Cautions
R e a d th i s in s truc t ion m a nu a l c are fu lly be for e c o m m e n c i n g o p e r a t i o n o r u n d e r t a k i n g
i n sp ec ti on o f th e M o de l M W P Ex p a n s i on V al v e. K ee p t h i s m an u al in a c on v e n i en t,
e a s i ly - ac c e ss i b l e lo c a t io n n e ar th e ex p an s ion v a lv e .
“WARNING” indicates a hazardous situation in which failure to observe
WARNING all safety precautions may lead to death or injury and major damage
to the system.
“CAUTION” indicates a hazardous situation in which failure to observe
CAUTION all safety precautions could lead to injury or damage to the system.
WARNING
● Prior to commencing utilization of the expansion valve, read this manual carefully.
● If this manual is lost, destroyed or damaged, a replacement should be obtained from
Mayekawa Mfg. Co., Ltd. or its nearest representative.
● If ownership of this expansion valve passes to another party, the expansion valve should
always be accompanied by this instruction manual.
● Mycom reserves the right to change the contents of this manual and/or any description
contained herein without notice according to technical improvement to or upgrading of the
quality of the product. Accordingly, it is possible that the end user may encounter a
situation not covered by this manual or find a portion different from the description. If
the end user encounters a situation as described above, contact either the nearest Mycom
service outlet, Mycom Japan or Mycom TS-21 Co., Ltd., Japan.
Specifications
Refrigerant used Ammonia (R717)
Maximum Pressure 3.0MPa
Orifice ※ A B BC C D E F G H
CV Value 0.04 0.08 0.11 0.14 0.22 0.3 0.37 0.44 0.5
Actuation Pressure [MPa] 1.9 1.5
Pressure-tight testing pressure 4.5MPa
Hermetic testing pressure 3.6MPa
-50∼+55℃ (When ambient temperature exceeds +35℃, refer to
Ambient temperature
YOSAKU Valve Coil Temperature Table on Page 7/8)
※ AC100V 50Hz/AC100∼110V 60Hz
Rated voltage of AC110V 50Hz/AC120 60Hz
power source and AC120V 50Hz
frequency AC200V 50Hz/AC200∼220V 60Hz
(For 30 min.) AC220V 50Hz/AC240 60Hz
AC240V 50Hz
Allowable range of voltage ±5% of rated voltage.
Power Consumption 40VA
Electric Insulation Thermal Resi
Class B.
stance Class
Always use within the ranges indicated in the specifications.
*Before mounting the expansion valve, confirm the Model No., Voltage and Frequency of the
power source as well as the size of the orifice, all of which are indicated on the Name Plate.
Page 1/8
MWP(NH3)
MYCOM
● M o d e l N um be r
MWP−1520-NP−A−AC200V−50Hz−KF
--Without fuse
KF---Built-in quick fusible
fuse inside terminal
box of expansion valve.
Frequency
Refer to
Power source voltage specifications
Orifice
● Pi p i ng a nd As s e m bl y W o r k
■ Mounting position
WARNING
・ D o n ot m o u n t t h e e x p an s i o n v al v e i n s i d e t h e f r e ez er o r f r e ez in g r o o m, w h i c h a r e p r o n e
t o d e w g e n e r a t io n an d f r e e z in g . S p e c i al c ar e mu s t be t a k e n to av o i d mo unt ing in a
p l a c e e x p o s e d t o p o t e n t i a l d ir e c t c on t a c t w it h d r a i n w at e r o r w a t e r s h o w e r .
・ T h e m o u n t i n g p o s i t i o n o f t h e e x p a n s i o n v a l v e s h o u l d b e s e l ec te d t a k in g a c c e s s i b i l it y
f o r p ar ts r e n e w a l in to c o n s i d e r a ti o n . En s u r e a t le as t 5 0c m o r m o r e o f sp a c e a b o v e
th e e x p an s io n v alv e t o f ac i l it at e i n s pe c t i o n an d m a in t e n an c e .
Page 2/8
MWP(NH3)
MYCOM
Position smaller
coil end at top
N P Or i f i c e
10 N・ m
Plunger case (Flat 14mm) NP Orifice
70 N・ m Assembly
( F l at 2 9 mm ) Plunger case
assembly Small packing Coat with
compressor oil
Large packing
膨
Coat with
compressor oil Mounting hole
Expansion Valve Body
2 -φ6.5
● E le c tr ic a l W ir in g
WARNING
・ W i r in g w o r k f o r t h e e x p an s i on v a l v e s h o u l d n ev e r b e u n d e r t a k e n b e f or e
d i s c o n n e c t i n g t h e p o w e r s o u r c e , o th er w i se t h e r e i s a r i s k o f e le c t r i c s h o c k .
・ E l e c t r i c a l w ir in g w o r k s h ou l d be c ar r i e d ou t fo l low i ng al l s af e t y r u l e s an d
s t a n d ar d s f o r e l e c t r ic al d e v ic e in st a l l a t io n .
Page 3/8
MWP(NH3)
MYCOM
※ Confirm that the voltage and frequency shown on the label are exactly the same as
that of the power source.
※ Do not apply excessive tension on the lead wire or the terminal box, otherwise
major damage to the expansion valve may result.
※ Mount two quick fusible fuses on the power source line of the expansion valve (outlet
side of controller)
※ If there is a potential for dew generation on the expansion valve, attach a leak breaker
on the power source line of the valve and fill the terminal box of the expansion valve
with silicon grease.
