Beruflich Dokumente
Kultur Dokumente
Help
Code No. LIT-12011147
Software Release 3.1
Issued November 9, 2007
Supersedes May 2, 2007
Help Appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Help Window Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Help Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Introduction Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Concepts Section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Steps Section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Screens Section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Printing the Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Printing the Navigation and Search Pane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Logic Blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
CCT User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Menu Bar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Select System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Sideloop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Define Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Connections Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Parameters Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Balancer Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Logic View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Opening a Controller Application File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
CCT User Interface Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Upgrading Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
System Upgrade (with Modules) Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Setting Default Object Naming and Signal Preferences . . . . . . . . . . . . . . . . . . . . . . . 148
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Selecting a System (Creating a New System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Panning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Zooming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
New System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
MUX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Port Exposure (For BACnet System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Configuring the Local Controller Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Selecting Points to Appear on Display Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Configure Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Starting Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Navigating Between the Control View and a Module’s Logic View. . . . . . . . . . . . . . . 243
Panning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Zooming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Printing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Simulation Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Controller Selection Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Upload. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Uploading a Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Load Device Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Making Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Making an Ethernet Passthru Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
Panning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Zooming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Printing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Commissioning Device Wizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Setup Screen for Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Performing a Box Flow Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Box Flow Test Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 775
Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 776
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 792
Subtract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 794
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 794
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 798
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 802
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 804
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 809
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 811
Module Use in Applications (WarmupCooldown Determination) . . . . . . . . . . . . . . . . . . . . 811
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 813
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 815
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 817
Module Use in Applications (Flow Calculation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 818
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 821
Module Use in Applications (Flow Differential Calculation) . . . . . . . . . . . . . . . . . . . . . . . . 821
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 825
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 827
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 831
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 833
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 835
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 837
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 839
Module Use in Applications (VAV Dual Duct Constant Flow Endpoint Calculation) . . . . . 839
Module Use in Applications (VAV Dual Duct Minimum Flow Determination). . . . . . . . . . . 841
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 843
Module Use in Applications (VAV Dual Duct Variable Flow Endpoint Calculation) . . . . . . 844
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 846
Module Use in Applications (VAV Single Duct Minimum Flow Determination) . . . . . . . . . 846
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 849
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 857
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 859
Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 860
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 860
Last Value (Boolean, Enum, Float). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 860
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 860
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 863
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 866
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 871
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 875
Module Use in Applications (Load Calculation v2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 878
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 880
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 883
Module Use in Applications (Count On Inputs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 883
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 884
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 886
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 890
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 895
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 900
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 902
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 905
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 908
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 915
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 917
Module Use in Applications (Availability Determination) . . . . . . . . . . . . . . . . . . . . . . . . . . 917
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 920
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 927
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 930
Module Use in Applications (Emergency Mode Sequencing) . . . . . . . . . . . . . . . . . . . . . . 930
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 932
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 935
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 939
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 942
Module Use in Applications (Start Stop Sequencing [AHU 100% OA]) . . . . . . . . . . . . . . . 943
Attributes (Start Stop Sequencing [AHU 100% OA]) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 943
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 947
Module Use in Applications (Start Stop Sequencing [AHU Mixed Air]) . . . . . . . . . . . . . . . 948
Attributes (Start Stop Sequencing [AHU Mixed Air]) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 949
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 957
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 961
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 971
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 975
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 978
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 980
Module Use in Applications (Occupied Zone Sequencing [HP]) . . . . . . . . . . . . . . . . . . . . 980
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 983
Module Use in Applications (Occupied Zone Sequencing [UV Cycle 1]). . . . . . . . . . . . . . 983
Attributes (Occupied Zone Sequencing [UV Cycle 1]) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 984
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 986
Module Use in Applications (Occupied Zone Sequencing [UV Cycle 2]). . . . . . . . . . . . . . 986
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 989
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 991
Module Use in Applications (Occupied Zone Sequencing [UV Cycle W]) . . . . . . . . . . . . . 991
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 997
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1005
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1007
Module Use in Applications (Fan Determination [Terminal Units]) . . . . . . . . . . . . . . . . . 1007
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1010
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1014
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1016
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1018
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1021
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1024
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1026
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1029
Module Use in Applications (Unoccupied Sequencing [AHU Mixed Air ZN-T]) . . . . . . . . 1029
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1032
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1035
Module Use in Applications (Unoccupied Sequencing [UV]) . . . . . . . . . . . . . . . . . . . . . . 1035
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1038
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1044
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1048
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1055
Module Use in Applications (Fan Determination [VAV Parallel Flow Based]) . . . . . . . . . 1055
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1058
Module Use in Applications (Fan Determination [VAV Parallel Temp Based]) . . . . . . . . 1058
Attributes (Fan Determination [VAV Parallel Temp Based]) . . . . . . . . . . . . . . . . . . . . . . 1059
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1060
Module Use in Applications (Fan Determination [VAV Series]) . . . . . . . . . . . . . . . . . . . . 1060
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1068
Attributes (Flow Setpoint [VAV Attributes (Flow Setpoint [VAV Dual Duct]) . . . . . . . . . . 1069
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1071
Module Use in Applications (Flow Setpoint [VAV Single Duct]). . . . . . . . . . . . . . . . . . . . 1071
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1074
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1076
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1078
Module Use in Applications (Slave Supply Flow Setpoint Control Dual Duct) . . . . . . . . . 1078
Primary States (Slave Supply Flow Setpoint Control Dual Duct) . . . . . . . . . . . . . . . . . . . 1079
Module Use in Applications (Heat Exchanger with Return Water Control) . . . . . . . . . . . 1080
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1083
Module Use in Applications (Plant Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1083
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1086
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1089
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1092
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097
Module Use in Applications (Secondary Pump PID) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1097
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1099
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1100
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1103
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106
Module Use in Applications (Damper Control for UV Cycle 1, 2, or W) . . . . . . . . . . . . . . 1106
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1109
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1112
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1115
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1119
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1122
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1125
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1128
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1131
Module Use in Applications (Min OA Fan Variable Capacity Flow Control). . . . . . . . . . . 1131
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1138
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1142
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1145
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1146
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1148
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1151
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1154
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1156
Module Use in Applications (Fan Relief Variable Capacity BSP Control) . . . . . . . . . . . . 1156
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1158
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1161
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1167
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1170
Module Use in Applications (Fan Return or Exhaust Volume Match Control) . . . . . . . . . 1170
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1174
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1178
Module Use in Applications (Fan Supply Duct Static for UL-864-UUKL). . . . . . . . . . . . . 1181
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1185
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1189
Module Use in Applications (2 Pipe 2 Position Valve with DA-T Low Limit) . . . . . . . . . . 1189
Attributes (2 Pipe 2 Position Valve with DA-T Low Limit) . . . . . . . . . . . . . . . . . . . . . . . . 1190
Primary States (2 Pipe 2 Position Valve with DA-T Low Limit) . . . . . . . . . . . . . . . . . . . . 1192
Module Use in Applications (2 Pipe FBPD 2 Position Valve with Low Limit) . . . . . . . . . . 1194
Attributes (2 Pipe FBPD 2 Position Valve with Low Limit) . . . . . . . . . . . . . . . . . . . . . . . . 1195
Primary States (2 Pipe FBPD 2 Position Valve with Low Limit) . . . . . . . . . . . . . . . . . . . . 1197
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1199
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1203
Module Use in Applications (2 Pipe Proportional Valve with DA-T Low Limit). . . . . . . . . 1203
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1207
Module Use in Applications (2 Pipe Proportional Valve with Low Limit) . . . . . . . . . . . . . 1207
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1212
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1215
Module Use in Applications (Cooling FBPD 2 Position Valve with Dehumidification) . . . 1215
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1219
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1221
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1225
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1228
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1231
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1238
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1241
Module Use in Applications (Heat Recovery Wheel with 2 Pos Bypass Dampers) . . . . . 1241
Primary States (Heat Recovery Wheel with 2 Pos Bypass Dampers) . . . . . . . . . . . . . . . 1243
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1245
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1250
Module Use in Applications (Heating 2 Position Valve) . . . . . . . . . . . . . . . . . . . . . . . . . . 1250
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1253
Module Use in Applications (Heating 2 Position Valve with DA-T Low Limit) . . . . . . . . . 1253
Attributes (Heating 2 Position Valve with DA-T Low Limit) . . . . . . . . . . . . . . . . . . . . . . . 1253
Primary States (Heating 2 Position Valve with DA-T Low Limit) . . . . . . . . . . . . . . . . . . . 1255
Module Use in Applications (Heating FBPD 2 Position Valve with DA-T Low Limit) . . . . 1256
Attributes (Heating FBPD 2 Position Valve with DA-T Low Limit) . . . . . . . . . . . . . . . . . . 1257
Primary States (Heating FBPD 2 Position Valve with DA-T Low Limit) . . . . . . . . . . . . . . 1258
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1259
Module Use in Applications (Heating FBPD 2 Position Valve with Low Limit). . . . . . . . . 1259
Primary States (Heating FBPD 2 Position Valve with Low Limit). . . . . . . . . . . . . . . . . . . 1261
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1263
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1268
Module Use in Applications (Heating Proportional Valve with DA-T Low Limit) . . . . . . . 1271
Primary States (Heating Proportional Valve with DA-T Low Limit) . . . . . . . . . . . . . . . . . 1273
Heating Proportional Valve with Low Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1274
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1274
Module Use in Applications (Heating Proportional Valve with Low Limit) . . . . . . . . . . . . 1274
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1278
Module Use in Applications (Heating Sequenced Valves with Low Limit) . . . . . . . . . . . . 1278
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1282
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1285
Module Use in Applications (Heating Staged Outputs with DA-T Low Limit). . . . . . . . . . 1285
Primary States (Heating Staged Outputs with DA-T Low Limit). . . . . . . . . . . . . . . . . . . . 1287
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1288
Module Use in Applications (Heating Staged Outputs with Low Limit) . . . . . . . . . . . . . . 1288
Attributes (Heating Staged Outputs with Low Limit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1289
Module Use in Applications (Preheat Proportional Valve with Return Water Control). . . 1292
Primary States (Preheat Proportional Valve with Return Water Control). . . . . . . . . . . . . 1294
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1296
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1299
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1302
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1308
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1314
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1316
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1320
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1324
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1328
Sideloop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1330
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1330
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1330
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1334
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1339
Attributes (Sideloop PI Staged Output) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1339
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1342
Attributes (Sideloop PI With Reset Staged Output) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1343
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1346
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1348
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1365
Timing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1374
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1374
Totalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1380
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1380
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1380
Module Use in Applications (Totalization) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1381
Compare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1458
Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1460
Container . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1460
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1461
MSC Pre-Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1461
PID Pre-Processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1463
PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1465
PVDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1471
Math. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1474
Psychrometric . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1475
Absolute Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1475
Dew Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1476
Enthalpy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1477
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1482
Statistical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1483
Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1484
Execution Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1484
Custom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1494
Chapter 40: Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1495
Chapter 41: Application and Module Reference Table . . . . . . . . . . 1497
Chapter 42: Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1537
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1537
A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1537
B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1538
C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1538
D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1539
E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1539
F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1540
H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1540
I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1540
L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1541
M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1541
N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1542
O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1542
P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1542
R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1543
S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1543
T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1544
U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1544
V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1544
W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1545
Chapter 43: Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1547
Chapter 44: Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . 1549
Chapter 45: Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1551
Concepts
Accessing the CCT Help
You can access the CCT Help in the following ways:
• On the Help menu in CCT, select Topics.
If you access the Help via the Help menu, you start at the beginning and
navigate to the topic you are looking for.
• Click the Help button on a dialog box or press F1 while working in CCT.
Dialog box Help buttons and the F1 key open the Help to the appropriate topic
for the currently active view or dialog box. The entire Help system opens, but
you start at a topic relevant to your location in the application.
Internet Explorer Information Bar Security Message
When you access the Help from a computer running the Windows XP operating
system with SP2 (or similar system configuration) and Internet Explorer, the
following security message may appear in the Internet Explorer Information Bar
due to Microsoft security settings:
To help protect your security, Internet Explorer has restricted this file from
showing active content that could access your computer. Click here for
options...
To open the Help:
1. Click Click here for options... and select Allow Blocked Content. A Security
Warning dialog box appears stating:
Allowing active content such as script and ActiveX controls can be useful, but
active content might also harm your computer. Are you sure you want to let
this file run active content?
2. Click Yes. The CCT Help system opens.
Tabs
This Help system offers several ways to navigate and search for information using
tabs on the left side of the Help window:
Contents
The Contents tab contains the table of contents,
which is the hierarchy of the entire Help system
based on the paragraph headings.
Buttons
Buttons allow you to navigate the Help system and print. The buttons in this Help
are the following:
Show in Contents
The Show in Contents button synchronizes the information in the Contents tab
to your current location in the Help system. If the Contents tab is not active on
the left side of the Help, it is brought forward. Highlighted text in the Contents
list indicates where you are in the Help system.
Previous button
The Previous button takes you to the topic preceding the one you are viewing.
In other words, it takes you to the prior topic in the table of contents.
Tip: To go back to the last screen you visited, use the browser Back button.
Next button
The Next button takes you to the topic that follows the one you are viewing. In
other words, it takes you to the next topic in the table of contents.
Tip: To go to the next screen in your browsing sequence, use the browser
Forward button.
Tip: If no related topics exist, the Related Topics button appears dimmed.
Tip: The related topics that appear when you click the Related Topics button at
the top of the Help are the same topics that appear when you click
in the body of the Help.
Links
Drop-Down Lists
When you view the Help content, drop-down lists can be either open or closed. In
a closed drop-down list, only the introduction text appears at first, bold and black
with an arrow next to it. When you click on the introduction text, the list opens up.
In an open drop-down list, the list appears when you first view the Help. When you
click on the introduction text, the list closes and only the introduction text is
visible. Click it again to re-open the list.
Note: Information in a drop-down list only prints if you have the list open on the
screen.
Jumps
Jumps take you to a different section in the Help system. Jumps appear as blue,
underlined text like.
Pop-Ups
Pop-ups appear as blue text without an underline. When you move the mouse
cursor over the pop-up text, explanatory text appears in a pop-up window. If you
click on a pop-up, you jump to its entry in the glossary or other topic.
Note: Pop-up window content does not print.
Introduction Section
The Introduction section contains the introductory and overview information of the
topic. Introduction headings appear in the Contents tab on the left side of the Help
and in the information on the right.
Concepts Section
The Concepts section contains information key to understanding the topic.
Concepts headings appear in the Contents tab on the left side of the Help and in the
information on the right.
Steps Section
The Steps section appears only in the Help topics that have procedures associated
with them. The steps appear in the Contents tab on the left side of the Help.
Screens Section
The Screens section contains descriptions of the views, wizards, and dialog boxes
you might encounter. Screen headings appear in the Contents tab on the left side of
the Help and in the information on the right.
Concepts
CCT Commissioning Only Software
A Commissioning mode only version of the CCT software is available to the
Johnson Controls branch offices for individuals having only commissioning tasks
(for example, balancing contractors). The CCT Commissioning software allows
you to focus on the commissioning tasks you need to perform without being
distracted by the tasks done in the other two modes. For example, you can issue
commands and commission devices, but you cannot make configuration changes,
define hardware, load, or simulate devices. You can print the system, use the Test
Mode, and view system selections, hardware definitions, controller information,
connections, and item details. The Configuration and Simulation modes are
disabled in the CCT Commissioning software.
System
In CCT, a system is represented by the mechanical equipment and the logic needed
to control that equipment, independent of hardware definition. The System
Selection Wizard in CCT describes the make-up of a mechanical system to aid you
in creating the group of logic components that work together to control the
mechanical system. See System Types and Configurations in the Configuring a
System section.
Application
An application is a collection of the components that make up the control logic of a
system, including modules, logic blocks, custom logic, and hardware definition.
For information on the types of applications you can create, see the Applications
section.
User Interface 75
Controller Application File (.caf)
A Controller Application File (.caf) is a file which contains all the logic
components needed to represent a system. CCT prompts you to save a controller
application file for each system you create. Saving this file allows you to access it
again later to make changes or to use it for additional systems.
The default location to save a Controller Application File is C:\Documents and
Settings\username.
You cannot use certain characters when saving a Controller Application File.
Illegal characters include:
: * ?"<>|/ \
Modules
A module is a component made up of logic blocks used to create portions of the
overall control logic of a system. Module inputs are used to influence the state or
values of outputs. You can view and/or edit modules highlighted in tan in the
Control View, but changes should not be made until the default configuration is
thoroughly understood and the effect of changes on the connected outputs is
considered. To view or change default values used in a module, see Details
Configuration in the Configuring a System section. To view or change connections
to a module, see Control View Configuration in the Configuring a System section.
See the Modules section.
Logic Blocks
A logic block is a component used to construct the control logic of a system. You
can view and work with logic blocks in the Logic View of CCT. Logic block
inputs are used to influence the state or values of outputs. You can view and/or edit
logic contained within modules highlighted in tan in the Control View, but
changes should not be made until the default logic is thoroughly understood and
the effect of changes on the connected outputs is considered. To view or change
default values used in a block, see Details Configuration in the Configuring a
System section.
See the Logic section for information on logic blocks.
Menu Bar
Modes and
Operations
Buttons
Quick
Navigation
Menu
Control/Logic
View
Workspace
(Control View
shown here)
Status Bar
The slider bars of the center and side panels have arrows allowing you to expand
the Parameters, Connections, or Balancer tabs to achieve the desired view (circled
in red in Figure 2-1). Click the arrows to show and hide the panels. If you click the
slider bar and drag it to the desired location, clicking the arrows returns the view to
the location you moved the slider bar. Clicking the arrows a second time shows/
hides the entire panel. The sliders maintain their location between sessions.
User Interface 77
Menu Bar
The CCT menu bar includes the following options:
Table 2-1: Menu Bar Options (Part 1 of 3)
Menu Option Keyboard Description
Shortcut
File New Ctrl + N Opens the New System dialog box. See the Configuring a
System section.
Open Ctrl + O Opens the Open dialog box to select an existing Controller
Application File (.caf) to use.
The default location of a Controller Application File is
C:\Documents and Settings\username.
Note: You cannot open a .caf file in the CCT Commissioning
only software. You must Commission to show a system in
the CCT UI.
Close Closes the open Controller Application File. You must be in
Configuration mode to close the Controller Application File.3
Note: You cannot close a .caf file in the CCT Commissioning
only software. You must stop Commissioning mode to
remove a system from the CCT UI.
Save Ctrl + S Saves the current system as a Controller Application File (.caf). If
you have not already saved the system, CCT opens the Save
dialog box.
Illegal characters include:
: * ?"<>|/ \
Save As Opens the Save dialog box to allow you to save the system as a
Controller Application File (.caf) using a different name.
Illegal characters include:
: * ?"<>|/ \
Print Ctrl + P Opens the Summary Report Options dialog box to print a
summary of the open Controller Application File (.caf) in PDF
format.
Exit Closes the CCT software. You must be in Configuration mode to
exit CCT.
Note: In the CCT Commissioning only software, you can exit
CCT after you stop Commissioning.
Modes1 Configure2 Switches to Control View in Configuration mode.3, 4 The
Configure button text changes to Stop Simulation when in
Simulation mode and to Stop Commissioning when in
Commissioning mode. See the Configuring a System section.
Simulate2 Opens the Simulation dialog box to enter Simulation mode.3 See
the Simulating a System section.
Commission Opens the Commission Device wizard to enter Commissioning
mode.3, 4 See the Commissioning a System section.
User Interface 79
Table 2-1: Menu Bar Options (Part 3 of 3)
Menu Option Keyboard Description
Shortcut
Tools Box Flow Test Opens the Box Flow Test application. See the Performing a Box
Flow Test section.
Preferences > Opens the Preferences - Naming and Signal screen. See the
Naming and Signal Setting and Using Preferences section.
Preferences > Opens the Preferences - System Selection screen. See the
System Selection Setting and Using Preferences section.
Preferences > Opens the Preferences - Localization screen. See the Setting
Localization and Using Preferences section. This option is available only
when a .caf file is not open.
Controller When in Commissioning mode, opens the Controller Information
Information wizard to display information from the controller on the field bus
to which you are currently connected and commissioning. See
the Commissioning a System section.
When in Configuration mode, opens the Controller Information
wizard to display information from one or more controllers on a
field bus. See the Configuring a System section.
System Rename Opens the System Rename dialog box to rename the current
system. This option does not change the name of the Controller
Application File (.caf).
Job Information Opens the Job Information dialog box to enter information
specific to the current job and open Controller Application File
(.caf).
Configure Display Opens the Configure Display dialog box to set up the Local
Controller Display. This option is available in Configuration mode.
See the Configuring the Local Controller Display section.
Upgrade System Opens the System Upgrade dialog box to upgrade the open .caf
file to the latest version. See the Upgrading System Files section.
Help Topics F1 Opens the CCT Help system.
About CCT Opens the About dialog box displaying the CCT version,
database information, and file version.
1. See the Changing Modes section for information on entering and exiting modes.
2. The Configuration (Configure) and Simulation (Simulate) modes are not available in the CCT Commissioning only
software version.
3. If you made changes to the system, the Save Confirmation or Confirm dialog box opens prompting you to save.
4. When switching from Simulation mode, a Confirm dialog box appears prompting you to save or discard the changes
made during simulation.
5. Menu options appear in the Action menu as appropriate for the selected item. If an item is not selected, the Action
menu may appear empty.
Configuration
Note: The Configuration mode is not available in the CCT Commissioning only
software version.
The Configuration mode is the default mode of CCT. When you add or select a
system, it opens the system in Configuration mode. This mode allows you to
design and edit a system. Configuration tasks include selecting a system,
modifying parameters, creating custom logic (as necessary), and other tasks to set
up a system. See the Configuring a System section for details.
The Configure button/menu text changes to Stop Simulation when in Simulation
mode and to Stop Commissioning when in Commissioning mode. The
Configuration mode also acts as a transitional mode when you need to switch from
Simulation to Commissioning mode and vice versa. See the Changing Modes
section.
You must be in Configuration mode to close a Controller Application File (.caf) or
exit CCT.
Back to Modes.
Simulation
Note: The Simulation mode is not available in the CCT Commissioning only
software version.
When you enter Simulation mode, the Simulation dialog box appears allowing you
to set the Simulation Speed (up to 5x real time) and the startup values for the
simulation session. The settings you select are saved and appear in the Simulation
dialog box the next time you enter Simulation mode. Simulation mode allows you
to see your system as though it were in Commissioning mode. This allows you to
test your system and make adjustments before downloading it into a device. See
the Simulating a System section for information on how to simulate your system.
Back to Modes.
User Interface 81
Commissioning
Commissioning mode allows you to connect to a device and view actual data from
that device. You can use this mode to monitor your device and set Offsets, COVs,
and Polarity in addition to other Parameter and Detail changes. For example, you
can change the Min Out and Max Out values of an Output to fine tune the range of
a 2-10 VDC proportional valve. In addition, the Commissioning mode has a
Balancer tab in the Control View for VAV applications to easily autocalibrate
VAV boxes and set flow constants in one location. See the Commissioning a
System section.
Back to Modes.
Operations
In addition to the options in the Operations menu to perform specific tasks, the
CCT UI has operation buttons: Select System, Sideloop, Define Hardware, and
Load. See the Select System, Sideloop, Define Hardware, and Load sections for
descriptions of the operations.
Sideloop
The Sideloop operation opens the System Selection Wizard for creating a sideloop.
See the Creating a Sideloop and Sideloop Applications sections for more
information.
Define Hardware
The Define Hardware operation opens the Hardware Definition wizard to define
the hardware for your system. See the Defining Hardware section for details.
Back to Operations.
Load
The Load operation opens the Load wizard to upload applications into the CCT
and to download to devices. See the Loading Devices section for details.
Back to Operations.
User Interface 83
Quick Navigation Menu
The Quick Navigation menu is a drop-down menu that allows you to navigate from
the Control View to the Logic View of any module that makes up the system, and
vice versa. This menu also allows you to view the logic of the entire application
and print it if desired. The Quick Navigation menu appears in the upper left-hand
side of the CCT screen above the Control/Logic View workspace.
The Quick Navigation menu indicates the displayed item first (for example, a
specific module or the system name). The System name appears first in the menu
list. The second item in the menu is always the View Application Logic option.
Lastly, any modules that can be viewed/modified appear in alphabetical order. If a
module has a child, the child does not appear in the menu until after the parent is
viewed once. For example, the OA Percent Min Flow Determination child module
does not appear in the menu until the Min Flow Determination parent module is
viewed. Figure 2-2 shows the Quick Navigation menu.
The View Application Logic option is available only in the Configuration mode.
Figure 2-2: Quick Navigation Menu
Displayed Item
System Name
Logic of the Entire
Application that can
be Viewed/Printed
See Application Logic View, Navigating between Control View and Logic View,
and Viewing/Printing Application Logic in the Configuring a System section for
more information.
1. Read-only
2. You cannot modify outputs of modules from the Parameters table.
3. Select parameters only
4. Only available in Test Mode.
User Interface 85
See the following sections for information on the Control View components:
• Modes
• Operations
• Control View Module Categories
• Control View Status Colors and Icons
• Right-Click Menus (Control View)
• Connections Table
• Parameters Table
Inputs
The Inputs category appears in the Control View of CCT (Figure 2-1). This section
lists the inputs defined for the system. An input defines an interface to the actual
hardware in a system. An input can represent a physical sensor in the system or an
input associated with a sensor. Inputs get data directly from hardware input points
of a device.
See Inputs in the Modules section for information on input modules.
Back to Control View Module Categories.
Setpoint/Miscellaneous
The Setpoint/Miscellaneous category appears in the Control View of CCT
(Figure 2-1). This section lists the setpoint and miscellaneous modules defined for
the system. A setpoint or miscellaneous module contains logic that calculates a
setpoint or provides other calculations for a system. This section lists modules for
other miscellaneous calculations required by a system.
See Setpoint Determination/Misc in the Modules section for information on
setpoint/miscellaneous modules.
Back to Control View Module Categories.
User Interface 87
State Generation
The State Generation category appears in the Control View of CCT (Figure 2-1).
This section lists the state generators defined for the system. The state generators
are listed according to priority, where the state generators appearing at the top have
a higher priority than those listed below them. This order typically corresponds to
the order in a State Selection Table when viewing the State Tables. A state
generation module calculates a state, that is prioritized by the State Table, which
calculates a mode to be controlled by an Output Controller.
See State Generators in the Modules section for information on state generation
modules.
Back to Control View Module Categories.
State Selection
The State Selection category appears in the Control View of CCT (Figure 2-1) in
Configuration mode. You also can access State Selection by right-clicking the
State Generation header in Configuration, Simulation, or Commissioning mode.
The State Tables define how the states of the inputs of the State Tables control the
outputs in the system. See the State Tables section for information.
Back to Control View Module Categories.
State Tables
You can access the State Tables screen using the right-click menu of the State
Selection header in the Control View of CCT (Figure 2-1) in Configuration mode
or by using the right-click menu of the State Generation header in Configuration,
Simulation, or Commissioning mode. You can modify the State Tables only in
Configuration mode. The State Tables are used to set the hierarchical priority of
incoming states and to define the appropriate mode of operation of each output
controller for each state in the State Selection Tables.
The individual tables in the State Tables correspond to the State Generators and the
column headings are the Output Controllers. For each State Generator state, there
is a corresponding Output Controller state. The States column lists the states from
highest priority to lowest priority in descending order from top to bottom. An
asterisk (*) or an X appearing instead of a valid Output Controller state indicates
that the current State Generator has no interaction with the Output Controller, and
the Output Controller is controlled by the next highest priority State Generator
showing a valid Output Controller state. An X also indicates that the field should
not be modified unless certain control specifications are required.
For information on how to use the state tables, see Viewing and Modifying State
Selection Tables in the Configuring a System section.To see an example of how the
State Tables are used, see the Control View Application Example section.
Back to Control View Module Categories.
Network Outputs
The Network Outputs category appears in the Control View of CCT (Figure 2-1).
This section lists the network outputs defined for the system. A network output
module acts as a network variable read from a supervisory device. When a network
output is not mapped to a supervisory device, it can only be viewed from the
Commissioning mode of CCT. Network outputs connect from other modules or
the State Table.
See Network Outputs in the Modules section for information on network output
modules. Also, see Peer-to-Peer Communication in the Configuring a System for
information on peer-to-peer communication in CCT.
Back to Control View Module Categories.
Outputs
The outputs category appears in the Control View of CCT (Figure 2-1). This
section lists the outputs defined for the system. An output defines an interface to
the actual hardware in a system. An output can represent a physical hardware point
in the system or a point associated with an output. Outputs send data to hardware
output points of a device.
See Outputs in the Modules section for information on output modules.
Back to Control View Module Categories.
User Interface 89
Control View Application Example
The following figure shows how modules in the Control View interact (using
Show Involvement in Simulation mode).
Figure 2-3: Fan Coil Application Example (Show Involvement)
This example is of a Fan Coil application. Based on the network inputs and input
readings in this example, the State Tables have determined that the highest priority
state generator that should be in Control is FC-ZN-T SEQUENCING (Zone
Sequencing [FC]), which is set to the Cooling state. As a result, the Proportional
Cooling Control output control is set to Control, which modulates the cooling
valve open (CLG-O output).
The following drawing and text further explain the interaction between the cooling
modules.
Setpoint
Flush
Position
User Interface 91
Figure 2-5: Fan Coil Application Example (State Tables)
In this example, the Water System Flush Pass Through has the highest priority and
Fan Determination has the lowest. The Water System Flush Pass Through state is
set to False, and the cells have an X, which means no behavior change occurs and
the next table is evaluated.
When the Unit Enable Determination state is set to Shutdown, then the Mode is set
to Off for the Proportional Cooling Control, Proportional Heating Control, and
Single Speed Fan Control. The Unit Enable Determination state is set to Enable
and the cells have an X, and the next table is evaluated.
User Interface 93
Control View Status Colors and Icons
Table 2-3 lists the status colors and icons used in the Control View of CCT.
Table 2-3: Control View Status Colors
Status Color Appears in Mode Description
White All modes Indicates a non-editable module.
Tan All modes Indicates an editable module; that is, it contains logic
that you can view and/or edit. You can use the View >
Logic option for this type of module.
Blue All modes Indicates the selected module.
Green All modes In Configuration mode, indicates modules that contain
exposed ports that are compatible (that is, the
enumeration set and units match) with the current port
you are connecting. See Viewing and Modifying
Connections in the Configuring a System section.
In Simulation and Commissioning modes, indicates the
active state generator(s).
Magenta Simulation and In Simulation and Commissioning modes, shows the
Commissioning modes involvement of other modules to the selected Output
module.
Orange Simulation and In Simulation and Commissioning modes, indicates
Commissioning modes when the software value does not match hardware value
of the item.
Note: In Simulation mode, inputs and outputs are
orange because the associated hardware has
not yet been defined.
Red All modes Indicates an input or output that is not assigned properly.
Delete such inputs and outputs from CCT.
All modes Identifies a module that has been modified by a user.
(Green
Triangle) If the changes were made in Configuration mode, this
icon appears directly to the left of the module name
(first row).
If the changes were made in Simulation or
Commissioning mode, the green triangle appears
directly to the left of the module’s Default Element value
(second row).
All modes Identifies that the input or output is assigned to a
(Network Network Sensor (Network Duct Sensor or Network Zone
Sensor)1 Sensor).
All modes Identifies that the input or output is assigned to a
wireless sensor and has a wireless Ethernet signal.
(Wireless
Ethernet
Sensor)
All modes Identifies that the input or output is assigned to an
Eaton Variable Speed Drive.
(VSD)
All modes Identifies that the input or output is assigned to an FEC.
(FEC)
All modes Identifies that the input or output is assigned to an IOM.
(IOM)
1. Device and Port label information appears after the module name for assigned Inputs and Outputs.
Miscellaneous
Generation
Selection
Setpoint/
Network
Network
Outputs
Outputs
Control
Output
Inputs
Inputs
State
State
New (Header Configuration X X X X X X X Adds a new module.
Only)
Simulation
Commissioning
Delete Configuration X X X X X X X Removes the module.
Simulation
Commissioning
Rename Configuration X X X X X Changes the name of the
module.
Simulation
Commissioning
View Details Configuration X X X X X X X X Displays the Details dialog
box to view the details of the
Simulation X X X X X X X
selected module.
Commissioning X X X X X X X
View Configuration X X X X X X X X Displays the connections of
Connections the selected module(s) in the
Simulation X X X X X X X
Connections tab.
Commissioning X X X X X X X
View Logic1 Configuration X X X X X X X Opens the Logic View for the
selected module. This menu
Simulation X X X X X X X
option is available only when
Commissioning X X X X X X X the module has logic that can
be viewed and/or modified
(indicated by a tan
background).
View State Configuration X Opens the State Selection
Tables Tables. This option is
Simulation X
available from the State
Commissioning X Generation header or the
State Selection header.
Commands Configuration Opens the Commands dialog
box to command items.
Simulation X X X X X X X
Commissioning X2 X2 X2 X2 X2 X2 X2
Metasys Configuration Opens the Metasys
Commands Commands dialog box to
Simulation
issue a Metasys system
Commissioning X X command to the selected
item.
User Interface 95
Table 2-4: Right-Click Menus (Control View) (Part 2 of 2)
Menu Option Appears in Control View Section Description
Mode
Miscellaneous
Generation
Selection
Setpoint/
Network
Network
Outputs
Outputs
Control
Output
Inputs
Inputs
State
State
Setup Configuration X X Allows you to change the
signal type of Inputs and
Simulation
Outputs in Configuration
Commissioning X X mode. Allows you to
Commission Inputs and
Outputs in Commissioning
mode.
Show Configuration Highlights the connected
Involvement modules in the Control View.
Simulation X
Commissioning X
Hide Configuration Removes the highlighting on
Involvement the connected modules in the
Simulation X
Control View.
Commissioning X
1. Only available for modules containing logic that can be viewed and/or modified (indicated by a tan background). See
the Control View Status Colors and Icons section.
2. Only available in Test Mode.
Connections Table
The Connections table appears in the Connection tab of the Control View
workspace in all modes. This table can show the connections for one or more
modules. The Connections table displays the source and destination module and
port data with the associated input and output connection of the selected module.
Inputs appear yellow and outputs appear turquoise in this table.
By default, connections appear for all modules. You can select to view connections
for one module, multiple modules in a module category, or you can select a
column header of one of the module categories to view connections for all modules
in that section. To return to the default, showing all module connections, right-
click within the overall table header and select Show All.
Figure 2-6: Connections Table Show All Menu
Header
Parameters Table
The Parameters table lists key parameters/attributes used by the system. In
Configuration mode, default values appear only for parameters/attributes that can
be edited. To add other parameters/attributes to the Parameters table, enable the
inputs and outputs for BACnet network exposure by editing the individual
module’s BACnet Exposed attribute to True in the Details dialog box. You cannot
modify outputs of modules from the Parameters table. See the Control View
Screen section for a description of this table’s components.
Balancer Tab
The Balancer tab appears in the Control View workspace in Commissioning mode
only for VAV applications. This tab includes a parameters table and task buttons to
autocalibrate VAV boxes and set flow constants easily in one location. See the
Control View Screen section for a description of this table’s components, and see
the Commissioning a System section for details on using this tab.
User Interface 97
Logic View
Figure 2-7 shows the Logic View in the workspace. Click on the links to the left of
the graphic or click an area of the graphic for information on the Logic View
components.
Figure 2-7: Logic View
Toolbar
Control Block
Palette
Logic Diagram
(Workspace)
The Logic View of CCT allows you to view and modify the control logic used in
your system. This view displays the logic blocks visually to provide information
about your system. The Logic View is divided into three sections: a toolbar,
control block palette, and logic diagram area. Depending on the mode in which
CCT is operating, you are able to perform certain tasks in the Logic View. For
information on the CCT modes, see the Modes section.
See the following sections for information on the Logic View components:
• Toolbar (Logic View)
• Right-Click Menus (Logic View)
• Control Block Palette
• Logic Diagram
• Logic View Status Colors
User Interface 99
Toolbar (Logic View)
Table 2-7 describes the icons in the Logic View toolbar. These options appear in
all modes, unless otherwise noted.
Table 2-7: Logic View Toolbar
Icon Command Description
Print Opens the Print dialog box to print the logic diagram.
Pan Turns the cursor into a hand that allows you to pan over
the logic diagram by dragging.
Interactive Zoom Zooms in and out on a logic diagram when you hold the
mouse button down.
Zoom – Fit Window Zooms the logic diagram to fit within the window.
Selective Zoom Allows you to select the percentage zoom applied to the
logic diagram.
Trace Mode Removes all the connection lines in the logic diagram.
Live values remain. This option is available in the
Commissioning and Simulation modes only.
Note: This option is available in the Configuration mode
only when viewing logic of the entire application
(View Application Logic option of the Quick
Navigation menu).
Set Default Element Selects a default element for the block/module. The
default element indicates the value displayed in the
Control View in Simulation and Commissioning modes.
This option is available for configuration in the
Configuration mode only.
Note: This option is not available when viewing logic of
the entire application (View Application Logic
option of the Quick Navigation menu).
Export Module Exports the module logic by adding it to the Custom
folder in the Control Block Palette. Use the export
feature to share custom modules. This option is
available in the Configuration mode only. See Exporting
a Module in the Configuring a System section.
Note: This option is not available when viewing logic of
the entire application (View Application Logic
option of the Quick Navigation menu).
Block Finder
The Block Finder appears in the Control Block palette before the folders
containing available blocks for selection. You can drag the Block Finder to the
logic diagram workspace, search for a block, and select the block to add to the
diagram. When you click OK, the block appears in the logic diagram. Adjust the
placement of the block as needed. See Searching for a Block Using the Block
Finder in the Configuring a System section.
Logic Blocks
(Label in Blue)
Default Element
Logic is generally executed following a left-to-right flow across the logic diagram.
Connection lines between elements may be visible or hidden. When hidden, each
connection has a hidden edge label at the origination point and at each destination
point. At the origination point, the hidden edge label may contain two numbers,
where the first number indicates the connection number and the second indicates
the number of instances. For example, a hidden edge label of 5:7 means there are
seven instances of connection number five.
Note: You can change the label of a hidden edge. See Changing the Hidden Edge
Label of a Connection in the Configuring a System section.
For each Logic block, you can select one parameter/attribute as the Default
Element, which becomes the value that displays dynamic data in Simulation and
Commissioning modes.
Similarly, when you command the output of a block to a different value, the
existing value appears first and is followed by the commanded value. Figure 2-10
is an example of a block with double values.
