4b and 6a6b are optional.
VH type
Auxiliary contact
VL/VH Type
Item Resistive load (A) Inductive load (A) Remarks
250V 10 5
AC
125V 10 5
Contact
250V 10 5 For all models
configuration
DC 125V 10 5
30V 10 5
41
Accessory
VL type VH type
VL type
ᆞIt is installed inside of a breaker to trip when the main power or control power voltage drops below certain value.
Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil and UVT
time delay controller.
ᆞThe closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT.
To close the circuit breaker, 65~85% of rated voltage should be applied.
ᆞUVT and secondary trip coil will not be selected together.
VL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130 250V
VH Type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V
42
Position Switch: A3, A4, A5 Installed inside of a breaker as an option
VL VH
ᆞThis switch is used to indicate the breaker position (CONNECT, TEST), and contact configuration
is 2a2a or 2a2b, 1a3b.
VL VH
Position
switch
Position
switch
Contact configuration
1 3 5 7 1 3 5 7 1 3 5 7
2 4 6 8 2 4 6 8 2 4 6 8
1a1b(TEST) 2b(SERVICE) 2a(TEST) 2a(SERVICE) 1a1b(TEST) 1a1b(SERVICE)
43
Accessory
VH type
ᆞThis switch works in conjunction with the
mechanism of the breaker. It checks if the
breaker is ready to be closed.
ᆞWhen the mechanism is OFF and the closing
spring is at charged status the switch becomes
"ON", which means the mechanism is ready to
be closed.
ᆞIf the latch is not in a proper position the switch
prevents the breaker from closing.
In case of VH type it is connected internally in
series with the closing coil.
Latch checking
switch
VL/VH type
ᆞIt displays the total number of ON/OFF
operations of a breaker.
44
Keylock: A7 Installed inside of a breaker as an option
VL type
ᆞThe key is to unlock the locking device first to
close the breaker electrically and mechanically.
*How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked status.
- Pushing "OFF" switch of a breaker turn the key
counter-clockwise to the locked position and pull
it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.
- Insert the key and turn clockwise and then the
breaker can be closed electrically and
mechanically.
Keylock
VH type
*How to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked status.
- Trip the breaker first and then turn the key
counter-clockwise to the locked position and pull
it out.
- It is not possible to close the breaker electrically
and mechanically in the locked position.
Keylock
45
Accessory
VL type
ᆞIt is to prevent manual operation of ON/OFF
button due to user’s wrong handling.
ᆞIt is not possible to handle ON/OFF operation
under the “Button lock” status.
Button Padlock
VH type
Button Padlock
46
Button Cover: A9 Installed outside of a breaker as an option
VL type
ᆞIt is a protection cover to prevent an accident
due to unintended operation of ON/OFF button.
ᆞUse the push-bar to operate the ON/OFF
button.
Push Bar
Button Cover
VH type
Push Bar
Button Cover
47
Accessory
VL/VH type
Lead wire
ᆞIt is to connect with the control circuit of a
breaker from outside. (supply wire length: 2m)
ᆞA type connector is supplied for P/E/F/G type of
VL VCB.
A type connector
ᆞB type connector is supplied for P type of VH
VCB.
ᆞIn case of H type breaker of VL and VH models
the Lead wire is installed in the cradle when
supplied. B type connector
Cradle type P E F G H
VCB model
Enclosed in the breaker
VL Enclosed in the breaker
Installed in the cradle (option)
VL/VH type
ᆞIt is connector to connect with the connector installed in the breaker. (supply connectors and terminal only for lead wire)
ᆞType of connector is depends on the type of connector installed in the breaker- A or B.
48
Plug interlock: AC Installed inside of a breaker as an option
VL/VH type
Plug interlock
ᆞIt checks if the control power connector on the
cradle (H type) is connected with the connecting
terminal of the breaker before the proceeding of
draw-in or out.
ᆞIt is not allowed to seperate the control power
connector from the breaker in the position of
draw-in /out or CONNECT, but TEST position.
VL/VH type
ᆞWith this door options for H type cradle draw- in/
out is allowed only when the door is closed.
ᆞIf draw-in /out is necessary when the door is
open, use the operation lever put in the slot of
the breaker handle.
Insert it into the hole in the bottom of door
interlock.