■ Connect the quick fusible fuse in the terminal box of the expansion valve
( E x t e r n a l t e m p e r a t u r e o f t h e e x p a n s i o n v a l v e : -40℃∼+55℃)
Page 4/8
MWP(NH3)
MYCOM
2P ELCB(30AF/10AT)
× ×
30mA 0.1sec. with Alarm
Switch. Model EG32FC-K
(Fuji Electric. Works)
Start Signal
2 16 17 8 8 3 1
SSR(Omron Co., Ltd.)
○
1
○ ○
SHC211 ○ S H C 2 1 1○ ○ ○
○
G3 N A- 20 5 B
FG 3 20 19 9 9 4 2
○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○
RC
SC
/
○ /
○ / / / /
FG F1 F1
F1 F1
Control circuit ○ ○
+ −
H L CV CV CV
TC
F1 F1
Built-in quick fusible fuse
within terminal box. ○
/ ○
/
■ If the ambient temperature is below ‒40℃ or lower, connect the quick fusible
fuse inside the control panel.
Page 5/8
MWP(NH3)
MYCOM
Start Signal
○2 ○16 ○ 17 ○3 ○1
8○ 8 ○
SSR (Omron Co., Ltd.)
○1 SHC211 SHC211
Mode l G3 NA -2 05B
○ 19 9○ 9 ○ ○4 ○ 2
F G ○3 ○ 20
RC F2 F2 F2 F2
SC
/
○ /
○ ○ /
○ /
○ /
○ /
○
Control
circuit
FG CV CV CV
○ ○
+ −
H L /
○ /
○
TC
Built-in quick fusible fuse
F2 F2
within control panel.
● O p e r a tio n , In s pe c t io n a n d M a in t e n a n c e
■ Cautions during Operation
WARNING
‧ If t he e xpa n si on v al ve i s o p e r at e d fo r a n e x t en d e d pe ri o d o f ti m e wh i l e t h e i n l e t o f
t h e v al ve i s t o t al l y cl ose d , t h e pl u n g e r c as e of t h e e x p an si on v al ve w i l l b r e a k a n d
t h e re i s po t e n t i al f or r e f ri ge r an t l e a k a g e du e t o c oun t e r- f l ow f r om t h e o ut l et po rt
o f t he e x p an si on v al ve .
‧ If the expansion valve is forcibly opened at the commencement of cooling down operation
or the valve is impressed continuously at 100% opening, the temperature of the molded
coil will exceed the heat resistance limit and burn out the coil.
・ Set the valve opening level between min. 5% and max. 95%.
If the ambient temperature of the expansion valve exceeds +35℃, preset the maximum
temperature so as not to exceed the level indicated by in Y O S A K U V a l v e C o i l
Te m pe rat ur e s Ta b le be l o w.
Pag e 6/ 8
MWP(NH3)
MYCOM
60 111 133 152 159 so that the Coil Temperature does not reach the
■ M a i n t e na n c e
WARNING
‧ Maintenance work of the expansion valve should be carried out only when
there is no power supply, otherwise there is potential for electric shock.
‧ Disassembly of the expansion valve should be performed only af ter disposition
of any refrigerant remaining inside the valve.
‧ When ON-OFF frequency reaches two million cycles or within one year following
previous maintenance, whichever comes first, renew the NP ori fice assembly,
NP plunger assembly and t he plunger case together.
‧ W h e n c ar r y i n g o u t r e n ew a l o f c o mpo n e n t p a r ts, d o n o t f o r g e t to r e se t th e O N- O F F
F r e qu e n c y C o u n te r o f t h e C o n tr o l l e r ( M Y P R O SH C - 2 11 ) to “ 0”.
‧ I n c a s e o f A m m o n i a r e f r i g e r a n t , a l w a y s u s e l ar g e a n d s m a l l p ac k i n g s o f A l u m i n u m.
‧ D o n o t d i s c o n n e c t t h e c oi l p or t i o n , p l u n g e r , p lu n g e r c as e , e t c . o f t h e e x p an si on
v alv e . If p o w e r e d u p, o th e r w i se c o il bu r n in g w il l o c c u r .
‧ D u r i n g p e r i o d i c i n s pe c t i o n a n d r en e w a l o f c omp onen t p ar t s, c ar r y out the fo ll owing
inspec ti on of the mo ld ed co il. B efor e un der ta k i ng i n s p ec t i on, t ur n off t he p o w er
sou r c e an d d i sc o n n e c t th e e l e c tr i c c i r c u i t to th e m o l d e d c o i l .
① M e asu r e th e i n su l a ti o n r e si s t a n c e v a l u e b etwe en the c oi l le ad wir e and t h e
b ody o f th e ex p an si on v alv e u sin g a 5 0 0V M eg a - t e st er .
➜ If the in sul a ti on re si s t a n ce va lue i s be low 0. 2 M Ω, r e p l ac e th e c o i l p o r ti o n .
② Di s man t le the c o i l por t ion an d c o nfir m th a t t h e c o i l i s f r e e o f c r a c k s, s c a r s ,
de f o r ma t i o n , e tc .
➜ I f c r ac k s , sc ar s o r o th e r a bn o r ma l s ig n s ar e f o u n d , r e p l ac e th e c o i l p o r t i o n
w i th a n e w o n e .
Pag e 7/ 8
MWP(NH3)
MYCOM
I f a n y q u e s t i o n s r e m a i n o r u n c e r t a i n t y i s e n c o u n te r e d , c o n t ac t th e M Y C O M r ep r e -
se n ta t i v e i n y o u r ar e a, M ay e k aw a M f g . Co. , L t d . , o r M ay e k a w a T S- 2 1 C o . , L t d .
W e r e se r v e th e r i g h t to c h an g e t h i s m an u al w i t h o u t n ot i c e i n o r d er t o u p g r a d e t h e
q u a l i t y o f t h e M o d e l N WP T h e r m o E x p an si on V a l v e .
P ag e 8/ 8