Figure 2-10: Double Values in Logic View (Commands)
When you place your cursor over an input or output of a logic block, the input/
output name and default value appear.
When making a connection, a tooltip indicates if there is no valid connection for
the selected input/output. An invalid connection is when the data type of the source
and destination do not match (for example, a Boolean source and a Float
destination).
For information on the individual logic blocks, see the Logic section. Also, see the
Logic View Status Colors section.
For information on configuring logic blocks, including information on how the
Hybrid Activity block works, see Logic View Steps and Configuring a Hybrid
Activity in the Configuring a System section.
Language Options
The CCT software installation program allows you to select the languages to
support and set the default language in which to run CCT. You can change these
language selections after initial installation without re-running the entire
installation program. The CCT Installation Instructions explains how to initially
set up and later change these language options. See the Related Documentation for
information on accessing this document.
You also can define preferences for localization. See the Setting and Using
Preferences section.
Changing Modes
Note: CCT opens a Controller Application File (.caf) in Configuration mode by
default. The Configuration and Simulation modes are not available in the
CCT Commissioning only software version.
To change from Configuration mode to Simulation or Commissioning mode, click
the Simulate or Commission button. Or, select the menu options from the Modes
menu.
Note: The Configure button/menu text changes to Stop Simulation when in
Simulation mode and to Stop Commissioning when in Commissioning
mode.
To return to Configuration mode from Simulation or Commissioning mode, click
the Stop Simulation or Stop Commissioning button. Or, select the menu options
from the Modes menu.
Note: The Configuration mode acts as a transitional mode when you need to
switch from Simulation to Commissioning mode and vice versa. To change
from Simulation mode to Commissioning mode, for example, you must
first change to Configuration mode.
Note: When stopping simulation (Stop Simulation), a Confirm dialog box
appears prompting you to save or discard the changes made during
simulation.
Note: If you made changes to the system in a particular mode, CCT opens the
Save Confirmation dialog box prompting you to save. Click Yes to save the
changes before changing modes or No to discard them. If you select No,
CCT does not revert to the previous version and closes the system.
Exiting CCT
To exit CCT, select Exit from the File menu.
Note: You must be in Configuration mode to exit CCT. In the CCT
Commissioning only software, you can exit CCT after you stop
Commissioning.
Steps
Configuration and Simulation Tasks
Configuration and Simulation tasks include the following:
1. Set or import naming and signal preferences and System Selection Wizard
defaults if you plan to add a new system (optional) (Setting and Using
Preferences).
2. Create a new system or open an existing system (Controller Application File)
(Configuring a System).
Note: You may be prompted to upgrade your system when opening an
existing file. For details, see the Upgrading System Files section.
3. Edit a system (Configuring a System):
• Add Inputs and Outputs (optional).
• Edit attributes/parameters.
- Change Input and Output signals (optional).
- Set up peer-to-peer communication on Network Inputs or Network
Outputs (optional).
• Edit the State Table (optional).
• Add custom logic (optional).
4. Simulate a system (Simulating a System).
5. Define hardware (Defining Hardware).
6. Save the Controller Application File (File > Save).
Concepts
System Module and File Upgrades
When you open a Controller Application File (.caf) that requires an upgrade, CCT
automatically displays a dialog box prompting you to either upgrade the modules
or keep the modules at the current version. Depending on the type of upgrade, CCT
displays two different dialog boxes: a dialog box that displays modules that need to
be upgraded and a dialog box that appears if no modules require upgrading. The
following list describes the two dialog boxes:
• system upgrades with module upgrades
If the file requires module upgrades, then a dialog appears displaying a list of
standard modules included as part of the upgrade process. This dialog box also
displays a list of user-modified modules, if any. CCT does not upgrade
user-modified modules. User-modified modules appear in the Control View
with a triangle next to the module.
• system upgrades without module upgrades
If the file does not require module upgrades, then a smaller dialog box appears
prompting you to upgrade the system.
If you choose not to upgrade the modules, the status bar displays the status of
Upgradeable and the functionality of CCT becomes limited. With this limited
functionality, CCT only allows you to:
• edit detail views
• commission the current application
• edit parameters (default values only)
• view the Hardware Definition Wizard
• view the System Selection tree
If necessary, CCT provides a menu option to upgrade your file at a later time
(Tools > Upgrade System).
Backup Files
When you upgrade your system, CCT creates a backup version of the original file
and stores the file in the same directory as the original file. The backup file has the
same name as the original file; however, the backup file has a .bak extension. To
use the backup file, you need to remove the extension from the file name.
Concepts
Object Naming and Signal Preferences
Object naming and signal preferences determine the naming conventions to use
when adding input and output objects to your system (via the System Selection
process or when you manually add inputs and outputs after System Selection). The
names and signals you define in the object naming preferences are used when
adding inputs and outputs during the System Selection process, as well as when
adding them manually in the Control View.
An object name consists of a defined Object Name Prefix and a defined Object
Name Suffix. The object name is created by combining them. For example, the
Object Name Prefix BLDG added to the Object Name Suffix of SP results in an
object name of BLDG-SP. Similar functionality is available to define an expanded
identifier for each object.
1. The UI on VMA1610 and VMA1620 controllers does not support the 4-20 mA signal.
2. Incremental outputs use two binary hardware slots for opening and closing an actuator.
3. Start stop outputs use two binary hardware slots for starting and stopping a device.
4. You can use Relay Outputs to drive incremental/floating 3-wire actuators; however, we
recommend using triac outputs instead of Relay Outputs for the following control loop types:
VAV Flow Control, Airflow, Airflow%, Airflow Diff, Bldg Static, and Duct Static.
Unit Preferences
You can set the units of measurement to use when working in CCT from the New
System dialog box (File > New) during the System Selection process. After setting
the units and closing CCT, CCT remembers the last unit’s setting. The selected
units are used until you change them in the New System dialog box. See Selecting
a System (Creating a New System) in the Configuring a System section.
3. In the drop-down menu to the right of the selected filtering operator, enter the
information to filter or select an item from the list.
4. Click OK. CCT displays the filtered information.
Note: To remove the filter, select All from the drop-down menu for the
desired column.
Note: To narrow the items further, you can filter on other columns.
IMPORTANT: If you are selecting a locale/language for the first time, exit
CCT. Then, open CCT again to automatically populate the language data that
was provided during the installation process.
3. On the Naming tab, type the desired text translation in the Translated Value
column.
4. On the Systems tab, type the desired text translation in the Translated Value
column.
5. On the Views tab, type the desired text translation in the Translated Value
column.
6. On the Selection Trees tab, select a selection tree in the navigation pane and
type the desired text translation in the Translated Value column in the right
pane.
7. Click Save.
8. Click Close.
Details Configuration
The Details dialog box allows you to view and modify the attribute/parameter,
input, output, and hardware details of modules/blocks selected from the Control
View or Logic View. See the Steps section for details on how to perform the
configuration tasks in the Details dialog box. See the User Interface section for a
description of the Details dialog box interface and its contents.
Simulation
After configuring your system, verify your system is configured properly in
Simulation mode. Simulation mode allows you to see your system as though it
were in Commissioning mode. This allows you to test your configuration and
make adjustments before setting up communications to devices and going farther
in the workflow. See the Simulating a System section for information on how to
simulate your system.
Hardware Definition
After configuring your system, define the hardware for your system using the
Hardware Definition wizard. This wizard allows you to define devices such as
FECs and IOMs, map points to hardware slots, and define network settings. See
the Defining Hardware section for details.
Renaming a System
To rename a system:
1. With a system open, select System Rename from the Tools menu. The System
Rename Dialog box appears.
2. In the System Name text box, type the desired name. Illegal characters include:
:*?"<>|/[]#@
3. Click OK.
Note: This option does not change the name of the Controller Application File
(.caf).
Before modifying System Selections, print a copy of the current System Selections
using the System Selection Summary option in the Summary Report Options
dialog box. See Printing Summary Reports in the User Interface section.
To view and modify System Selections:
1. Select a system, open an existing Controller Application File, or upload a
Controller Application File from a device. See the Selecting a System
(Creating a New System), Opening an Existing Controller Application File, or
the Loading Devices sections for details.
2. Click the Select System button in the CCT user interface. The CCT System
Selection Wizard appears with the Mechanical System Selection screen active.
Note: Adding Inputs and Outputs used for monitoring only purposes should
not be done by modifying the System Selection if custom logic or
changes were made after the initial System Selection process. For
information on manually adding modules, see the Creating Custom
Logic (Adding Modules) section.
3. View the mechanical options for your system and make any changes.
Note: You can only make changes to System Selection in Configuration
mode. See the System Selection Tree section for information on tree
behavior and use (for example, using the check boxes, radio buttons,
and the + and - next to a node in the tree to show and hide selections).
4. Click Next. The CCT System Selection Wizard appears with the Control Logic
Selection screen active.
5. View the control logic options for your system and make any changes
(Configuration mode only).
6. If you did not make any changes (or do not wish to apply any of the changes
you made), click Cancel to close the wizard. Clicking Cancel prevents the
selections from being laid down over your previously selected system and
overwriting any customization changes made. Stop here.
Any customization changes made are lost when your selections are laid
down. If you made changes, click Finish. A Rebuild Application Warning
dialog box appears. Click Yes to continue. The CCT software rebuilds your
system and closes the wizard. The system you selected appears in the Control
View of CCT in Configuration mode.
Details
For information on the attribute/parameter, input, and output data of the selected
module, see the Modules section.
To view and modify the Details:
1. Click the Details tab (if applicable and if it is not already active). A table of
attributes/parameters appears in the left pane of the view, and tables of inputs
and outputs appear in the right pane of the view.
Note: The splitter bar between the panes has left and right arrows allowing
you to achieve the desired view. Click the arrows to show/hide the
panes. If you click the splitter bar and drag it to the desired location,
clicking the left/right arrows returns the view to the location you moved
the splitter bar. Clicking the left/right arrows a second time shows/
hides the entire pane.
2. Click Edit.
3. Make changes to the attribute/parameter, input, and output data using the text
boxes and drop-down menus and click Apply.
4. Click Close.
Note: If you modify a custom module to expose ports for BACnet systems, close
and reopen the Controller Application File (.caf) to view the input/output
ports in the Parameters table.
Changing a Connection
To change a connection in the Connections table:
1. Right-click an input or output that has an existing connection and select
Change Connection. All modules that have exposed ports with compatible
units or enumerations sets turn green.
Note: A module output can have more than one connection (fan-out). A
module input cannot have more than one connection (fan-in is not
allowed).
2. Click the desired module highlighted in green. The Port Selection dialog box
appears.
3. Select the input/output port in which to connect from the Port List and click
OK.
Breaking a Connection
To break a connection in the Connections table, right-click an input or output that
has an existing connection and select Break Connection.
Adding a Module
System Selection adds all the necessary modules required for your system. You do
not need to add modules if you are not modifying logic after selecting the system.
See one of the following sections to add modules:
• Adding a Network Input
• Adding an Input
• Adding a Setpoint/Miscellaneous Module
• Adding a State Generation Module
• Adding an Output Control Module
• Adding a Network Output
• Adding an Output
Deleting a Module
To delete a module:
1. Right-click the module to delete and select Delete, or select multiple modules
by holding down the Ctrl key while selecting the modules, then right-click and
select Delete. The Confirm dialog box appears asking you to confirm that you
want to delete the module(s). See the Confirm (Delete) screen section.
2. Click Yes.
Deleting a Block
To delete a block in the Logic View:
1. Right-click the block to delete and select Delete, or select multiple blocks by
holding down the Ctrl key while selecting the blocks, then right-click and
select Delete. The Confirm dialog box appears asking you to confirm that you
want to delete the block(s). See the Confirm (Delete) screen section.
2. Click Yes.
IMPORTANT: Not all logic blocks support the New Port feature. The Logic
section indicates the blocks that support this feature. You can add up to 99 input
connections for blocks that support the New Port feature.
Although the New Port feature may appear for some logic blocks, only use this
feature for the blocks that indicate New Port support as documented in the
Logic section. Using the New Port feature to add ports to blocks that do not
support the feature may break your logic.
Deleting a Connection
See the Logic View screen description in the User Interface section.
To delete a connection line:
1. Right-click the connection line or hidden edge label (numbered circle next to
an Activity Input, Activity Output, block input, or block output: , , or
) and select Delete. The Confirm dialog box appears asking you to confirm
the deletion. See the Confirm (Delete) screen section.
2. Click Yes.
Note: When a hidden edge label indicates multiple connections (for example,
1:5), only the connected added last is deleted. If you need to delete a
specific connection, unhide the connection lines and remove the
appropriate connection.
Tip: To change the label of a column, right-click the column header and select
Change Column Label. The Port Name Dialog appears. Type a name in
the Port label text box and click OK. We recommend leaving this text box
empty so that dynamic naming may be used.
Tip: To add an enumeration input column, right-click the column header and
select Add Enum Column. After adding an enumeration input column,
make sure you select the appropriate enumeration set to use. The default
set is Off/On.
Tip: To add a boolean input column, right-click the column header and select
Add Boolean Column.
Tip: To remove a column, right-click the column header and select Remove
Column. When removing a column that you wish to replace with another,
make sure you remove the existing column first, then add the new
column. For example, to replace the I1 column that has an Off/On
enumeration input with a boolean input column, first remove the existing
I1 column, then add a boolean input column and rename the column to I1.
Tip: To change the enumeration set of a column (including the State column),
right-click the column header and select Change Column Enum Set. The
Enum Set Change Dialog appears. Select the Enum Set and click OK.
Tip: To add a row, right-click a cell and select Insert Row.
Tip: To add 5 rows, right-click a cell and select Insert 5 Rows.
Tip: To add 10 rows, right-click a cell and select Insert 10 Rows.
Tip: To remove a row, right-click a cell and select Delete Row.
Tip: To copy a row, right-click a cell and select Copy Row. The copied row
appears at the end of the table.
Tip: To move a row, right-click a cell and select Move Row Up or Move Row
Down. Or, select a row and use the up or down arrows to the right of the
table.
Panning
See the Logic View screen description in the User Interface section.
To pan in the logic diagram:
1. Click the Pan (hand) button in the Logic View toolbar.
2. Click and hold the cursor down while moving the mouse.
3. Release the hold when you reach the desired location.
4. In the Start Stop Sequencing DA-T table, set the Lighting to Off when the State
is Off and On when the State is On.
Figure 6-22: Start Stop Sequencing DA-T and Lighting State Table
Configuration
1. For Sideloops, there is only one Selection screen called Sideloop Selection. The Previous button is enabled but
does not work. The Next button is disabled. For information on creating sideloops, see the Creating a Sideloop
section.
Object Memory Usage % Displays the memory usage for the controllers.
Copy To Clipboard Copies the selected device’s data to the clipboard for
pasting into another program.
Line Segment
See Configuring the Line Segment Block.
Table 6-56: Line Segment
Field Description
Input Points Lists the inputs associated with the line segment.
Output Points Lists the outputs associated with the line segment.
OK Applies the changes and closes the dialog box.
Cancel Closes the dialog box without applying the changes.
Help Opens the CCT Help system.
1. The number of Input X - Mode(s) fields is determined by the number selected in the Input field.
Mode Selection
See Configuring the MUX Block.
Table 6-58: Mode Selection
Field Description
Mode Allows you to select a value to use for the input mode of a MUX
block.
OK Applies the changes and closes the dialog box.
Cancel Closes the dialog box without applying the changes.
Help Opens the CCT Help system.
Details
See the Details dialog box description in the User Interface section. See Viewing
and Modifying Details.
Port Selection
See Making a Connection and Changing a Connection.
Table 6-64: Port Selection
Field Description
Port List Lists the input/output ports to which you can connect.
OK Applies the changes and closes the dialog box.
Cancel Closes the dialog box without applying the changes.
Help Opens the CCT Help system.
Confirm (Delete)
The Confirm dialog box appears after selecting to delete a module or block. Click
Yes to delete it or No to cancel the deletion. See Deleting a Module, Deleting a
Block, and Deleting a Connection.
Rename (Module/Block)
See Renaming a Module and Renaming a Block.
Table 6-65: Rename (Module/Block)
Field Description
User Name Allows you to type a name for the module/block.
Standard Name Displays a Johnson Controls standard name for the module/block.
OK Applies the name change and closes the dialog box. The name
change appears in the Control View or Logic View.
Cancel Closes the dialog box without applying the change.
Help Opens the CCT Help system.
Job Information
See Entering or Viewing Job Information.
Table 6-67: Job Information
Field Description
Operator Name Allows you to enter or view the name of the operator responsible for
the open Controller Application File (.caf).
Job Name Allows you to enter or view the name of the job associated with the
open Controller Application File (.caf).
Contract Number Allows you to enter or view the contract number associated with the
job and Controller Application File (.caf).
History Allows you to enter or view notes indicating the history of the job and
Controller Application File (.caf).
OK Applies the changes and closes the dialog box.
Cancel Closes the dialog box without applying the changes.
Concepts
Local Controller Display Configuration
You can customize many items particular to the display from the
Tools > Configure Display menu option while in Configuration mode. The
Configure Display menu option allows you to:
• define which points appear on the Display pages (Input/Output View,
Parameter/Setpoint View, and Idle View) and in what order
• define which points are read-only (cannot be commanded using the display)
• edit point user names and descriptions
• set display attributes including contrast and backlight intensity
• select timeout settings
• select authorization including password definition
After configuring the display, you can download the application to the controller
with CCT. The changes then become effective.
4. Click OK. The Local Controller Display configuration is saved. This change
becomes effective after you download the application to the controller. See
Downloading the Application to the Display Device.
Downloading
Concepts
Simulation Overview
When you simulate your system, you are in the Test Mode. You can set the
simulation speed (1-5) and the default values for network inputs and outputs.
Simulation speed allows processes like time delays on Binary Outputs (BO) or
Stroke Times on Actuators to run 5 times as fast. For example, a 60 second delay
timer runs in 12 seconds if the simulation time is set to 5.
Use the start up values to modify the defaulted starting points for all the Network
Inputs and Inputs. The start up values display the values that the Network Inputs
and Inputs use in the system because they are not connected to physical hardware.
Once simulation is running, you can command the values to see how the system
behaves.
Stopping Simulation
To stop the simulation mode:
1. Click Stop Simulation. The Simulation Exit - Confirmation Dialog Box
appears.
2. Click Yes to confirm that you want to stop simulation.
3. If you made changes during Simulation session, a second Confirm dialog box
appears.
4. Click Yes if you want to apply the changes you made during the simulation
session or No to discard the changes.
Commanding Items
To command items:
1. In the Control view, right-click on an item that can be viewed and/or modified.
The right-click menu appears.
2. Select Commands. The parameter/attribute’s specific command dialog box
appears.
3. Make your selections.
4. Click Send or OK depending on which button appears. If you clicked Send, the
command is issued and the dialog box closes and you are finished. If you
clicked OK, a second dialog box appears. Continue to Step 5.
5. Make your selections.
6. Click Send.
Viewing Connections
You can view connections in the Configuration mode, Simulation mode, and
Commissioning mode. See Viewing Connections in the Configuring a System
section for more information.
Viewing Logic
To view logic, on the Action menu, select View Logic.
Note: You can also right-click on a module containing logic that can be
viewed and/or modified. The right-click menu appears. Select View
Logic. The Logic View appears and displays the logic diagram for that
module.
Panning
You pan in the logic view in the Configuration mode, Simulation mode, and
Commissioning mode. See Panning in the Configuring a System section for more
information.
Zooming
You can zoom in the Configuration mode, Simulation mode, and Commissioning
mode. See Zooming in the Configuring a System section for more information.
Printing
You can print in the Configuration mode, Simulation mode, and Commissioning
mode. See Printing the Logic Diagram in the Configuring a System section for
more information.
Simulation Screen
See the Starting Simulation section.
Table 8-71: Simulation Parameters
Field Description
Simulation Speed Allows you to indicate the speed of the simulation. The
speed range is 1-5.
Item Displays the name of the item.
Startup Value Displays the item’s starting value.
Units Displays the item’s units.
OK Applies the changes and closes the dialog box.
Cancel Closes the screen without applying the changes.
Help Opens the CCT Help system.
Concepts
Hardware Definition Wizard
The Hardware Definition Wizard consists of three main sections: controller
selection, point assignment, and network settings. A summary of the three main
selections appears after you complete the main sections. When you define your
hardware assignments, you are assigning items to the device.
Hardware Considerations
When you define your hardware, keep the following points in mind about Network
Sensors (Network Duct Sensors or Network Zone Sensors), Network VSDs, and
VMA Hardware for Integrated Flow and Integrated Actuators.
In addition to these considerations, note that the Network Sensors, Network VSDs,
and Local Controller Displays are SAB devices.
Network Sensors (Network Duct Sensors or Network Zone Sensors)
During the System Selection process, the Temperature Sensor functions can be
defaulted to use Network Sensors based on naming and signal preference settings.
The points do not count towards the Hardware Slot Summary calculation. The
Network Sensor shows up as an SA Bus device in Step 3 of the Hardware
Definition Wizard (where you can set the address).
Network VSDs
During the System Selection process, the key points for variable speed fans or
pumps can be defaulted to use Network VSDs based on naming and signal
preference settings. The points do not count towards the Hardware Slot Summary
calculation. The Network VSD shows up as an SA Bus device in Step 3 of the
Hardware Definition Wizard (where you can set the address). For more
information, see the VSD document referenced in the Related Documents table.
Steps
Defining Hardware
This section includes selecting a device, assigning points, and defining network
settings device.
Selecting a Device
To select a device:
1. Click Define Hardware. The Hardware Definition Wizard opens with the
Controller Selection screen active.
Note: You can also use the Operations menu > Define Hardware to open the
Hardware Definition Wizard.
2. Click Select next to the Field Device row. The Controller Device Selection
Dialog Box appears.
3. Select the desired field device (for example, a VMA1610 or an FEC1610) and
click OK. The Add Device dialog box appears.
Note: If necessary you can filter devices. To filter devices, select an item to
filter from the drop-down menu of the desired column. Only items of
that type appear on the screen. To narrow the items further, you can
filter other columns.
Note: To perform custom filters, select Custom from the drop-down menu,
select the filtering operator, and enter the information to filter.
4. Enter a device name and click OK. The device name appears in the Field
Device text box.
5. Verify the devices you selected meet the requirements of the selected system in
the Hardware Slot Summary. If any of the fields are red, then you need to add
an IOM device (described in Step 6) to support the System Selection.
Assigning Points
CCT automatically assigns the points based on the selections made. Points that it
could not assign appear in the Unassigned Points list. You need to assign the points
in the Unassigned Points list. You cannot proceed until all points are assigned.
To assign points:
1. Assign your points. Use the right arrow to assign a point to an object. Use the
left arrow to unassign a point from an object. Use drag-and-drop functionality
to move a point up and down the Assigned Points list.
Note: An alert message appears if you attempt to move a point to an invalid
location and the point remains in its original location.
Note: The slider bar between the Unassigned Points and Assigned Points lists
has left and right arrows allowing you to achieve the desired view.
Click the arrows to show/hide the lists. If you click the slider bar and
drag it to the desired location, clicking the left/right arrows returns the
view to the location you moved the slider bar. Clicking the left/right
arrows a second time shows/hides the entire list.
2. Click Next. The Network Settings screen appears. See Defining Network
Settings.
1. You can use Relay Outputs to drive incremental/floating 3-wire actuators; however, we
recommend using triac outputs instead of Relay Outputs for the following control loop
types: VAV Flow Control, Airflow, Airflow%, Airflow Diff, Bldg Static, and Duct Static.
Concepts
Load Wizard
The Load Wizard allows you to perform uploads and downloads to a device. The
Load Wizards determines the network connection method by the Connections-
either Ethernet NAE Passthru or Bluetooth Wireless.
Upload
You can upload devices using the Load Wizard. You are able to discover available
devices. The Discover option is only available when you upload devices.
Download
You can download devices using the Load Wizard. You can only download fully
mapped (hardware assigned) systems.
Connections
Bluetooth Wireless
The Bluetooth Wireless connection mode consists of three steps: Load Type,
Device Selection, and Summary.
Boot Code
The boot code is the start up code for the device. The boot code acts like a mini-
operating system in the device and supports the communications necessary to
download the Main Code. The boot code is a minimal size version of the main
code.
Main Code
The main code acts like an on-board library and gives the device information on
the modules. You need to update the main code whenever there is a change to a
module (used in the Application Code). Together the boot code and main code
make up the firmware.
Application Code
The application code tells the device the actual code/sequence and priorities of the
control strategy created in CCT. For example, definitions of the Inputs, Outputs,
Control Logic, and Network variables.
Concepts
System and Device Connections
There are two connection options available: Ethernet NAE Passthru and Bluetooth
Wireless.
Test Mode
The Test Mode allows you to command inputs, modules, and outputs to assist in
commissioning your system. During Test Mode, the controller being
commissioned is taken offline from the supervisory system to ensure that only the
commands from the CCT Commissioning session override the inputs and outputs.
You must exit Test Mode before you exit the Commissioning mode. See the
Working with the Test Mode section.
Commissioning a Device
To commission a device:
1. Click Commission. The Commission Device Wizard appears.
2. Choose the application type and the connection point information.
3. Click Next.
4. From the Device Selection screen, select a device.
Note: If the application type is Application in Controller and no devices
appear on the Device Selection screen, click Discover.
5. Click Next. The Commission Summary appears.
6. Click Finish. The application appears to be commissioned in the Control View.
Note: If the application type is Application in Controller, CCT uploads the
application from the selected device.
Commanding Items
You can command items in the Commissioning mode and Simulation mode. You
must be in Test mode to issue commands while commissioning. The controller
goes offline and the field point displays ???? as well as the value sent using the
Commands option. The commands you perform in Test mode are temporary. CCT
releases these commands when you leave Test mode in Commissioning mode. The
controller goes online, and the point value returns to its value. See Commanding
Items in the Simulating a System section.
Viewing Connections
You can view connections in the Configuration mode, Simulation mode, and
Commissioning mode. See Viewing and Modifying Connections in the
Configuring a System section for more information.
Modifying Offsets
To modify offsets:
1. Right-click on an input. The right-click menu appears.
2. Select Setup. The Setup Screen for Inputs appears.
3. Enter the desired offset value.
4. Click OK.
OR
OR
OR
Use the Trace Mode button to show and hide the Connection Lines in the
logic diagram.
Panning
You can pan in the logic view in the Configuration mode, Simulation mode, and
Commissioning mode. See Panning in the Configuring a System section for more
information.
Zooming
You can zoom in the Configuration mode, Simulation mode, and Commissioning
mode. See Zooming in the Configuring a System section for more information.
Printing
You can print the logic diagram in the Configuration mode, Simulation mode, and
Commissioning mode. See Printing the Logic Diagram in the Configuring a
System section for more information.
Modifying Outputs
You can view and modify output attributes/parameters in the Configuration mode,
Simulation mode, and Commissioning mode. See Viewing and Modifying
Parameters in the Configuring a System section.
Restoring Flow
To restore the flow:
1. Click the Flow Restore button on the Balancer tab. The Flow Restore
Command dialog box appears asking if you want to send the restore flow
command.
2. Click Send.
Return to the Using the Balancer Tab section.
Polarity Allows you to enter the polarity for the selected output.
Object Memory Usage % Displays the memory usage for the controller.
Balancer Tab
The Balancer tab user interface is described in the Control View Screen topic of the
User Interface section. See the Using the Balancer Tab section for information on
tasks to perform in the Balancer tab.
The following dialog boxes appear when performing the various tasks in the
Balancer tab:
• Auto Calibrate Command Dialog Box
• Flow Override Command Dialog Box
• Flow Restore Command Dialog Box
• Calculate K-Factors Command Dialog Box
Concepts
Box Flow Test Overview
You can run the Box Flow Test on a single duct VAV application after you
download the initial application. The air handling unit must be running to
implement the Box Flow Test. After completion of the test, the error summary
report shows which devices and applications were not installed or set up correctly.
The Box Flow Test consists of two tabs: Setup/Progress and Results. You can
Discover the test results from the device. After you initiate the Box Flow Test, you
can disconnect from the network and return later to collect and review the results.
Reading Results
To read results after the Box Flow Test completes:
1. Select the devices (if they are not already selected).
2. Click Read Results. The Results tab enables.
Note: If the test is still in progress, it displays in the Setup/Progress tab in the
State column. Wait until the test completes and read the results again.
Applications 285
Application Descriptions
The application sections contain the following topics:
• Application Introduction
• Core Logic Modules
• Mechanical System Selection
• Control Logic Selection
Note: The Sideloop application has one Sideloop Selection screen instead of the
Mechanical System Selection and Control Logic Selection screens.
Application Introduction
This section describes the application and provides links to its detailed
descriptions.
Modules (MASD)
All Mixed Air Single Duct Applications use the core logic listed below.
Network Inputs
• APP-MODE (Application Mode)
See the Network Inputs section.
State Generation
• Application Mode Determination: This module separates out the Water
Flush application mode for separate connection to State Selection and
passes the remaining application modes to State Selection.
• Water System Flush Pass Through: This module passes the Water Flush
system mode to a separate State Selection input so that when water flush is
requested, the valves always open.
• Mixed Air Single Duct HR Sequencing
Output Control
• Heating Required LV
• Cooling Required LV
Fans (MASD)
These selections provide the logic for the main fans.
The selection options for Fans are:
Supply Fan
• Single Speed
• Variable Speed
- Two Duct Static Pressure Sensors
• Fan Status
- Loss of Airflow Strategy
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
• Alarm Management
- Lockout Switch
- Frequency Converter Fault
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Motor Overload Tripped
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Belt Alarm
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
Modules (MADD)
All Mixed Air Dual Duct Applications use the core logic listed below.
Network Inputs
• APP-MODE (Application Mode)
See the Network Inputs section.
Inputs
• CD-T (Cold Deck Temperature)
See the Inputs section.
State Generation
• Start Stop Sequencing (AHU Mixed Air)
• Application Mode Determination: This module separates out the Water
Flush application mode for separate connection to State Selection and
passes the remaining application modes to State Selection.
• Water System Flush Pass Through: This module passes the Water Flush
system mode to a separate State Selection input so that when water flush is
requested, the valves always open.
• Mixed Air Cold Duct Sequencing
Output Control
• Heating Required LV
• Cooling Required LV
Fans (MADD)
These selections provide the logic for the main fans.
The selection options for Fans are:
Supply Fan
• Single Speed
• Variable Speed
• Fan Status
- Loss of Airflow Strategy
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
• Alarm Management
- Lockout Switch
- Frequency Converter Fault
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Motor Overload Tripped
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Belt Alarm
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
Modules (OASD)
All 100% Outdoor Air Single Duct Applications use the core logic listed below.
Network Inputs
• APP-MODE (Application Mode)
See the Network Inputs section.
Inputs
• DA-T (Discharge Air Temperature)
See the Inputs section.
State Generation
• 100 OA Start Stop Sequencing
• Application Mode Determination: This module separates out the Water
Flush application mode for separate connection to State Selection and
passes the remaining application modes to State Selection.
• Water System Flush Pass Through: This module passes the Water Flush
system mode to a separate State Selection input so that when water flush is
requested, the valves always open.
• 100 OA Single Duct Sequencing
Setpoint/Miscellaneous
• Discharge Air Setpoint Determination
Output Control
• Heating Required LV
• Cooling Required LV
Fans (OASD)
These selections provide the logic for the main fans.
The selection options for Fans are:
Supply Fan
• Single Speed
• Variable Speed
- Two Duct Static Pressure Sensors
• Fan Status
- Loss of Airflow Strategy
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
• Alarm Management
- Lockout Switch
- Frequency Converter Fault
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Motor Overload Tripped
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Belt Alarm
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
Modules (OADD)
All 100% Outdoor Air Dual Duct Applications use the core logic listed below.
Network Inputs
• APP-MODE (Application Mode)
See the Network Inputs section.
Inputs
• CD-T (Cold Deck Temperature)
See the Inputs section.
State Generation
• 100 OA Start Stop Sequencing
• Application Mode Determination: This module separates out the Water
Flush application mode for separate connection to State Selection and
passes the remaining application modes to State Selection.
• Water System Flush Pass Through: This module passes the Water Flush
system mode to a separate State Selection input so that when water flush is
requested, the valves always open.
• 100 OA Cold Duct Sequencing
Output Control
• Heating Required LV
• Cooling Required LV
Fans (OADD)
These selections provide the logic for the main fans.
The selection options for Fans are:
Supply Fan
• Single Speed
• Variable Speed
• Fan Status
- Loss of Airflow Strategy
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
• Alarm Management
- Lockout Switch
- Frequency Converter Fault
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Motor Overload Tripped
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Belt Alarm
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
Modules (RTU)
All Rooftop Applications use the core logic listed below.
Network Inputs
• APP-MODE (Application Mode)
See the Network Inputs section.
State Generation
• Application Mode Determination: This module separates out the Water
Flush application mode for separate connection to State Selection and
passes the remaining application modes to State Selection.
• Water System Flush Pass Through: This module passes the Water Flush
system mode to a separate State Selection input so that when water flush is
requested, the valves always open.
• Mixed Air Single Duct HR Sequencing
Output Control
• Heating Required LV
• Cooling Required LV
Fans (RTU)
These selections provide the logic for the main fans.
The selection options for Fans are:
• Supply Fan - Single Speed
- Fan Status
- Loss of Airflow Strategy
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
Modules (MADD-MZ)
The Air Handling Unit configuration portion of Multizone (Mixed Air Dual Duct)
applications use the core logic listed below. The following modules are loaded if
the AHU Only or AHU + Zones configuration options are selected.
Network Inputs
• APP-MODE (Application Mode)
See the Network Inputs section.
Inputs
• CD-T (Cold Deck Temperature)
See the Inputs section.
State Generation
• Start Stop Sequencing (AHU Mixed Air)
• Application Mode Determination: This module separates out the Water
Flush application mode for separate connection to State Selection and
passes the remaining application modes to State Selection.
• Water System Flush Pass Through: This module passes the Water Flush
system mode to a separate State Selection input so that when water flush is
requested, the valves always open.
• Mixed Air Cold Duct Sequencing
Output Control
• Heating Required LV
• Cooling Required LV
Fans (MADD-MZ)
These selections provide the logic for the Air Handling Unit fans.
The selection options for Fans are:
Supply Fan – Single Speed
• Fan Status
- Loss of Airflow Strategy
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
• Alarm Management
- Lockout Switch
- Motor Overload Tripped
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
- Belt Alarm
• Automatic Restart
• Manual Restart
- Unit Reset Switch (BI)
Misc (FC)
The Miscellaneous selections provide binary inputs for the Energy Hold Off
Determination and Unit Enable Determination State Generators.
The selection options for Miscellaneous are:
• Energy Hold Off Switch: This option allows the unit to shut down based on
the energy hold off Hardware Input (BI). If Energy Hold Off is selected in the
Optional Features section, then the Hardware Input or the Network Input can
activate the mode. This feature is typically used to shut down the temperature
and airflow control when a window or loading door is open (for example, a
window switch).
• Unit Enable Switch: This option determines whether the application operates
based on the Hardware Input (BI). If Unit Enable is selected in the Optional
Features section, then when the Network Input does not have a valid command
from the network, it is considered unreliable (and the unit is enabled). If both
BI and BV are selected, the state of both must be Enable for the unit to operate
(that is, either input can be in a shutdown state to cause the unit to stop).
Modules (VAV-SD)
The core set of modules created for all Single Duct applications are the zone
temperature and flow logic required for a Pressure Independent Cooling Only
application. Specific selections in the Single Duct tree provide the required Inputs,
Outputs, and Network Input connections for the core logic set and integrate the
specific Output Controller options for Box Heating, Supplemental Heating, Series
or Parallel Fans, and Exhaust Boxes.
The following is the list of modules created by the core logic.
Network Inputs
• AUTOCAL-C (Auto Calibration Command): This module is a Network
Input for the Autocalibration Sequence State Generator.
• OA-PERCENT: This module is a Network Input that provides an interface
to the Minimum Flow Determination module to bias the Supply Damper
based on fresh air requirements for the zone under control.
• SYSTEM-MODE: This module is a Network Input for the System Mode
Determination State Generator used to force the unit into a mode of
operation.
See the Network Inputs section.
Setpoint/Miscellaneous
• Minimum Flow Determination: This module determines the minimum flow
for the VAV box and sets up the flow setpoint parameters for unoccupied
and warm-up modes.
• Supply Damper Control Stroke Time: This module provides the stroke time
for the Supply Damper.
• Supply Flow Calculation: This module calculates the supply flow based on
the Supply Velocity Pressure.
• ZN-T Setpoint Determination: This module determines the Effective
Heating and Cooling Setpoints.
Occupancy (VAV-SD)
The selection options for Occupancy are:
• Always Occupied: This option sets the default value of Occupied for the ZN-T
Setpoint Determination and Balancer Override modules to Occupied.
• Scheduled Occupancy: This option creates the interface for the Supervisory
system scheduling logic.
- Override Support: This option creates the local override interfaces from
optional Occupancy Sensors or Networked Sensor Temporary Occupancy
interfaces.
Modules (VAV-DD)
The core set of modules created for all Dual Duct applications are the zone
temperature and basic flow logic. Specific selections in the tree provide the
required Inputs and Outputs connections for this core set and add the necessary
Output Controllers for Supplemental Heating and Exhaust Box Integration.
All Dual Duct VAV Applications use the following base set of modules:
Network Inputs
• AUTOCAL-C (Auto Calibration Command): This module is a Network
Input for the Autocalibration Sequence State Generation.
• SYSTEM-MODE: This module is a Network Input for the System Mode
Determination State Generator used to force the unit into a mode of
operation.
See the Network Inputs section.
Setpoint/Miscellaneous
• Minimum Flow Determination - Dual Duct: This module determines the
minimum flows for the VAV box and sets up the flow setpoint parameters
for unoccupied and warm-up modes.
• Supply Flow Calculation
• ZN-T Setpoint Determination: This module determines the Effective
Heating and Cooling Setpoints.
State Generation
• Autocalibration Sequence: This module provides the signals to close the
damper and recalculate the offset for the flow sensor.
• Balancer Override DD: This module is loaded for applications without an
Exhaust Damper to set up the Supply Dampers Area, K-Factor, and the
Occupied Flow parameters. This module also interfaces with specific
Network Sensor models used by the Balancing Contractor.
Note: CCT provides specific Balancer Override State Generators for
applications with and without Exhaust Box logic.
• Balancer Override DDX: This module is loaded for applications with an
Exhaust Damper.