ᆞPadlock is also optional, which can lock to
prevents the draw-in/out of the breaker in the
position of TEST and CONNECT.
Door interlock
49
Accessory
VL type
ᆞIt must be installed in the breaker to drive the
MOC installed in H type cradle.
ᆞMOC, Mechanically operated cell switch is the
device to indicates the Closed/Trip status of
VCB in 'CONNECT' position only.
ᆞThis MOC drive device in the breaker should be
installed when MOC in the cradle is used.
MOC
VH type
MOC
50
Locking magnet: AF Installed inside of a breaker as an option
VL type
ᆞIt allows the drawing-in of the breaker in the
TEST position under the condition that the
control power connector on the cradle (H type)
is connected with the connecting terminal of the
breaker and the power is supplied.
ᆞDuring the drawing-in or in the CONNECT
position draw-in/out is allowed without supplying
power.
* Control power rating is the same as that of a motor.
Locking
magnet
VH type
Locking magnet
51
Accessory
VL type
ᆞDevice for monitoring the functions of the trip
coils.
ᆞSupplied as standard for VL model and optional
for VH model.
ᆞTo monitor the trip coils connect its terminals
with the trip coil monitoring relay as shown on
the circuit diagram.
- If the trip coil is normal: closed-circuit
consisting
- If the trip coil is damaged: open circuit
1) T erminals A5 and A6 monitor the trip coils in
closed position of the breaker.
2) T erminal A6 and aux. contact terminal 34
monitor the trip coils in trip position of the
breaker.
ᆞCoil Test Unit is opional, which enable
monitoring the coils by connecting in parallel
with the trip coil operation switch.
ᆞIn case Secondary Trip Coil Monitoring contact,
Trip Coil T1,T2,T3 are available.
VH type
Secondary trip coil with TCM Contact
52
Coil Test Unit: CTU Installed outside of a breaker as an option
ᆞWhen no current flows through the coil it gives the test current which does not cause the coil to operate to check
whether the coil is disconnected or not.
- If the test current flows normally: coil normal
- If the test current does not flow through: coil disconnected
※ As it is connected in parallel with the control part of the coil the normal operation of the coil is not affected.
※ Monitoring of the running coils is not possible.
※ One test unit can monitor up to two coils.
Input voltage
AC/DC 75~264V
Fail 1
24~250V
(AC/DC) Alarm 1
Shunt 1
Coil
Test
Fail 2
Unit
24~250V
(AC/DC) Alarm 2
Shunt 2
CTU CTU
Input voltage Input voltage
Coil drive power(+) (+) (+)
1 2
Coil drive power
5 Fail (LED)
Fail (RELAY)
7
Coil Alarm (LED)
Coil test current Alarm (RELAY)
Coil Test Unit
Coil drive power(-)
53
Accessory
Ratings
Ratings Specification ᆞIt gets a circuit breaker tripped electrically within
regular time when control power supply is
Model CB - T1 CB - T2 broken down and is used with Shunt coil, SHT.
Rated input voltage (V) AC 100/110 AC 200/220 In case there is no DC power, It can be used as
the rectifier which supplies DC power to a circuit
Frequency (Hz) 50/60 50/60
breaker by rectifying AC power.
Rated charge voltage (V) 140/155 280/310
ᆞTripping within 30 seconds on the power failure
Charging time Within 10sec. Within 10sec. is possible. However after that automatic trip
Trip possible time Within 30sec. Within 30sec. circuit must be configured separately in the
switchgear.
Range of Input voltage 85%~110% 85%~110%
Condenser capacity (μF) 1,000 560
(Mounting hole)
Circuit diagram
54
UVT Time delay: UDC Installed outside of a breaker as an option
ᆞUVT time delay, UDC is to delay the trip signal from UVT.
Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the breaker
even in the the momentary power failure.
ᆞUDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure.
ᆞIt can be installed on the cradle or inside of the switchgear.
ᆞUDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker.
b contact is closed at normal state and a contact is closed at trip.