• System Mode Determination: This module separates out the Water Flush
system mode for separate connection to State Selection and passes the
remaining system modes to State Selection.
• VAV-ZN-T Sequencing: This module determines which device should be
operating to control the space temperature.
Modules (CC)
All Central Cooling applications use the core logic listed below.
Network Inputs
• OA-T (Outdoor Air Temperature): This module is loaded if the Outdoor
Air Temperature (OA-T) optional sensor is not selected.
• SYSTEM-EN (System Enable)
See the Network Inputs section.
Setpoint/Miscellaneous
• PMPDOWN-TIME (Pump Down Time): This floating constant delays
the pump stop command allowing the primary cooling equipment to
maintain flow after shutdown.
State Generation
• Chilled Water System Enable: This module enables and disables other
modules based on the SYSTEM-EN and Outdoor Air Temperature values.
Modules (CH)
All Central Heating applications use the core logic listed below.
Network Inputs
• SYSTEM-EN (System Enable): This network input enables the heating
system via network command or schedule.
• OA-T (Outdoor Air Temperature): This network input is loaded unless
the system has an OA-T sensor.
See the Network Inputs section.
Setpoint/Miscellaneous
• PMPDOWN-TIME (Pump Down Time): This floating constant delays
the pump stop command allowing the primary heating equipment to
maintain flow after shutdown.
State Generation
• Hot Water System Enable: This module enables and disables other
modules based on the SYSTEM-EN and Outdoor Air Temperature values.
Modules 773
Module Descriptions
The Setpoint Determination/Misc, State Generators, and Output Controller module
sections contain the following topics to describe the modules:
• Module Category Introduction
• Module Group Overview
• Module Overview
• Module Use in Applications
• Attributes
• Primary States
• Reliability
If a section does not apply to a particular module, it is not included.
The Network Inputs, Inputs, Network Outputs, and Outputs sections contain
similar information, but cover the modules as a general group.
Module Overview
This section describes the module’s operation, behavior, and use. This section also
indicates if you can view and modify the modules in this group’s logic using CCT
software.
Modules 775
Primary States
This section describes Normal transitions for complex modules. When applicable,
this section also includes a Command Hierarchy table showing the common inputs
and states.
Reliability
This section describes the module’s handling of the reliability of its inputs
(paragraph or table format).
Inputs 789
790 CCT Help: Modules
Chapter 24: CCT Help: Modules
Setpoint Determination/Misc
Introduction
The Setpoint Determination/Misc group includes modules that provide setpoints or
input to other modules (typically not state selection).
Setpoint Determination/Misc modules fall into one of the following categories:
• Central Plant
• Device Enable
• Device Mode Determination
• Fan Lockout
• Flow Calculation
• Setpoint Calculation
• Sideloop Signal Conditioning
• Timing
• Damper Trouble Detection
See the Upgrading System Files section for a list and description of the module and
System Selection changes that were made since the last release of CCT.
Add-8
Overview
The Add-8 module is responsible for adding up to eight inputs. This module
accepts as inputs an Input 1 through Input 8 and has one output. This module adds
Input 1 through Input 8 with one output as the total.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Add-8)
• Attributes (Add-8)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Subtract module subtracts two inputs. This module accepts as inputs Input 1
and Input 2, and has one output. This module subtracts Input 1 from Input 2 and
the differential is the output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Subtract)
• Attributes (Subtract)
Attributes (Subtract)
The following table describes the attributes used by the Subtract modules:
Table 24-106: Subtract Attributes
Name Type1 Description Default Value
CHWTEMP-DIFF or V Indicates the differential of Input 1 0
CHWFLOW-DIFF subtracted from Input 2.
[Output (Float)]
Input 1 Indicates the floating variable from which 0
Input 2 is subtracted.
Input 2 Indicates the variable that is subtracted 0
from Input 1.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Economizer Availability
Overview
The Economizer Availability module defines the suitability of the economizer
based on a number of possible inputs (including outdoor air temperature and
humidity, return air temperature, and humidity), a hardware switch commonly
know as Enthalpy Switch, and a network command that most likely originates in a
supervisory controller.
You can view and modify the modules in this group’s logic using CCT software;
however, the Free Cooling Availability contained within this module that performs
much of the module’s calculations cannot be viewed or modified.
For more information on this module, see the following sections:
• Module Use in Applications (Economizer Availability)
• Attributes (Economizer Availability)
• Reliability (Economizer Availability)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Economizer Availability RA-T Compare module compares the outdoor air
temperature with the return air temperature to determine economizer availability.
If the return air temperature is greater than the outdoor air temperature by the
Temp Difference SP value and the outdoor air temperature is less than the Change
Over Temperature minus the Change Over Differential, then the economizer is
available. When the difference drops below this value by the Temp Difference
Differential, the economizer is not available. If the outdoor air temperature rises
above the Change Over Temperature, the economizer is not available.
You can view and modify the modules in this group’s logic using CCT software;
however, the Free Cooling Availability contained within this module that performs
much of the module’s calculations cannot be viewed or modified.
For more information on this module, see the following sections:
• Module Use in Applications (Economizer Availability RA-T Compare)
• Attributes (Economizer Availability RA-T Compare)
• Reliability (Economizer Availability RA-T Compare)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module monitors the status of the Airflow Proving Switch as compared to the
commanded Fan Mode. The module adds some error checking to remove short
glitches in the signal and also indicates a fault should the fan command be on for a
length of time without any indication of proof of flow.
You can view and modify the modules in this group’s logic using CCT software,
but the Airflow Proving FSM contained within cannot be modified.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Status Determination)
• Attributes (Flow Status Determination)
• Primary States (Flow Status Determination)
• Reliability (Flow Status Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates a True, False, or Fault state to indicate to a parallel staged
device that the airflow requirements have been met. For a parallel device (a
parallel fan in a single duct VAV box application), the only requirement to enable
the device is that the fan is commanded on.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Staged Device Enable Determination Parallel)
• Attributes (Staged Device Enable Determination Parallel)
• Primary States (Staged Device Enable Determination Parallel)
• Reliability (Staged Device Enable Determination Parallel)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the True, False, or Fault state to indicate to a staged device
that the airflow requirements have been met. If either the fan command (on/off) is
on or the supply flow is greater than the minimum flow value, the state is True.
This module is designed for use with VAV boxes that contain a heating coil in the
discharge air stream (series). This module can be used for VAV boxes with or
without a fan. If a fan does not exist, the default Fan Mode value is Off and the
default for the State does not change if the Fan Mode is not connected.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Staged Device Enable Determination Series)
• Attributes (Staged Device Enable Determination Series)
• Primary States (Staged Device Enable Determination Series)
• Reliability (Staged Device Enable Determination Series)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate alarm state for a device. The Status Alarm
Determination module monitors the command and flow status to determine
whether the current state is Normal or Alarm.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Status Alarm Determination)
• Attributes (Status Alarm Determination)
• Primary States (Status Alarm Determination)
• Reliability (Status Alarm Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Summer Winter Mode module is designed to switch a unit that controls a
2-pipe coil between summer and winter operation based on the supply water
temperature. This module accepts supply water temperature, setpoint, and
differential as inputs. The module has a state output. If the supply water
temperature is greater than the setpoint, the unit operates in the winter mode, and if
the supply water temperature is less than the setpoint (with a differential), the unit
operates in the summer mode. The module use the last reliable water temperature
when the water temperature becomes unreliable.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (SummerWinter Mode Determination)
• Attributes (SummerWinter Mode Determination)
• Primary States (SummerWinter Mode Determination)
• Reliability (SummerWinter Mode Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module determines the effective WarmupCooldown status for single duct
VAV applications by evaluating the Network Input and the automatic Warmup
mode based on the supply air temperature. The module issues a warmup status
ANY TIME the SA-T (Supply Air Temperature) meets the requirements necessary
for warmup (that is, both SA-T and ZN-T are reliable and SA-T > [ZN-
T+Differential]). If both SA-T and ZN-T are reliable and the SA-T is not warm
enough to trigger warmup, the WC-C (WarmupCooldown) network input is not
allowed to force warmup (remains in Normal). The module state output is the
effective WarmupCooldown mode for the application.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (WarmupCooldown Determination)
• Attributes (WarmupCooldown Determination)
• Primary States (WarmupCooldown Determination)
• Reliability (WarmupCooldown Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Unocc Cooling Fan Lockout module locks out the fan in the unoccupied mode
when there is no cooling available. This module’s Boolean output indicates
whether or not the fan can run.
For more information on this module, see the following sections:
• Module Use in Applications (Unocc Cooling Fan Lockout)
• Attributes (Unocc Cooling Fan Lockout)
• Reliability (Unocc Cooling Fan Lockout)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Unocc Heating Fan Lockout module locks out the fan in the unoccupied mode
when there is no heating available. This module’s Boolean output indicates
whether or not the fan can run.
For more information on this module, see the following sections:
• Module Use in Applications (Unocc Heating Fan Lockout)
• Attributes (Unocc Heating Fan Lockout)
• Reliability (Unocc Heating Fan Lockout)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Flow Calculation
Overview
This module calculates flow from a differential pressure input. It is applicable for
use with pitot tube sensors that are commonly provided with variable air volume
terminal units.
This module supports automated offset (that is, zero flow) calibration of the
differential pressure sensor input. The application can take advantage of this by
closing the dampers or equalizing the intakes of the differential pressure sensor
input and then setting the Autocalibrate Now input temporarily to True.
As long as this input is True, the module calculates the average Autocalibration
Offset that would cause the flow calculation Effective dP to equal zero. This
average is done recursively using the EWMA function that does a simple average
for the first 1000 samples. Typically, the Autocalibrate Now input is set True for
only 5 to 10 seconds at a time and must reset to False by the connected source.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Calculation)
• Attributes (Flow Calculation)
• Pickup Gain Calculations (Flow Calculation)
• Reliability (Flow Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module subtracts two flows and attaches the reliability of the two inputs onto
the result. (The resultant reliability is unreliable if either of the inputs is
unreliable).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Differential Calculation)
• Attributes (Flow Differential Calculation)
• Reliability (Flow Differential Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module adds two flows and attaches the reliability of the two inputs onto the
result. (The resultant reliability is unreliable if either of the inputs is unreliable).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Sum Calculation)
• Attributes (Flow Sum Calculation)
• Reliability (Flow Sum Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module sets the minimum damper position to the Occ Min Damper Value
when the Occupancy is Occupied or Bypass and sets it to zero otherwise.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Minimum Position Determination)
• Attributes (Damper Minimum Position Determination)
• Reliability (Damper Minimum Position Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is designed to reset the damper minimum position based on the space
CO2. The module has an input for the space CO2, two inputs to define the CO2
reset band (CO2 Reset A and CO2 Reset B), and two inputs for damper minimum
position and the low and high ends of the band (Min Pos Low Setpoint and Min
Pos High). This module has an output for the Damper Minimum Position.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Minimum Position Reset by CO2)
• Attributes (Damper Minimum Position Reset by CO2)
• Reliability (Damper Minimum Position Reset by CO2)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Discharge Air Setpoint Determination module sets the DA-T Setpoint based
on the operating modes of the air handler. The module accepts as input the
Unoccupied Status, the WarmupCooldown state, the occupied setpoint, the
unoccupied heating and cooling setpoints, and a default DA-T setpoint. The
EFFDAT-SP (Discharge Air Setpoint) is set to the Occ Setpoint, the
DATHTGUNOCC-SP (Unocc Heating Setpoint), or the DATCLGUNOCC-SP
(Unocc Cooling Setpoint) based on the WarmupCooldown input first, and the
Unocc Status input if WarmupCooldown does not equal Warmup or Cooldown.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Discharge Air Setpoint Determination)
• Attributes (Discharge Air Setpoint Determination)
• Reliability (Discharge Air Setpoint Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is designed to reset the discharge air temperature setpoint based on a
reset process variable (typically the outdoor air temperature). The module has two
inputs that define the temperature reset band (OA Reset A and OA Reset B), and
two inputs that specify the DA-T setpoints at each end of that band (Discharge Air
Low Limit and Discharge Air High Limit). This module has an output for the
DAT-SP (Discharge Air Temperature Setpoint).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Discharge Air Setpoint Reset)
• Attributes (Discharge Air Setpoint Reset)
• Reliability (Discharge Air Setpoint Reset)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for generating the differential flow setpoint based upon
the occupancy input.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Differential Setpoint Calculation)
• Attributes (Flow Differential Setpoint Calculation)
• Reliability (Flow Differential Setpoint Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module calculates the setpoint offset based on the outdoor air temperature.
The Setpoint Reset by OA-T module has an input for the outdoor air temperature,
two inputs for the outdoor air setpoints (OA High Setpoint and OA Low Setpoint),
and two inputs for the offset span (Setpoint and Setpoint Span). The output of this
module is the Setpoint Offset.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Setpoint Reset by OA)
• Attributes (Setpoint Reset by OA)
• Reliability (Setpoint Reset by OA)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Summer Winter Compensation module provides local calculation of setpoint
shifts based on the outdoor air temperature. This method is sometimes used for
units serving building entry areas (lobbies, vestibules, and more) to save energy by
allowing the temperature setpoint to shift closer to the outdoor conditions.
Alternatively, in poorly insulated buildings, the heating shift may increase the
temperature setpoint in all exterior spaces to compensate for cold wall
temperatures.
The ZN-T Setpoint Determination module uses these shifts as well as other
influences to calculate the zone heating setpoints and zone cooling setpoints.
When the Outdoor Air Temp is Reliable, the effective shift values are calculated.
Otherwise, the shift values are set to zero.
In the Winter example, the Winter Setpoint determines the Outdoor Air
Temperature at which the module begins shifting the setpoints. The Winter Gain is
the gain of the shift expressed in the number of degrees shift per number of degrees
deviation from the Outdoor Air Temperature. The Winter Change Limit limits the
maximum amount of shift allowed (positive or negative).
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Summer Winter Compensation)
• Attributes (Summer Winter Compensation)
• Reliability (Summer Winter Compensation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for generating minimum and maximum deck flows for
both the cold and hot decks of a constant volume dual duct application. The
module accepts the minimum deck flow setpoints and the maximum box flow
setpoint. The module outputs individual deck minimum and maximum flow
setpoints.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (VAV Dual Duct Constant Flow Endpoint
Calculation)
• Attributes (VAV Dual Duct Constant Flow Endpoint Calculation)
• Reliability (VAV Dual Duct Constant Flow Endpoint Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module determines the minimum deck flow setpoints (heating and cooling)
according to the occupied and warmupcooldown conditions within a VAV dual
duct application. The module accepts Occupancy, WarmupCooldown modes, and
flow setpoints. The module outputs the minimum deck flows. During conditions of
Standby, the unoccupied flow setpoints are issued. During conditions of
Unoccupied, the unoccupied flow setpoints are also issued unless there is a
warmup/cooldown mode. During conditions of Occupied or Bypass, the occupied
flow setpoints are issued.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (VAV Dual Duct Minimum Flow Determination)
• Attributes (VAV Dual Duct Minimum Flow Determination)
• Reliability (VAV Dual Duct Minimum Flow Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates minimum and maximum deck flows for both the cold and
hot deck of a standard dual duct application. These values are based upon the input
minimum and maximum flows and ventilation requirements.
The module is designed to meet the following three conditions (listed from highest
priority):
• Do not exceed the user entered maximum flows. There is a heating maximum
flow and a cooling maximum flow and under the appropriate heating/cooling
conditions, these total flows are not exceeded.
• Do not provide individual deck flows that are less than the user entered
minimum flows. This condition is obeyed unless it causes the condition above
to be exceeded. In this situation, the minimum flows is adjusted down.
• Meet the outdoor air requirements. This condition is met as long as it does not
cause the above conditions to be exceeded. As part of this condition, the
outdoor air requirements may be compromised when the sum of the two OA
percentages is less than 10 percent. This is done to ensure that the individual
deck minimums change smoothly as the outdoor air percentages change. For
example, a change from 2% to 3% in outdoor air percent does not cause the
minimum flow rate to jump from 500 cfm to 333 cfm.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (VAV Dual Duct Variable Flow Endpoint
Calculation)
• Attributes (VAV Dual Duct Variable Flow Endpoint Calculation)
• Reliability (VAV Dual Duct Variable Flow Endpoint Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for determining the minimum flow setpoint (heating
and cooling) according to the occupied and warmup/cooldown conditions. During
conditions of Standby, the unoccupied flow setpoints are issued. During conditions
of Unoccupied, the unoccupied flow setpoints are also issued unless there is a
warmup/cooldown mode. During conditions of Occupied or Bypass, the occupied
flow setpoints are issued, including adjustments made by the reset scheme.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (VAV Single Duct Minimum Flow
Determination)
• Attributes (VAV Single Duct Minimum Flow Determination)
• Reliability (VAV Single Duct Minimum Flow Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The configuration options for the ZN-T Setpoint Determination module are done
with a combination of system selection choices under the Temperature/Setpoint
Adjust section of the selection tree and the module’s configuration settings in the
Details dialog box. The resulting configuration provides the Zone Setpoints for
Heating and Cooling used by any applications configured for a zone temperature
control strategy.
The following block diagram highlights the standard and optional interfaces to this
module.
Figure 24-26: ZN-T Setpoint Determination Interfaces
If these values are never adjusted, the system uses the Occupied, Standby, and
Unoccupied Heating or Cooling Setpoints as the Effective Heating and Cooling
Setpoints. This occurs based on the state generated from the Occupancy Mode
Determination State Generation module.
As you change the Network or Local Zone Setpoint, the module automatically
derives an Absolute Setpoint Offset Value (AbsOffset). The Absolute Setpoint
Offset (AbsOffset) is calculated as the difference between the Network or Local
Setpoint and the mean of the Occupied Heating and Occupied Cooling setpoints.
Standby Heating Shift2 Contains the value for shifting standby heating 0.0 Deg C, 0.0 Deg F
setpoints.
Unocc Cooling Shift2 Contains the value for shifting unoccupied 0.0 Deg C, 0.0 Deg F
cooling setpoints.
Unocc Heating Shift2 Contains the value for shifting unoccupied 0.0 Deg C, 0.0 Deg F
heating setpoints.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
2. Shift attributes are set by the Summer Winter Compensation module.
Overview
This module averages the inputs to produce the output. The module accepts two
inputs and outputs the average of the inputs. The user can add more inputs to the
module.
You can view and modify the modules in this group’s logic using CCT software.
To see this module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Average Inputs)
• Reliability (Sideloop Average Inputs)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module selects the maximum value of the inputs to produce the output. The
module accepts two inputs and outputs the maximum of the inputs. The user can
add more inputs to the module.
You can view and modify the modules in this group’s logic using CCT software.
To see this module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Maximum Selector)
• Reliability (Sideloop Maximum Selector)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module selects the minimum value of the inputs to produce the output. The
module accepts two inputs and outputs the minimum of the inputs. You can add
more inputs to the module.
You can view and modify the modules in this group’s logic using CCT software.
To see this module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Minimum Selector)
• Reliability (Sideloop Minimum Selector)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module adds the inputs together to produce the output. The module accepts
two inputs and outputs the sum of the inputs. The user can add more inputs to the
module.
You can view and modify the modules in this group’s logic using CCT software.
To see this module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Sum Inputs)
• Reliability (Sideloop Sum Inputs)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This section describes the Last Value modules of the Setpoint Determination/Misc
type. For information on the Last Value modules of the Output Control type, see
Timing in the Output Controller section.
The Last Value module holds the value that its input had at the end of the previous
execution (of the Control System) for use by the current execution. This module is
used when you want to compare the current value of a variable with the value from
the last execution. If this module is not operated continuously (for example, placed
in the state section of a hybrid activity), it starts at its Default Value when
re-enabled. One additional constraint is that connections from Hybrid Activity
Inputs are not allowed to be made directly to the Input of the Last Value module in
one of its State Sections. If such logic is needed, a no-op component (such as
adding zero to a float) should be connected between the Input and the Last Value.
This is required because the Hybrid Activity inputs are considered part of the
Event Section and are therefore earlier in the sequence order than all State Section
components.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Last Value)
• Attributes (Last Value)
• Reliability (Last Value)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Damper Trouble Detection module determines the trouble status of the
damper control within VAV applications. This module provides position detection
for VAV dampers and also provides an indication of failure due to the damper not
opening or closing properly. This module is used for UL 864 UUKL Smoke
Control support to validate the VAV damper is in the commanded position. This
module monitors the Damper Percent Cmd and outputs a Trouble warning after the
specified Delay under the following circumstances:
• The flow is not near zero if the damper is commanded closed.
• The flow is not near maximum if the damper is commanded to 100%.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Trouble Detection)
• Attributes (Damper Trouble Detection)
• Reliability (Damper Trouble Detection)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module provides the ability to latch the inputs to the module. The module
applies the OR operator to the result and passes it to the output. The Latching
Alarm Manager module contains an input that attaches the OR operator to all of
the results to cascade multiple modules.
When the Setup attribute is set to Automatic, the Output is Alarm when the value
of any of the inputs is Alarm, and equals Normal when all input values are Normal.
When the Setup attribute is set to Manual, the Output is Alarm when the value of
any of the inputs is Alarm, and equals Normal when all input values are Normal
and the Reset input is set to Reset.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Latching Alarm Manager)
• Attributes (Latching Alarm Manager)
• Primary States (Latching Alarm Manager)
• Reliability (Latching Alarm Manager)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Calculate Building Load module provides the logic necessary to evaluate cold
and hot water loads. The module inputs include system flow, supply and return
temperatures media, a Heating or Cooling Switch, and glycol concentration. This
module considers Pure water, Water-Ethylene Glycol solution, and Water-
Propylene Glycol solution. You can select the media and the concentration of
Glycol in percentage, as necessary. The output of this module is the heating or
cooling heat transfer rate. A positive output value in the Heating mode indicates a
heating load and a positive output value in the Cooling mode indicates a cooling
load.
The required physical properties (density and heat capacity) are calculated for
water as functions of temperature. The Glycol solutions are calculated as functions
of both temperature and concentration according to the following equations.
Load Calculation
Load is calculated according to the following equation.
Load = Flow x 10-3 x ρ x Cp x ΔT
where
• Flow: Volumetric Flow [gpm input converted to l/s]
• ρ: Density [kg/m3]
• cp: Specific Heat Capacity [kJ/kg-°C]
• ΔT: Temperature Differential (Treturn - Tsupply) [°F input converted
to°C]
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Load Calculation v2 module provides the logic necessary to evaluate cold and
hot water loads. The module inputs include system flow, supply and return
temperatures media, a Heating or Cooling Switch, and glycol concentration. This
module considers Pure water, Water-Ethylene Glycol solution, and
Water-Propylene Glycol solution. You can select the media and the concentration
of Glycol in percentage, as necessary. The output of this module is the heating or
cooling heat transfer rate. A positive output value in the Heating mode indicates a
heating load and a positive output value in the Cooling mode indicates a cooling
load.
The required physical properties (density and heat capacity) are calculated for
water as functions of temperature. The Glycol solutions are calculated as functions
of both temperature and concentration according to the following equations.
Load Calculation
Load is calculated according to the following equation.
Load = Flow x 10-3 x ρ x Cp x ΔT
where
• Flow: Volumetric Flow [gpm input converted to l/s]
• ρ: Density [kg/m3]
• cp: Specific Heat Capacity [kJ/kg-°C]
• ΔT: Temperature Differential (Treturn - Tsupply) [°F input converted
to°C]
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate frost protection state.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Central Heating Low Temp Control)
• Attributes (Central Heating Low Temp Control)
• Primary States (Central Heating Low Temp Control)
• Reliability (Central Heating Low Temp Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for determining if any of the interlock devices are on.
The module accepts eight status inputs as well as a limit input value that acts as a
high limit. Based on the input commands and the parameter settings, the module
outputs the number of devices that are ON.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Count On Inputs)
• Attributes (Count On Inputs)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Device Availability Calculation module calculates the number of available
devices that are able to run. This module accepts eight device enable inputs as well
as a limit input value that acts as a high limit. Based on the input commands and
the attribute settings, the module outputs a number (floating value) of devices that
are currently available.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Device Availability Calculation)
• Attributes (Device Availability Calculation)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The PID Sequencer module is responsible for sequencing the cooling tower valve
and the cooling tower fans and making sure that the tower valve is open before
starting the cooling tower fans. This module accepts as inputs a Delay, an Input 1,
an Input 2, and a System Enable. Based on the input commands and the attribute
settings, the module outputs a state for sequencing the valve and fans.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (PID Sequencer)
• Attributes (PID Sequencer)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Plant Sequencing-Building Load module is responsible for sequencing pumps,
interlocks, and stages of a discrete plant system to meet a building load. This
module accepts as inputs a stage capacity, a load, a percent deadband, a Stabilize
Delay, an Up Delay, a Down Delay, a System Interlock Status, a Start-Up Delay,
Minimum Running Devices, and a System Enable. Based on the input commands
and the attribute settings, the module outputs a state for sequencing pumps,
interlocks, and stages of a discrete plant system and an output for the number of
devices to run.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Plant Sequencing-Building Load)
• Attributes (Plant Sequencing-Building Load)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Plant Sequencing-Decouple module is responsible for sequencing pumps,
interlocks, and stages of a discrete plant system to maintain a decouple flow
setpoint. This module accepts as inputs a process variable, a setpoint, an Up Delay,
a Down Delay, a Number of Devices Running, a System Interlock Status, a
Stabilize Delay, a Start-Up Delay, Minimum Running Devices, Device Mode, and
a System Enable. Based on the input commands and the attribute settings, the
module outputs a state for sequencing pumps, interlocks, and stages of a discrete
plant system and an output for the number of devices to run.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Plant Sequencing-Decouple)
• Attributes (Plant Sequencing-Decouple)
• Primary States (Plant Sequencing-Decouple)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Plant Sequencing-Discrete module is responsible for sequencing pumps,
interlocks, and stages of a discrete plant system to maintain a setpoint. This
module accepts as inputs a process variable, a setpoint, a deadband, a heating/
cooling flag, a Stabilize Delay, an Up Delay, a Down Delay, a Number of Devices
Running, a System Interlock Status, a Start-Up Delay, Minimum Running
Devices, and a System Enable. Based on the input commands and the attribute
settings, the module outputs a state for sequencing pumps, interlocks, and stages of
a discrete plant system and an output for the number of devices to run.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Plant Sequencing-Discrete)
• Attributes (Plant Sequencing-Discrete)
• Primary States (Plant Sequencing-Discrete)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Plant Sequencing-Modulating module is responsible for sequencing pumps,
interlocks, and stages of modulating plant equipment to maintain a setpoint. This
module accepts as inputs a process variable, a stageup setpoint, a number of stages
running, an Up Delay, a Down Delay, a System Interlock Status, a Stabilize Delay,
a Start-Up Delay, and a System Enable. Based on the input commands and the
attribute settings, the module outputs a state for sequencing pumps, interlocks, and
stages of modulating plant equipment and an output for the number of devices to
run. This module provides an output for a stagedown setpoint that is calculated
based on the number of devices running.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Plant Sequencing-Modulating)
• Attributes (Plant Sequencing-Modulating)
• Primary States (Plant Sequencing-Modulating)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Plant Sequencing-OA-T module is responsible for sequencing stages of a
discrete heating system based on an outdoor air temperature setpoint. This module
accepts as inputs an outdoor air temperature, an OA heating enable setpoint, a low
limit setpoint, a Number Available, a System Interlock Status, Minimum Running
Devices, and a System Enable. Based on the input commands and the attribute
settings, the module outputs a state for sequencing pumps, interlocks, and stages of
a discrete plant system and an output for the number of devices to run.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Plant Sequencing-OA-T)
• Attributes (Plant Sequencing-OA-T)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The System Enable module enables or locks out a heating or cooling device. This
module accepts as inputs outdoor air temperature, outdoor air enable setpoint,
outdoor air enable differential, heating/cooling selection, and a network
isAvailable. The module has a state output that indicates if the module is enabled.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (System Enable)
• Attributes (System Enable)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Tower Sequencing 1 Speed module is responsible for sequencing cooling
tower fans to maintain a setpoint. This module accepts as inputs a mode, a process
variable, a setpoint, a minimum on time, a minimum off time, a rotate now,
process units, a device x runtime (where x is 1-12), and a device x enable (where x
is 1-12). Based on the input commands and the attribute settings, the module
outputs a control status and a device x out (where x is 1-12).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Tower Sequencing 1 Speed)
• Attributes (Tower Sequencing 1 Speed)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Tower Sequencing-2 Speed module is responsible for sequencing two speed
cooling tower fans to maintain a setpoint. This module accepts as inputs a mode, a
process variable, a setpoint, a minimum on time, a minimum off time, a rotate
now, process units, a device x runtime (where x is 1-6), and a device x enable
(where x is 1-6). Based on the input commands and the attribute settings, the
module outputs a control status and a device x out (where x is 1-12).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Tower Sequencing-2 Speed)
• Attributes (Tower Sequencing-2 Speed)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Tower Sequencing-3 Speed module is responsible for sequencing cooling
tower fans to maintain a setpoint. This module accepts as inputs a mode, a process
variable, a setpoint, a minimum on time, a minimum off time, a rotate now,
process units, a device x runtime (where x is 1-8), and a device x enable (where x
is 1-8). Based on the input commands and the attribute settings, the module outputs
a control status and a device x out (where x is 1-12).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Tower Sequencing-3 Speed)
• Attributes (Tower Sequencing-3 Speed)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Tower Sequencing-Vernier module is responsible for sequencing cooling
tower fans to maintain a setpoint. This module accepts as inputs a mode, a process
variable, a setpoint, a minimum on time, a minimum off time, a rotate now,
process units, a device x runtime (where x is 1-12), and a device x enable (where x
is 1-12). Based on the input commands and the attribute settings, the module
outputs a control status, an output for modulating the vernier device, and a device x
out (where x is 1-12). You can view and modify the modules in this group’s logic
using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Tower Sequencing-Vernier)
• Attributes (Tower Sequencing-Vernier)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Device Enable Pass Through modules provide an automatic connection to the
State Selection module. They typically take Network Inputs and connect them to
State Selection. The Device Enable category’s Pass Through modules have the
same configuration as the Pass Through category’s Pass Through (Boolean, Enum)
module.
For more information on this module, see the following sections:
• Module Use in Applications (Device Enable Pass Through)
• Pass Through (Boolean, Enum)
Overview
The Availability Determination module enables or locks out a heating or cooling
device. The module accepts as inputs outdoor air temperature, outdoor air enable
setpoint, outdoor air enable differential, heating/cooling selection, network
isAvailable, and a resolution mode. The module has a state output that indicates if
the device should be enabled. When the output is True, the heating or cooling
device is enabled. When the output is False, the heating or cooling device is not
enabled.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Availability Determination)
• Attributes (Availability Determination)
• Primary States (Availability Determination)
• Reliability (Availability Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Recovery Enthalpy Suitability Determination module determines
whether the conditions are suitable for using the heat recovery function for heating
or cooling. This module uses outdoor air and return/exhaust air enthalpy to
determine whether to use heat recovery. The return/exhaust air dry bulb
temperature is adjusted by the amount of the Deadband/2 to make sure enough
energy can transfer to justify the operation of heat recovery. The module compares
the return/exhaust air temperature with the outdoor air temperature to make the
decision. If any of the temperature or humidity inputs are unreliable, the heat
recovery is set to not suitable.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Enthalpy Suitability
Determination)
• Attributes (Heat Recovery Enthalpy Suitability Determination)
• Primary States (Heat Recovery Enthalpy Suitability Determination)
• Reliability (Heat Recovery Enthalpy Suitability Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Recovery Suitability Determination Module determines whether the
conditions are suitable for using the heat recovery function for heating or cooling.
The module checks the reliability of all analog inputs and compares the exhaust air
temperature with the outdoor air temperature to make the decision.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Suitability Determination)
• Attributes (Heat Recovery Suitability Determination)
• Primary States (Heat Recovery Suitability Determination)
• Reliability (Heat Recovery Suitability Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is designed for the sequencing the dehumidification process. While
dehumidifying, the dehumidification devices are controlled based on the return or
zone air relative humidity and the relative humidity setpoint. This module
monitors the controlled relative humidity and the status of the cooling and heating
devices to determine the current dehumidification control state.
For more information on this module, see the following sections:
• Module Use in Applications (Dehumidification Sequencing)
• Attributes (Dehumidification Sequencing)
• Primary States (Dehumidification Sequencing)
• Reliability (Dehumidification Sequencing)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module processes the emergency command and determine the current
emergency mode. This module accepts the emergency command, four safety
switch inputs, and a shutdown delay duration. The module has a state output.
For more information on this module, see the following sections:
• Module Use in Applications (Emergency Mode Sequencing)
• Attributes (Emergency Mode Sequencing)
• Primary States (Emergency Mode Sequencing)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The HR Low Limit Sequencer module manages a heat recovery device and
activates an alternative control mode if the low limit process variable falls below
the low limit setpoint. This module could be used with either a glycol loop or an
energy wheel to prevent the exhaust temperature from dropping below the low
limit setpoint. This module accepts inputs for the limit temperature and setpoint,
and the heat recovery output controller control status. The module has an output
for the state.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Low Limit Sequencing)
• Attributes (Heat Recovery Low Limit Sequencing)
• Primary States (Heat Recovery Low Limit Sequencing)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is designed for sequencing the humidification process. While
humidifying, the humidification device modulates based on the humidity and the
humidity setpoint. This state machine has a limited humidification state for the
case where too much moisture is added to the discharge air. This module monitors
the status of the zone or return air humidity, discharge air humidity, and setpoints
to determine the current humidification control state.
For more information on this module, see the following sections:
• Module Use in Applications (Humidification Sequencing)
• Attributes (Humidification Sequencing)
• Primary States (Humidification Sequencing)
• Reliability (Humidification Sequencing)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate no air flow state for an air handler
application. The module, in addition to the State, provides two other outputs to
show the supply fan status. The module monitors the supply fan command and
flow and determine whether the current state should be Normal, Manual Reset
Fault, Self Reset Fault, or Low Flow.
For more information on this module, see the following sections:
• Module Use in Applications (Loss of Airflow Sequencing)
• Attributes (Loss of Airflow Sequencing)
• Primary States (Loss of Airflow Sequencing)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The 100 OA Start Stop Sequencer module sequences the fans and dampers for a
controlled start and controlled stop in a 100% outdoor air system. The module
accepts Heating Required and Cooling Required inputs that are used to initiate a
start or stop sequence. The module accepts several user adjustable times such as
Fan Start Delay and Fan Stop Delay. The module accepts inputs for static pressure
such as Duct Static Pressure 1, Duct Static Pressure 2, and Duct Static Pressure
Setpoint. The module accepts a configuration input Supply Fan Type. The module
also has supply fan status inputs such as Supply Fan OnOff and Supply Fan
Percent Cmd. The module has a state output and a duct static pressure output.
The unit initiates a start sequence if any of the following is true:
• Cooling Required = True
• Heating Required = True
The unit goes through the shutdown sequence if either of the following conditions
is met:
• Cooling Required = False AND Heating Required = False
• The duct static pressure sensors fail.
The unit goes directly to Off, without passing through the normal shutdown
sequence if the Supply Fan Control Status stops responding. This happens when a
higher level sequencer, such as the No Air Flow Sequencer or the Emergency
Mode Sequencer, takes control of the supply fan.
You can view and modify the modules in this group’s logic using CCT software.
The Finite State Machine cannot be modified.
For more information on this module, see the following sections:
• Module Use in Applications (Start Stop Sequencing [AHU 100% OA])
• Attributes (Start Stop Sequencing [AHU 100% OA])
• Primary States (Start Stop Sequencing [AHU 100% OA])
• Reliability (Start Stop Sequencing [AHU 100% OA])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Mixed Air Start Stop Sequencer module sequences the fans and dampers for a
controlled start and controlled stop in a mixed air system. The module accepts
several inputs which are use to initiate a start or stop sequence such as Preheat
Percent Cmd, Reheat Percent Cmd, Cooling Required, Heating Required, and
Occupancy. The module accepts several user adjustable times such as Fan Start
Delay, Stabilize delay, Damper Close Delay, Fan Stop Delay. The module accepts
inputs for static pressure such as Duct Static Pressure 1, Duct Static Pressure 2, and
Duct Static Pressure Setpoint. The module accepts configuration inputs such as
First Fan To Start, Supply Fan Type, and Intermittent Fan. The module has inputs
for a preheat bonnet switch and a reheat bonnet switch which may be used to
provide a heating fan on delay. The module also has supply fan status inputs such
as Supply Fan OnOff and Supply Fan Percent Cmd. The module has a state output,
a duct static pressure output, and a fan ready indicator output.
The unit initiated a start sequence if any of the following is true:
• Cooling Required = True
• Preheat Bonnet Switch = Hot AND Preheat Percent Cmd > 0 AND Heating
Required = True
• Reheat Bonnet Switch = Hot AND Reheat Percent Cmd > 0 AND Heating
Required = True
The unit will go through the shutdown sequence if either of the following
conditions is met:
• Cooling Required = False AND Heating Required = False
• The duct static pressure sensor fails.
The unit goes directly to Off, without passing through the normal shutdown
sequence if the Supply Fan Control Status stops responding. This will happen
when a higher level sequencer, such as the No Air Flow Sequencer or the
Emergency Mode Sequencer, takes control of the supply fan.
You can view and modify the modules in this group’s logic using CCT software.
The Finite State Machine cannot be modified.
For more information on this module, see the following sections:
• Module Use in Applications (Start Stop Sequencing [AHU Mixed Air])
• Attributes (Start Stop Sequencing [AHU Mixed Air])
• Primary States (Start Stop Sequencing [AHU Mixed Air])
• Reliability (Start Stop Sequencing [AHU Mixed Air])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Occupied Sequencing (AHU 100% OADD) module is responsible for
generating the appropriate temperature control state for a the cold deck of a 100%
Outdoor Air Dual Duct Air Handler Unit (AHU) application. This module accepts
the temperature and setpoint inputs listed below as well as the heating, cooling,
and heat recovery control statuses. The module outputs the current state.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [AHU 100% OADD])
• Attributes (Occupied Sequencing [AHU 100% OADD])
• Primary States (Occupied Sequencing [AHU 100% OADD])
• Reliability (Occupied Sequencing [AHU 100% OADD])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Occupied Sequencing (AHU 100% OASD) module is responsible for
generating the appropriate temperature control state for a 100% Outdoor Air
Single Duct Air Handler Unit (AHU) application. It is to be used for discharge air
control sequencing only. This module accepts the discharge temperature and
setpoint, heating, cooling, and heat recovery devices statuses. The module outputs
the current operational state.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [AHU 100% OASD])
• Attributes (Occupied Sequencing [AHU 100% OASD])
• Primary States (Occupied Sequencing [AHU 100% OASD])
• Reliability (Occupied Sequencing [AHU 100% OASD])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Occupied Sequencing (AHU MADD) module generates the appropriate
temperature control state for the cold deck on a mixed air dual deck Air Handler
Unit (AHU) application. This module accepts the temperature and setpoint inputs
listed below as well as the heating, cooling, and damper control statuses.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [AHU MADD])
• Attributes (Occupied Sequencing [AHU MADD])
• Primary States (Occupied Sequencing [AHU MADD])
• Reliability (Occupied Sequencing [AHU MADD])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Occupied Sequencing (AHU MADD w HR) module generates the appropriate
temperature control state for the cold deck on a mixed air dual deck AHU
application. This module accepts the temperature and setpoint inputs listed in the
attributes table as well as the heating, cooling, and damper control statuses.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [AHU MADD w HR])
• Attributes (Occupied Sequencing [AHU MADD w HR])
• Primary States (Occupied Sequencing [AHU MADD w HR])
• Reliability (Occupied Sequencing [AHU MADD w HR])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a mixed air,
single duct Air Handler Unit (MASD AHU) rooftop application. This module
accepts the temperature and setpoint inputs listed below as well as preheat, reheat,
cooling, and damper control statuses. The module outputs the current state.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [AHU MASD])
• Attributes (Occupied Sequencing [AHU MASD])
• Primary States (Occupied Sequencing [AHU MASD])
• Reliability (Occupied Sequencing [AHU MASD])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a mixed air,
single duct AHU (MASD AHU) with Heat Recovery application. This module
accepts the temperature and setpoint inputs listed in the attribute table, as well as
preheat, reheat, cooling, and damper control statuses. The module outputs the
current state.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [AHU MASD w HR])
• Attributes (Occupied Sequencing [AHU MASD w HR])
• Primary States (Occupied Sequencing [AHU MASD w HR])
• Reliability (Occupied Sequencing [AHU MASD w HR])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Occupied Sequencing (Single Device) module generates the appropriate
temperature control state for a single heating or cooling device in an Air Handler
Unit (AHU) application. This module can be used when the preheat device
controls the mixed air temperature, the heating device controls the hot deck
temperature, or the cooling device is not sequenced with preheat or economizer
such as a cooling only 100% Outdoor Air Unit. This module accepts the
temperature and setpoint inputs listed below as well as the control status.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Sequencing [Single Device])
• Attributes (Occupied Sequencing [Single Device])
• Primary States (Occupied Sequencing [Single Device])
• Reliability (Occupied Sequencing [Single Device])
1. The AHU Mixed Air Dual Duct and Multizone applications use both Preheat Sequencing and Mixed
Air Hot Deck Sequencing.
2. The AHU 100% Outdoor Air Dual Duct application uses 100 OA Hot Deck Sequencing instead of
Preheat Sequencing.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is generates the appropriate temperature control state for a zone
control application. This module monitors the status of the heating and cooling
controllers and setpoints to determine whether the current state should be satisfied,
heating, cooling, or temperature unreliable.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [FC/AHU])
• Attributes (Occupied Zone Sequencing [FC/AHU])
• Primary States (Occupied Zone Sequencing [FC/AHU])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a heat pump
application. This module monitors the status of the heating, cooling, damper,
supplemental heating controllers, setpoints, and occupancy to determine the
current zone control state.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [HP])
• Attributes (Occupied Zone Sequencing [HP])
• Primary States (Occupied Zone Sequencing [HP])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a Unit
Ventilator ASHRAE Cycle 1 zone control application. This module accepts the
temperature and setpoint inputs listed below as well as the heating, cooling, and
damper control statuses. The module outputs the current state as calculated by the
ZN-T Sequencing Finite State Machine.
ASHRAE Cycle 1 supplies 100% outside air at all times, except during the
warmup state. As the zone temperature rises into the range of the heating setpoint,
the outside air damper is fully opened. The heating valve is modulated in response
to the zone temperature to maintain setpoint. Low discharge air temperature can
override zone heating control to maintain a minimum discharge air temperature
into the space. Low limit control logic can also override the damper position if
opening the heating valve is unable to maintain either the zone or discharge
setpoints.
Note: If the discharge air temperature is not reliable, no discharge air low limit
operation takes place and the module controls the zone temperature only.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [UV Cycle 1])
• Attributes (Occupied Zone Sequencing [UV Cycle 1])
• Primary States (Occupied Zone Sequencing [UV Cycle 1])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a Unit
Ventilator ASHRAE Cycle 2 zone control application. This module accepts the
temperature and setpoint inputs listed below as well as the heating, cooling, and
damper control statuses. The module outputs the current state as calculated by the
ZN-T Sequencing Finite State Machine.
As the zone temperature rises to near the heating setpoint, ASHRAE Cycle 2 opens
the outdoor air damper to the minimum position. A fixed minimum amount of
outside air, normally 15 to 50%, is admitted during the heating and ventilating
states. The percentage is gradually increased to 100%, if required, during the
ventilating state. The heating valve and outside air dampers are operated in
sequence as required to maintain zone temperature. Low discharge air temperature
can override the zone temperature’s action on the heating valve to open the valve.
Low discharge air temperature can also override the zone temperature’s action on
the damper to close the damper to minimum. As the discharge temperature
continues to drop, the heating output goes to 100% and the outside damper closes
to prevent discharge air from dropping below a minimum temperature.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [UV Cycle 2])
• Attributes (Occupied Zone Sequencing [UV Cycle 2])
• Primary States (Occupied Zone Sequencing [UV Cycle 2])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a Unit
Ventilator ASHRAE Cycle 3 zone control application. This module accepts the
temperature and setpoint inputs listed below as well as the heating, cooling, and
damper control statuses. The module outputs the current state as calculated by the
ZN-T Sequencing Finite State Machine.
In ASHRAE Cycle 3, a mixed air sensor controls the mixed air temperature.
During the heating, ventilating, and cooling states, Cycle 3 supplies a variable
amount of outside air as required to maintain a fixed temperature (typically 55°F)
entering the heating coil. As the zone temperature rises into the range of the
heating setpoint, ventilation dampers control the air temperature entering the
heating coil at the mixed air setpoint. Zone temperature is controlled by
positioning the heating valve as required. The zone sensor directly controls the
heating element without low limit interference.
Note: The mixed air temperature is read and used for control of the damper
within the UV Cycle 3 Damper Output module; it is not an input in this
module.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [UV Cycle 3])
• Attributes (Occupied Zone Sequencing [UV Cycle 3])
• Primary States (Occupied Zone Sequencing [UV Cycle 3])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a Unit
Ventilator ASHRAE Cycle W zone control application. The module accepts the
temperature and setpoint inputs listed below as well as the heating, cooling, and
damper control statuses. The module outputs the current state as calculated by the
ZN-T Sequencing Finite State Machine.
ASHRAE Cycle W is the same as ASHRAE Cycle 2 with one exception: the
discharge air low limit sensor controls only the outside and recirculated air
dampers. The zone sensor directly controls heating without interference from the
low limit. As the zone temperature rises to the normal operating temperature, the
outside air damper is opened to minimum. A fixed minimum amount of outside air,
normally 15 to 50%, is admitted during the heating and satisfied states. The
percentage is gradually increased to 100%, if required, in the economizer and
cooling states. The heating valve and outside air dampers are operated in sequence
as required to maintain zone temperature. The discharge air sensor can override the
zone sensor action on the damper to close the damper to minimum. As the
discharge temperature continues to drop, the OA damper closes to prevent
discharge air from dropping below a minimum temperature.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [UV Cycle W])
• Attributes (Occupied Zone Sequencing [UV Cycle W])
• Primary States (Occupied Zone Sequencing [UV Cycle W])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the appropriate temperature control state for a VAV zone
control application. This module monitors the status of the heating and cooling
controllers and setpoints to determine whether the current state should be satisfied,
unreliable, one of the stages of heating, or one of the stages of cooling.
For more information on this module, see the following sections:
• Module Use in Applications (Occupied Zone Sequencing [VAV])
• Attributes (Occupied Zone Sequencing [VAV])
• Primary States (Occupied Zone Sequencing [VAV])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Pass Through modules provide an automatic connection to the State Selection
module. They typically take Network Inputs and connect them to State Selection
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Pass Through)
• Attributes (Pass Through)
• Reliability (Pass Through)
A pass through module takes a value from a Network Input and connects it to State
Selection.
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
AHU applications have an Application Mode input that allows you to force the
unit into a mode of operation. The possible modes are Cool Only, Heat Only, Fan
Only, Water Flush, Purge, Vent, and Auto. This module separates the Water Flush
mode to a separate output to allow it to be separately connected to State Selection.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Application Mode Determination)
• Attributes (Application Mode Determination)
• Primary States (Application Mode Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Overview
This module resolves two energy hold off inputs, one hardware mode and one
network mode, into a single energy hold off output. This single output is generated
from the two inputs based on the resolution mode setting and the reliability of the
inputs. Energy Hold Off is typically used with Zone Low Limit Determination for
applications serving zones with direct openings outside the building, including
loading docks and offices with operable windows. When the Energy Hold Off is
active (that is, window open), all heating and cooling is de-activated. The Zone
Low Limit option should be selected if heat is needed to prevent the zone from
cold outdoor air conditions.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Energy Hold Off Determination)
• Attributes (Energy Hold Off Determination)
• Primary States (Energy Hold Off Determination)
• Reliability (Energy Hold Off Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module monitors the airflow status and the fan command. If the fan is
commanded on and the air flow status goes to a fault state, the fan alarm output is
set to Alarm. The output remains in the Alarm state until manually reset.
The Fan Alarm module is used by the Unit Ventilator and Heat Pump applications
when the user has requested that the Fan be locked off when a failure has been
detected. When a fan failure is detected, the fan is locked off until a reset is
received.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Alarm Status)
• Attributes (Fan Alarm Status)
• Primary States (Fan Alarm Status)
• Reliability (Fan Alarm Status)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the on or off state for the control of a fan within a zone
control application. It looks at the heating, cooling, and damper command values
fed back from the output controllers and the occupancy status to determine
whether the fan is required to operate. The heating or cooling command must
exceed the fan on threshold while the damper command must exceed the minimum
damper position to turn the fan on. The module can be configured to operate the
fan continuously during occupied and bypass or cycle based on demand.
This module can be used to provide the on command to single speed fans, three
speed fans, or proportional fans. It can also be set up to continue to operate the fan
for a period of time following the call for heat by setting the Heating Purge
Duration parameter to a positive value.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Determination [Terminal Units])
• Attributes (Fan Determination [Terminal Units])
• Primary States (Fan Determination [Terminal Units])
• Reliability (Fan Determination [Terminal Units])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
Most standard applications use the Occupancy Mode Determination module which
can make use of up to four different occupancy inputs. These inputs (Occupancy
Override, Temporary Occupancy, Occupancy Schedule, and Occupancy Sensor)
from highest to lowest priority are used to determine the effective occupancy used
by other modules throughout the application.
The following example illustrates the common use of the various inputs:
A particular system is responsible for maintaining temperature control of a large
conference room. The output of this module, Effective Occupancy, is used by
other modules in determining the effective setpoint. You can use Occupancy
Override to perform manual control of the Occupancy Mode. The building
schedule dictates the Occupancy Schedule input for daily Occupied/Unoccupied
operation. The room has an Occupancy Sensor to allow the system to use the
Standby heating and cooling setpoints and lower outdoor air requirements if the
room is not being used during scheduled Occupied hours. Finally, the room has a
Temporary Occupancy push-button on the local zone temperature sensor to allow
the occupants to activate Occupied temperature control after normal business
hours.
See the Primary States (Occupancy Mode Determination) section for a detailed
description of the interaction between these inputs in determining the effective
occupancy.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Occupancy Mode Determination)
• Attributes (Occupancy Mode Determination)
• Primary States (Occupancy Mode Determination)
• Reliability (Occupancy Mode Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
1. Input is set to be Not Set by default when no value has been written to it following a reset. This would typically
mean that the input does not have any value assigned and it is represented by this value Not Set.
2. When the Occupancy Schedule is set to Occupied, the Bypass Timer is reset. For that reason, this row in the table
is never active (the output of the Bypass Timer is reset to False before this table is evaluated following the
Occupancy Schedule transition to Occupied). It is shown to avoid the potential confusion that could be caused if
one of the combinations of the inputs was not handled in the Decision Table logic.
3. The use of NOT in the table indicates that any other value than the one specified following the NOT (including Not
Set) is received for that input.
4. Default Occupancy is initially set to Occupied but the user can change the value.
Overview
This module extends the base Occupancy Mode Determination module with
support for a Temporary Occupancy input for up to eight zones (with the zone
number designated here by X, representing zones 1-8). You can view and modify
this module using CCT software; however, you cannot change the key behavior
performed by the Occupancy Mode Determination module.
For more information on this module, see the following sections:
• Module Use in Applications (Occupancy Mode Determination [MZ])
• Attributes (Occupancy Mode Determination [MZ])
• Primary States (Occupancy Mode Determination [MZ])
• Reliability (Occupancy Mode Determination [MZ])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
Terminal Unit applications have a System Mode input that allows you to force the
unit into a mode of operation. The possible modes are Cool Only, Heat Only, Fan
Only, Water Flush, Purge, and Auto. This module splits out the Water Flush mode
to a separate output to allow it to be separately connected to State Selection.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (System Mode Determination)
• Attributes (System Mode Determination)
• Primary States (System Mode Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Overview
This module generates a unit enable command. This command is generated from a
combination of a network and hardware mode and the parameters for controlling
the power fail restart.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Unit Enable Determination)
• Attributes (Unit Enable Determination)
• Primary States (Unit Enable Determination)
• Reliability (Unit Enable Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module specifies whether a low limit condition exits. This condition is
determined based on the zone temperature, the low limit setpoint, and the low limit
differential. When the zone temperature drops below the low limit setpoint the
module outputs a low limit state. When the zone temperature is unreliable, the last
reliable value is used in the comparison.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Zone Low Limit Determination)
• Attributes (Zone Low Limit Determination)
• Primary States (Zone Low Limit Determination)
• Reliability (Zone Low Limit Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates an Unocc Status. When not in Unoccupied, the Unocc
Status is Unocc Cntrl Not Req’d which allows other sequencers to control the
devices. When unoccupied, the zone temperature is monitored to determine when
the temperature exceeds the band specified by the two unoccupied temperature
setpoints. When this occurs, the Unocc Status is set to the appropriate heating or
cooling state. The module remains in this state until the appropriate setpoint has
been satisfied for the Satisfied Timer Duration. After that period of time the status
is set to Satisfied.
When unoccupied, if the temperature is unreliable, the Unocc Status is set to
Temperature Unreliable.
For more information on this module, see the following sections:
• Module Use in Applications (Unoccupied Sequencing [Common])
• Attributes (Unoccupied Sequencing [Common])
• Primary States (Unoccupied Sequencing [Common])
• Reliability (Unoccupied Sequencing [Common])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates an Unoccupied Status for AHUs that perform DA-T
Control (both constant DA-T and single zone Cascaded DA-T). When not
Unoccupied, the Status is Unocc Cntrl Not Req'd.
When unoccupied, the zone temperature is monitored to determine when the
temperature exceeds the band specified by the two unoccupied temperature
setpoints. When this occurs, the Unoccupied status is set appropriately (Unocc
Cooling or Unocc Heating) until the zone temperature is satisfied for the length of
time specified by the satisfied timer duration. After that period of time, the status is
set to Satisfied.
If the temperature is unreliable when unoccupied, the Unoccupied Status is set to
Unreliable. When commanded to Vent, the unit runs with maximum outdoor air.
When units that serve multiple zones (that is, Cascaded Zone Control = False) are
commanded to Warmup or Cooldown, the units run continuously to provide warm
or cool air. In both cases, the sequencer switches to Not Unoccupied to allow the
main AHU sequencer to control the heating and cooling devices.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Unoccupied Sequencing [AHU])
• Attributes (Unoccupied Sequencing [AHU])
• Primary States (Unoccupied Sequencing [AHU])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates an Unocc Status for the AHU zone temperature control
applications. When not in Unoccupied, the Unocc Status is Unocc Cntrl Not
Req’d which allows other sequencers to control the devices. When unoccupied,
the zone temperature is monitored to determine when the temperature exceeds the
band specified by the two unoccupied temperature setpoints. When this occurs, the
Unocc Status is set to the appropriate heating or cooling state. The module remains
in this state until the appropriate setpoint has been satisfied for the Satisfied Timer
Duration. After that period of time the status is set to Satisfied.
When unoccupied, if the temperature is unreliable, the Unocc Status is set to
Temperature Unreliable.
For more information on this module, see the following sections:
• Module Use in Applications (Unoccupied Sequencing [AHU Mixed Air ZN-
T])
• Attributes (Unoccupied Sequencing [AHU Mixed Air ZN-T])
• Primary States (Unoccupied Sequencing [AHU Mixed Air ZN-T])
• Reliability (Unoccupied Sequencing [AHU Mixed Air ZN-T])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is used as part of a Multizone AHU that provides air to up to eight
zones. The unit may cycle during unoccupied based on the minimum or maximum
zone temperature. When the temperatures exceed the band specified by the two
unoccupied temperature setpoints, the Unocc status is set appropriately (Unocc
Cooling, Unocc Heating, or Unocc Htg Clg) until all zone temperatures are
satisfied for the length of time specified by the Satisfied Timer Duration.
If some zones are calling for heating while others are calling for cooling, then the
unit runs without any device restrictions. Zones that are unreliable are ignored
(input element Failsoft = True and the Default Value is between unoccupied
setpoints).
The Warmup or Cooldown command allows this type of unit to run continuously
to provide warm or cool air. Similarly, the Vent command allows the unit to run
with maximum outdoor air. In both cases, the sequencer switches to Not
Unoccupied to allow the main AHU sequencer to control the heating and cooling
devices.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Unoccupied Sequencing [MZ])
• Attributes (Unoccupied Sequencing [MZ])
• Primary States (Unoccupied Sequencing [MZ])
• Reliability (Unoccupied Sequencing [MZ])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates an Unocc Status for Unit Ventilators. When not in
Unoccupied, the Unocc Status is Unocc Cntrl Not Req’d which allows other
sequencers to control the devices. When unoccupied, the zone temperature is
monitored to determine when the temperature exceeds the band specified by the
two unoccupied temperature setpoints. When this occurs, the Unocc Status is set to
the appropriate heating or cooling state. The module remains in this state until the
appropriate setpoint has been satisfied for the Satisfied Timer Duration. After that
period of time the status is set to Satisfied.
When unoccupied, if the temperature is unreliable, the Unoccupied Status is set to
Temperature Unreliable.
If the user selects the Monitor OA During Unoccupied option, the outdoor air
temperature also is monitored and if the OA-T is below the Low OA
Temperature Setpoint, the heating valve is opened to a user-defined position.
This operation does not take precedence over unocc heating, unocc cooling,
warmup, or cooldown operation.
For more information on this module, see the following sections:
• Module Use in Applications (Unoccupied Sequencing [UV])
• Attributes (Unoccupied Sequencing [UV])
• Primary States (Unoccupied Sequencing [UV])
• Reliability (Unoccupied Sequencing [UV])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates an Unocc Status for the VAV applications. When not in
Unoccupied, the Unocc Status is Unocc Cntrl Not Req’d which allows other
sequencers to control the devices. When unoccupied and Warmup or Cooldown
are active, the Unocc Status is Unocc Cntrl Not Req’d. When unoccupied and
Warmup and Cooldown are not active, the zone temperature is monitored to
determine when the temperature exceeds the band specified by the two unoccupied
temperature setpoints. When this occurs, the Unocc Status is set to the appropriate
heating or cooling state. The module remains in this state until the appropriate
setpoint has been satisfied for the Satisfied Timer Duration. After that period of
time the status is set to Satisfied.
When unoccupied, if the temperature is unreliable, the Unoccupied Status is set to
Temperature Unreliable.
For more information on this module, see the following sections:
• Module Use in Applications (Unoccupied Sequencing [VAV])
• Attributes (Unoccupied Sequencing [VAV])
• Primary States (Unoccupied Sequencing [VAV])
• Reliability (Unoccupied Sequencing [VAV])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Autocalibration Sequence
Overview
The Autocalibration Sequence module controls the timing for automatically
calibrating (that is, recalculating the zero offset) of the velocity pressure sensors.
The sequence for calibration involves commanding the dampers to close, waiting
sufficient time for the dampers to close, signaling the calibration process itself, and
then returning the application to normal control. It is used in standard VAV control
applications.
The calibration sequence is enabled to occur automatically if the input Days
between Autocals is greater than zero. If that is the case, the first autocalibration is
initiated automatically after controller download, startup, power enable, and so on.
The delay before this first autocalibration is equal to five times the FCB MAC
address of the controller so that not all VAV applications on a given network trunk
calibrate at the same time.
If automatic calibration is enabled, an autocalibration sequence occurs periodically
based on the Days between Autocals input. The timer used to determine the next
automatic calibration is restarted whenever a calibration sequence completes.
The calibration sequence can also be manually initiated on a rising edge (False to
True transition) of the Autocalibration Request input (connected by default from
the AUTOCAL-C network input.
For more information on this module, see the following sections:
• Module Use in Applications (Autocalibration Sequence)
• Attributes (Autocalibration Sequence)
• Primary States (Autocalibration Sequence)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Balancer Override modules provides a known interface for external balancing
tools to gather data from the VAV application logic and to interact with the
application to calibrate the flow calculations. They provide a single point of
interface for values that are used in several places in the applications. They also
allow the user to configure a subset of that data.
The outputs of this block can be configured by a balancer UI from CCT or a
balancing version of the Network Sensor. See the Network Sensor documentation
listed in the Related Documentation section.
You cannot view or modify the modules in this group’s logic using CCT software.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
2. The attributes specific to the Balancer Override SD also apply to the Balancer Override SDX, and the attributes
specific to the Balancer Override DD also apply to the Balancer Override DDX.
Overview
The Box Flow Test module can be used to verify and diagnose the operation of
VAV Single Duct applications. It provides the timing, output control, and data-
gathering functions for testing the flow control performance of a VAV application.
It can identify eight different potential errors including Large dP Offset, Flow Not
Reliable, Damper Command Not Responding, Poor Flow Response, Insufficient
Flow, Excessive Flow, Non-Increasing Flow, and Excessive Hysteresis. The Box
Flow Test module supports only Single Duct applications. It does not support
exhaust box or hot deck applications.
You cannot view or modify this modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Box Flow Test)
• Attributes (Box Flow Test)
• Primary States (Box Flow Test)
• Reliability (Box Flow Test)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for generating a WarmupCooldown status. For VAV
Single Duct, it sequences the primary heating (hot supply air), box heating and
supplemental heating. For warmup, it starts with primary heating and then adds
box or supplemental heating based on the heating priority. For VAV Dual Duct,
the hot duct is considered box heating and there is no primary heating. For
warmup, it uses supplemental heating or box heating based on the heating priority.
You can view and modify the module in this group’s logic using CCT software,
but the finite state machine logic cannot be modified.
For more information on this module, see the following sections:
• Module Use in Applications (WarmupCooldown Sequencing)
• Attributes (WarmupCooldown Sequencing)
• Primary States (WarmupCooldown Sequencing)
• Reliability (WarmupCooldown Sequencing)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the on or off state for the control of a parallel fan within a
VAV application according to a flow based algorithm.
If the unit is in Occupied, Standby or Bypass mode and the flow is less the Parallel
Fan Occ Min Flow setting, the state output is on. Additionally, if the heating or
cooling command are greater than the Fan On Threshold, the state output is on.
When the heating and cooling command are both below the Fan Off Threshold, the
state output is off. If the Heating Purge Duration is greater than zero, the Heating
Command must be below the Fan Off Threshold for the time specified before the
state output is off.
This module can be used to provide the on command to single speed fans, three
speed fans, or proportional fans.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Determination [VAV Parallel Flow Based])
• Attributes (Fan Determination [VAV Parallel Flow Based])
• Primary States (Fan Determination [VAV Parallel Flow Based])
• Reliability (Fan Determination [VAV Parallel Flow Based])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for generating the on or off state for the control of a
parallel fan within a VAV application according to a temperature based algorithm.
If the heating or cooling command are greater than the Fan On Threshold, the state
output is on. When the heating and cooling command are both below the Fan Off
Threshold, the state output is off. If the Heating Purge Duration is greater than
zero, the Heating Command must be below the Fan Off Threshold for the time
specified before the state output is off.
This module can be used to provide the on command to single speed fans, three
speed fans, or proportional fans.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Determination [VAV Parallel Temp Based])
• Attributes (Fan Determination [VAV Parallel Temp Based])
• Primary States (Fan Determination [VAV Parallel Temp Based])
• Reliability (Fan Determination [VAV Parallel Temp Based])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module generates the on or off state for the control of a parallel fan within a
VAV application according to a flow based algorithm.
If the unit is in Occupied, Standby mode, or Bypass mode, the state output is on. If
the unit is in the Unoccupied mode and the damper, heating or cooling command
are greater than the Fan On Threshold, the state output is on. When the damper,
heating and cooling command are all below the Fan Off Threshold, the state output
is off. If the Heating Purge Duration is greater than zero, the heating command
must be below the Fan Off Threshold for the time specified before the state output
is off.
This module can be used to provide the on command to single speed fans, three
speed fans, or proportional fans.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Determination [VAV Series])
• Attributes (Fan Determination [VAV Series])
• Primary States (Fan Determination [VAV Series])
• Reliability (Fan Determination [VAV Series])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module resets the discharge air temperature setpoint based on the zone
temperature error. This module should only be used when the air handler is
controlling one zone. The module has inputs for the control temperature, heating
and cooling setpoints, PID configuration inputs, and min and max heating and
cooling DAT setpoints. The module may operate in one of several modes which
include Off, Hold, Htg DA-Tsp Reset, or Clg DA-Tsp Reset. This module has
outputs for the DA-T setpoint.
Figure 26-27: Cascaded DA-T Setpoint
DA-T Setpoint
DA-T sp
Zone Satisfied
Satisfied
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Cascaded Discharge Air Setpoint Determination)
• Attributes (Cascaded Discharge Air Setpoint Determination)
• Primary States (Cascaded Discharge Air Setpoint Determination)
• Reliability (Cascaded Discharge Air Setpoint Determination)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module provides the flow setpoint to be controlled by a module (typically a
Supply Damper Control). This module is designed to control zone temperature
while keeping the flow within the minimum and maximum flow settings. The
module accepts as inputs a mode, a process variable, a setpoint, the measured flow,
and configuration values. Based upon the input mode and configuration settings,
the module outputs a flow setpoint, a flow percent, and a Control Status. This
module is intended for use within dual duct applications.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Setpoint [VAV Dual Duct])
• Attributes (Flow Setpoint [VAV Attributes (Flow Setpoint [VAV Dual Duct])
• Primary States (Flow Setpoint [VAV Dual Duct])
• Reliability (Flow Setpoint [VAV Dual Duct])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module provides the flow setpoint to be controlled by a module (typically a
Supply Damper Control). This module is designed to control zone temperature
while keeping the flow within the minimum and maximum flow settings. The
module accepts as inputs a mode, a process variable, a setpoint, the measured flow,
and configuration values. Based upon the input mode and configuration settings,
the module outputs a flow setpoint, a flow percent, and a Control Status.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Flow Setpoint [VAV Single Duct])
• Attributes (Flow Setpoint [VAV Single Duct])
• Primary States (Flow Setpoint [VAV Single Duct])
• Reliability (Flow Setpoint [VAV Single Duct])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module determines the hot deck flow setpoint to complement the cold deck
flow setpoint in a constant volume dual deck VAV application. The generated flow
setpoint is to be controlled by a module (typically a Supply Damper Control).
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (HD Constant Flow Setpoint)
• Attributes (HD Constant Flow Setpoint)
• Reliability (HD Constant Flow Setpoint)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module provides the flow setpoint controlled by a module (typically a Supply
Damper Control). This module controls air flow while keeping the flow within the
minimum and maximum flow settings. The module accepts as inputs a mode, a
flow percent, and configuration values. Based upon the input mode and
configuration settings, the module outputs a flow setpoint. This module is intended
for use within slave VAV single duct applications.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Slave Supply Flow Setpoint Control)
• Attributes (Slave Supply Flow Setpoint Control)
• Primary States (Slave Supply Flow Setpoint Control)
• Reliability (Slave Supply Flow Setpoint Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module provides the flow setpoint to be controlled by a module (typically a
Supply Damper Control). This module controls air flow while keeping the flow
within the minimum and maximum flow settings. The module accepts as inputs a
mode, a flow percent, and configuration values. Based upon the input mode and
configuration settings, the module outputs a flow setpoint. This module is intended
for use within slave VAV dual duct applications.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Slave Supply Flow Setpoint Control Dual Duct)
• Attributes (Slave Supply Flow Setpoint Control Dual Duct)
• Primary States (Slave Supply Flow Setpoint Control Dual Duct)
• Reliability (Slave Supply Flow Setpoint Control Dual Duct)
Module Use in Applications (Slave Supply Flow Setpoint Control Dual Duct)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-347: Slave Supply Flow Setpoint Control Dual Duct Uses in
Application System Selection Trees
Module Instance Name Applications
Slave CD Constant Flow Setpoint Control VAV Slave Dual Duct Application
Slave CD Flow Setpoint Control VAV Slave Dual Duct Application
Slave HD Flow Setpoint Control VAV Slave Dual Duct Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Exchanger with Return Water Control module controls a heat exchanger
that uses superheated hot water as its heating source. This module manages the
output water temperature. If the leaving heating source water temperature drops
below the limit setpoint, the control valve is modulated to control the leaving
heating source water at its low limit.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Exchanger with Return Water Control)
• Attributes (Heat Exchanger with Return Water Control)
• Primary States (Heat Exchanger with Return Water Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for controlling a central plant device (for example, a
Boiler, Chiller, or Tower Fan). This module accepts as inputs a mode, command,
on delay, safety, interlock status, interlock off delay, alarm delay, percent
command, ramp time, percent limit, and maintenance switch. Based on the input
command and attribute settings, the module outputs a rotate enable, device onoff,
alarm command, interlock device command, and an output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Plant Control)
• Attributes (Plant Control)
• Primary States (Plant Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Pump Control module is responsible for controlling a pump. This module
accepts as inputs a mode, a command, an on delay, off delay, a status, an alarm
delay, a percent command, a ramp time, a percent limit, and a maintenance switch.
Based on the input command and attribute settings, the module outputs a rotate
enable, a device on off, an alarm command, and an output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Pump Control)
• Attributes (Pump Control)
• Primary States (Pump Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Pump Control module is responsible for controlling a pump. This module
accepts as inputs a mode, a command, an on delay, off delay, a status, an alarm
delay, a percent command, a ramp time, a percent limit, and a maintenance switch.
Based on the input command and attribute settings, the module outputs a rotate
enable, a device on off, an alarm command, and an output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Pump Control v2)
• Attributes (Pump Control v2)
• Primary States (Pump Control v2)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Rotation Small module provides the same logic as the Sequencer 08 module
(See the Sequencer 01 through Sequencer 16 section.). The Sequencer module
provides multiple stage sequence control. This module is designed to control
discrete systems where the relative capacities of the stages are known. This
module uses relative capacities to determine which outputs to turn on or off. For
example, three boilers with different capacities (x btu, y btu, and z btu) allow for
8 stages of control. The method is based on the split-range control concept and
allows multiple stages to be controlled by a single feedback controller, such as a
PID. This module should be operated continuously (that is, do not place this
module in a hybrid activity because the activity disables all modules associated
with a specific state when that state is not active.)
You cannot view and modify this modules in this group’s logic using CCT
software.
For more information on this module, see the following sections:
• Module Use in Applications (Rotation Small)
• Attributes (Rotation Small)
• Primary States (Rotation Small)
• Reliability (Rotation Small)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Overview
The Secondary Pump PID module controls a proportional source within a control
application. This module accepts the following inputs: a mode, a process variable,
a setpoint, and more. Based on the input mode and parameter settings, the module
outputs a percent command and control status. This module has a delay timer.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Secondary Pump PID)
• Attributes (Secondary Pump PID)
• Primary States (Secondary Pump PID)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Sequenced Output module takes one proportional output and spans it over two
proportional outputs. This module accepts as inputs an Input (float) and a Valve 1
Percent Capacity. Based on the input commands, the module outputs two
proportional outputs.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Sequenced Output)
• Attributes (Sequenced Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Tower Control module controls a single or multiple speed cooling tower fan.
This module accepts as inputs a mode, a command, a speed 2, a speed 3, a fan
status, an on delay, a safety, an alarm delay, a percent command, a ramp time, a
percent limit, and a maintenance switch. Based upon the input command and
attribute settings, the module outputs a rotate enable, a fan onoff, a fan onoff x
(where x is 1-3), an alarm command, and an output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Tower Control)
• Attributes (Tower Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Tower Control module controls a single or multiple speed cooling tower fan.
This module accepts as inputs a mode, a command, a speed 2, a speed 3, a delay, a
safety, a percent command, a ramp time, a percent limit, and a maintenance switch.
Based upon the input command and attribute settings, the module outputs a rotate
enable, a fan onoff, a fan onoff x (where x is 1-3), and an output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Tower Control v2)
• Attributes (Tower Control v2)
• Primary States (Tower Control v2)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for outside air damper control for Unit Ventilator zone
control applications. The module accepts as inputs; a mode, a process variable, a
setpoint, a low limit process variable, and a low limit setpoint. The module outputs
a percent command and the control status based on the input mode and parameter
settings.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Control for UV Cycle 1, 2, or W)
• Attributes (Damper Control for UV Cycle 1, 2, or W)
• Primary States (Damper Control for UV Cycle 1, 2, or W)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for outside air damper control. It is used by two
applications, the Unit Ventilator ASHRAE Cycle 3 zone control application and
the Heat Pump application. When in the Control Limit mode, the module selects
the minimum percent command from the normal control and the low limit control
to position the OA Damper. The module accepts inputs in the form of a mode,
process variable, setpoint, low limit process variable, and low limit setpoint. The
module outputs a percent command and the control status based on the input mode
and parameter settings.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Control with Low Limit)
• Attributes (Damper Control with Low Limit)
• Primary States (Damper Control with Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls the Exhaust Air Damper (EAD), Outdoor Air Damper
(OAD), and the Return Air Damper (RAD). The module is designed so that the
EAD and OAD positions are the same, and the RAD position is complementary
(the sum of the RAD and OAD positions is 100%). The module has functions for
economizer control and low limit control of the dampers. It also has functions to
ramp the damper to minimum position and maximum position. The module also
accepts commands for pressurize, depressurize, and purge. In the normal control
modes, the damper control is modulated closed as the Low Limit Process Variable
drops below the Low Limit Setpoint.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Control for Economizer)
• Attributes (Damper Control for Economizer)
• Primary States (Damper Control for Economizer)
• Reliability (Damper Control for Economizer)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls the Outdoor Air Damper (OAD) and Return Air Damper
(RAD) in a system with a relief fan. The module is designed so that OAD and the
RAD are staged as shown in the following figure and ASHRAE Guideline16-2003 -
Selecting Outdoor, Return, and Relief Dampers for Air-Side Economizer Systems.
Figure 26-28: Dampers Staged for Control with a Relief Fan
100%
Minimum
Position
0%
0% 50% 100%
For temperature control modes, the OAD modulates from minimum position to
100%, Once the OAD is 100% open, the RAD modulates from 100% to 0%. The
module has functions for economizer control and low limit control of the dampers.
It also has functions to ramp the dampers to minimum position and maximum
position. The module also accepts commands for pressurize, depressurize, and
purge.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls the Exhaust Air Damper (EAD), Outdoor Air Damper
(OAD), and the Return Air Damper (RAD). The module controls air flow by
modulating the EAD instead of the OAD; therefore, the EAD is modulated, the
OAD is controlled like a 2-position damper, and the RAD position becomes the
complement of the EAD position. Controlling the dampers in this fashion (with
Return Fan Volume Matching Control) helps make sure that all outdoor air drawn
into the unit comes through the outdoor air damper (and is not drawn in through
the exhaust damper).
The module has functions for economizer and low limit control. It also has
functions to ramp the damper to minimum position, and maximum position. The
module also accepts commands for pressurize, depressurize, and purge.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Control for Volume Matching)
• Attributes (Damper Control for Volume Matching)
• Primary States (Damper Control for Volume Matching)
• Reliability (Damper Control for Volume Matching)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a 2 position damper. The module accepts a mode input a well
as inputs for low limit protection. It has an output to command the damper open or
close.
For more information on this module, see the following sections:
• Module Use in Applications (Min OA Damper 2 Position)
• Attributes (Min OA Damper 2 Position)
• Primary States (Min OA Damper 2 Position)
• Reliability (Min OA Damper 2 Position)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
The Damper Lockout is False when the low limit process variable is less then the
low limit setpoint, or it is false when the low limit process variable is unreliable.
While damper lockout is false, the damper may not open.
Overview
This module is designed to control a proportional minimum outdoor air damper.
The module is used to provide a minimum outdoor air flow. During normal
operation, the minimum OA damper is either closed or at its operational position.
The module also accepts a Mode input, a minimum OA position input which
allows the minimum OA damper position to be reset externally, and a ramp rate
input. The module outputs a 0% to 100% control signal to a proportional minimum
OA damper.
For more information on this module, see the following sections:
• Module Use in Applications (Min OA Damper Proportional Output)
• Attributes (Min OA Damper Proportional Output)
• Primary States (Min OA Damper Proportional Output)
• Reliability (Min OA Damper Proportional Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a minimum OA damper and a minimum OA injection fan.
Both components are two position devices.
For more information on this module, see the following sections:
• Module Use in Applications (Min OA Fan Constant Capacity)
• Attributes (Min OA Fan Constant Capacity)
• Primary States (Min OA Fan Constant Capacity)
• Reliability (Min OA Fan Constant Capacity)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
The Min Flow Control Enable Input indicates that the damper may be opened, and
the fan may be energized. This input is True when the Low Limit Process variable
is reliable, and it is more than the Low Limit Setpoint.
The Damper Ready input indicates that the damper has started to open, the damper
delay has expired, and the fan is now allowed to start.
Overview
This module controls a two position minimum outdoor air damper and a variable
capacity minimum outdoor air injection fan. The two components are used to
provide and control a minimum outdoor air flow. The module accepts a mode
input, a flow and flow setpoint input, and an unreliable mode input which defines
the module behavior when the flow sensor is unreliable. The module has a binary
control output for the minimum OA damper, a binary and an analog output for the
injection fan, and an output which gives PID status information.