1. Characteristics
48~60 48
100~130 100~130 0.65~0.85 Vn 0.4~0.65 Vn 200 ≤ 5 0.5, 1, 1.5, 3
200~250 200~250
- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)
Rated voltage (V) Rated current (A), Resistive load Max. switching voltage (A) Max. switching current (A)
24V DC ≤ 12
110V DC
120V AC ≤ 12 15
250V AC
250V AC ≤ 10
3. Wiring diagram
Delayed
trip signal
5 7
14 16
18(a)
Operating UVT Delay
UVT output 19(c)
18 19 20 contact 20(b) Controllor
a c b
0.5
1
Signal for 1.5
tripping 14 16
3
DC48~60V
AC48
[sec]
Instantaneous
5 7 trip signal
Time Delay for UVT
D1
D2
UVT
55
Accessory
monitoring unit: TM
VL/VH type
ᆞTemperature Alarm Unit displays the input
temperature detected through the temperature
sensor installed in H-type cradle.
Temperature
ᆞTemperature sensor can be installed up to three Sensor
(R, S, T phase).
ᆞTemperature Alarm Unit converts the
temperatures detected from the senser in the
cradle and displays the maximum value and can
transmit it throug communication.
ᆞIf the input temperature is above standard it
may cause alarm.
Temperature Alarm Unit supports Modbus/
RS-485 communication and contact us Profibus-
DP communication.
56
Earthing Switch: A1 Built-in a cradle as an option
VL/VH type
ᆞFor the safety during the maintenance of
switchgear in the position of TEST/Drawout
discharge the charging current in the load side
of a VCB with this earthing switch.
It is available onlt for H type drawout breaker.
Earthing
Switch
ᆞIn case of using earthing switch it can be added to indicate the ON / OFF
status of the earthing switch.
57
Accessory
ᆞIn case of using earthing switch it can be added for two types
of interlocking.
1) Interlock to keep opening
2) Interlock to keep earthing
ᆞIn case of using earthing switch it can be added to prevent the earthing
switch from opening or earthing before it is energized.
ᆞVerify if the locking magnet is energized before opening or earthing the
earthing switch.
ᆞControl voltage
- DC 24V / DC 48V / DC 110V / DC 125V / DC 220V
- AC 48V / AC 110V / AC 220V
58
Shutter padlock: AE Built-in a cradle as an option
VL/VH type
ᆞIt is the locking device to lock the primary and
secondary shutter in closed state for safety
while the breaker is drawn out for maintenance.
ᆞWhen the breaker is drawn in, the shutter is
automatically opened.
ᆞThere is a hole for padlock to lock the shutter.
ᆞIt can be applied only to H type cradle.
Shutter
padlock
VL/VH type
ᆞThis auxiliary switch is used to indicate the
'CONNECT' position of VCB. It is installed in the
bottom of a H type cradle and operated by the
frame of a breaker.
VL type
ᆞTOC is consisted of 4 cell switches with
changeover contacts as below diagram.
Circuit diagram
121 122 124 125 127 128 130 131
VH Type
TOC
59
Accessory
(MOC: AG)
VL/VH type
ᆞThis auxiliary switch is used to indicate the
Close/Trip of VCB. It is operated mechanically
at the CONNECT position and installed in the
bottom of a H type cradle and operated by the
frame of a breaker.
ᆞMOC is consisted of 4 cell switches with
changeover contacts as below diagram.
VL type
Circuit diagram
102 101 105 104 108 107 111 110
MOC
VH Type
a Contact: 101-103, 104-106, 107-109, 110-112,
b Contact: 102-103, 105-106, 108-109, 111-112
VL/VH type
ᆞIt is outside door for H type cradle.
ᆞAccessories are available for the door.
Door
60
Door Interlock: AJ Built-in a cradle as an option
VL/VH type
ᆞWhen the Door is installed to H type cradle, this
door interlock prevents opening it at CONNECT
position.
VL/VH type
ᆞIt is used to enable the Close/Trip of the breaker
manually from outside of the door installed to H
type cradle during an emergency.
ᆞPush the ON/OFF button by ON/OFF handle
supplied seperately.
61
Accessory
VL/VH type
ᆞThis sensor is used to detect the temperature in
H-type cradle combined with Temperature
monitoring unit. Temperature
Sensor
ᆞIt can be installed up to three (R, S, T phase).
Type Cradle Racking in/out handle Charging handle Operating handle for earthing S/W
55223172407
A
VL Not required
55223172403
B
H
K 55223172405 55213143006
C
VH
55223172406
D
A B
C D
62
Type H Cradle Lead Wire: AM~AO Built-in a cradle as an option
VL/VH type
ᆞIn case of H type breaker of VL and VH models
the Lead wire is installed in the cradle when
supplied.
ᆞ4a4b or 10a10b contacts are selectable
according to the auxiliary contact of the breaker.
Flame retardant cable is used for 4a4b.
Lead
Wire
VL/VH type
ᆞIt is supplied with a door for H type cradle as
standard.
ᆞIt can be locked by seperate padlock to prevent
entering the maunal handle.
Door
Padlock
63
Accessory
B If dimension A in Fig. 1 is
less than 120mm B type
pallet can be used.
Width :≤ 550mm In case of more than 120mm
550
Bottom
<Fig 1>
64
Auxiliary switch
Trip coil monitoring contact
Secondary trip coil with TCM Contact
VL-05/15
10a(9a) 10b(9b)
P P P
4a 4b Position switch
<2a(TEST),2a(CONNECT)>
TEST CONNECT
D1 11 22 24 26 28 40 42 44 46 48 60 34 36 38 50 52 54 56 58 70 72 74 1 3 5 7
A1 9 A3 13 A5
Position switch
<1a1b(TEST),1a1b(CONNECT)>
1 3 5 7
LS4 LS5 LS6 LS7
2 4 6 8
M Position switch
<1a1b(TEST),2b(CONNECT)>
Control circuit diagram
C 1 3 5 7
2 4 6 8
A2 10 14 D2 12 23 25 27 29 41 43 45 47 49 61 37 39 51 53 55 57 59 71 73 75 2 4 6 8
A4 A6
N N N
Current Trip Coil(1A,5A) indicating contact
* Above the circuit diagram is based on the “ OPEN” state of the VCB and the closing spring is charged.
* Note 12
Closing Spring Contact(Charge complete indicating contact)
22 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
23
42
43
22
23
A1
A2
A1
A2
Ø : External terminal of the VCB CS : Closing spring charged indication limit switch A
24
25
44
45
24
25
A4
A4
A3
A3
B
52 : Vacuum circuit breaker LS4, LS5 : Position S/W (TEST position)
46
47
26
27
26
27
A5
A5
C
D
9
9
M : Spring charging motor LS6, LS7 : Position S/W (CONNECT position)
48
49
28
29
28
29
40
41
60
61
D1
A6 10 D2
D1
A6 10 D2
/11
/12
/11
/12
TC : Trip coil (SHT)
TC1 : Secondary Trip coil (SHT1)
34
34
TEST : 1a1b TEST : 2a TEST : 1a1b (4a4b)
C : Closing coil (CC) S/W
14
14
13
13
36
37
36
37
56
57
1
2
38
39
58
59
38
39
UVT : Under Voltage Trip A3 A4 A5 A
4
4
3
3
50
51
70
71
50
51
5
6
6
C
52
53
52
53
72
73
7
8
74
75
54
55
In case TC1 is selected and auxiliary switch is 10a10b, Some 'a' contact
(Terminal No.: 40, 41) and 'b' contact (Terminal No.: 54, 55) are not available
5. Secondary Trip Coil Monitoring Contact (Terminal No.: 36)
CTC2 CTC3
In case Secondary Trip Coil TCM Contact is Selected and auxiliary switch is 9a8b, Some 'a' contact
(Terminal No.: 40, 41)and 'b' contact (Terminal No.: 36, 37) are not available.