For more information on this module, see the following sections:
• Module Use in Applications (Min OA Fan Variable Capacity Flow Control)
• Attributes (Min OA Fan Variable Capacity Flow Control)
• Primary States (Min OA Fan Variable Capacity Flow Control)
• Reliability (Min OA Fan Variable Capacity Flow Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls the exhaust flow through a damper to maintain a difference
between this flow and the supply flow. This difference is calculated as Exhaust
Flow - Supply Flow. The responsibility of this module is to maintain this
difference at the Differential Setpoint by adjusting the output percent, thereby
controlling the Flow. This module accepts as inputs a mode, an exhaust flow
(measured), a supply flow (measured), a differential setpoint (positive or negative),
and configuration values. Based upon the input mode and configuration settings,
the module outputs a percent command representing the desired position of the
damper and a Control Status. If either of the flows are detected as unreliable, this
controller switches to pressure dependent control. If a request to control a flow
near zero (0.2% of Rated Flow) is detected, the module instead closes the damper
rather than control zero flow. The adjustable parameters provide a way for the user
to configure the module to operate in the correct manner for any size damper
whether a positive or negative differential is desired.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Control [VAV Exhaust])
• Attributes (Damper Control [VAV Exhaust])
• Primary States (Damper Control [VAV Exhaust])
• Reliability (Damper Control [VAV Exhaust])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module specifies the damper position in flow control modules and
applications. This module accepts a mode as close, open, hold, control, box flow
test, and failsoft and adjusts the output accordingly. Should control be requested
and the flow is unreliable, it sets the damper position to a value proportional to the
PD Max Position. Unreliable flow results in operation as a pressure dependent
controller. Attempts to control near zero result in the damper being closed. The
adjustable parameters provide a way for the user to configure the module to
operate in the correct manner for control of any size damper.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Damper Control [VAV Supply])
• Attributes (Damper Control [VAV Supply])
• Primary States (Damper Control [VAV Supply])
• Reliability (Damper Control [VAV Supply])
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Fan Proportional
Overview
This module controls a proportional fan. The module accepts as inputs a command,
a heating percentage and a cooling percentage. Based upon the input command and
parameter settings, the module outputs a percent command and an on/off
command.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Proportional)
• Attributes (Fan Proportional)
• Primary States (Fan Proportional)
• Reliability (Fan Proportional)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module passes the state selection output to the output and is used for
consistency in the User Interface.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Parallel Fan Control)
• Attributes (Parallel Fan Control)
• Reliability (Parallel Fan Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module passes the state selection output to the output and is used for
consistency in the User Interface.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Single Speed Fan Control)
• Attributes (Single Speed Fan Control)
• Primary States (Single Speed Fan Control)
• Reliability (Single Speed Fan Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Overview
This module controls a three-speed fan. The module accepts a single input mode
and produces three separate output On/Off commands. As the fan stages up, the
module turns off the lower speed output first before turning on the higher speed
output (following a very short delay so that both contacts are not closed at the same
time). As the fan stages down, the module provides a user defined delay after
turning off the higher speed output before turning on the lower speed output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Three Speed)
• Attributes (Fan Three Speed)
• Primary States (Fan Three Speed)
• Reliability (Fan Three Speed)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for controlling a single-speed fan. The module accepts
an input mode and an adjustable speed and produces fan output.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan VAV Series)
• Attributes (Fan VAV Series)
• Primary States (Fan VAV Series)
• Reliability (Fan VAV Series)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a 2 position fan. The module accepts a mode input and it has
an output to turn the fan on or off.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Single Speed)
• Attributes (Fan Single Speed)
• Primary States (Fan Single Speed)
• Reliability (Fan Single Speed)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Relief Fan BSP module controls building static pressure using a variable
speed relief fan in an air handler application. This module accepts building static
pressure and setpoints. The module has outputs for controlling a variable speed
relief fan.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Relief Variable Capacity BSP Control)
• Attributes (Fan Relief Variable Capacity BSP Control)
• Primary States (Fan Relief Variable Capacity BSP Control)
• Reliability (Fan Relief Variable Capacity BSP Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Fan Relief BSP for UL-864-UKL module controls building static pressure
using a variable speed relief fan in an air handler application. This module accepts
building static pressure, PID tuning parameters, and setpoints. The module has
outputs for controlling a variable speed relief fan. This module accepts commands
from a Firefighter Smoke Control Station (FSCS). The FSCS input takes
precedence over the mode input.
For more information on this module, see the following sections:
• Attributes (Fan Relief BSP for UL-864-UUKL)
• Primary States (Fan Relief BSP for UL-864-UUKL)
• Reliability (Fan Relief BSP for UL-864-UUKL)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Return Fan BSP module controls a variable speed fan and building static
pressure (BSP) in an air handler application. This module accepts building static
pressure, and setpoints. The module has outputs for controlling a variable speed
return fan.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Return or Exhaust BSP Control)
• Attributes (Fan Return or Exhaust BSP Control)
• Primary States (Fan Return or Exhaust BSP Control)
• Reliability (Fan Return or Exhaust BSP Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Fan RF or EF BSP for UL-864-UUKL module controls a variable speed fan
and Building Static Pressure (BSP) in an AHU application. This module accepts
building static pressure, PID tuning parameters, and setpoints. The module has
outputs for controlling a variable speed return fan. This module accepts commands
from a Firefighter Smoke Control Station (FSCS). The FSCS input takes
precedence over the mode input.
For more information on this module, see the following sections:
• Module Use in Applications (Fan RF or EF BSP for UL-864-UUKL)
• Attributes (Fan RF or EF BSP for UL-864-UUKL)
• Primary States (Fan RF or EF BSP for UL-864-UUKL)
• Reliability (Fan RF or EF BSP for UL-864-UUKL)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Return Fan track Output Controller module is designed to control a variable
speed return fan in an air handler application. The return fan tracks the supply fan.
The module has outputs for controlling a variable speed return fan.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Return or Exhaust Tracking)
• Attributes (Fan Return or Exhaust Tracking)
• Primary States (Fan Return or Exhaust Tracking)
• Reliability (Fan Return or Exhaust Tracking)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Fan Return or Exhaust Volume Match Control module controls a variable
speed fan and maintains a volume differential between the supply and return or
exhaust ducts in an air handler application. This module accepts return or exhaust
and supply flows, a low limit temperature, and setpoints. The module has outputs
for controlling a variable speed return or exhaust fan. In addition to the volume
matching capabilities, this module also has a low limit function where the
differential flow setpoint is decreased when the low limit temperature is below the
low limit setpoint.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Return or Exhaust Volume Match Control)
• Attributes (Fan Return or Exhaust Volume Match Control)
• Primary States (Fan Return or Exhaust Volume Match Control)
• Reliability (Fan Return or Exhaust Volume Match Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Fan RF or EF Vol Match for UL-864-UUKL module controls a variable speed
fan and maintains a volume differential between the supply and return or exhaust
ducts in an AHU application. This module accepts discharge and supply flows, a
low limit temperature, PID tuning parameters, and setpoints. The module has
outputs for controlling a variable speed return or exhaust fan. In addition to the
volume matching capabilities, this module also has a low limit function where the
differential flow setpoint is decreased when the low limit temperature is below the
low limit setpoint. This module accepts commands from a Firefighter Smoke
Control Station (FSCS). The FSCS input takes precedence over the mode input.
For more information on this module, see the following sections:
• Module Use in Applications (Fan RF or EF Vol Match for UL-864-UUKL)
• Attributes (Fan RF or EF Vol Match for UL-864-UUKL)
• Primary States (Fan RF or EF Vol Match for UL-864-UUKL)
• Reliability (Fan RF or EF Vol Match for UL-864-UUKL)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is designed to use the supply fan to control the supply air duct static
pressure. The module has inputs for the desired mode, a ramp rate, pressure,
pressure setpoint, and process units. The module is also designed to accept
commands from a firefighter smoke control station (FSCS). The FSCS input takes
precedence over the mode input.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Supply Duct Static Control)
• Attributes (Fan Supply Duct Static Control)
• Primary States (Fan Supply Duct Static Control)
• Reliability (Fan Supply Duct Static Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module uses the supply fan to control the supply air duct static pressure. The
module has inputs for the following items: desired mode, desired mode when the
pressure sensor is unreliable, a ramp rate, pressure, pressure setpoint, and process
units. The module is also designed to accept commands from a firefighter smoke
control station (FSCS). The FSCS input takes precedence over the mode input.
For more information on this module, see the following sections:
• Module Use in Applications (Fan Supply Duct Static for UL-864-UUKL)
• Attributes (Fan Supply Duct Static for UL-864-UUKL)
• Primary States (Fan Supply Duct Static for UL-864-UUKL)
• Reliability (Fan Supply Duct Static for UL-864-UUKL)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a two-position valve where the temperature of the source
water is either hot or cold (depending on the season). The module accepts as inputs
a cooling mode and a heating mode, a process variable, two setpoints, and the
SummerWinter setting. The module outputs the calculated Percent Command,
which is typically passed to the MSC module which in turn translates the percent
value into pulses of the binary output. The module also outputs the calculated
cooling and heating percentages and statuses.
This module controls a single two-position valve that dynamically switches from a
heating (winter) to a cooling (summer) mode. This module provides this control
within a zone control application.
The module accepts as inputs a cooling mode, a heating mode, a process variable,
heating and a cooling setpoint, a SummerWinter setting, a limited max value, a
flush position, and configuration information. Based upon the input commands,
other inputs and the parameter settings, the module outputs the calculated Percent
Command, which is typically passed to the MSC module, which in turn translates
the percent value into pulses of the binary output. The module also outputs the
calculated cooling and heating percentages and statuses.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (2 Pipe 2 Position Valve)
• Attributes (2 Pipe 2 Position Valve)
• Primary States (2 Pipe 2 Position Valve)
• Reliability (2 Pipe 2 Position Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a single two positional source that is dynamically switched
from a heating (winter) to a cooling (summer) mode. It also supports a discharge
low limit for the heating mode. The module accepts as inputs a mode, a process
variable, a low limit process variable, setpoints, and configuration information.
The module outputs the representative percent commands, control status, and
Multistage Output configuration information. The Percent Cmd is typically passed
to the MSC module, which in turn translates the percent value into pulses of the
binary output.
For more information on this module, see the following sections:
• Module Use in Applications (2 Pipe 2 Position Valve with DA-T Low Limit)
• Attributes (2 Pipe 2 Position Valve with DA-T Low Limit)
• Primary States (2 Pipe 2 Position Valve with DA-T Low Limit)
Module Use in Applications (2 Pipe 2 Position Valve with DA-T Low Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-439: 2 Pipe 2 Position Valve with DA-T Low Limit Uses in
Application System Selection Trees
Module Instance Name Application
UV 2 Pipe 2 Position Control Unit Ventilator Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heating Cooling 2-position Valve with Face and Bypass Damper Output
Module controls a 2-position valve with a face and bypass damper that
dynamically switches between heating and cooling. The module can be configured
for DA-T or ZN-T control. The module has been designed with temperature
control, Limited Max control, and a Low OA Temperature mode. In addition to the
2-position valve and face and bypass damper, this module is also designed to
control a circulating pump.
For more information on this module, see the following sections:
• Module Use in Applications (2 Pipe FBPD 2 Position Valve with Low Limit)
• Attributes (2 Pipe FBPD 2 Position Valve with Low Limit)
• Primary States (2 Pipe FBPD 2 Position Valve with Low Limit)
• Reliability (2 Pipe FBPD 2 Position Valve with Low Limit)
Module Use in Applications (2 Pipe FBPD 2 Position Valve with Low Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-442: 2 Pipe FBPD 2 Position Valve with Low Limit Uses in
Application System Selection Trees
Module Instance Name Applications
FBPD 2 Position Valve 2 Pipe Control AHU Mixed Air Single Duct Application
AHU 100% Outdoor Air Single Duct Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a single proportional source that dynamically switches from
a heating (winter) to a cooling (summer) mode. This module is designed to provide
this control within a zone control application.
The module accepts as inputs a cooling mode, heating mode, process variable,
heating and cooling setpoints, SummerWinter setting, limited max value, flush
position, and configuration information. Based upon the input commands, other
inputs, and the parameter settings, the module outputs a percent command (the
proportional signal) along with the calculated cooling and heating percentages and
statuses for feedback purposes.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (2 Pipe Proportional Valve)
• Attributes (2 Pipe Proportional Valve)
• Primary States (2 Pipe Proportional Valve)
• Reliability (2 Pipe Proportional Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Overview
This module controls a single proportional source that is dynamically switched
from a heating (winter) to a cooling (summer) mode. It also supports a discharge
low limit for the heating mode. The module accepts as inputs a summer/winter
changeover, cooling mode, heating mode, process variable, limit variable, cooling
setpoint, heating setpoint, limit setpoint, and configuration information. The
module outputs a cooling percent command, heating percent command, percent
command, cooling control status, and a heating control status.
For more information on this module, see the following sections:
• Module Use in Applications (2 Pipe Proportional Valve with DA-T Low
Limit)
• Attributes (2 Pipe Proportional Valve with DA-T Low Limit)
• Primary States (2 Pipe Proportional Valve with DA-T Low Limit)
Module Use in Applications (2 Pipe Proportional Valve with DA-T Low Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-448: 2 Pipe Proportional Valve with DA-T Low Limit Uses in
Application System Selection Trees
Module Instance Name Applications
UV 2 Pipe Proportional Control Unit Ventilator Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Table 26-450: 2 Pipe Proportional Valve with DA-T Low Limit Command
Hierarchy
SummerWinter Heating Cooling Mode State
Mode
Winter Off * Off
Max * Max Heating
Limited Max * Limited Max Heating
Water Flush * Water Flush Heating
Hold * Hold
Control Limit * Control Limit
Control * Control Heating
Failsoft * Failsoft Heating
Summer * Off Off
Max Max Cooling
Limited Max Limited Max Cooling
Water Flush Water Flush Cooling
Hold Hold
Control Control Cooling
Failsoft Failsoft Cooling
Overview
The Heating and Cooling 2-pipe Control with 2-position Valve and Proportional
valve Module controls a 2-position valve and a proportional valve for either reheat
or cooling. The module can be configured for DA-T, RA-T, or ZN-T control. The
module is designed with temperature control, low limit control, and a Low OA
Temperature mode. In addition to the proportional valve, this module is also
designed to control a circulating pump.
For more information on this module, see the following sections:
• Module Use in Applications (2 Pipe Proportional Valve with Low Limit)
• Attributes (2 Pipe Proportional Valve with Low Limit)
• Primary States (2 Pipe Proportional Valve with Low Limit)
• Reliability (2 Pipe Proportional Valve with Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a two-position cooling valve within a zone control
application. This module determines the required percent of capacity and then
provides the appropriate control inputs to a MSC. The module accepts as inputs a
mode, process variable, and a setpoint. Based upon the input mode, the module
produces outputs intended to be connected to the MSC module that controls the
actual two-position valve.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Cooling 2 Position Valve)
• Attributes (Cooling 2 Position Valve)
• Primary States (Cooling 2 Position Valve)
• Reliability (Cooling 2 Position Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Cooling Control with 2-position Valve and Face and Bypass Damper (FBPD)
Output Module is designed to control a 2-position valve and a face and bypass
damper for either cooling or dehumidification. The module can be configured for
DA-T, RA-T, or ZN-T control as well as dehumidification. This module accepts a
control temperature, a low limit temperature, relative humidity, and setpoints. The
module has outputs for controlling a face and bypass damper, a 2-position valve,
and a circulating pump.
For more information on this module, see the following sections:
• Module Use in Applications (Cooling FBPD 2 Position Valve with
Dehumidification)
• Attributes (Cooling FBPD 2 Position Valve with Dehumidification)
• Primary States (Cooling FBPD 2 Position Valve with Dehumidification)
• Reliability (Cooling FBPD 2 Position Valve with Dehumidification)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional Cooling source within a zone control
application. The module accepts as inputs a mode, process variable, and a setpoint.
Based upon the input mode and parameter settings, the module outputs a percent
command and control status.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Cooling Proportional Valve)
• Attributes (Cooling Proportional Valve)
• Primary States (Cooling Proportional Valve)
• Reliability (Cooling Proportional Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Cooling Proportional Valve Output Module controls a proportional valve for
either cooling or dehumidification. The module can be configured for DA-T, RA-
T, or ZA-T control and it may be configured for RA-H or ZN-H control. The
module has been designed with temperature control, dehumidification, and several
different protection modes. This module also can control a circulating pump.
For more information on this module, see the following sections:
• Module Use in Applications (Cooling Proportional Valve with
Dehumidification)
• Attributes (Cooling Proportional Valve with Dehumidification)
• Primary States (Cooling Proportional Valve with Dehumidification)
• Reliability (Cooling Proportional Valve with Dehumidification)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for controlling a discrete Cooling device within a zone
control application. The module accepts an input mode, a process variable, a
setpoint, and configuration information. The module outputs the representative
percent command and a control status. The outputs are sent to a MSC module
which provides the control for the actual binary outputs.
For more information on this module, see the following sections:
• Module Use in Applications (Cooling Staged Outputs)
• Attributes (Cooling Staged Outputs)
• Primary States (Cooling Staged Outputs)
• Reliability (Cooling Staged Outputs)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Staged Cooling Output Module is designed to control staged compressors for
either cooling or dehumidification. The temperature control can be configured for
DA-T, RA-T, or ZA-T control and the dehumidification may be configured for
RA-H or ZN-H. The module accepts inputs for temperature, relative humidity,
temperature setpoint, humidity setpoint, and compressor minimum on and off
times. The module has outputs for controlling the MSC module.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Cooling Staged Outputs with Dehumidification)
• Attributes (Cooling Staged Outputs with Dehumidification)
• Primary States (Cooling Staged Outputs with Dehumidification)
• Reliability (Cooling Staged Outputs with Dehumidification)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls heat pump compressors and reversing valves that are
dynamically switched from a heating to a cooling mode. This module is designed
to provide this control within a zone control application.
The module accepts as inputs a cooling mode and a heating mode, process
variable, two setpoints, and configuration information. Based upon the input
modes and Proof of Airflow input, the module outputs a percent command along
with the calculated cooling and heating percentages for feedback purposes. Prior to
commanding, the compressor on the module commands the reversing value to the
proper position. The heating and cooling control status are also output.
You can view and modify the modules in this group’s logic using CCT software.
The Finite State Machine cannot be modified.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Pump Staged Compressors)
• Attributes (Heat Pump Staged Compressors)
• Primary States (Heat Pump Staged Compressors)
• Reliability (Heat Pump Staged Compressors)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Recovery Glycol Loop Output Module recovers energy from the exhaust
air using a glycol loop. The module can be configured for DA-T, EA-T, or ZN-T
control. This module accepts heating and cooling mode inputs, a suitability input,
control temperature and setpoint inputs, and limit temperature and setpoint inputs.
It has an analog output and a binary output for controlling the glycol valve and a
binary signal for controlling a circulating pump.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Glycol Loop)
• Attributes (Heat Recovery Glycol Loop)
• Primary States (Heat Recovery Glycol Loop)
• Reliability (Heat Recovery Glycol Loop)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Recovery Energy Wheel Output Module recovers energy from the
exhaust air using an energy wheel. The module can be configured for DA-T, EA-
T, or ZN-T control. This module accepts heat and cooling mode inputs, a
suitability input, control temperature and setpoint inputs, limit temperature and
setpoint inputs, a maximum speed input, and a Limited Max Speed input. It has an
analog output and a binary output for controlling the energy wheel.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Wheel)
• Attributes (Heat Recovery Wheel)
• Primary States (Heat Recovery Wheel)
• Reliability (Heat Recovery Wheel)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Recovery Wheel with 2 Pos Bypass Dampers output module recovers
energy from the exhaust air using an energy wheel with a two-position bypass
damper. The module can be configured for DA-T, EA-T, or ZN-T control. This
module accepts heat and cooling mode inputs, a suitability input, control
temperature and setpoint inputs, limit temperature and setpoint inputs, and
maximum speed and limited max speed inputs. It has an analog output and a binary
output for controlling the energy wheel, and a second binary output to control the
two-position bypass damper.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Wheel with 2 Pos Bypass
Dampers)
• Attributes (Heat Recovery Wheel with 2 Pos Bypass Dampers)
• Primary States (Heat Recovery Wheel with 2 Pos Bypass Dampers)
• Reliability (Heat Recovery Wheel with 2 Pos Bypass Dampers)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heat Recovery Wheel with Bypass Dampers output module recovers energy
from the exhaust air using an energy wheel. The module can be configured for
DA-T, EA-T, or ZN-T control. This module accepts heat and cooling mode inputs,
a suitability input, control temperature and setpoint inputs, and limit temperature
and setpoint inputs. It has two analog outputs for outdoor air and exhaust face and
bypass dampers, and a binary output for controlling the energy wheel.
For more information on this module, see the following sections:
• Module Use in Applications (Heat Recovery Wheel with Bypass Dampers)
• Attributes (Heat Recovery Wheel with Bypass Dampers)
• Primary States (Heat Recovery Wheel with Bypass Dampers)
• Reliability (Heat Recovery Wheel with Bypass Dampers)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a two-position heating valve within a zone control
application. This module determines the required percent of capacity and then
provides the appropriate control inputs to a MSC. The module accepts as inputs, a
mode, a process variable, a setpoint. Based upon the input mode, the module
produces outputs intended to be connected to the MSC module that controls the
actual two-position valve.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating 2 Position Valve)
• Attributes (Heating 2 Position Valve)
• Primary States (Heating 2 Position Valve)
• Reliability (Heating 2 Position Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for controlling a two-position heating valve within a
zone control application. This module determines the required percent of capacity
and then provides the appropriate control input to a MSC. This module also
provides for discharge air low limit control in Unit Ventilator applications.
The module accepts as inputs a mode, process variable, setpoint, low limit process
variable, low limit setpoint, and other configuration inputs. The module outputs a
representative percent command, a percent request, a control status, and other
outputs which feed the MSC module. It passes the outputs to the MSC module that
controls the actual binary outputs.
For more information on this module, see the following sections:
• Module Use in Applications (Heating 2 Position Valve with DA-T Low Limit)
• Attributes (Heating 2 Position Valve with DA-T Low Limit)
• Primary States (Heating 2 Position Valve with DA-T Low Limit)
Module Use in Applications (Heating 2 Position Valve with DA-T Low Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-486: Heating 2 Position Valve with DA-T Low Limit Uses in
Application System Selection Trees
Module Instance Name Application
UV 2 Position Heating Control Unit Ventilator Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module is responsible for face and bypass damper control within a Unit
Ventilator zone control application. The module accepts as inputs a mode, process
variable, setpoint, limit setpoint, limit process variable, and other configuration
inputs. The module outputs a damper percent command, control status, a valve
open/close command for a two-position valve, and state based on the input mode
and parameter settings.
For more information on this module, see the following sections:
• Module Use in Applications (Heating FBPD 2 Position Valve with DA-T Low
Limit)
• Attributes (Heating FBPD 2 Position Valve with DA-T Low Limit)
• Primary States (Heating FBPD 2 Position Valve with DA-T Low Limit)
Module Use in Applications (Heating FBPD 2 Position Valve with DA-T Low
Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-488: Heating FBPD 2 Position Valve with DA-T Low Limit Uses
in Application System Selection Trees
Module Instance Name Applications
UV Face and Bypass Heating Control Unit Ventilator Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heating Control with 2-position Valve and Face and Bypass Damper Output
Module controls a 2-position valve and a proportional face and bypass damper for
either preheat or reheat. The module can be configured for DA-T, RA-T, ZN-T, or
PH-T control. The module has been designed with temperature control, low limit
control, and a Low OA Temperature mode. In addition to the valve and
proportional damper, this module is also designed to control a circulating pump.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating FBPD 2 Position Valve with Low Limit)
• Attributes (Heating FBPD 2 Position Valve with Low Limit)
• Primary States (Heating FBPD 2 Position Valve with Low Limit)
• Reliability (Heating FBPD 2 Position Valve with Low Limit)
Module Use in Applications (Heating FBPD 2 Position Valve with Low Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-490: Heating FBPD 2 Position Valve with Low Limit Uses in
Application System Selection Trees
Module Instance Name Applications
FBPD 2 Position Valve Preheat Control AHU Mixed Air Single Duct Application
AHU Mixed Air Dual Duct Application
AHU 100% Outdoor Air Single Duct Application
AHU 100% Outdoor Air Dual Duct Application
AHU Multizone (Mixed Air Dual Duct) Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heating Control with Proportional Valve and Face and Bypass Damper
Output Module controls both a proportional valve and a face and bypass damper
for either preheat or reheat. The valve is the controlled device if the OA
Temperature is above the Switchover Setpoint, and the face and bypass damper is
the controlled device if the OA Temperature is less than the Switchover Setpoint.
When the valve is in control, the face and bypass damper is 100% face. When the
face and bypass damper is in control, the valve is 100% open. The module can be
configured for DA-T, RA-T, ZN-T, or PH-T control. The module has been
designed with temperature control, low limit control, and protection modes. This
module is also designed to control a circulating pump.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating FBPD Proportional Valve with Low
Limit)
• Attributes (Heating FBPD Proportional Valve with Low Limit)
• Primary States (Heating FBPD Proportional Valve with Low Limit)
• Reliability (Heating FBPD Proportional Valve with Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional heating source within a zone control
application. The module accepts as inputs mode, process variable, and a setpoint.
Based upon the input mode and parameter settings, the module outputs a percent
command and control status.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Proportional Valve)
• Attributes (Heating Proportional Valve)
• Primary States (Heating Proportional Valve)
• Reliability (Heating Proportional Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional heating source within a zone control
application. Besides controlling the primary source temperature (typically the
zone), this module specifies functionality for controlling a discharge air low limit
temperature. The module accepts as inputs a mode, process variable, setpoint, limit
variable, limit setpoint, limited max value, flush position, and inputs to the PID
blocks within the module. Based upon the input command and parameter settings,
the module outputs a percent command and control status.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Proportional Valve with DA-T Low
Limit)
• Attributes (Heating Proportional Valve with DA-T Low Limit)
• Primary States (Heating Proportional Valve with DA-T Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Heating Proportional Valve Output Module controls a proportional valve for
either preheat or reheat. The module can be configured for DA-T, RA-T, ZA-T, or
PH-T control. The module has been designed with temperature control, low limit
control, and protection modes such as Low OA Temperature based on OA
Temperature. In addition to the proportional valve, this module is also designed to
control a circulating pump.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Proportional Valve with Low Limit)
• Attributes (Heating Proportional Valve with Low Limit)
• Primary States (Heating Proportional Valve with Low Limit)
• Reliability (Heating Proportional Valve with Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Htg 2 Sequenced Valves Output Module controls two sequenced proportional
steam valves for either preheat or reheat. The capacity ratio of the valves is a
required input from the user. When controlling a temperature, the first (smaller)
valve starts to modulate. When this valve is fully open the second valve starts to
modulate. When the control temperature increases, the second valve (larger) closes
first. When the second valve is fully closed, the first valve starts to close. The
module can be configured for DA-T, RA-T, ZA-T, or PH-T control. The module
has been designed with temperature control, low limit control, Low OA
Temperature and Failsoft.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Sequenced Valves with Low Limit)
• Attributes (Heating Sequenced Valves with Low Limit)
• Primary States (Heating Sequenced Valves with Low Limit)
• Reliability (Heating Sequenced Valves with Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a discrete heating device within a zone control application.
The module accepts an input mode, a process variable, a setpoint, and
configuration information. The module outputs the representative percent
command and a control status. The outputs are sent to a MSC module that provides
the control for the actual binary outputs.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Staged Outputs)
• Attributes (Heating Staged Outputs)
• Primary States (Heating Staged Outputs)
• Reliability (Heating Staged Outputs)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a discrete heating device within a zone control application.
The module accepts an input mode, process variable, setpoint, low limit process
variable, low limit setpoint, and configuration information. The module outputs
the representative percent command, and a control status. The outputs are sent to a
MSC module which provides the control for the actual binary outputs.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Staged Outputs with DA-T Low Limit)
• Attributes (Heating Staged Outputs with DA-T Low Limit)
• Primary States (Heating Staged Outputs with DA-T Low Limit)
Module Use in Applications (Heating Staged Outputs with DA-T Low Limit)
The application System Selection trees in the CCT software use the individual
modules in this group using the names in the following table.
Table 26-512: Heating Staged Outputs with DA-T Low Limit Uses in
Application System Selection Trees
Module Instance Name Applications
UV Staged Heating Control Unit Ventilator Application
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Staged Heating Output Module is designed to control staged electric or gas
heat for either heating or low limit control. The temperature control can be
configured for DA-T, RA-T, or ZA-T. The module accepts inputs for temperature,
temperature setpoint, and minimum on and off times. The module has outputs for
controlling the MSC module.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Heating Staged Outputs with Low Limit)
• Attributes (Heating Staged Outputs with Low Limit)
• Primary States (Heating Staged Outputs with Low Limit)
• Reliability (Heating Staged Outputs with Low Limit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Preheat Proportional Valve with Return Water Control module controls a
proportional valve for preheat. The module can be configured for DA-T, RA-T,
ZN-T, or PH-T. The proportional valve is modulated to control the configured
Process Variable. If the return water temperature falls below the Low Limit
Setpoint, the valve opens beyond the current control position (maximum 100%) to
warm up the return water temperature.The module has temperature control, low
limit control, and protection modes such as Low OA Temperature based on OA
Temperature. In addition to the proportional valve, this module controls a
circulating pump.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Preheat Proportional Valve with Return Water
Control)
• Attributes (Preheat Proportional Valve with Return Water Control)
• Primary States (Preheat Proportional Valve with Return Water Control)
• Reliability (Preheat Proportional Valve with Return Water Control)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Humidification Packaged Unit module controls a packaged humidification
device. The humidity control may be configured for either RA-H or ZN-H. When
the percent cmd is greater than 1%, the Humidity Enable output is set to on to
activate the unit. In addition, the module is designed with a humidity high limit
control to prevent the duct humidity from rising above a duct high humidity
setpoint. The module accepts inputs from the control relative humidity and
setpoint and the high limit humidity and setpoint.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Humidification Packaged Unit)
• Attributes (Humidification Packaged Unit)
• Primary States (Humidification Packaged Unit)
• Reliability (Humidification Packaged Unit)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Humidification Proportional Steam Output module controls a proportional
steam humidification device. The module includes an Isolation Valve Command
and On Delay input to configure the time that the Isolation Valve is on before the
proportional output is allowed to open. The humidity control may be configured
for either RA-H or ZN-H. In addition, the module has a humidity high limit control
to prevent the duct humidity from rising above a duct high humidity setpoint. The
module accepts inputs from the control relative humidity and setpoint and the high
limit humidity and setpoint.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Humidification Proportional Steam Output)
• Attributes (Humidification Proportional Steam Output)
• Primary States (Humidification Proportional Steam Output)
• Reliability (Humidification Proportional Steam Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Humidification Scrubber Output module controls a scrubber that provides
humidification. A scrubber is a two-position humidification device. The basin fills
and the pump runs when humidification is required. If the pump is off for a
user-defined period of time, the fill line closes and the basin drains.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Humidification Scrubber Output)
• Attributes (Humidification Scrubber Output)
• Primary States (Humidification Scrubber Output)
• Reliability (Humidification Scrubber Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Humidity Staged output module is designed to control staged humidification
devices. The relative humidity control may be configured for either RA-H or ZN-
H. The module is also designed with a humidity high limit control to prevent the
duct relative humidity from rising above a duct high humidity setpoint. The
module accepts inputs for relative humidity and setpoint, the high limit humidity
and setpoint, and minimum on and off times. The module has outputs for
controlling the MSC module.
You can view and modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Humidification Staged Outputs)
• Attributes (Humidification Staged Outputs)
• Primary States (Humidification Staged Outputs)
• Reliability (Humidification Staged Outputs)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Lighting
Overview
The Lighting Control module provides lighting operation. It accepts a two-state
enumerated input and outputs a two-state enumerated Present Value. The Present
Value typically is sent to a Binary Output object that controls the physical lighting
hardware. For Pulse type lighting outputs, the Lighting Control module monitors
the Light Status input and changes (if necessary) the Polarity output to synchronize
the lighting hardware with the desired Present Value.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Lighting)
• Attributes (Lighting)
• Primary States (Lighting)
• Reliability (Lighting)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Reliability (Lighting)
The following reliability states only apply when Feedback Provided = True.
Otherwise, the last reliable input values are used.
• Reliability is set to Failed to Synchronize if LC is unable to make the Light
Status reflect the desired Present Value (after 1 minute delay - 30 seconds
before changing the Polarity output and another 30 seconds waiting for
synchronization).
• Reliability returns to Reliable from Failed to Synchronize if the Light Status
changes at a later time (without the Present Value changing) so that it now
matches the desired Present Value.
• Reliability changes to Failed to Synchronize if Light Status changes so that it
no longer matches the desired Present Value.
Blocking Protection
Overview
The Motor Protection module monitors the output command for a motor. If the
command is off for an extended period of time, the motor starts for a short amount
of time.
You can view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Motor Protection)
• Attributes (Motor Protection)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls the zone dampers on a multizone unit. You can view and
modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Zone Damper)
• Attributes (Zone Damper)
• Primary States (Zone Damper)
• Reliability (Zone Damper)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module sequences the control of the zone dampers on a multizone unit with a
2 position heating valve. You can view and modify the modules in this group’s
logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Zone Damper w 2 Position Heating Valve)
• Attributes (Zone Damper w 2 Position Heating Valve)
• Primary States (Zone Damper w 2 Position Heating Valve)
• Reliability (Zone Damper w 2 Position Heating Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module sequences the control of the zone dampers on a multizone unit with a
proportional heating valve. You can view and modify the modules in this group’s
logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Zone Damper w Proportional Heating Valve)
• Attributes (Zone Damper w Proportional Heating Valve)
• Primary States (Zone Damper w Proportional Heating Valve)
• Reliability (Zone Damper w Proportional Heating Valve)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Overview
This module sequences the control of the zone dampers on a multizone unit with
staged electric heating. You can view and modify the modules in this group’s logic
using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Zone Damper w Staged Heating)
• Attributes (Zone Damper w Staged Heating)
• Primary States (Zone Damper w Staged Heating)
• Reliability (Zone Damper w Staged Heating)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Pass Through modules provide an automatic connection from State Selection.
They typically take Outputs and connect to them from State Selection.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Pass Through)
• Attributes (Pass Through)
• Reliability (Pass Through)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module selects the value sent to a proportional output based on the
enumerated input value (typically from a Binary Input). The value may be delayed
based on the selected delay type (none, on, off, or both.)
You can view and modify the modules in this group’s logic using CCT software.
The Sideloop Interlock Binary to Analog modules work with the state selection
mode (optional).
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Interlock Binary to Analog)
• Primary States (Sideloop Interlock Binary to Analog)
• Reliability (Sideloop Interlock Binary to Analog)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module passes the enumerated value (typically from a Binary Input) to an
enumerated output (typically connect to a Binary Output). The value may be
delayed based on the selected delay type (None, On, Off, or Both.)
You can view and modify the modules in this group’s logic using CCT software.
The Sideloop Interlock Binary to Binary modules work with the state selection
mode (optional).
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Interlock Binary to Binary)
• Primary States (Sideloop Interlock Binary to Binary)
• Reliability (Sideloop Interlock Binary to Binary)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional source within a control application. The
module accepts as inputs, a mode, a process variable, a setpoint, and so on. Based
upon the input mode and parameter settings, the module outputs a percent
command and control status. This module is a simplified version of Cooling
Proportional Output or Heating Proportional Output and supports only three Mode
states, namely, Off, Max, and Control.
You can view and modify the modules in this group’s logic using CCT software.
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop PI Proportional Output)
• Primary States (Sideloop PI Proportional Output)
• Reliability (Sideloop PI Proportional Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional source within a control application. The
module accepts as inputs, a mode, a process variable, a setpoint, and so on. Based
upon the input mode and parameter settings, the module outputs a percent
command and control status. This module allows the setpoint to reset according to
the change in Reset Input.
You can view and modify the modules in this group’s logic using CCT software.
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop PI with Reset Proportional Output)
• Primary States (Sideloop PI with Reset Proportional Output)
• Reliability (Sideloop PI with Reset Proportional Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional source within a control application. The
module accepts as inputs, a mode, a process variable, a setpoint, and so on. Based
upon the input mode and parameter settings, the module outputs a percent
command and control status. It passes the outputs to the MSC module that controls
the actual binary outputs. This module is a simplified version of Cooling Staged
Outputs or Heating Staged Outputs and only supports three Mode states, namely,
Off, Max and Control.
You can view and modify the modules in this group’s logic using CCT software.
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop PI Staged Output)
• Primary States (Sideloop PI Staged Output)
• Reliability (Sideloop PI Staged Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module controls a proportional source within a control application. The
module accepts as inputs, a mode, a process variable, a setpoint, and so on. Based
upon the input mode and parameter settings, the module outputs a percent
command and control status. It passes the outputs to the MSC module that controls
the actual binary outputs. This module is a simplified version of Cooling Staged
Outputs or Heating Staged Outputs and only supports three Mode states, namely,
Off, Max, and Control. This module allows the setpoint to be reset according to the
change in Reset Input.
You can view and modify the modules in this group’s logic using CCT software.
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop PI With Reset Staged Output)
• Primary States (Sideloop PI With Reset Staged Output)
• Reliability (Sideloop PI With Reset Staged Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
This module spans the input using coordinates of a straight line. The Output is the
result of the span. The module accepts as inputs, a mode, an input, input range low,
input range high, output range low, and output range high. The module outputs a
value based on the input mode and parameter settings.
You can view and modify the modules in this group’s logic using CCT software.
To see a module’s connections and how modules interact with it:
• view the Connection tab in the Control View. See Connections Table in the
User Interface section and Viewing and Modifying Connections in the
Configuring a System section for details.
• use the Show Involvement option in the Control View while in the Simulation
or Commissioning mode. See Showing and Hiding Involvement in the
Commissioning a System section for details.
For more information on this module, see the following sections:
• Attributes (Sideloop Reset Output)
• Primary States (Sideloop Reset Output)
• Reliability (Sideloop Reset Output)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Multi-Stage Controller (MSC) module provides sequencing operations for
multi-stage systems (typically smaller tonnage rooftop multi-stage DX systems,
heat pumps, and electric heat). This module uses relative capacities to determine
which outputs to turn on or pulse (cycle a device on and off while respecting the
Min On Time and Min Off Time) to meet a specific load requirement. The method
is based on the split-range control concept and it allows multiple stages to be
controlled by a single feedback controller, such as a PID. The module uses Pulse
Modulation Adaptive Control (PMAC) to provide the pulse train for the device
that is pulsed. The Multistage Controller module multiplexes the PMAC pulse
train with the multistage control outputs and passes the resultant to a set of outputs.
It also monitors the Min On Time and Min Off Time for each element of the
outputs to make sure that a device does not turn off or on too rapidly.
Disabling this module is the same as setting the Instant Shutdown to True.
The Multistage Controller module establishes a means of activating 1 to 12
individual devices. The Multistage Controller algorithm performs the following
main functions:
• Allows you to set up the number and capacities of configured devices. See
Number of Devices and Device Capacity for details.
• Determines the appropriate device combination automatically. This module
determines the switch points between stage combinations using the relative
capacities, the capacity requirement, and the Staging Hysteresis. You do not
need to provide make/break limits. See Determining Device Combinations for
details.
• Provides a vernier output representing the difference between required
capacity and actual capacity. The PMAC algorithm uses the vernier output to
provide behavior that is similar to proportional operation between the current
capacity and the next larger capacity. The module provides an output to
indicate which device is being pulsed at the current capacity. See Vernier
Output and Pulsed Device for details.
• Provides equipment protection by enforcing minimum on and off times. See
Minimum On and Minimum Off for details.
Note: You can bypass this protection by interacting directly with the Binary
Output objects.
• Allows instant deactivation of all devices based on an Instant Shutdown input
or Instant Shutdown command. See Instant Shutdown for details.
Vernier Signal
for Current Stage
Deadzone
with
Hysteresis
0%
0% Input 100%
The example shown in the previous table has three devices with the capacities
5 tons, 10 tons, and 15 tons. Only the first (5 ton) and second (10 ton) devices
are pulseable. The first stage would pulse the first device as the vernier signal
goes from 0 to 100%. To go from the capacity of 5 tons to the capacity of
10 tons, the second device would be pulsed while the first device is on
continuously. When the capacity reaches 10 tons, the first device is pulsed
while the second device now runs continuously. If the current combination is
the second to last combination from the table and the input reaches 100%, the
last stage is not chosen if there is an existing pulsable device in the second to
last combination. But, the pulsable device (in the second to last combination) is
controlled by PMAC. PMAC receives 100% from the vernier (in effect giving
full 100% capacity) and the second to last combination is maintained. If the
current combination is not the second to last combination and the input goes to
100%, the last stage combination (all 1s or On's) is chosen immediately,
checking for existing timers first, by virtue of the Deadzone divided by two
rule.
FIG:Example Pulse
Cycle Time
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Reliability (MSC)
• If the Device Capacity inputs produce more than fifty combinations, the
module becomes unreliable and the Reliability is set to Inconsistent Inputs.
• If the Process Variable is unreliable, the module generates a pulse train based
on the Input and the last valid Process Variable. If the Input is unreliable, the
system generates a pulse train based on the last valid Input.
Overview
The Sequencer module behaves the same as the Sequencer block in the Metasys
system extended architecture NAE. See the Sequencer block description in the
Logic Connector Tool (LCT) section of the Metasys system Help.
The Sequencer module provides a Control System with multiple stage sequence
control. This module controls discrete systems where the relative capacities of the
stages are known. This module uses relative capacities to determine which outputs
to turn on or off. The method is based on the split-range control concept and it
allows multiple stages to be controlled by a single feedback controller, such as a
PID. This module should be operated continuously (that is, do not place this
module in a hybrid activity). The activity disables all modules associated with a
specific state when that state is not active. There is no user interface to this disable/
enable behavior.
The sequencer module establishes a means of sequentially activating 1 to X stages
of individual devices. The sequencer control algorithm performs the following
main functions:
• Handles transitions between stage combinations using make and break limits.
See Configuration Details for details on make and break limits. See Staging
Up and Staging Down for details on staging up and staging down.
• Provides equipment protection by enforcing minimum on and off times. See
Minimum On and Minimum Off for details.
Note: The user can defeat this protection by interacting directly with the
output points.
• Provides inter-stage on and off delays. See Inter-Stage Timing for details.
• Allows instant deactivation of all outputs based on an Instant Shutdown input.
See Instant Shutdown for details.
• Provides intelligent rotation of the start and stop order of the outputs based on
the rank and the device status. The sequencer module also allows the user to
force a rotation to occur immediately. See Lead Rotation for details on lead
rotation.
Attributes (Sequencer)
The following table describes the attributes used by the Sequencer XX (where XX
is 01 through 16) modules.
Table 26-567: Sequencer 01 through Sequencer 16 Attributes (Part 1 of 3)
Name Type1 Description Default Value
Break Limit Represents the limits at which each
successive stage deactivates. If Proactive
is True, the first limit applies to the second
stage, the second limit applies to the third
stage, and so on. Each successive value
must be greater than the previous break
limit and also less than its corresponding
make limit. The size of this array is set to
Number of Outputs (or Number of
Outputs - 1 if Proactive is True) at
configuration time.
Current Stage G, V Indicates the number of the active outputs
of the sequencer.
Device X Enable Establishes the enable status of the True
sequencer device outputs. A value of
False takes the associated device out of
service. In Device X Enable, X is 1-16.
Device X Out V Contains the output value for the
corresponding device. In Device X Out, X
is 1-16.
Device X Rank These float values represent the ranking of 0.0
each device. This value establishes the
order by which the device outputs are
activated. In Device X Rank, X is 1-12.
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Reliability (Sequencer)
• The reliability associated with the Sequencer module may report the input
unreliable. When the input is unreliable, all outputs hold the last value set when
the input was reliable during this situation.
• If the Sequencer is unable to stage up or down because the remaining outputs
are disabled, the Sequencer’s reliability is Unreliable.
Overview
This section describes the Last Value modules of the Output Controller type. For
information on the Last Value modules of the Setpoint Determination/Misc type,
see Timing in the Setpoint Determination/Misc section.
The Last Value module holds the value that its input had at the end of the previous
execution of the control logic for use by the current execution. Use this module
when you want to compare the current value of a variable with the value from the
last execution. If this module does not operate continuously (that is, is placed in the
state section of a hybrid activity), it starts at its Default Value when re-enabled.
One additional constraint is that connections from Hybrid Activity Inputs are not
allowed to be made directly to the Input of Last Value module in one of its State
Sections. If such logic is needed, a no-op component (such as adding zero to a
float) should be connected between the Input and the Last Value. This is required
because the Hybrid Activity inputs are considered part of the Event Section and are
therefore earlier in the sequence order than all State Section components.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Last Value)
• Attributes (Last Value)
• Reliability (Last Value)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning Modes
Only, V - Calculated Value (Outputs)
Overview
The Totalization (Enum Runtime) modules compute the runtime for the staged
outputs in the AHU applications. These outputs can be preheat, reheat or cooling
outputs.
You cannot view or modify the modules in this group’s logic using CCT software.
For more information on this module, see the following sections:
• Module Use in Applications (Totalization)
• Attributes (Totalization)
• Reliability (Totalization)
1. C - Configuration Mode Only, G - Generated State (Default Element), SC - Simulation and Commissioning
Modes Only, V - Calculated Value (Outputs)
Reliability (Totalization)
The Totalization module reports the following reliability values:
• Overflow: Takes place when the Present Value, Accumulator, Rollover
Amount, or Rollover Count exceeds the maximum value that can be expressed
by single floating-point number. At Overflow, the Present Value keeps its
previous value and stops updating.
• Round Off Error: Because the Present Value is implemented as a single
floating-point number, it has 7 digits precision.
• Input Unreliable: If input is unreliable, the module stops Totalization.
Outputs 1387
1388 CCT Help: Modules
Chapter 29: CCT Help: Objects
CCT Input and Output Object Overview
CCT Input and Output Objects
The input and output objects in this section appear in CCT on the Hardware View
tabs in the Details dialog box of inputs and outputs. To see the objects, right-click
an input, output, network input, or network output and select View Details. The
Object Type attribute indicates the object by which the input or output is
represented.
During Commissioning, the Present Value appears in the Inputs and Outputs
section of the Control View. Two values appear (for example 70, 70), where the
first value comes from the hardware, while the second value is the value being
used by the software.
The default values for the attributes vary depending on the configuration you are
using. Often, values are filled in automatically and you will not need to edit the
individual values.
An SAB device such as a network sensor (duct or zone) may be represented by an
Analog Input (zone temperature or zone relative humidity), Analog Value
(setpoint request or zone temperature display), Binary Value (occupancy request),
or Multistate Value (fan speed request, fan status display, or occupancy status
display) object.
Click the following section names to view the attribute and command details for
each object:
• Analog Input Object
• Analog Output Object
• Analog Value Object
• Binary Input Object
• Binary Output Object
• Binary Value Object
• Counter Input (Accumulator) Object
• Multistate Value Object
• Position Adjust Output Object
When viewing these objects through the UI of an NAE or ADS/ADX, you see
them as MS/TP Field Device object children.
For details, see Inputs, Outputs, Network Inputs, and Network Outputs. For details
about command priorities, see Command Priority Levels. For details about object
attributes, see Object Attributes.
1. Attributes in this table are updated by the controller to the specified values (online); however, you can modify them
if desired.
IMPORTANT: Not all logic blocks support the New Port feature. Although
the New Port feature may appear for some logic blocks, only use this feature for
the blocks that indicate New Port support as documented in this section. Using
the New Port feature to add ports to blocks that do not support the feature
may break your logic.
Logic 1441
Activity Inputs
The Activity Inputs folder in the control block palette contains boolean, float, and
enumeration input blocks. Use Activity Inputs to provide an incoming connection
point to custom logic modules.
Table 39-594: Activity Input Blocks
Type Description
Input (Boolean) Provides a Boolean type of input for connection to other blocks in the logic diagram.
Input (Enum) Provides an Enumeration (Enum) type of input for connection to other blocks in the
logic diagram.
Input (Float) Provides a Floating (Float) type of input for connection to other blocks in the logic
diagram.
Activity Outputs
The Activity Outputs folder in the control block palette contains boolean, float,
and enumeration output blocks. Use Activity Outputs to provide an outgoing
connection point to custom logic modules.
Table 39-595: Activity Output Blocks
Type Description
Output (Boolean) Provides a Boolean type of output for connections from other blocks in the logic
diagram.
Output (Enum) Provides an Enumeration (Enum) type of output for connection from other blocks in
the logic diagram.
Output (Float) Provides a Floating (Float) type of output for connection from other blocks in the
logic diagram.
1. The inputs and outputs of this block are exposed for connection by default.
2. An example use of the Reliability Check and Reliability Merge blocks is the min select option of duct static
pressure sensors. Use the minimum value from two duct sensors if both are Reliable, or use the Reliable value if
only one sensor is Reliable. Set the effective value to Unreliable if both sensors are not Reliable. See the following
State Generators, General Sequencing sections for details: Reliability in the Start Stop Sequencing (AHU 100%
OA) section and Reliability in the Start Stop Sequencing (AHU Mixed Air) module section.
Logic 1443
Calculation
The Calculation folder in the control block palette contains blocks that perform
various fixed calculations. The Calculation blocks include:
• EWMA
• Line Segment
• Span
• Totalization (Analog Integration)
• Totalization (Boolean Event)
• Totalization (Boolean Runtime)
• Totalization (Enum Event)
• Totalization (Enum Runtime)
EWMA
The EWMA logic block provides both signed (Input A - Input B) and absolute
(ABS [Input A - Input B]) EWMA statistics for estimating a time-series of values.
Use EWMA blocks for forecasting, control charts, and fault detection. The
response of the calculation can be set by choosing an appropriate Process ID or by
directly configuring the Time Constant of the process data (if Process ID = other).
The EWMA calculation is active when Update Ewma is set to False.
The following table describes the inputs and outputs of the EWMA logic block.
Table 39-597: EWMA Block Inputs and Outputs (Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Input A Float Yes Indicates the value of the first input, Input A, 0.0
used in the EWMA equation as previously
described.
Input B Float Yes Indicates the value of the second input, Input 0.0
B, used in the EWMA equation as previously
described.
Process ID Enum No Identifies the process that the EWMA is being ZN-T
used to evaluate. If the Process ID is any
value other than Other, the EWMA looks up
the Eff Time Constant. Otherwise, the Time
Constant input directly sets the Eff Time
Constant.
Time Constant Float No Indicates the time required for a system to 720 Seconds
reach 63% of its final magnitude given a
100% step change. When the Process ID is
Other, this input is used to specify the Eff
Time Constant and thus calculates the
Interval; otherwise, it is ignored.
Update Ewma Boolean No Indicates if the logic block should hold the last True
value or perform the EWMA calculations.
Logic 1445
Line Segment
The Line Segment logic block provides linear scaling and biasing of an input value
using one or more line segments where two points define a single line segment.
You must double-click this block to configure its Input Points and Output Points.
See Configuring the Line Segment Block in the Configuring a System section.
The following table describes the inputs and outputs of the Line Segment logic
block.
Table 39-598: Line Segment Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Clamp First Boolean No Indicates the behavior when the Input is True
less than the first value in the Input Points
array.
Clamp Last Boolean No Indicates the behavior when the Input is True
greater than the last value in the Input
Points array.
Input Float Yes Indicates the signal that is transferred to the 0.0
Present Value based on the line segment
that the input falls within.
Outputs
Present Value1 Float Yes Indicates the result of the linear scaling and 0.0
biasing performed by the block.
Properties
Input Points Float N/A Provides an array of values that contains 0, 100
Array the X values for the breaking points of the Number of
linearization. Segments plus 1
Number of Number Indicates how many segments are used by Minimum Value = 1
Segments the linearization.
Output Points Float N/A Provides an array of values that contains 0, 100
Array the Y values for the breaking points of the Number of
linearization. Segments plus 1
Logic 1447
Totalization (Analog Integration)
The Totalization (Analog Integration) logic block provides totalization to integrate
an analog input over time. This block is typically used to record the usage of a
consumable (for example, electricity, steam, and chilled water) monitored by the
analog input. The following table describes the inputs and outputs of the
Totalization (Analog Integration) logic block.
Table 39-600: Totalization (Analog Integration) Block Inputs and Outputs
(Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Active Boolean No Prevents or allows the updating of Present True
Value.
Input Float Yes Indicates the Input value that the block uses 0.0
to provide totalization.
Reference State Float No This attribute is not used for Analog
Integration.
Reset Boolean No Resets the Present Value, Accumulator, False
Rollover Count, and Rollover Amount to
zero.
Scale Factor Float No Provides unit conversion. 1
Outputs
Accumulator Float No Accumulates the remainders in the 0.0
calculation of the Present Value due to the
precision limit of a single floating-point
number. The sum of the Present Value and
the Accumulator provide a double floating-
point expression of the current totalized
value for the block.
Error Since Last Boolean No Indicates any errors that occurred since the False
Reset time of the last Reset. Since the last Reset, if
the block’s Reliability is any value other than
Reliable, this output is set to True. If the
Reset input changes from False to True or a
Reset command is issued, this output is set
to False.
Present Value1 Float Yes Indicates the current value of the block. The 0.0
sum of the Present Value and the
Accumulator provide a double floating-point
expression of the current totalized value for
the block.
Rollover Float No Increments this value by the current value of 0.0
Amount Present Value.
Rollover Count Float No Indicates the value by which the Present 0.0
Value is incremented.
Properties
Period Float N/A Indicates the execution period of this block 60 Seconds
when Setup is Analog Integration or Time in
State.
Logic 1449
Totalization (Boolean Event)
The Totalization (Boolean Event) logic block provides totalization to count the
number of occurrences of one state of a Boolean input over time. An example use
is to record how many times a device starts or stops. The following table describes
the inputs and outputs of the Totalization (Boolean Event) logic block.
Table 39-601: Totalization (Boolean Event) Block Inputs and Outputs
(Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Active Boolean No Prevents or allows the updating of Present True
Value.
Input Boolean Yes Indicates the Input value that the block uses False
to provide totalization.
Reference State Boolean No Adds 1 to the Present Value every time the False
input switches to this Reference State.
Reset Boolean No Resets the Present Value, Accumulator, False
Rollover Count, and Rollover Amount to zero.
Scale Factor Float No Provides unit conversion. 1
Outputs
Accumulator Float No Accumulates the remainders in the 0.0
calculation of the Present Value due to the
precision limit of a single floating-point
number. The sum of the Present Value and
the Accumulator provide a double floating-
point expression of the current totalized value
for the block.
Error Since Last Boolean No Indicates any errors that occurred since the False
Reset time of the last Reset. Since the last Reset, if
the block’s Reliability is any value other than
Reliable, this output is set to True. If the
Reset input changes from False to True or a
Reset command is issued, this output is set
to False.
Present Value1 Float Yes Indicates the current value of the block. The 0.0
sum of the Present Value and the
Accumulator provide a double floating-point
expression of the current totalized value for
the block.
Rollover Float No Increments this value by the current value of 0.0
Amount Present Value.
Rollover Count Float No Indicates the value by which the Present 0.0
Value is incremented.
Properties
Period Float N/A Indicates the execution period of this block 60 Seconds
when Setup is Analog Integration or Time in
State.
Rollover Limit Float N/A Sets a value that automatically rolls over the 10,000
Present Value when the Present Value
exceeds the value (that is, the block adds the
Present Value to the Rollover Amount, adds
1 to the Rollover Count, and sets the Present
Value and Accumulator to 0).
Logic 1451
Totalization (Boolean Runtime)
The Totalization (Boolean Runtime) logic block provides tracking of the total time
that a Boolean input resides in a state. An example use is to record the total time a
value is True or False. The following table describes the inputs and outputs of the
Totalization (Boolean Runtime) logic block.
Table 39-602: Totalization (Boolean Runtime) Block Inputs and Outputs
(Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Active Boolean No Prevents or allows the updating of Present True
Value.
Input Boolean Yes Indicates the Input value that the block uses False
to provide totalization.
Reference State Boolean No Updates the Present Value periodically as False
long as the input stays in the Reference
State.
Reset Boolean No Resets the Present Value, Accumulator, False
Rollover Count, and Rollover Amount to zero.
Scale Factor Float No Provides unit conversion. 1
Outputs
Accumulator Float No Accumulates the remainders in the 0.0
calculation of the Present Value due to the
precision limit of a single floating-point
number. The sum of the Present Value and
the Accumulator provide a double floating-
point expression of the current totalized value
for the block.
Error Since Last Boolean No Indicates any errors that occurred since the False
Reset time of the last Reset. Since the last Reset, if
the block’s Reliability is any value other than
Reliable, this output is set to True. If the
Reset input changes from False to True or a
Reset command is issued, this output is set
to False.
Present Value1 Float Yes Indicates the current value of the block. The 0.0
sum of the Present Value and the
Accumulator provide a double floating-point
expression of the current totalized value for
the block.
Rollover Float No Increments this value by the current value of 0.0
Amount Present Value.
Rollover Count Float No Indicates the value by which the Present 0.0
Value is incremented.
Properties
Period Float N/A Indicates the execution period of this block 60 Seconds
when Setup is Analog Integration or Time in
State.
Logic 1453
Totalization (Enum Event)
The Totalization (Enum Event) logic block provides totalization to count the
number of occurrences of one state of an Enum input over time. The following
table describes the inputs and outputs of the Totalization (Enum Event) logic
block.
Table 39-603: Totalization (Enum Event) Block Inputs and Outputs (Part 1
of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Active Boolean No Prevents or allows the updating of Present True
Value.
Input Enum Yes Indicates the Input value that the block uses 1st Enum
to provide totalization.
Reference State Enum No Adds 1 to the Present Value every time the 1st Enum
input switches to this Reference State.
Reset Boolean No Resets the Present Value, Accumulator, False
Rollover Count, and Rollover Amount to zero.
Scale Factor Float No Provides unit conversion. 1
Outputs
Accumulator Float No Accumulates the remainders in the 0.0
calculation of the Present Value due to the
precision limit of a single floating-point
number. The sum of the Present Value and
the Accumulator provide a double floating-
point expression of the current totalized value
for the block.
Error Since Last Boolean No Indicates any errors that occurred since the False
Reset time of the last Reset. Since the last Reset, if
the block’s Reliability is any value other than
Reliable, this output is set to True. If the
Reset input changes from False to True or a
Reset command is issued, this output is set
to False.
Present Value1 Float Yes Indicates the current value of the block. The 0.0
sum of the Present Value and the
Accumulator provide a double floating-point
expression of the current totalized value for
the block.
Rollover Float No Increments this value by the current value of 0.0
Amount Present Value.
Rollover Count Float No Indicates the value by which the Present 0.0
Value is incremented.
Properties
Period Float N/A Indicates the execution period of this block 60 Seconds
when Setup is Analog Integration or Time in
State.
Rollover Limit Float N/A Sets a value that automatically rolls over the 10,000
Present Value when the Present Value
exceeds the value (that is, the block adds the
Present Value to the Rollover Amount, adds
1 to the Rollover Count, and sets the Present
Value and Accumulator to 0).
Logic 1455
Totalization (Enum Runtime)
The Totalization (Enum Runtime) logic block provides tracking of the total time
that an Enum input resides in a state. An example use is to record the total time a
device is ON or OFF. See Totalization in the Output Controller section for more
information. The following table describes the inputs and outputs of the
Totalization (Enum Runtime) logic block.
Table 39-604: Totalization (Enum Runtime) Block Inputs and Outputs
(Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Active Boolean No Prevents or allows the updating of True
Present Value.
Input Enum Yes Indicates the Input value that the Enum
block uses to provide totalization.
Reference State Enum No Updates the Present Value 1st Enum
periodically as long as the input
stays in the Reference State.
Reset Boolean No Resets the Present Value, False
Accumulator, Rollover Count, and
Rollover Amount to zero.
Scale Factor Float No Provides unit conversion. 1
Outputs
Accumulator Float No Accumulates the remainders in the 0.0
calculation of the Present Value due
to the precision limit of a single
floating-point number. The sum of
the Present Value and the
Accumulator provide a double
floating-point expression of the
current totalized value for the block.
Error Since Last Boolean No Indicates any errors that occurred False
Reset since the time of the last Reset.
Since the last Reset, if the block’s
Reliability is any value other than
Reliable, this output is set to True. If
the Reset input changes from False
to True or a Reset command is
issued, this output is set to False.
Present Value1 Float Yes Indicates the current value of the 0.0
block. The sum of the Present Value
and the Accumulator provide a
double floating-point expression of
the current totalized value for the
block.
Rollover Float No Increments this value by the current 0.0
Amount value of Present Value.
Rollover Count Float No Indicates the value by which the 0.0
Present Value is incremented.
Properties
Period Float N/A Indicates the execution period of this 60 Seconds
block when Setup is Analog
Integration or Time in State.
Logic 1457
Compare
The Compare folder in the control block palette contains comparison blocks such
as Greater Than or Not Equal. All compare blocks have three inputs (though the
differential only has influence for floating point comparisons). The blocks
compare input number 1 with input number 2 using the differential (input number
3). The type of comparison depends on the statistical type.
Table 39-605: Compare Blocks (Part 1 of 2)
Type Description Inputs Outputs
Equal (Boolean) Provides equal logic for Boolean inputs. Input 1 (Boolean)1 Present Value
If the inputs are identical, the Present Value is
Input 2 (Boolean)1 (Boolean)1
True. Otherwise, the Present Value is False.
Differential (Float)
Equal (Enum) Provides equal logic for Enumeration (Enum) Input 1 (Enum)1 Present Value
inputs. (Boolean)1
Input 2 (Enum)1
If the inputs are identical, the Present Value is
True. Otherwise, the Present Value is False. Differential (Float)
Equal (Float) Provides equal logic for Floating (Float) inputs. Input 1 (Float)1 Present Value
When the Differential is 0, the numbers must be
Input 2 (Float)1 (Boolean)1
the same for the Present Value to be True. If
the absolute value of Input 1 minus Input 2 is Differential (Float)
greater than half of the Differential, then the
Present Value is False. If the Present Value is
already False, the sign of the difference
between Input 1 and Input 2 must change or
become zero, and the absolute value of the
difference must be less than or equal to half of
the Differential for the Present Value to change
to True.2
Greater Than or Provides greater than or equal logic where Input 1 (Float)1 Present Value
Equal Input 1 must be greater than or equal to Input 2 (Boolean)1
for the Present Value to change to True. If the Input 2 (Float)1
Present Value is already True, Input 1 must be Differential (Float)
less than Input 2 minus the Differential for the
Present Value to change to False.
Greater Than Provides greater than logic where Input 1 must Input 1 (Float)1 Present Value
be greater than Input 2 for the Present Value to (Boolean)1
change to True. If the Present Value is already Input 2 (Float)1
True, Input 1 must be less than or equal to Differential (Float)
Input 2 minus the Differential for the Present
Value to change to False.
Less Than or Provides less than or equal logic where Input 1 Input 1 (Float)1 Present Value
Equal must be less than or equal to Input 2 for the (Boolean)1
Present Value to change to True. If the Present Input 2 (Float)1
Value is already True, Input 1 must be greater Differential (Float)
than Input 2 plus the Differential for the Present
Value to change to False.
Less Than Provides less than logic where Input 1 must be Input 1 (Float)1 Present Value
less than Input 2 for the Present Value to (Boolean)1
change to True. If the Present Value is already Input 2 (Float)1
True, Input 1 must be greater than or equal to Differential (Float)
Input 2 plus the Differential for the Present
Value to change to False.
Not Equal Provides NOT equal logic for Boolean inputs. Input 1 (Boolean)1 Present Value
(Boolean) If the inputs are identical, the Present Value is (Boolean)1
Input 2 (Boolean)1
False. Otherwise, the Present Value is True.
Differential (Float)
Not Equal (Float) Provides NOT equal logic for Floating (Float) Input 1 (Float)1 Present Value
inputs. (Boolean)1
Input 2 (Float)1
If the absolute value of Input 1 minus Input 2 is
greater than half of the Differential, then the Differential (Float)
Present Value is True. If the Present Value is
already True, the sign of the difference between
Input 1 and Input 2 must change or become
zero, and the absolute value of the difference
must be less than or equal to half of the
Differential for the Present Value to change to
False. When the Differential is 0, any difference
between Input 1 and Input 2 makes the Present
Value True.2
True
False
>
<
>=
<=
<>
FIG:Comparison
(Input 1 - Input 2)
Logic 1459
Constant
The Constant folder in the control block palette contains blocks that pass a
constant value to block inputs. Constant blocks can have multiple connections to
the output of the block. Constant blocks can be any one of the following:
Table 39-606: Constant Blocks
Block 1 Description Outputs2
Constant (Boolean) Provides a configurable constant value of Boolean type. Present Value (Boolean)
Constant (Enum) Provides a configurable constant value of Enumeration Present Value (Enum)
(Enum) type.
Constant (Float) Provides a configurable constant value of Floating Present Value (Float)
(Float) type.
1. For a constant block, the current Boolean, Enumeration, or Floating value appears in the header of the block.
2. The outputs of this block are exposed for connection by default.
Container
The Container folder in the control block palette contains the Activity and Hybrid
Activity blocks that act as containers for other blocks.
Table 39-607: Container Blocks
Type Description
Activity Contains additional logic than what is displayed in the current logic
diagram. This block allows you to display only the output in the diagram.
Hybrid Activity Contains state-based logic. You can define different logic for each state in
the chosen enumeration set. You also can add the Hybrid Activity to the
State Tables. For information on working with this block, see Configuring a
Hybrid Activity in the Configuring a System section.
MSC Pre-Processor
The MSC Pre-Processor logic block provides configuration for the Multistage
Controller. This block also filters the Process Variable of a PID when it is used in
conjunction with the Multistage Controller to control staged (discrete) devices.
The MSC Pre-Processor is connected between the PID Pre-Processor and the PID
to adjust the default tuning data based on the constraints of controlling a set of
staged devices.
Note: An external deadband is required for the process variable when using the
MSC with the adaptive tuning feature of the PID. For proper configuration of
the PID Pre-Processor with the MSC Pre-Processor and PID, see the Cooling Staged
Outputs and Heating Staged Outputs modules (that is, view their logic).
The following table describes the inputs and outputs of the MSC Pre-Processor
logic block.
Table 39-608: MSC Pre-Processor Block Inputs and Outputs (Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Max Capacity Float No Indicates the ratio of the largest capacity 0.33%
Fraction device to the sum of all of the device Display
capacities. This value is obtained from the Precision: 100ths
MSC module.
Min Off Time Float No Indicates the requested minimum time that an 120 Seconds
output must remain Off before being
reactivated to an On condition following
deactivation.
Min On Time Float No Indicates the requested minimum time 240 Seconds
interval that an output must remain On before
being deactivated to an Off condition
following activation.
Minimum Tune Float Yes Provides a value used to determine the Eff 0.0
Band Min Tune Band if User Overwrite Minimum
Tune Band is set to True.
Process Range Float Yes Indicates the range of the process. 22, 40
Process Float Yes Indicates the value from the area being 0.0
Variable controlled. This value typically comes from a
sensor or after some signal processing is
passed to the MSC Pre-Processor block.
Logic 1461
Table 39-608: MSC Pre-Processor Block Inputs and Outputs (Part 2 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Time Constant Float Yes Indicates the dominant time constant of the 720 Seconds
process.
Units Enum No Contains the units for the Process Variable, Deg C, Deg F
Process Range, Minimum Tune Band,
Present Value, and Eff Min Tune Band.
Outputs
Eff Min Off Time Float No Indicates the minimum time interval that an 120 Seconds
output must remain Off before being
reactivated to an On condition following
deactivation. This value is always greater
than or equal to the Min Off Time.
Eff Min On Time Float No Indicates the minimum time interval that an 240 Seconds
output must remain On before being
deactivated to an Off condition following
activation. This value is always greater than
or equal to the Min On Time.
Eff Min Tune Float No Provides the Minimum Tune Band used by 10, 16
Band the PID algorithm and the control band used
by the PMAC algorithm.
Eff Time Float No Provides the time constant used by the PID 720 Seconds
Constant and PMAC algorithms.
Interval Float No Indicates the period for this block and for the 24 Seconds
MSC's PMAC Interval. The calculation for the
Interval must truncate the resulting value to
an integer.
Present Value1 Float Yes Indicates the current output of the MSC Pre- 0.0
Processor block. This value is the filtered
Process Variable.
Properties
Min Period Number N/A Indicates the shortest period that can be 1 Second
executed.
PMAC Number N/A Indicates the number of PMAC executions per 30
Executions Time Constant.
Settling Time Number N/A Indicates the being used with the EWMA to 720 Seconds
filter the Process Variable.
Standard Boolean N/A Indicates whether to use the default True
Minimum Tune calculation for the Eff Min Tune Band or to
Band use the user-defined Minimum Tune Band to
determine the Eff Min Tune Band.
Logic 1463
Table 39-609: PID Pre-Processor Block Inputs and Outputs (Part 2 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Units Enum No Specifies the units used for the process being Deg C, Deg F
controlled. For each Process Identifier, only a
certain set of units is allowed (see Process ID
Configuration Restrictions). If the Process
Identifier is set to a value that does align with
the current Units, the block’s reliability is set
to Input Out of Range and the logic
continues to use the last reliable value.
However, if Standard Tuning is False, the
Process ID and Units inputs are ignored, the
block is Reliable, and the outputs are
calculated based on the current values of the
Process Time Constant, Process Dead Time,
and Process Range inputs.
Outputs
Eff Process Float Yes Indicates the dead time determined by the 72 Seconds
Dead Time block to pass to the PID.
Eff Process Float Yes Indicates the process range determined by 22, 40
Range the block to pass to the PID.
Eff Time Float Yes Indicates the time constant determined by the 720 Seconds
Constant block to pass to the PID.
Minimum Tune Float Yes Indicates the region around the PID setpoint 0.88, 1.6
Band that the PRAC+ does not attempt to tune.
Properties
Output Float N/A Provides a value equal to the resolution of the 0.01
Resolution digital to analog converter for the process
output. This value is used to calculate the
Minimum Tune Band.
The Output Resolution is calculated as 1/100
based on the worst case number of steps for
a 0-10V actuator with a 0.1V response
resolution.
1. Setting the Process ID to Other requires configuration of the Time Constant, Process Dead Time, and Process
Range inputs.
Logic 1465
Table 39-611: PID Block Inputs and Outputs (Part 2 of 6)
Name Data Exposed for Description Default
Type Connection Value
by Default
Low Limit Float No Indicates the minimum value the PID Present 0.0
Value can assume. The Low Limit must be less
than or equal to the High Limit. If the Low Limit is
set to a value greater than the High Limit, the
block’s reliability is set to Input Out of Range and
the logic sets the Present Value to the Low Limit;
otherwise, the block behaves as if the limits are
equal.
If the Low Limit is set to the same value as the
High Limit, the logic sets the Present Value to this
value and calculates the Saturation Status. The
Saturation Status calculation is based on the
current value for the Setpoint, Process Variable,
and Direct Acting inputs (If these inputs are equal,
the block’s Reliability is not set to Input Out of
Range).
When Direct Acting is True, if the Process
Variable is less than the Setpoint, the block sets
the Saturation Status to Low. If the Process
Variable is greater than the Setpoint, the block
sets the Saturation Status to High. If the Process
Variable is equal to the Setpoint, the Saturation
Status is set to Normal. When Direct Acting is
False, the opposite behavior occurs (Saturation
Status is High if the Process Variable is less than
the Setpoint and vice versa).
When the limits are equal, the block may execute
on any input change or on the block’s normal
periodic interval. The Error and Execution Count
are updated when the block executes its logic.
The diagnostic outputs (EWMAs) are held at their
last values. The PRAC function is skipped and the
PRAC Status output is set to Normal.
Minimum Tune Float Yes Indicates the region around the Setpoint that the 0.88, 1.6
Band PRAC+ does not attempt to tune. The PID Pre-
Processor and PMAC Pre-Processor blocks
calculate this value based on the outputs being
controlled.
Offset Float No Indicates the value added to the sum of the 0.0
proportional term, integral term, and derivative
term used to generate the Present Value. The
Present Value equals the Offset when the
proportional, integral, and derivative terms are
equal to zero. The Offset has no effect for PI or
PID control (that is, the Offset’s effect is negated
by the bumpless transfer to the Startup Value).
Process Dead Float Yes Indicates the time required for the process to 72 Seconds
Time begin to reflect the results of a step change. When
the Manual Tuning property is False, this input is
used to calculate the initial tuning setup.
Logic 1467
Table 39-611: PID Block Inputs and Outputs (Part 4 of 6)
Name Data Exposed for Description Default
Type Connection Value
by Default
PRAC Status Enum No Indicates the results of the most recent PRAC+ Normal
calculation execution:
• Normal: Normal operation
• Monitoring Setpoint Change: Feature
extraction following large setpoint change in
progress
• Monitoring Load Disturbance: Feature
extraction following large load disturbance in
progress
• Tuning NOT Updated: Insignificant pattern or
control output saturated observed
• Normal Tuning Update: New gain and integral
time have been computed
• Gain Decreased: New decreased gain
computed because of fast oscillations
Present Value1 Float Yes Indicates the current output of the PID block. This 0.0
value is typically passed to an actuator to provide
repositioning information or provides the setpoint
to another PID block when using cascaded control
loops. The Present Value equals the sum of the
proportional, integral, derivative, and offset terms.
Present Value Float No Provides an EWMA of the current Present Value 0.0%
EWMA scaled to a percent where the Percent Present
Value = 100.0 x (Present Value - Low Limit) /
(High Limit - Low Limit).
Saturation Enum Yes Indicates the current operational status of the PID Normal
Status block. This value is based on the output and the
amount of time that the output is at the high or low
limits. The Saturation Status is set to Normal the
first execution after the PID is Enabled (or
Re-Enabled). The Saturation Status is Normal for
at least one execution after returning from a non-
Normal state. For example, if the Saturation
Status is Timing High and the Present Value
becomes equal to the Low Limit, the Saturation
Status is Normal for one execution before
transitioning to Timing Low at the next execution.
Note: The Enumeration Set for Saturation Status
contains the Overridden state, but the PID
does not set this attribute to that value. The
Overridden state is used by other
applications.
Properties
Actual Period Float N/A Indicates the actual instantaneous period of 120 Seconds
execution, measured as the actual time between
successive executions of the PID algorithm. This
value is not computed after the first periodic
execution (startup, restart, or enable after
disable), in which case the value is assigned the
value of Eff Period.
Deadband Float N/A Sets the Eff Deadband when Manual Tuning is 0.0
True. This value is a band centered around the
Setpoint where the error is considered zero (+/-
DB/2).
Logic 1469
Table 39-611: PID Block Inputs and Outputs (Part 6 of 6)
Name Data Exposed for Description Default
Type Connection Value
by Default
Proportional Float N/A Sets the Eff Proportional Band when Manual 16.0, 28.8
Band Tuning is True. This value is the amount of
change in the Process Variable that produces a
full range change (High Limit - Low Limit) in the
Present Value. This value must be a positive
number, and must be greater than zero. The
action is set using the Direct Acting input rather
than by the sign of the Proportional Band.
Saturation Time Float N/A Sets the Eff Saturation Time when Manual Tuning 720 Seconds
is True. This value is the duration the Present
Value must meet or exceed either the Low or High
Limit for the saturation status to be set to Low or
High.
Setpoint Float N/A Determines when a setpoint change is large 1.0, 1.8
Differential enough for immediate execution when Manual
Tuning is True.
Smoothing Float N/A Indicates the value used in the EWMA calculation. 3.703704 E-
Constant 03
1/270
Tuning Updated Boolean N/A Indicates if PRAC+ has updated the tuning False
parameters.
Logic 1471
Table 39-612: PVDC Block Inputs and Outputs (Part 2 of 3)
Name Data Exposed for Description Default Value
Type Connection
by Default
Startup Value Float No Indicates the startup value of PVDC 0.0%
output. This value is used when startup
or restart is the value of the PVDC
Present Value.
Outputs
Absolute Effort Float No Provides an EWMA value for the 0.0%
EWMA absolute value of the controller effort.
Absolute Error Float No Provides an EWMA value for the 0.0
EWMA absolute value of the flow error (flow
setpoint - flow measurement).
Error EWMA Float No Indicates the EWMA value of the flow 0.0
error (flow setpoint - flow measurement).
Present Value1 Float Yes Indicates the position, in percentage of 0.0%
maximum output, being requested by the
PVDC Controller of the motor actuator.
The Present Value is limited from 0 to
100%. When the calculation results in a
value beyond a limit, the Present Value
should be set to that limit.