6. CTC2 - Current Trip Coil (Terminal No.: 13, 14)
CTC3 - Current Trip Coil (Terminal No.: D1, D2)
7. Close and Trip coil is One Pulse type, excluding Trip coil (DC110, 220V) 14 D2
8. In above optional accessories, UVT, CTC and TC1 can not be selected simultaneously.t
9. CTC Ccontrol Circuit
65
66
Trip coil monitoring contact
VH-27
Auxiliary switch Secondary trip coil with TCM Contact Note6)
P P P P 10a 10b
Note2)
Position switch
4a 4b <2a(TEST),2a(SERVICE)>
CS CS TEST SERVICE
A1 9 A3 D1 11 A5 15 22 24 26 28 40 42 44 46 48 60 34 36 38 50 52 54 56 58 70 72 74 1 3 5 7
Position switch
LS2 3 1 LS3 1 3 4 <1a1b(TEST),1a1b(SERVICE)>
Ya
4 2 2 4 6
1 Note5) 1 3* 5 7*
1
LM LS4 LS5 LS6 LS7
Yb
5 2
Note1) 1 2 4* 6 8*
LCS1
2
22 24 26 28 40 42 44 46 48 60 34 36 38 50 52 54 56 58 70 72 74
5 82 6 1 3 5 7
30
52b 52a LS4 LS5 LS6 LS7 Position switch
M
6 31 2
<1a1b(TEST), 2b(SERVICE)>
83 6' 4 6 8
23 25 27 29 41 43 45 47 49 61 35 37 39 51 53 55 57 59 71 73 75
3 7
1 3* 5* 7*
C Y Note4) LS4 LS5 LS6 LS7
1 Note3)
UVT TC1 TC
A2 10 A4 D2 12 A6 16 23 25 27 29 41 43 45 47 49 61 37 39 51 53 55 57 59 71 73 75 2 4 6 8
N N N N
charge completion indicating contact
<Connecting terminal arrangement>
Note) 1. Above circuit diagram is based on 'OFF' status of VCB and closing spring is charged.
2. TC1(Option) - Secondary Trip Coil(Spare trip coil, terminal No.11, 12)
3. Please follow direction of P,N marked in the above circuit diagram.
67
Dimensions - VL type
589
642
359.5
492 301 Stroke:220
310
Ø35
691
643.5
300
185
96
Ø19.5
41.5
36
503 7 284 45
53 338
436
469
642
301 Stroke:220
310
Ø79
691
666.5
300
185
96
Ø19.5
41.5
653 7 284
36
53 338
436
469
68
VL-05/15
4-Ø13
152 40
178
212
10
M12
509
(Earthing hole)
281
96.5
46.8
450 212
295
670
650
10
320
470 315 156
589 523.5
753
210 210
40 80
4-Ø14
40
4-Ø13
178
212
152
10
M12
523.5
(Earthing
281
hole)
46.8
96.5
600 212
295
670
650
20
320
69
Dimensions - VL type
152 40
178
212
10
4-Ø13 M12
509
(Earthing hole)
281
96.5
46.8
280
450 212
295
690
670
670
650
556.5
10
320
470 315 156
589 523.5
606.5
4-Ø13
40
178
212
10
M12
(Earthing
523.5
hole)
152
281
96.5
46.8
455
600 212
295
690
650
670
20
320
70
VL-05/15
150 150
550
560
562
Ø35
155 155 32
1277 188
1570
600 25 560
10-Ø11 4-Ø10
(Earthing hole) (Mounting hole)
8-M8
65
240
315
240
310
240
1140
330
315
240
485
270
315
240
80
30
20
25 860 50
560
2
Ø1
Connecting busbar method
(with earthing switch)
25 Busbar : 10t×50, (2 sheets) <1200A>
83.3
4
2-Ø12 Ø1
10.0
TUBE
25
Detail A
83.3 20
2-M8(DP:18)
43.4
Detail B
Scale 2/15
See Detail B
Section XSEC-XSEC
71
Dimensions - VL type
150 150
550
Ø35
725 184.7
1017.7
420
400
310
1140
400
400
485
212.5
212.5
8-Ø11 65 285 150 150 261.7
(Mounting
hole)
550
2
Ø1
Connecting busbar method
(with earthing switch)
25 Busbar : 10t×50, (2 sheets) <1200A>
83.3
4
2-Ø12 Ø1
10.0
TUBE
25
Detail A
87.3 20
2-M8(DP:18)
43.4
Detail B
Scale 1/5
See Detail B
72
VL-05/15
150 150
560
556
550
Ø35
420 220 220 155 155 32
1277 178
1570
40
60
(Mounting hole)
8-M8
240
125
220
10-M8
240
315
350
310
240
315
370
240
1980
315
240
240
1245
272.5
330
175 272.5
270
130
980 2-M8
560
2
Ø1 Connecting busbar method
(with earthing switch)
20 Busbar : 10t×50, (2 sheets) <1200A>
83.3
4
2-Ø12 Ø1
10.0
TUBE
25
Detail A
83.3 20
2-M8(DP:18)
43.4
See Detail B
Detail B
Scale 2/15
Section XSEC-XSEC
73
Dimensions - VL type
30
210
720
700
210
Ø79
155 38
1128 197.2
1420.2
720
750 710
4-Ø10
40
Ø11 (Mounting hole)
55
(Mounting hole)
8-M8
240
240
310
240
1140
330
475
485
270
315
80
4-M8
25
30
25 860 50
2
Ø1
Connecting busbar method
(with earthing switch)
Busbar : 10t×100, (2 sheets)
20
74.1 30
35
4
Ø1
2-Ø12
10.0
TUBE
30
30
74.1 20
2-M8(DP:18)
63.4
Detail A
See Detail A
74
VL-05/15
35
210
700
210
Ø79
725 197.2
1017.2
400
420
310
1140
400
400
485
212.5
2
Ø1
Connecting busbar method
(with earthing switch)
Busbar : 10t×100, (2 sheets)
20
74.1 30
32
4
Ø1
10.0
2-Ø12
TUBE
30
30
73.8 20
2-M8(DP:18)
63.4
Detail C
See Detail C Scale 1/5
Section A-A
75
Dimensions - VL type
210 210
706
700
720
30
30
Upper Terminal Lower Terminal
2-M16
740 (For assembly of
Ø79
Ø79
1110 lifting hook)
1128
40
(Mounting hole)
82 158 240 62
8-M8
597
350
310
240
370
133 240
470
1980
240
4-M8
1245
175 272.5 272.5
330
775
130 270
720
980 2-M8
700
2
Ø1
Connecting busbar method
(with earthing switch)
Busbar : 10t×100, (2 sheets)
20
74.1 30
35
4
Ø1
2-Ø12
10.0
TUBE
30
30
74.1 20
2-M8(DP:18)
63.4
See Detail C
Detail C
Scale 1/10
76
VL-05/15
30
210 210
720
706
700
2-M16
740
Ø79
(For assembly of lifting hook)
1128 197.2
1420.2
40
123 62
240
8-M8
240
350
310
240
370
490
1980
315
240
4-M8
1245
175 272.2 272.2
330
775
130 270
980
2-M8
710
2
Ø1
Connecting busbar method
(with earthing switch)
Busbar : 10t×100, (2 sheets)
20
74.1 30
35
4
Ø1
2-Ø12
10.0
TUBE
30
30
74.1 20
2-M8(DP:18)
63.4
See Detail C
Detail C
Scale 1/10
Section A-A
77
27kV, 25kA, 1200/2000A
Fixed (P type)
(Mounting hole)
1042.5
551.5
(Earthing hole)
294.1
220.1
115.5
Withdrawable (H type unit)
Racking in/out
Stroke:440
78
VH-27
5 11 4 466
14
300
6. 5 40
01. 5
300
15
1
16. 5
1 00 505
48
<Detail dimension for bushing part>
00
400
15 0
855
03. 8
50.5
61 563 463
1 6. 7 140.5
46
740
56.1
10
846
873.4
30 40 87.5 30
14
60
7
53.5
Detail A
See Detail A
53.5
03. 8
604
104
79
Dimensions - VH type
195 195
11.5 722
698
101
54
360
815
359
696 53 532 60
10
648
718
171 171
11.5 722
698
117
79
360
815
359
696 53 532 60
10
658
728
80
VH-05/15
254
2-M12
745.4
776
(DP:25)
54
254
36
540 350 4- 14 117 123
(Mounting hole)
287.5 710
250 12- 14
(Mounting hole)
370
360
1035
212.8
370
449
212.5
165.5
89
816 1019.3 6.7 14 233
1156.8 (Earting hole)
81
Dimensions - VH type
254
4-M12
745.4
776
(DP:25)
79
254
50
540 350 4- 14 117 123 50
(Mounting hole)
287.5 710
250 12- 14
(Mounting hole)
370
360
1035
212.8
370
449
212.5
165.5
89
816 1019.3 6.7 14 233
1156.8 (Earting hole)
82
VH-05/15
254 254
11.5 722
698
101
54
815
719
696 53 532 60
10
648
718
Earthing truck(Lower)
254 254
11.5 722
698
101
54
815
359
696 53 532 60
648
10
718
83
Dimensions - VH type VH-05/15
11.5 722
698
54
101
360
815
359
696 53 532 60
648.3
10
718
11.5 722
698
117
79
360
815
359
696 53 532 60
658
10
728
84
Technical data
Number[ops.]