Present Value Float No Indicates the EWMA value of the Present 0.0%
EWMA Value.
Saturation Enum Yes Indicates the current operational status of Normal
Status the PVDC block. This value is based on
the output and the amount of time that
the output is at the high or low limits
(100% or 0%, respectively). The
Saturation Status is set to Normal the
first execution after the PVDC is Enabled
(or Re-Enabled). The Saturation Status is
Normal for at least one execution after
returning from a non-Normal state. For
example, if the Saturation Status is
Timing High and the Present Value
becomes equal to the Low Limit, the
Saturation Status is Normal for one
execution before transitioning to Timing
Low at the next execution.
Note: The Enumeration Set for
Saturation Status contains the
Overridden state, but the PVDC
does not set this attribute to that
value. The Overridden state is
used by other applications.
Properties
Actual Period Float N/A Indicates the actual instantaneous period 1 Second
of execution, measured as the actual
time between successive periodic
executions of the PVDC algorithm. This
value is not computed after the first
periodic execution (startup, restart, or
enable after disable) or when the block
executes for any other reason (for
example, when an input changes value).
Dynamic Float N/A Indicates the smoothed Deadzone value. 0.0
Deadband
Logic 1473
Math
The Math folder in the control block palette contains blocks that perform
mathematical functions on one or more inputs, producing a single output. The
number of inputs to a Math block depends on the number of inputs supported by
the type of math function. The Logic View allows you to add multiple connections
to the output of the block.
Table 39-613: Math Blocks
Type Description Inputs (Float)1 Outputs (Float)1
Absolute Value Absolute Value I1 Present Value
ACOS2 Arc Cosine I1 Present Value
Add Add I1 Present Value
I2
New Port
ASIN2 Arc Sine I1 Present Value
1. The inputs and outputs of this block are exposed for connection by default.
2. This block uses radians instead of degrees. To convert from degrees to radians, multiply the value
by 0.0174533, that is, pi/180.
Absolute Humidity
The Absolute Humidity logic block calculates the density of the water vapor
element of air. The absolute humidity is the ratio of the mass of water vapor to
volume. The following table describes the inputs and outputs of the Absolute
Humidity logic block.
Table 39-614: Absolute Humidity Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Dry Bulb Float Yes Indicates the temperature of air as 25 Deg F, 77 Deg C
Temperature measured with a simple thermometer.
Relative Float Yes Indicates the relative humidity of air. 50%
Humidity Range: 0-100%
Outputs
Absolute Float Yes Indicates the density of water vapor in air. 11.5, 0.000718
Humidity1 Units: lb/c ft, g/c m
Properties
Unit Set Enum N/A Indicates the units of measurement used by SI, IP
the block.
Logic 1475
Dew Point
The Dew Point logic block calculates the dew point temperature of air. The
following table describes the inputs and outputs of the Dew Point logic block.
Table 39-615: Dew Point Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Dry Bulb Float Yes Indicates the temperature of air as 25 Deg F, 77 Deg C
Temperature measured with a simple thermometer.
Relative Float Yes Indicates the relative humidity of air. 50%
Humidity Range: 0-100%
Outputs
Dew Point Float Yes Indicates the dew point temperature of air, 14.0 Deg F, 57.0
Temperature1 which is the temperature at which moisture Deg C
condenses out of the air.
Properties
Unit Set Enum N/A Indicates the units of measurement used by SI, IP
the block.
Logic 1477
Free Cooling is Available
The Free Cooling is Available logic block provides economizer decision logic to
determine when outdoor air, in excess of the minimum amount required for
ventilation, can be used to reduce the cooling coil load.
The output is evaluated when the Supply Fan Status input changes and then
subsequently only on its Interval (configurable property in the Advanced Details
dialog box). This block does not constantly calculate its outputs as the inputs
change.
Different methods include:
• Dry Bulb Temperature Economizer where if the supply fan is running and
the Outside Air Temp is less than the Change Over Temp, then Free Cooling
Available is True.
• Temperature and Enthalpy Economizer where measurements of Outside
Air Temp, Outside Air Humidity, Return Air Temp, and Return Air Humidity
are used to calculate the enthalpy of the outside air and return air streams. Free
Cooling Available is True when:
- the supply fan is running
- the calculated outside air enthalpy is less than the calculated return air
enthalpy
- the outside air dry bulb temperature is less than the return air dry bulb
temperature
• Model Based Economizer where measurements of Outside Air Temp,
Outside Air Humidity, Return Air Temp, and Return Air Humidity as well as
an estimate of the temperature leaving the cooling coil are used for
calculations.
The following table describes the inputs and outputs of the Free Cooling is
Available logic block.
Table 39-617: Free Cooling is Available Block Inputs and Outputs (Part 1
of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Bypass Percent Float No Indicates the percent of air passing through 20%
the coil that is unaffected by the coil (%). Range: 0-50%
This value is used for the Model-Based
Economizer Type.
Change Over Float No Indicates the change over dry bulb 20.0 Deg F, 68.0
Temperature temperature used to determine if free Deg C
cooling is available for the Dry Bulb
Temperature economizer option.
Cooling Float Yes Indicates the effective discharge air 12.0 Deg F, 55.0
Discharge temperature for the cooling coil. This value Deg C
Temperature is used for the Model-Based Economizer
Type.
Logic 1479
Relative Humidity
The Relative Humidity logic block calculates the Relative Humidity of air given
dry bulb temperature and either the dew point or wet bulb temperature. The
following table describes the inputs and outputs of the Relative Humidity logic
block.
Table 39-618: Relative Humidity Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Dew Point Float No Indicates the dew point temperature of air, 14.0 Deg F, 57.0
Temperature which is the temperature at which moisture Deg C
condenses out of the air. If the Setup
property is DP, this input represents the air
dew point temperature that is used to
calculate Enthalpy. If the Setup property is
WB, this input is ignored.
Dry Bulb Float Yes Indicates the temperature of air as 25 Deg F, 77 Deg C
Temperature measured with a simple thermometer.
Elevation Float No Indicates the distance above or below sea 0 ft, 0 m
level. Below sea level is represented with a
negative value.
Wet Bulb Float No Indicates the wet bulb temperature. If the 18.0 Deg F, 64.4
Temperature Setup property is WB, this input represents Deg C
the air wet bulb temperature that is used to
calculate Relative Humidity. If the Setup
property is DP, this input is ignored.
Outputs
Relative Float Yes Indicates the relative humidity of air. 50%
Humidity1 Range: 0-100%
Properties
Setup Enum N/A Indicates if wet bulb or dew point WB
temperature is used as the second
independent variable to calculate Relative
Humidity.
Unit Set Enum N/A Indicates the units of measurement used by SI, IP
the block.
Logic 1481
Selection
The Selection folder in the control block palette contains Command Hierarchy and
MUX blocks that perform multiplexing for 2 inputs and one mode input,
producing a single output. Based on the current mode assigned to each input, the
selector chooses which input to pass through to the output. The Logic View allows
you to add multiple connections to the output of the block. You must double-click
a Selection block to configure it (for example, to specify the number of input ports
for a MUX block or to add and delete input ports in a Command Hierarchy block).
See Configuring the MUX Block, Configuring the Command Hierarchy Block, and
Configuring the Translation Blocks in the Configuring a System section.
Table 39-620: Selection Blocks
Type Description Inputs1 Outputs1
Boolean to Enum Provides a pre-configured Command I1 (Boolean) State (Enum)
Translation Hierarchy block with a single Boolean
input translated to an Enumeration
(Enum) output.
Command Hierarchy Provides truth table evaluation capability I1 (Enum) State (Boolean)
(Boolean Output) to convert or resolve multiple inputs into I2 (Boolean)
a single output State of Boolean type.
Command Hierarchy Provides truth table evaluation capability I1 (Enum) State (Enum)
(Enum Output) to convert or resolve multiple inputs into I2 (Boolean)
a single output State of Enumeration
(Enum) type.
Enum to Boolean Provides a pre-configured Command I1 (Enum) State (Boolean)
Translation Hierarchy block with a single
Enumeration (Enum) input translated to
a Boolean output.
MUX (Boolean IO, Provides source-switching operation. A Mode (Boolean) Present Value
Boolean Mode) Multiplexor is equivalent to a switch, I1 (Boolean) (Boolean)
which directs one of the Inputs, based I2 (Boolean)
on the Mode, to the Present Value.
This block has Boolean inputs and a
Boolean mode.
MUX (Boolean IO, Enum Same as previous, except this block has Mode (Enum) Present Value
Mode) Boolean inputs and an Enumeration I1 (Boolean) (Boolean)
(Enum) mode. I2 (Boolean)
MUX (Enum IO, Boolean Same as previous, except this block has Mode (Boolean) Present Value
Mode) Enumeration (Enum) inputs and a I1 (Enum) (Enum)
Boolean mode. I2 (Enum)
MUX (Enum IO, Enum Same as previous, except this block has Mode (Enum) Present Value
Mode) Enumeration (Enum) inputs and an I1 (Enum) (Enum)
Enumeration mode. I2 (Enum)
MUX (Float IO, Boolean Same as previous, except this block has Mode (Boolean) Present Value
Mode) Floating (Float) inputs and a Boolean I1 (Float) (Float)
mode. I2 (Float)
MUX (Float IO, Enum Same as previous, except this block has Mode (Enum) Present Value
Mode) Floating (Float) inputs and an I1 (Float) (Float)
Enumeration (Enum) mode. I2 (Float)
1. The inputs and outputs of this block are exposed for connection by default.
1. The inputs and outputs of this block are exposed for connection by default.
Logic 1483
Timing
The Timing folder in the control block palette contains blocks that perform timing
functions such as Pulse, On Delay, and Off Delay. Timing blocks are used to break
up feedback loops. The Timing blocks include:
• Execution Status
• Last Value (Boolean)
• Last Value (Enum)
• Last Value (Float)
• Latch
• Rate Limiter
• Timer
Execution Status
The Execution Status logic block provides information about the conditions of the
current execution:
• Power Up: First execution following controller power cycle
• Restart: First execution following controller reboot without the power being
lost
• Re-Enabled: Neither of the above conditions are true and this is the first
execution after being re-enabled
• Normal: None of the above conditions are true
An example use of the Execution Status block is to execute alternate logic the first
execution following a power failure or controller restart by using the Present Value
to set the State of a Hybrid Activity.
Similarly, you can use this block to perform a different calculation the first
execution after a particular State of a Hybrid Activity is enabled (for example,
Execution Status - Present Value connecting to a MUX within a Hybrid Activity
State section).
Logic 1485
Last Value (Boolean)
The Last Value (Boolean) logic block holds the value that its input (Boolean type)
had at the end of the previous execution of the control logic for use by the current
execution. Use this block to compare the current value of a variable with the value
from the last execution.
We do not recommend connecting multiple Last Value blocks. You cannot use
Last Value blocks to create a moving average because the execution interval of the
control logic is not periodic. If a signal requires filtering or you need a moving
average, use the EWMA block.
We do not recommend using the Last Value blocks in an attempt to integrate a
value. Use the Totalization (Analog Integration) block to integrate a value.
When the control logic completes its execution and a new change (value,
reliability, or command) gets written to the input of a Last Value block (causing
the current value of the input to change), the block requests to execute again
immediately. If the logic is designed so that the input to the Last Value block
changes every execution, an infinite loop is created resulting in impaired
performance of the controller. Avoid configuring the Last Value block in this
manner.
If this block does not operate continuously (that is, is placed in the state section of
a hybrid activity), it starts at its Default Value when re-enabled. One additional
constraint is that connections from Hybrid Activity Inputs are not allowed to be
made directly to the Input of Last Value block in one of its State Sections. If such
logic is needed, a no-op component (such as adding zero to a float) should be
connected between the Input and the Last Value. This is required because the
Hybrid Activity inputs are considered part of the Event Section and are therefore
earlier in the sequence order than all State Section components.
For more Last Value information, see the Timing Output Controller and Timing
Setpoint Determination/Misc sections. The following table describes the inputs
and outputs of the Last Value (Boolean) logic block.
Table 39-623: Last Value (Boolean) Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Input Boolean Yes Passes the Default Value of this Input to the False
Present Value on the first execution after
startup or being enabled. Otherwise, the
Current Value of the Input is passed to the
Present Value.
Outputs
Present Value1 Boolean Yes Indicates the output of the block. False
Properties
Include State Boolean N/A Indicates if the block passes or drops the True
Status command signature from the input.
Logic 1487
Last Value (Float)
The Last Value (Float) logic block holds the value that its input (Floating [Float]
type) had at the end of the previous execution of the control logic for use by the
current execution. Use this block to compare the current value of a variable with
the value from the last execution.
We do not recommend connecting multiple Last Value blocks. You cannot use
Last Value blocks to create a moving average because the execution interval of the
control logic is not periodic. If a signal requires filtering or you need a moving
average, use the EWMA block.
We do not recommend using the Last Value blocks in an attempt to integrate a
value. Use the Totalization (Analog Integration) block to integrate a value.
When the control logic completes its execution and a new change (value,
reliability, or command) gets written to the input of a Last Value block (causing
the current value of the input to change), the block requests to execute again
immediately. If the logic is designed so that the input to the Last Value block
changes every execution, an infinite loop is created resulting in impaired
performance of the controller. Avoid configuring the Last Value block in this
manner.
If this block does not operate continuously (that is, is placed in the state section of
a hybrid activity), it starts at its Default Value when re-enabled. One additional
constraint is that connections from Hybrid Activity Inputs are not allowed to be
made directly to the Input of Last Value block in one of its State Sections. If such
logic is needed, a no-op component (such as adding zero to a float) should be
connected between the Input and the Last Value. This is required because the
Hybrid Activity inputs are considered part of the Event Section and are therefore
earlier in the sequence order than all State Section components.
For more Last Value information, see the Timing Output Controller and Timing
Setpoint Determination/Misc sections. The following table describes the inputs
and outputs of the Last Value (Float) logic block.
Table 39-625: Last Value (Float) Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Input Float Yes Passes the Default Value of this Input to the 0.0
Present Value on the first execution after
startup or being enabled. Otherwise, the
Current Value of the Input is passed to the
Present Value.
Outputs
Present Value1 Float Yes Indicates the output of the block. 0.0
Properties
Include State Boolean N/A Indicates if the block passes or drops the True
Status command signature from the input.
Logic 1489
Rate Limiter
The Rate Limiter logic block controls the rate at which the Output changes with
variations in the Input value. If rate limiting is disabled, this block passes the value
of the Input to the Output. If rate limiting is enabled, this block limits changes to its
Output to an increment determined by the Step Equation. The Rate Limiter block
updates every 5 seconds.
Step Equation = Rate Limit x 5/60.0
The following table describes the inputs and outputs of the Rate Limiter logic
block.
Table 39-627: Rate Limiter Block Inputs and Outputs
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Input Float Yes Provides an Analog Value to the block. 0.0
Startup Value Float No Sets the output to this value when the block 0.0
is enabled.
Rate Limit Float No Provides an Analog Value used in the step 100.0
equation. The output is incremented or Units: Change per
decremented by this value. Minute
Limit Active Boolean No Enables the block to operate when set to True
True. If Limit Active is False, the output is
set to equal the input.
Outputs
Present Value1 Float Yes Indicates the output of the block. 0.0
Properties
Actively Boolean N/A Provides the following behavior: False
Limiting • If Limit Active is True, then this value is
True if the Present Value does not
reach the Input at that execution. This
value is False on the execution when
the Present Value reaches the Input.
• If Limit Active is False, then this value
remains False.
Interval Float N/A Indicates the amount of time between 5.0 Seconds
updates of the block’s output when Actively
Limiting is True.
Logic 1491
• Minimum Off: The Present Value tracks the Input except that it must remain
False for the Duration time before following the Input to True. For example,
once a chiller is turned off, it must be left off for a minimum time to allow
refrigerant to equalize.
The following table describes the inputs and outputs of the Timer logic block.
Table 39-628: Timer Block Inputs and Outputs (Part 1 of 2)
Name Data Exposed for Description Default Value
Type Connection
by Default
Inputs
Duration Float No Indicates the time period used for the 5 Seconds
specified Timer configuration.
You can change the Duration during the
execution of a Timer. If the Duration is
changed when the Timer is running a timing
cycle, the Time Remaining is set to equal the
new Duration.
For values less than 6,535 seconds, the
timing resolution is set to the nearest second.
For values greater than 6,535 seconds, the
timing resolution is rounded to the nearest
minute.
Note: CCT prevents updates to this block if
you attempt to set the Duration out of
range (Default Value and Test Value).
The block clamps the Eff Duration
property at end of the allowed range (5
to 3,888,000).
Input Boolean Yes Provides a Boolean signal that drives the False
Timer block for all Setup values other than
Free Running.
Reset Boolean No Restarts the operation, forcing the Present False
Value to False. Reset has no effect when
Setup is Minimum On or Minimum Off.
Reset Action Enum No Defines the behavior of the Timer block’s Wait
Present Value when Reset is changed from
True to False. This attribute only affects the
operation of the Timer when the value of
Setup is Pulse, Cancelable Pulse, or
Retriggerable Pulse. You can change the
Reset Action during the execution of the
Timer. The change takes effect on the next
execution.
Setup Enum No Identifies the type of timer function being used Pulse
for the Timer block. You can change the
Setup (type of timer) of the Timer at any time.
Changing the Setup cancels the Timer block's
previous activities and causes the Timer to
behave as if it were just re-enabled.
Outputs
Present Value1 Boolean Yes Indicates the current value of the output of the False
block.
Logic 1493
Custom
The Custom folder only appears in the control block palette after exporting and/or
sharing custom modules.
An exported module is saved in a file in the C:\Program
Files\Johnson Controls\CCT\Custom Control Modules directory on your computer
using the current name of the module with a .caf.module file extension.
You can share the exported file with other users by placing a copy of the file in the
C:\Program Files\Johnson Controls\CCT\Custom Control Modules directory on a
different computer and the module appears in the Custom folder in the palette the
next time CCT is started on that computer.
See Exporting a Module in the Configuring a System section.
Troubleshooting 1495
Table 40-629: CCT Troubleshooting (Part 2 of 2)
Problem Solution
You are experiencing problems Download devices over the SA Bus using the Point Schedule using
downloading devices over the SA Bus the following sequence:
using the Point Schedule. 1. Individually download the Main Code of the device that is
connected to the SA Bus.
2. Individually download the Application Code of the device that is
connected to the SA Bus.
3. Select all other devices at once, as necessary, for the required
operations.
You are experiencing problems Use the FC Bus to download multiple devices at once, if possible.
downloading multiple devices at once
(for example, using the Point Schedule).
You are experiencing slow speed while If you are using the NAE Point Schedule to perform multiple
downloading multiple devices at once downloads at once, overall download speed can be improved by first
(for example, using the Point Schedule). disconnecting the field bus from the NAE.
After selecting items to print from the This problem occurs only on some computers. To print the Summary
Summary Report Options dialog box, Report:
CCT does not display the selections in 1. Navigate to the Print.pdf file in the following location:
a PDF in Adobe Acrobat Reader C:\Program Files\Johnson Controls\CCT
software. 2. Double-click Print.pdf to open the file.
3. Print and/or save the PDF as desired from the Adobe Acrobat
Reader software.
Note: The Print.pdf file is overwritten each time you print (run) a
Summary Report from CCT.
The CCT Help does not fully open on a Microsoft Windows XP operating system with SP2 (or similar system)
computer running the Windows XP and Internet Explorer security settings may prevent Help systems with
Operating System with SP2 (or similar active content from opening without first verifying it is OK to open. To
system) and the following security open the Help:
message appears in the Internet 1. Click Click here for options... and select Allow Blocked Content.
Explorer Information Bar: A Security Warning dialog box appears stating:
To help protect your security, Allowing active content such as script and ActiveX
Internet Explorer has controls can be useful, but active content might
restricted this file from also harm your computer. Are you sure you want to
showing active content that let this file run active content?
could access your computer. 2. Click Yes. The CCT Help system opens.
Click here for options...
The CCT Help Favorites tab does not Enable the Java settings on your computer. See Help Appearance in
appear. the Using This Help System section.
A connection error occurs when you Check the SQL Server settings:
first run CCT and MSDE is installed on 1. Browse to the following folder: C:\Program Files\Microsoft SQL
your computer. Server\80\Tools\Binn\
2. Double-click svrnetcn.exe. The SQL Server Network Utility dialog
box appears with the General tab active.
3. Move Named Pipes and TCP/IP to the Enabled Protocols list.
4. Click OK.
5. Restart SQL Server.
6. Start CCT.
A
ACOS
Arc Cosine. See Math in the Logic section.
A/D
Analog to Digital Converter
ADS
Application and Data Server
ADX
Extended Application and Data Server
AHU
Air Handling Unit
AI
Analog Input
AO
Analog Output
Application
An application is a collection of the components that make up the control logic of a
system, including modules, logic blocks, custom logic, and hardware definition.
For information on the types of applications you can create, see the Applications
section.
ASHRAE
American Society of Heating, Refrigerating, and Air-Conditioning Engineers
ASIN
Arc Sine. See Math in the Logic section.
ATAN
Arc Tangent. See Math in the Logic section.
Glossary 1537
AV
Analog Value
AVG
Average. See Statistical in the Logic section.
Back to Glossary Introduction.
B
BAS
Building Automation System
BI
Binary Input
Block
See Logic Block.
BO
Binary Output
Boolean
Boolean logic and operators where data can only be true or false and manipulated
by operators such as AND, OR, and NOT. See Boolean in the Logic section.
BSP
British Standard Pipe
BV
Binary Value
Back to Glossary Introduction.
C
.caf
Controller Application File
CI
Counter Input
CO
Configurable Output
COS
Cosine. See Math in the Logic section.
COV
Change of Value
CPU
Central Processing Unit
CHW
Chilled Water
CW
Condenser Water
Back to Glossary Introduction.
D
D/A
Digital to Analog Converter
Back to Glossary Introduction.
E
Enum
Enumeration: A set of ordered data.
EWMA
Exponentially-Weighted Moving Average. See Calculation in the Logic section.
EXP
Exponent. See Math in the Logic section.
Back to Glossary Introduction.
Glossary 1539
F
FBPD
Face and Bypass Damper
FEC
Field Equipment Controller: The FEC is a configurable digital controller that uses
the BACnet MS/TP communications protocol.
FC Bus
Field Controller Bus: The FC Bus connects MS/TP field controllers to the Metasys
system Supervisory Controller.
FCB
Field Controller Bus. See FC Bus.
Float
Floating point
FSCS
Firefighter Smoke Control Station
FSM
Finite State Machine
Back to Glossary Introduction.
H
HW
Hot Water
HX
Heat Recovery
Back to Glossary Introduction.
I
IO
Input/Output
IOM
Input/Output Module: The IOM provides expanded Input/Output capabilities to
the FEC to support specific applications.
Back to Glossary Introduction.
Logic Block
A logic block is a component used to construct the control logic of a system. You
can view and work with logic blocks in the Logic View of CCT. Logic block
inputs are used to influence the state or values presented as outputs. You can view
and/or edit logic contained within modules highlighted in tan in the Control View,
but changes should not be made until the default logic is thoroughly understood
and the effect of changes on the connected outputs is considered. See the Logic
section for information on logic blocks.
Back to Glossary Introduction.
M
MAC Address
Media Access Control Address: The MAC Address is the same as the field device
address.
MADD
Mixed Air Dual Duct application. See the Air Handling Unit Applications section.
MASD
Mixed Air Single Duct application. See the Air Handling Unit Applications
section.
MAX
Maximum. See Statistical in the Logic section.
MIN
Minimum. See Statistical in the Logic section.
Module
A module is a component made up of logic blocks used to create portions of the
overall control logic of a system. Module inputs are used to influence the state or
values presented as outputs. You can view and /or edit modules highlighted in tan
in the Control View, but changes should not be made until the default
configuration is thoroughly understood and the effect of changes on the connected
outputs is considered. See the Modules section.
MSC
Multistage Controller. See Control in the Logic section.
Glossary 1541
MS/TP
Master-Slave/Token-Passing: MS/TP is a communications bus protocol based on
BACnet standard protocol SSPC-135, Clause 9. The MS/TP communications bus
connects supervisory controllers and field controllers to point interfaces.
MUX
Multiplexor. See Selection in the Logic section.
MV
Multistate Value
MZ
Multizone application. See the Multizone (Mixed Air Dual Duct) Application
section.
Back to Glossary Introduction.
N
NAE
Network Automation Engine
NCE
Network Control Engine: A controller that combines the network supervisor
capabilities and IP network connectivity of a NAE with the Input/Output point
connectivity and direct digital control capabilities of a Metasys Field Equipment
Controller.
Back to Glossary Introduction.
O
OADD
100% Outdoor Air Dual Duct application. See the Air Handling Unit Applications
section.
OASD
100% Outdoor Air Single Duct application. See the Air Handling Unit
Applications section.
Back to Glossary Introduction.
P
PAO
Position Adjust Output
PCHW
Primary Chilled Water
PDF
Portable Document Format. See the Printing the Entire Help System section.
PHW
Primary Hot Water
PID
Proportional plus Integral plus Derivative. See Control in the Logic section.
PVDC
Proportional Variable Deadband Control. See Control in the Logic section.
Back to Glossary Introduction.
R
RO
Relay Output
RTU
Rooftop Unit. See the Rooftop Unit Application section.
Back to Glossary Introduction.
S
SA Bus
Sensor/Actuator Bus: The SA Bus connects point devices (IOMs, VSDs, Local
Controller Displays, or Network Sensors [Duct or Zone]) to the field devices.
SAB
Sensor/Actuator Bus. See SA Bus.
SCW
Secondary Condenser Water
SCHW
Secondary Chilled Water
SHW
Secondary Hot Water
Glossary 1543
SIN
Sine. See Math in the Logic section.
SQRT
Square Root. See Math in the Logic section.
System
In CCT, a system is represented by the mechanical equipment and the logic needed
to control that equipment, independent of hardware definition. The System
Selection Wizard in CCT describes the make up of a mechanical system to aid you
in creating the group of logic components that work together to control the
mechanical system. See System Types and Configurations in the Configuring a
System section.
Back to Glossary Introduction.
T
TAN
Tangent. See Math in the Logic section.
Back to Glossary Introduction.
U
UI
Universal Input (for hardware mapping) or User Interface. See the User Interface
section.
UL
Underwriters Laboratories Inc.
UO
Universal Output
Back to Glossary Introduction.
V
VAV
Variable Air Volume
VAVDD or VAV-DD
VAV Dual Duct application. See the VAV Applications section.
VAVSD or VAV-SD
VAV Single Duct application. See the VAV Applications section.
VSD
Variable Speed Drive
Back to Glossary Introduction.
W
Wireless Commissioning Converter
The Wireless Commissioning Converter is a communications converter that
provides a temporary connection between the laptop running the CCT software
and the device to commission, synchronize, and balance field devices.
Back to Glossary Introduction.
Glossary 1545
1546 CCT Help: Reference
Chapter 43: CCT Help: Reference
Trademarks
Table 43-631: Trademarks
Terms ® TM Owner
ActiveX ® Microsoft Corporation
Adobe ® Adobe Systems Incorporated
ASHRAE ® ASHRAE
BACnet ® ASHRAE
Bluetooth ® Broadcom Corporation
Eaton ® Eaton Corporation
Echelon ® Echelon Corporation
Java ® Sun Microsystems
JavaScript ® Sun Microsystems
LONMARK ® Echelon Corporation
LONWORKS ® Echelon Corporation
Metasys ® Johnson Controls, Inc.
Microsoft ® Microsoft Corporation
Windows ® Microsoft Corporation
All other marks herein are the marks of their respective owners.
Trademarks 1547
1548 CCT Help: Reference
Chapter 44: CCT Help: Reference
Related Documentation
Use the following table to find information available outside this Help system.
Table 44-632: Related Documentation (Part 1 of 2)
For Information On See Document LIT or Part
Number
Metasys System Extended Metasys System Extended Architecture Overview LIT-1201527
Architecture Technical Bulletin
Metasys System Extended Metasys System Extended Architecture Glossary LIT-1201612
Architecture Terms and Acronyms Technical Bulletin
How to Use the Metasys System Metasys system Help LIT-12017931
Extended Architecture User Interface
Metasys System and CCT Metasys System Enumeration Sets Technical LIT-12011361
Enumeration Sets Bulletin
MS/TP Communications MS/TP Communications Bus Technical Bulletin LIT-12011034
How to Install the CCT Software CCT Installation Instructions Part No.
24-10110-77
How to Install the Wireless Wireless Commissioning Converter Installation Part No.
Commissioning Converter Instructions 24-10108-2
How to Set Up the Wireless Metasys CCT Bluetooth Technology LIT-12011038
Commissioning Converter Laptop Communication Commissioning Guide
How to Install the FEC16x0 FEC16x0 Field Equipment Controller Installation Part No.
Instructions 24-10143-4
How to Install the FEC26x0 FEC26x10 Field Equipment Controller Installation Part No.
Instructions 24-10143-12
How to Install the IOM1710 IOM1710 Input/Output Module Installation Part No.
Instructions 24-10144-9
How to Install the IOM2710 and IOM2710 and IOM3710 Input/Output Module Part No.
IOM3710 Installation Instructions 24-10144-17
How to Install the IOM4710 IOM4710 Input/Output Module Installation Part No.
Instructions 24-10144-25
How to Install the VMA1610 and VMA1600 Series Controllers Installation Part No.
VMA1620 Instructions 24-10143-20
How to Balance VAV Boxes VAV Balancing Sensor Technical Bulletin LIT-12011087
How to Install the NCE25 NCE25 Installation Instructions Part No.
24-10143-63
How to Commission and Configure NCE Technical Bulletin LIT-12011267
the NCE
How to Install the Local Controller DIS1710 Local Controller Display Installation Part No.