Number[ops.]
85
Technical data
Number[ops.]
86
Standard Use Environment for Susol VCB
The operation characteristic of Vacuum Circuit Breaker such as insulation and endurance is often influenced
largely by external environment and thus should be applied appropriately with conditions of the place where
it is used taken into consideration.
The following values are the limits have been set in accordance with IEC 62271-100 (IEC 62271-1)
Ambient Temperature
- maximum temperature: +40℃
- 24-hour average maximum temperature: +35℃
- minimum temperature: -5℃
Altitude
- 1000m or less above sea level
Relative Humidity
- 24 hours average value: 95% or less
- One month average: 90% or less
87
Technical data
The circuit breaker is designed for use in standard use environment specified in Section 2. 1 of IEC62271-1.
Concerning the special use environments as below the special use conditions are
required to be considered, thus please contact us in advance.
- where altitude and ambient temperature are out of standard use environment.(-40℃)
- where a strong sea breeze blows
- when usually used in a humid place
- where a lot of steam or oil steam exists
- where explosive, flammable and other harmful gases might permeate the breaker
- In a dusty place
- where abnormal vibration or shock exists
- where a lot of ice and snow exist
- other special conditions
70 36 170
50(65) 24 125
38 17.5 95
28(42) 12 75(82)
20 7.2 60
Ud [kV/1min] Ur[kV] Up [kV/1.2 50 ]
Power Frequency Impulse Withstand Voltage
Withstand Voltage
88
Special Use Environment
Correction parameter 1
1.45
1.4
1.35
1.3
1.25
1.2
1.15
1.1
1.05
1
1000 1500 2000 2500 3000 3500 4000
Altitude (m)
<Fig.1 > withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)
1
Correction parameter 2
0.95
0.9
0.85
0.8
0.75
0.7
0.65
0.6
0.55
0.5
1000 1500 2000 2500 3000 3500 4000
Altitude (m)
<Fig.2 > withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)
Ex) Selecting a breaker to be used in a place of 2500m above sea level with a rated voltage 7.2kV
(correction parameter 1 applied)
- correction parameter at 2500m is 1.2
- criteria of withstand voltage by rated voltage:
Power Frequency Withstand Voltage (Ud) = 20kV, Impulse Withstand Voltage (Up) = 60kV
- requirements withstand voltage criteria:
Power Frequency Withstand Voltage (Ud) = 20×1.2 = 24kV, Impulse Withstand Voltage (Up) = 72kV
Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage.
Ex) To apply a breaker with a rated voltage 12kV to the place of 2,500m above sea level
(correction parameter 2 applied)
- correction parameter at 2500m is 0.825
- dielectric strength of VCB : Power Frequency Withstand Voltage (Ud) = 28×0.825 = 23.1kV,
Impulse Withstand Voltage (Up) = 75×0.825 = 62kV/1.2×50 ㎲
Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.
89
Technical data
Ex) The calculation of the applicable load current value when a breaker with rated current
2000A is used at 55 ℃ ambient temperature
Ia = 2000×((105-55)/65)1/2 = 2000×0.87 = 1754A
90
• For your safety, please read user's manual thoroughly before operating.
• Contact the nearest authorized service facility for examination, repair, or adjustment.
• Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions • Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Overseas Branches
•LSIS Co.,Ltd. Rep.Office, Vietnam
Gema Dept Tower 18F,6 Le Thanh Ton,District 1,HCM,Vietnam
Tel: 84-8-3823-7890 / E-mail: hwyim@lsis.com
•LSIS Moscow Office, Russia
Specifications in this catalog are subject to change without notice due to 123610,Krasnopresnenskaya,nab,12,building1,office No.1005,Moscow,Russia
continuous product development and improvement. Tel: 7-495-258-1466,1467 / Fax: 7-495-258-1466,1467 / E-mail: jdpark1@lsis.com
2016. 03 Susol VCB ANSI Type (E) 2016.01/(01) 2016. 03 Printed in Korea Staffcom