Display Instructions 24-10240-9
How to Operate the Local Controller DIS1710 Local Controller Display Technical LIT-12011270
Display Bulletin
Index 1551
Analog Input Object . . . . . . . . . . . . 1393 Availability Determination . . . . . . . 917
Analog Input Attributes . . . . . . 1393 AVG . . . . . . . . . . . . . . . . . . . . . . . . 1483
Analog Input Commands . . . . . 1398
Analog Output Attributes . . . . . . . . 1400 B
Analog Output Commands . . . . . . 1403 B
Analog Output Object . . . . . . . . . . 1399 Attribute Type . . . . . . . . . . . . . . 775
Analog Output Attributes . . . . . 1400 Backup Files
Analog Output Commands . . . 1403 System Upgrades . . . . . . . . . . . . 139
Analog Value Attributes . . . . . . . . 1405 BACnet Exposed Parameter . . . . . . 775
Analog Value Commands . . . . . . . 1409 Balancer . . . . . . . . . . . . . . . . . . . 97, 266
Analog Value Object . . . . . . . . . . . 1405 Balancer Override . . . . . . . . . . . . . 1044
Analog Value Attributes . . . . . 1405 Balancer Override DD . . . . . . . . . . 1044
Analog Value Commands . . . . 1409 Balancer Override DDX . . . . . . . . 1044
AND . . . . . . . . . . . . . . . . . . . . . . . . 1443 Balancer Override SD . . . . . . . . . . 1044
Application Code . . . . . . . . . . . . . . . 260 Balancer Override SDX . . . . . . . . . 1044
Application Mode Determination . 1000 Balancer Tab . . . . . . . . . . . 97, 266, 274
Applications . . . . . . . . . . . . . . . . . . . 285 Balancing Parameters . . . . . . . . . . . 274
Air Handling Unit . . . . . . . . . . . 287
Basin Options
Central Cooling . . . . . . . . . . . . . 699 Central Cooling . . . . . . . . . . . . . 732
Central Heating . . . . . . . . . . . . . 737
Central Cooling Modules . . . . . . 732
Central Plant . . . . . . . . . . . . . . . 699
Binary Input Attributes . . . . . . . . . 1411
Fan Coil . . . . . . . . . . . . . . . . . . . 563 Binary Input Commands . . . . . . . . 1413
Heat Pump . . . . . . . . . . . . . . . . . 603
Binary Input Object . . . . . . . . . . . . 1411
Introduction . . . . . . . . . . . . . . . . 285
Binary Input Attributes . . . . . . 1411
Mixed Air Dual Duct . . . . . . . . . 347 Binary Input Commands . . . . . 1413
Mixed Air Single Duct . . . . . . . . 288
Binary Interlock Control . . . . . . . . . 696
Multizone (Mixed Air Dual Duct)
Binary Interlock Control Modules . . 696
. . . . . . . . . . . . . . . . . . . . . . . . . 514 Binary Output Attributes . . . . . . . . 1415
Outdoor Air Dual Duct . . . . . . . 444
Binary Output Commands . . . . . . . 1419
Outdoor Air Single Duct . . . . . . 398
Binary Output Object . . . . . . . . . . . 1415
Rooftop . . . . . . . . . . . . . . . . . . . 486 Binary Output Attributes . . . . . 1415
Sideloop . . . . . . . . . . . . . . . . . . . 691
Binary Output Commands . . . . 1419
Unit Ventilator (Unit Vent) . . . . 581 Binary Value Attributes . . . . . . . . . 1421
VAV . . . . . . . . . . . . . . . . . . . . . . 623 Binary Value Commands . . . . . . . . 1425
VAV Dual Duct . . . . . . . . . . . . . 655
Binary Value Object . . . . . . . . . . . 1421
VAV Single Duct . . . . . . . . . . . . 624 Binary Value Attributes . . . . . . 1421
VAV Slave Dual Duct . . . . . . . . 675 Binary Value Commands . . . . . 1425
VAV Slave Single Duct . . . . . . . 644
Block
ASHRAE Cycle Control Deleting . . . . . . . . . . . . . . . . . . . 177
Unit Ventilator . . . . . . . . . . . . . . 595 Renaming . . . . . . . . . . . . . . . . . . 177
Unit Ventilator Modules . . . . . . 596
Selecting a Block from the Control
ASIN . . . . . . . . . . . . . . . . . . . . . . . 1474 Block Palette . . . . . . . . . . . . . 176
ATAN . . . . . . . . . . . . . . . . . . . . . . 1474 Block Finder . . . . . . . . . . . . . . 102, 226
Attribute Tables . . . . . . . . . . . . . . . . 775
Searching for a Block Using . . . 176
Autocalibrate . . . . . . . . . . . . . . . . . . 274 Block Selection . . . . . . . . . . . . . . . . 226
Autocalibrate Now LV . . . . . . . . . . . 860 Blocking Protection . . . . . . . . . . . . 1311
Autocalibration Sequence . . . . . . . 1041
Index 1553
Condenser Options Modules . . . 731 Central Heating Control Logic Selection
Condenser Water System . . . . . . 716 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 766
Condenser Water System Modules Central Heating Core Logic . . . . . . . 737
. . . . . . . . . . . . . . . . . . . . . . . . . 718 Central Heating Low Temp Control 880
Cooling System Enable . . . . . . . 700 Central Heating Mechanical System
Cooling System Enable Modules 700 Selection . . . . . . . . . . . . . . . . . . . . 738
General Options . . . . . . . . . . . . . 736 Central Plant . . . . . . . . . . . . . . . . . . 699
General Options Modules . . . . . 736 Add-8 . . . . . . . . . . . . . . . . . . . . . 792
Secondary Chill Water Options . 734 Calculate Building Load . . . . . . 871
Secondary Chill Water Options Central Heating Low Temp Control
Modules . . . . . . . . . . . . . . . . . 735 . . . . . . . . . . . . . . . . . . . . . . . . . 880
Secondary Variable Speed Chill Count On Inputs . . . . . . . . . . . . . 883
Water Pumping . . . . . . . . . . . . 723 Device Availability Calculation . 884
Secondary Variable Speed Chill Heat Exchanger with Return Water
Water Pumping Modules . . . . 724 Control . . . . . . . . . . . . . . . . . 1080
Central Cooling Applications . . . . . 699 Load Calculation v2 . . . . . . . . . . 875
Central Cooling Control Logic Selection Output Controller Modules . . . 1080
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 727 PID Sequencer . . . . . . . . . . . . . . 886
Central Cooling Core Logic . . . . . . . 700 Plant Control . . . . . . . . . . . . . . 1083
Central Cooling Mechanical System Plant Sequencing-Building Load 888
Selection . . . . . . . . . . . . . . . . . . . . 700 Plant Sequencing-Decouple . . . . 890
Central Heating . . . . . . . . . . . . . . . . 737 Plant Sequencing-Discrete . . . . . 892
Boiler Options . . . . . . . . . . . . . . 766 Plant Sequencing-Modulating . . 895
Boiler Options Modules . . . . . . . 767 Plant Sequencing-OA-T . . . . . . . 898
General Options . . . . . . . . . . . . . 771 Pump Control . . . . . . . . . . . . . . 1086
General Options Modules . . . . . 772 Pump Control v2 . . . . . . . . . . . 1089
Heat Exchanger Options . . . . . . 769 Rotation Small . . . . . . . . . . . . . 1092
Heat Exchanger Options Modules Secondary Pump PID . . . . . . . . 1097
. . . . . . . . . . . . . . . . . . . . . . . . . 769 Sequenced Output . . . . . . . . . . 1099
Heat Exchangers . . . . . . . . . . . . 751 State Generators . . . . . . . . . . . . . 870
Heat Exchangers Modules . . . . . 753 Subtract . . . . . . . . . . . . . . . . . . . 794
Heating System Enable . . . . . . . 738 System Enable . . . . . . . . . . . . . . 900
Heating System Enable Modules 738 Tower Control . . . . . . . . . . . . . 1100
Hot Water/Steam Boilers . . . . . . 739 Tower Control v2 . . . . . . . . . . . 1103
Hot Water/Steam Boilers Modules Tower Sequencing-1 Speed . . . . 902
. . . . . . . . . . . . . . . . . . . . . . . . . 742 Tower Sequencing-2 Speed . . . . 905
Secondary Hot Water Options . . 770 Tower Sequencing-3 Speed . . . . 908
Secondary Hot Water Options Tower Sequencing-Vernier . . . . 911
Modules . . . . . . . . . . . . . . . . . 770 Central Plant Applications . . . . . . . . 699
Secondary Variable Speed Hot Water Change Modes . . . . . . . . . . . . . . . . . 108
Pumping . . . . . . . . . . . . . . . . . 759 Changing
Secondary Variable Speed Hot Water Column Label . . . . . . . . . . . . . . 207
Pumping Modules . . . . . . . . . 760 Connection . . . . . . . . . . . . . . . . . 171
Zone Loop Control . . . . . . . . . . . 764 Hidden Edge Label of a Connection
Zone Loop Control Modules . . . 764 . . . . . . . . . . . . . . . . . . . . . . . . . 181
Central Heating Applications . . . . . . 737 Input Signal . . . . . . . . . . . . . . . . 173
Output Signal . . . . . . . . . . . . . . . 173
Index 1555
Coils (Reheat) Configuration Mode . . . . . . . . . . . . . . 81
Mixed Air Single Duct . . . . . . . . 326 Configuration Options
Mixed Air Single Duct Modules 328 Multizone (Mixed Air Dual Duct)
Outdoor Air Single Duct . . . . . . 425 . . . . . . . . . . . . . . . . . . . . . . . . . 516
Outside Air Single Duct Modules Multizone (Mixed Air Dual Duct)
. . . . . . . . . . . . . . . . . . . . . . . . . 427 Modules . . . . . . . . . . . . . . . . . 516
Cold Deck Damper Actuator Configuration Tasks . . . . . . . . . . . . . 119
VAV Dual Duct . . . . . . . . . . . . . 658 Configure Display Screen . . . . . . . . 238
VAV Dual Duct Modules . . . . . 658 Configuring
VAV Slave Dual Duct . . . . . . . . 677 Command Hierarchy Block . . . . 185
VAV Slave Dual Duct Modules 677 Hybrid Activity . . . . . . . . . . . . . 182
Cold Deck Damper Trouble Detection Line Segment Block . . . . . . . . . 188
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 863 MUX Block . . . . . . . . . . . . . . . . 188
Cold Deck Discharge Air Setpoint Reset Translation Block . . . . . . . . . . . . 189
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 831 Configuring a System . . . . . . . . . . . 157
Cold Deck Flow Calculation . . . . . . 817 Applications . . . . . . . . . . . . . . . . . 75
Column Label Control View Configuration . . . 161
Changing . . . . . . . . . . . . . . . . . . 207 Controller Application File . . . . . 76
Combustion Damper Command . . 1328 Details Configuration . . . . . . . . . 161
Command Dialog Box . . . . . . . . . . . 245 Hardware Definition . . . . . . . . . 161
Command Hierarchy . . . . . . . 224, 1482 Logic Blocks . . . . . . . . . . . . . . . . 76
Command Hierarchy Block Logic View Configuration . . . . . 161
Configuring . . . . . . . . . . . . . . . . 185 Modules . . . . . . . . . . . . . . . . . . . . 76
Commanding Simulation . . . . . . . . . . . . . . . . . 161
Items . . . . . . . . . . . . . . . . . . . . . . 242 System . . . . . . . . . . . . . . . . . . . . . 75
Commissioning System Selection Tree . . . . . . . . 160
Device . . . . . . . . . . . . . . . . . . . . 267 System Selection Wizard . . . . . . 158
Inputs . . . . . . . . . . . . . . . . . . . . . 270 System Types and Configurations
Outputs . . . . . . . . . . . . . . . . . . . . 271 . . . . . . . . . . . . . . . . . . . . . . . . . 159
Commissioning a System . . . . . . . . . 265 Configuring the Local Controller Display
Bluetooth Wireless Connection . 265 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Ethernet NAE Passthru Connection Confirm (Delete) . . . . . . . . . . . . . . . 228
. . . . . . . . . . . . . . . . . . . . . . . . . 265 Confirm Dialog Box . . . . . . . . . . . . 245
System and Device Connections 265 Connecting
Commissioning and Servicing Tasks 120 Blocks . . . . . . . . . . . . . . . . . . . . 179
Commissioning Device Wizard . . . . 276 Connection
Commissioning Mode . . . . . . . . . . . . 82 Breaking a Connection . . . . . . . . 171
Commissioning Tasks . . . . . . . . . . . 120 Changing a Connection . . . . . . . 171
Compare . . . . . . . . . . . . . . . . . . . . . 1458 Changing the Hidden Edge Label
Compressor Max Cap Fract LV . . . 1374 . . . . . . . . . . . . . . . . . . . . . . . . . 181
Condenser Options Deleting . . . . . . . . . . . . . . . . . . . 181
Central Cooling . . . . . . . . . . . . . 731 Exposing Ports for Connection . 170
Central Cooling Modules . . . . . . 731 Making a Connection . . . . . . . . . 171
Condenser Water System Making Bluetooth Wireless
Central Cooling . . . . . . . . . . . . . 716 Connection . . . . . . . . . . . . . . . 267
Central Cooling Modules . . . . . . 718 Making Ethernet Passthru
Configuration and Simulation Tasks 119 Connection . . . . . . . . . . . . . . . 267
Index 1557
Fan Coil . . . . . . . . . . . . . . . . . . . 564 CWPs Available . . . . . . . . . . . . . . . . 884
Heat Pump . . . . . . . . . . . . . . . . . 604 CWPX Alarms . . . . . . . . . . . . . . . . . 866
Mixed Air Dual Duct . . . . . . . . . 348 CWPX Blocking Protection . . . . . . 1311
Mixed Air Single Duct . . . . . . . . 289 CWPX Status Alarm Determination 806
Multizone (Mixed Air Dual Duct)
. . . . . . . . . . . . . . . . . . . . . . . . . 515 D
Outdoor Air Dual Duct . . . . . . . 445 Damper Control . . . . . . . . . . . . . . . 1106
Outdoor Air Single Duct . . . . . . 399 Damper Control for UV Cycle 1, 2, or
Rooftop . . . . . . . . . . . . . . . . . . . 487 W . . . . . . . . . . . . . . . . . . . . . 1106
Unit Ventilator . . . . . . . . . . . . . . 582 Damper Control with Low Limit
VAV Dual Duct . . . . . . . . . . . . . 657 . . . . . . . . . . . . . . . . . . . . . . . . 1109
VAV Single Duct . . . . . . . . . . . . 626 Damper Control - AHU Econ . . . . 1112
VAV Slave Dual Duct . . . . . . . . 676 Damper Control for Economizer
VAV Slave Single Duct . . . . . . . 645 . . . . . . . . . . . . . . . . . . . . . . . . 1112
COS . . . . . . . . . . . . . . . . . . . . . . . . 1474 Damper Control for Relief Fan 1115
Count On Inputs . . . . . . . . . . . . . . . . 883 Damper Control for Volume
Counter Input Attributes . . . . . . . . 1427 Matching . . . . . . . . . . . . . . . 1119
Counter Input Commands . . . . . . . 1429 Damper Control - AHU Min OA . . 1122
Counter Input Object . . . . . . . . . . . 1427 Min OA Damper 2 Position . . . 1122
Counter Input Attributes . . . . . 1427 Min OA Damper Proportional Output
Counter Input Commands . . . . 1429 . . . . . . . . . . . . . . . . . . . . . . . . 1125
Create State Selection Column . . . . 223 Min OA Fan Constant Capacity 1128
Create State Selection Output . . . . . 697 Min OA Fan Variable Capacity Flow
Create State Selection Table . . . . . . 222 Control . . . . . . . . . . . . . . . . . 1131
Creating Damper Control - VAV . . . . . . . . . 1135
Custom Applications . . . . . . . . . 194 Damper Control (VAV Exhaust)
Custom Logic . . . . . . . . . . . . . . . 202 . . . . . . . . . . . . . . . . . . . . . . . . 1135
Monitoring/Supervisory Control Damper Control (VAV Supply) 1138
Only Applications . . . . . . . . . 210 Damper Control (VAV Exhaust) . . 1135
System . . . . . . . . . . . . . . . . . . . . 164 Damper Control (VAV Supply) . . . 1138
Custom Applications Damper Control for Economizer . . 1112
Creating . . . . . . . . . . . . . . . . . . . 194 Damper Control for Relief Fan . . . 1115
Custom Filters Damper Control for UV Cycle 1, 2, or W
Performing . . . . . . . . . . . . . . . . . 149 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106
Custom Logic Damper Control for Volume Matching
Creating . . . . . . . . . . . . . . . . . . . 202 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1119
Customizing Damper Control Status LV . . . . . . 1374
State Selection Tables . . . . . . . . 207 Damper Control with Low Limit . . 1109
CW Isolation Valve Status . . . . . . . . 883 Damper Minimum Position
CW Pump Rotation Small . . . . . . . 1092 Determination . . . . . . . . . . . . . . . . 825
CW Pump X Control . . . . . . . . . . . 1086 Damper Minimum Position Reset by
CW Pump X Control v2 . . . . . . . . . 1089 CO2 . . . . . . . . . . . . . . . . . . . . . . . 827
CW Pump X Enable LV . . . . . . . . 1374 Damper Output LV . . . . . . . . . . . . 1374
CW Pump X LV . . . . . . . . . . . . . . 1374 Damper Trouble Detection . . . . . . . 863
CW Pump X Totalization . . . . . . . 1380 DA-T sp Reset by OA . . . . . . . . . . . 835
CW Sequencing . . . . . . . . . . . . . . . . 886 Default Element of a Module
CW Sequencing LV . . . . . . . . . . . . 1374 Setting . . . . . . . . . . . . . . . . . . . . 190
Index 1559
Unit Ventilator . . . . . . . . . . . . . . 599 Existing System File
Unit Ventilator Modules . . . . . . 599 Open . . . . . . . . . . . . . . . . . . . . . . 165
Edit Exit CCT . . . . . . . . . . . . . . . . . . . . . 110
Balancing Parameters . . . . . . . . 274 Exp . . . . . . . . . . . . . . . . . . . . . . . . . 1474
Emergency Mode Pass Through . . . 997 Exporting
Emergency Mode Sequencing . . . . . 930 Module . . . . . . . . . . . . . . . . . . . . 191
Energy Hold Off Determination . . 1002 Object Naming Preferences . . . . 150
Energy Wheel Two Pos Byp . . . . . 1241 System Selection Preferences . . 152
Entering Exposing
Job Information . . . . . . . . . . . . . 165 Ports . . . . . . . . . . . . . . . . . . . . . . 178
Enthalpy . . . . . . . . . . . . . . . . . . . . . 1475 Exposing Ports for Connection . . . . 170
Enthalpy Wheel Control . . . . . . . . 1238
Enum Set Change Dialog . . . . . . . . . 225 F
Enum to Boolean Translation Block 189 Fan Alarm Status . . . . . . . . . . . . . . 1005
Equal . . . . . . . . . . . . . . . . . . . . . . . 1458 Fan Cmd LV . . . . . . . . . . . . . . . . . 1374
Ethernet NAE Passthru . . . . . . . . . . 259 Fan Coil . . . . . . . . . . . . . . . . . . . . . . 563
Ethernet NAE Passthru Connection . 265 Coils . . . . . . . . . . . . . . . . . . . . . . 567
EWMA . . . . . . . . . . . . . . . . . . . . . . 1444 Coils Modules . . . . . . . . . . . . . . 568
Execution Status . . . . . . . . . . . . . . 1484 Misc . . . . . . . . . . . . . . . . . . . . . . 574
Exhaust Air Flow Calculation . . . . . 817 Misc Modules . . . . . . . . . . . . . . 575
Exhaust Area LV . . . . . . . . . . . . . . . 860 Monitored Safeties . . . . . . . . . . . 574
Exhaust Damper Actuator Monitored Safeties Modules . . . 574
VAV Dual Duct . . . . . . . . . . . . . 662 Occupancy . . . . . . . . . . . . . . . . . 576
VAV Dual Duct Modules . . . . . 662 Occupancy Modules . . . . . . . . . 577
VAV Single Duct . . . . . . . . . . . . 629 Optional Equipment . . . . . . . . . . 571
VAV Single Duct Modules . . . . 629 Optional Equipment Modules . . 571
VAV Slave Dual Duct . . . . . . . . 681 Optional Features . . . . . . . . . . . . 578
VAV Slave Dual Duct Modules 681 Optional Features Modules . . . . 579
VAV Slave Single Duct . . . . . . . 648 Sensor Modules . . . . . . . . . . . . . 573
VAV Slave Single Duct Modules Sensors . . . . . . . . . . . . . . . . . . . . 572
. . . . . . . . . . . . . . . . . . . . . . . . . 648 Supply Fan . . . . . . . . . . . . . . . . . 565
Exhaust Damper Control . . . . . . . . 1135 Supply Fan Modules . . . . . . . . . 566
Exhaust Damper Trouble Detection . 863 Fan Coil Applications . . . . . . . . . . . 563
Exhaust Differential Setpoint Calculation Fan Coil Control Logic System Selection
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 833 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576
Exhaust Fan Alarms . . . . . . . . . . . . . 866 Fan Coil Core Logic . . . . . . . . . . . . 564
Exhaust Fan Blocking Protection . 1311 Fan Coil Mechanical System Selection
Exhaust Fan BSP Control for UL-864- . . . . . . . . . . . . . . . . . . . . . . . . . . . . 565
UUKL . . . . . . . . . . . . . . . . . . . . . 1164 Fan Control . . . . . . . . . . . . . . . . . . 1142
Exhaust Fan Command LV . . . . . . 1374 Fan Proportional . . . . . . . . . . . 1142
Exhaust Fan Status Alarm Determination Fan Three Speed . . . . . . . . . . . 1148
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 806 Fan VAV Series . . . . . . . . . . . . 1151
Exhaust Fan Volume Match Control for Parallel Fan Control . . . . . . . . . 1145
UL-864-UUKL . . . . . . . . . . . . . . 1174 Single Speed Fan Control . . . . 1146
Exhaust Flow Calculation . . . . . . . . 817 Fan Control - AHU . . . . . . . . . . . . 1153
Exhaust Pickup Gain LV . . . . . . . . . 860 Fan Relief BSP for UL-864-UUKL
. . . . . . . . . . . . . . . . . . . . . . . . 1158
Index 1561
Flow Setpoint (VAV Dual Duct) . . 1068 HD Constant Damper Control . . . . 1138
Flow Setpoint (VAV Single Duct) . 1071 HD Constant Flow Setpoint . . . . . . 1074
Flow Status Determination . . . . . . . 800 HD Constant Flow Setpoint Control
Flow Sum Calculation . . . . . . . . . . . 823 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1074
Free Cooling is Available . . . . . . . 1475 HD CS LV . . . . . . . . . . . . . . . . . . . 1374
Frost Protection Determination . . . . 880 HD Damper Control . . . . . . . . . . . . 1138
HD Flow Calculation . . . . . . . . . . . . 817
G HD Flow Setpoint Control . . . . . . . 1068
HD Pickup Gain LV . . . . . . . . . . . . 860
G
HD-T sp Reset by OA . . . . . . . . . . . 835
Attribute Type . . . . . . . . . . . . . . 775
Heat Exchanger Options
General Options
Central Heating . . . . . . . . . . . . . 769
Central Cooling . . . . . . . . . . . . . 736
Central Heating Modules . . . . . . 769
Central Cooling Modules . . . . . . 736
Heat Exchanger with Low Limit Output
Central Heating . . . . . . . . . . . . . 771
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1080
Central Heating Modules . . . . . . 772
Heat Exchanger with Return Water
General Sequencing . . . . . . . . . . . . . 926
Control . . . . . . . . . . . . . . . . . . . . 1080
Coil Circulation Pump Sequencing
Heat Exchangers
. . . . . . . . . . . . . . . . . . . . . . . . . 926
Central Heating . . . . . . . . . . . . . 751
Dehumidification Sequencing . . 927
Central Heating Modules . . . . . . 753
Emergency Mode Sequencing . . 930
Heat Pump . . . . . . . . . . . . . . . . . . . . 603
Heat Recovery Low Limit
Coils . . . . . . . . . . . . . . . . . . . . . . 607
Sequencing . . . . . . . . . . . . . . . 935
Coils Modules . . . . . . . . . . . . . . 607
Humidification Sequencing . . . . 937
Economizer Suitability . . . . . . . 616
Loss of Airflow Sequencing . . . 939
Economizer Suitability Modules 616
Smoke Control Sequencing for UL-
Misc . . . . . . . . . . . . . . . . . . . . . . 613
864-UUKL . . . . . . . . . . . . . . . 932
Misc Modules . . . . . . . . . . . . . . 613
Start Stop Sequencing (AHU 100%
Monitored Safeties . . . . . . . . . . . 612
OA) . . . . . . . . . . . . . . . . . . . . . 942
Monitored Safeties Modules . . . 612
Start Stop Sequencing (AHU Mixed
Occupancy . . . . . . . . . . . . . . . . . 614
Air) . . . . . . . . . . . . . . . . . . . . . 947
Occupancy Modules . . . . . . . . . 615
Generated State . . . . . . . . . . . . . . . . 775
Optional Equipment . . . . . . . . . . 609
Getting Started . . . . . . . . . . . . . . . . . 119
Optional Equipment Modules . . 609
Glossary . . . . . . . . . . . . . . . . . . . . . 1537
Optional Features . . . . . . . . . . . . 619
Glycol Loop Control . . . . . . . . . . . 1235
Optional Features Modules . . . . 620
Greater Than . . . . . . . . . . . . . . . . . 1458
Reversing Valve Outputs . . . . . . 618
Greater Than or Equal . . . . . . . . . . 1458
Sensor Modules . . . . . . . . . . . . . 611
H Sensors . . . . . . . . . . . . . . . . . . . . 610
Supply Fan . . . . . . . . . . . . . . . . . 605
Hardware Supply Fan Modules . . . . . . . . . 606
Defining . . . . . . . . . . . . . . . . . . . 248 Heat Pump Application . . . . . . . . . . 603
Hardware Considerations . . . . . . . . . 247 Heat Pump Control Logic System
Hardware Definition . . . . . . . . . . . . 161 Selection . . . . . . . . . . . . . . . . . . . . 614
Hardware Definition Wizard . . . . . . 247 Heat Pump Core Logic . . . . . . . . . . 604
Hardware Definitions . . . . . . . . . . . . 247 Heat Pump Mechanical System Selection
Hardware View Tab . . . . . . . . . 107, 169 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605
HD Area LV . . . . . . . . . . . . . . . . . . . 860 Heat Pump Staged Compressors . . 1231
Index 1563
Preheat Proportional Valve with Hiding
Return Water Control . . . . . . 1292 Connection Lines . . . . . . . . 181, 272
Heating 2 Position Valve . . . . . . . . 1250 Involvement . . . . . . . . . . . . 243, 269
Heating 2 Position Valve with DA-T Low High Temp Alarm Pass Through . . 1328
Limit . . . . . . . . . . . . . . . . . . . . . . 1253 Hot Deck Damper Actuator
Heating Availability Determination . 917 VAV Dual Duct . . . . . . . . . . . . . 659
Heating Control Status LV . . . . . . 1374 VAV Dual Duct Modules . . . . . 659
Heating Cooling Required LV . . . . 1374 VAV Slave Dual Duct . . . . . . . . 678
Heating FBPD 2 Position Valve with VAV Slave Dual Duct Modules 678
DA-T Low Limit . . . . . . . . . . . . 1256 Hot Deck Damper Trouble Detection
Heating FBPD 2 Position Valve with . . . . . . . . . . . . . . . . . . . . . . . . . . . . 863
Low Limit . . . . . . . . . . . . . . . . . . 1259 Hot Deck Discharge Air Setpoint Reset
Heating FBPD Proportional Valve with . . . . . . . . . . . . . . . . . . . . . . . . . . . . 831
Low Limit . . . . . . . . . . . . . . . . . . 1263 Hot Deck Discharge Air Setpoint Reset
Heating for Zones by EA-T . . . . . . . . . . . . . . . . . . . . 831
Multizone (Mixed Air Dual Duct) Hot Deck Discharge Air Setpoint Reset
. . . . . . . . . . . . . . . . . . . . . . . . . 557 by RA-T . . . . . . . . . . . . . . . . . . . . 831
Multizone (Mixed Air Dual Duct) Hot Deck Flow Calculation . . . . . . . 817
Modules . . . . . . . . . . . . . . . . . 557 Hot Gas Bypass Valve Control . . . 1328
Heating isAvailable Pass Through . . 915 Hot Water System Enable . . . . . . . . 900
Heating Max Cap Fract LV . . . . . . 1374 Hot Water/Steam Boilers
Heating Percent Cmd LV . . . . . . . . 1374 Central Heating . . . . . . . . . . . . . 739
Heating Priority Central Heating Modules . . . . . . 742
VAV Single Duct . . . . . . . . . . . . 640 HP . . . . . . . . . . . . . . . . . . . . . . . . . . 603
Heating Proportional Valve . . . . . . 1268 HP-ZN-T Sequencing . . . . . . . . . . . 980
Heating Proportional Valve with DA-T HR Energy Wheel Alarms . . . . . . . . 866
Low Limit . . . . . . . . . . . . . . . . . . 1271 HR Energy Wheel Blocking Protection
Heating Proportional Valve with Low . . . . . . . . . . . . . . . . . . . . . . . . . . . 1311
Limit . . . . . . . . . . . . . . . . . . . . . . 1274 HR Energy Wheel Status Alarm
Heating Required LV . . . . . . . . . . . 1374 Determination . . . . . . . . . . . . . . . . 806
Heating Sequenced Valves with Low Humidification
Limit . . . . . . . . . . . . . . . . . . . . . . 1278 Mixed Air Dual Duct . . . . . . . . . 387
Heating Staged Outputs . . . . . . . . . 1282 Mixed Air Dual Duct Modules . 388
Heating Staged Outputs with DA-T Low Mixed Air Single Duct . . . . . . . . 335
Limit . . . . . . . . . . . . . . . . . . . . . . 1285 Mixed Air Single Duct Modules 336
Heating Staged Outputs with Low Limit Multizone (Mixed Air Dual Duct)
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1288 . . . . . . . . . . . . . . . . . . . . . 549, 554
Heating System Enable Multizone (Mixed Air Dual Duct)
Central Heating . . . . . . . . . . . . . 738 Modules . . . . . . . . . . . . . . . . . 550
Central Heating Modules . . . . . . 738 Outdoor Air Dual Duct . . . . . . . 475
Heating Zone X Output . . . . . . . . . 1274 Outdoor Air Single Duct . . . . . . 433
Heating Zone X SP Reset . . . . . . . . 835 Outside Air Dual Duct Modules 476
Help Appearance . . . . . . . . . . . . . . . . 66 Outside Air Single Duct Modules
Help Content Pane . . . . . . . . . . . . . . . 71 . . . . . . . . . . . . . . . . . . . . . . . . . 434
Help Window Layout . . . . . . . . . . . . . 66 Rooftop . . . . . . . . . . . . . . . . . . . 505
Hidden Edge Label . . . . . . . . . . . . . 227 Rooftop Modules . . . . . . . . . . . . 505
Index 1565
Constant . . . . . . . . . . . . . . . . . . 1460 MAX . . . . . . . . . . . . . . . . . . . . . . . 1483
Container . . . . . . . . . . . . . . . . . 1460 Mechanical System Selection . . . . . 286
Control . . . . . . . . . . . . . . . . . . . 1461 Central Cooling . . . . . . . . . . . . . 700
Custom . . . . . . . . . . . . . . . . . . . 1494 Central Heating . . . . . . . . . . . . . 738
Math . . . . . . . . . . . . . . . . . . . . . 1474 Fan Coil . . . . . . . . . . . . . . . . . . . 565
Psychrometric . . . . . . . . . . . . . 1475 Heat Pump . . . . . . . . . . . . . . . . . 605
Selection . . . . . . . . . . . . . . . . . . 1482 Mixed Air Dual Duct . . . . . . . . . 349
Statistical . . . . . . . . . . . . . . . . . 1483 Mixed Air Single Duct . . . . . . . . 290
Timing . . . . . . . . . . . . . . . . . . . 1484 Multizone (Mixed Air Dual Duct)
Viewing . . . . . . . . . . . . . . . . . . . 244 . . . . . . . . . . . . . . . . . . . . . . . . . 516
Logic Blocks . . . . . . . . . . . . . . . . . . . 76 Outdoor Air Dual Duct . . . . . . . 446
Logic Diagram . . . . . . . . . . . . . . . . . 103 Outdoor Air Single Duct . . . . . . 400
Logic View . . . . . . . . . . . . . . . 114, 224 Rooftop . . . . . . . . . . . . . . . . . . . 488
Block Finder . . . . . . . . . . . . . . . 102 Unit Ventilator . . . . . . . . . . . . . . 583
Control Block Palette . . . . . . . . . 102 VAV Dual Duct . . . . . . . . . . . . . 658
Logic Diagram . . . . . . . . . . . . . . 103 VAV Single Duct . . . . . . . . . . . . 628
Right-Click Menus . . . . . . . . . . . 101 VAV Slave Dual Duct . . . . . . . . 677
Status Colors . . . . . . . . . . . . . . . 105 VAV Slave Single Duct . . . . . . . 647
Toolbar . . . . . . . . . . . . . . . . . . . . 100 Menu Bar . . . . . . . . . . . . . . . . . . . . . . 78
Logic View Configuration . . . . . . . . 161 Menus . . . . . . . . . . . . . . . . . . . . . . . . . 78
Logic View Details Right-Click (Control View) . . . . . 95
Viewing . . . . . . . . . . . . . . . . . . . 244 Right-Click (Logic View) . . . . . 101
Logic View Workspace . . . . . . . . 84, 98 Metasys System . . . . . . . . . . . . . . . 1549
Loss of Airflow Sequencing . . . . . . 939 MIN . . . . . . . . . . . . . . . . . . . . . . . . 1483
LV . . . . . . . . . . . . . . . . . . . . . . . . . 1484 Min OA Damper 2 Position . . . . . . 1122
Min OA Damper Proportional Output
M . . . . . . . . . . . . . . . . . . . . . . . . . . . 1125
Min OA Fan Constant Capacity . . . 1128
MADD . . . . . . . . . . . . . . . . . . . . . . . 347
Min OA Fan Variable Capacity Flow
MADD-MZ . . . . . . . . . . . . . . . . . . . 514
Main Code . . . . . . . . . . . . . . . . . . . . 260 Control . . . . . . . . . . . . . . . . . . . . 1131
Min Outdoor Air Fan Command LV
Making
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1374
Bluetooth Wireless Connection . 267
Min Outdoor Air Fan Status Alarm
Connections . . . . . . . . . . . . . . . . 267
Determination . . . . . . . . . . . . . . . . 806
Ethernet Passthru Connection . . 267
Min Position Determination . . . . . . 825
Making a Connection . . . . . . . . . . . . 171
Minimum Flow Determination . . . . 846
MASD . . . . . . . . . . . . . . . . . . . . . . . 288
Minimum Flow Determination - Dual
Master CD Constant Flow Setpoint Pass
Duct . . . . . . . . . . . . . . . . . . . . . . . 841
Through . . . . . . . . . . . . . . . . . . . . 997
Minimum OA Fan Alarms . . . . . . . . 866
Master CD Flow Setpoint Pass Through
Minimum OA Flow Calculation . . . 817
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 997
Minimum Outdoor Air Fan/ Damper
Master Flow Setpoint Pass Through 997
Mixed Air Single Duct . . . . . . . . 301
Master HD Flow Setpoint Pass Through
Minimum Outdoor Air Fan/Damper
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 997
Mixed Air Dual Duct . . . . . . . . . 360
Math . . . . . . . . . . . . . . . . . . . . . . . . 1474
Mixed Air Dual Duct Modules . 361
Index 1567
Reduce Outdoor Air on Low Modules . . . . . . . . . . . . . . . . . . . . . . 773
Temperature Modules . . . . . . 304 Enable Network Inputs . . . . . . . 780
Temperature Control Strategy . . 305 Generator Interface Network Inputs
Temperature Control Strategy . . . . . . . . . . . . . . . . . . . . . . . . . 778
Modules . . . . . . . . . . . . . . . . . 306 Generic Network Inputs . . . . . . . 788
Mixed Air Single Duct Application . 288 Generic Network Outputs . . . . 1386
Mixed Air Single Duct Control Logic Inputs . . . . . . . . . . . . . . . . . . . . . 789
System Selection . . . . . . . . . . . . . 341 Network Inputs . . . . . . . . . . . . . 777
Mixed Air Single Duct Core Logic . 289 Network Outputs . . . . . . . . . . . 1385
Mixed Air Single Duct HR Sequencing Output Control Interface Network
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 971 Outputs . . . . . . . . . . . . . . . . . 1385
Mixed Air Single Duct Mechanical Output Controller . . . . . . . . . . . 1063
System Selection . . . . . . . . . . . . . 290 Outputs . . . . . . . . . . . . . . . . . . . 1387
Mixed Air Single Duct Sequencing . 967 Rotation and Switch Network Inputs
Mixing Dampers for Zones . . . . . . . . . . . . . . . . . . . . . . . . . 786
Multizone (Mixed Air Dual Duct) Sensor and Setpoint Network Inputs
. . . . . . . . . . . . . . . . . . . . . . . . . 556 . . . . . . . . . . . . . . . . . . . . . . . . . 782
Multizone (Mixed Air Dual Duct) Setpoint Determination/Misc . . . 791
Modules . . . . . . . . . . . . . . . . . 556 State Generators . . . . . . . . . . . . . 865
Mode Selection (MUX) . . . . . . . . . . 226 Monitored Safeties
Modes . . . . . . . . . . . . . . . . . . . . . . . . . 81 Fan Coil . . . . . . . . . . . . . . . . . . . 574
Modifying Fan Coil Modules . . . . . . . . . . . 574
Connections . . . . . . . . . . . . . . . . 170 Heat Pump . . . . . . . . . . . . . . . . . 612
Control View Details . . . . . . . . . 243 Heat Pump Modules . . . . . . . . . 612
Details . . . . . . . . . . . . . . . . . . . . 168 Mixed Air Dual Duct . . . . . . . . . 397
Existing .caf File or Selected System Mixed Air Dual Duct Modules . 397
. . . . . . . . . . . . . . . . . . . . . . . . . 201 Mixed Air Single Duct . . . . . . . . 346
Module’s Logic . . . . . . . . . . . . . 173 Mixed Air Single Duct Modules 346
Output Parameter . . . . . . . . . . . . 273 Multizone (Mixed Air Dual Duct)
Parameters . . . . . . . . . . . . . 171, 243 . . . . . . . . . . . . . . . . . . . . . . . . . 562
State Selection Tables . . . . . . . . 172 Multizone (Mixed Air Dual Duct)
System Selections . . . . . . . . . . . 166 Modules . . . . . . . . . . . . . . . . . 562
Modulating HX or Boiler Sequencing Outdoor Air Dual Duct . . . . . . . 485
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 895 Outdoor Air Single Duct . . . . . . 443
Module Outside Air Dual Duct Modules 485
Adding . . . . . . . . . . . . . . . . . . . . 173 Outside Air Single Duct Modules
Deleting . . . . . . . . . . . . . . . . . . . 174 . . . . . . . . . . . . . . . . . . . . . . . . . 443
Exporting . . . . . . . . . . . . . . . . . . 191 Rooftop . . . . . . . . . . . . . . . . . . . 513
Renaming . . . . . . . . . . . . . . . . . . 174 Rooftop Modules . . . . . . . . . . . . 513
Module Selection (New) . . . . . . . . . 219 Unit Ventilator . . . . . . . . . . . . . . 593
Module Use in Applications . . . . . . 774 Unit Ventilator Modules . . . . . . 593
Module’s Logic Monitoring/Supervisory Control Only
Modifying . . . . . . . . . . . . . . . . . 173 Applications
Viewing . . . . . . . . . . . . . . . . . . . 173 Creating . . . . . . . . . . . . . . . . . . . 210
Motor Protection . . . . . . . . . . . . . . 1311
Blocking Protection . . . . . . . . . 1311
MS/TP . . . . . . . . . . . . . . . . . . . . . . 1549
Index 1569
Network Outputs . . . . . . . . . . . 89, 1385 Heat Pump Modules . . . . . . . . . 615
Generic (Add New) Modules . . 1386 Unit Ventilator . . . . . . . . . . . . . . 597
Output Control Interface Modules Unit Ventilator Modules . . . . . . 598
. . . . . . . . . . . . . . . . . . . . . . . . 1385 VAV Dual Duct . . . . . . . . . . . . . 671
Network Sensors . . . . . . . . . . . . . . 1549 VAV Single Duct . . . . . . . . . . . . 639
Network Settings Screen . . . . . . . . . 254 VAV Single Duct Modules . . . . 639
Networked Thermostats . . . . . . . . . 1549 Occupancy Control
New Modules . . . . . . . . . . . . . . . . . . 125 Mixed Air Dual Duct . . . . . . . . . 365
New Port . . . . . . . . . . . . . . . . . . . . . 180 Mixed Air Dual Duct Modules . 365
New System . . . . . . . . . . . . . . . . . . . 215 Mixed Air Single Duct . . . . . . . . 308
Normal Transitions . . . . . . . . . . . . . 776 Mixed Air Single Duct Modules 308
NOT . . . . . . . . . . . . . . . . . . . . . . . . 1443 Multizone (Mixed Air Dual Duct)
Not Equal . . . . . . . . . . . . . . . . . . . . 1458 . . . . . . . . . . . . . . . . . . . . . . . . . 526
Number of Devices Running LV . . 1374 Multizone (Mixed Air Dual Duct)
Number of SCHWP Running LV . 1374 Modules . . . . . . . . . . . . . . . . . 526
Number of SHWP Running LV . . . 1374 Outdoor Air Dual Duct . . . . . . . 453
Number of Towers Running LV . . 1374 Outdoor Air Single Duct . . . . . . 408
Number of Zones Outside Air Dual Duct Modules 453
Multizone (Mixed Air Dual Duct) Outside Air Single Duct Modules
. . . . . . . . . . . . . . . . . . . . . . . . . 554 . . . . . . . . . . . . . . . . . . . . . . . . . 408
Rooftop . . . . . . . . . . . . . . . . . . . 495
O Rooftop Modules . . . . . . . . . . . . 495
Occupancy Mode Determination . . 1010
OADD . . . . . . . . . . . . . . . . . . . . . . . 444
Occupancy Mode Determination (MZ)
OASD . . . . . . . . . . . . . . . . . . . . . . . . 399
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1014
Object Naming Preferences . . . . . . . 143
Occupied Sequencing . . . . . . . . . . . 952
Exporting . . . . . . . . . . . . . . . . . . 150
Occupied Sequencing (AHU
Filtering . . . . . . . . . . . . . . . . . . . 148
100% OADD) . . . . . . . . . . . . . 954
Importing . . . . . . . . . . . . . . . . . . 151
Occupied Sequencing (AHU
Performing Custom Filters . . . . . 149
100% OASD) . . . . . . . . . . . . . 957
Resetting . . . . . . . . . . . . . . . . . . 150
Occupied Sequencing (AHU
Sorting . . . . . . . . . . . . . . . . . . . . 149
MADD w HR) . . . . . . . . . . . . 964
Object Overview . . . . . . . . . . . . . . 1389
Occupied Sequencing (AHU
Objects
MADD) . . . . . . . . . . . . . . . . . 961
Analog Input Object . . . . . . . . . 1393
Occupied Sequencing (AHU
Analog Output Object . . . . . . . 1399
MASD w HR) . . . . . . . . . . . . 971
Analog Value Object . . . . . . . . 1405
Occupied Sequencing (AHU
Binary Input Object . . . . . . . . . 1411
MASD) . . . . . . . . . . . . . . . . . . 967
Binary Output Object . . . . . . . . 1415
Occupied Sequencing (Single
Binary Value Object . . . . . . . . 1421
Device) . . . . . . . . . . . . . . . . . . 975
Counter Input Object . . . . . . . . 1427
Occupied Zone Sequencing (FC) 978
Multistate Value Object . . . . . . 1431
Occupied Zone Sequencing (HP) 980
Object Overview . . . . . . . . . . . 1389
Occupied Zone Sequencing
Position Adjust Output Object . 1435
(UV Cycle 1) . . . . . . . . . . . . . 983
Occupancy
Occupied Zone Sequencing
Fan Coil . . . . . . . . . . . . . . . . . . . 576
UV Cycle 2) . . . . . . . . . . . . . . 986
Fan Coil Modules . . . . . . . . . . . . 577
Heat Pump . . . . . . . . . . . . . . . . . 614
Index 1571
Outside Air Single Duct Modules Humidification . . . . . . . . . . . . . . 433
. . . . . . . . . . . . . . . . . . . . . . . . . 438 Monitored Safeties . . . . . . . . . . . 443
Rooftop . . . . . . . . . . . . . . . . . . . 508 Occupancy Control . . . . . . . . . . 408
Rooftop Modules . . . . . . . . . . . . 509 Optional Equipment . . . . . . . . . . 442
Unit Ventilator . . . . . . . . . . . . . . 600 Optional Features . . . . . . . . . . . . 437
Unit Ventilator Modules . . . . . . 601 Optional Sensors . . . . . . . . . . . . 439
VAV Dual Duct . . . . . . . . . . . . . 672 Temperature Control Strategy . . 405
VAV Single Duct . . . . . . . . . . . . 640 Outdoor Air Single Duct Applications
VAV Single Duct Modules . . . . 642 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 398
Optional Sensors Outdoor Air Single Duct Core Logic 399
Mixed Air Dual Duct . . . . . . . . . 392 Output
Mixed Air Dual Duct Modules . 394 Adding . . . . . . . . . . . . . . . . . . . . 206
Mixed Air Single Duct . . . . . . . . 341 Output (Boolean) . . . . . . . . . . . . . . 1442
Mixed Air Single Duct Modules 343 Output (Enum) . . . . . . . . . . . . . . . . 1442
Outdoor Air Dual Duct . . . . . . . 480 Output Control . . . . . . . . . . . . . . . . . . 89
Outdoor Air Single Duct . . . . . . 439 Output Control Module
Outside Air Dual Duct Modules 482 Adding . . . . . . . . . . . . . . . . . . . . 205
Outside Air Single Duct Modules Output Control Module Selection . . 219
. . . . . . . . . . . . . . . . . . . . . . . . . 440 Output Controller Modules . . . . . . 1063
Rooftop . . . . . . . . . . . . . . . . . . . 510 Cascaded Zone Control . . . . . . 1064
Rooftop Modules . . . . . . . . . . . . 511 Central Plant . . . . . . . . . . . . . . 1080
OR . . . . . . . . . . . . . . . . . . . . . . . . . 1443 Damper Control . . . . . . . . . . . . 1106
Outdoor Air Dual Duct . . . . . . . . . . 446 Damper Control - AHU Econ . 1112
Coils (Cooling - Cold Deck) . . . 466 Damper Control - AHU Min OA
Coils (Heating - Hot Deck) . . . . 470 . . . . . . . . . . . . . . . . . . . . . . . . 1122
Coils (Preheat) . . . . . . . . . . . . . . 460 Damper Control - VAV . . . . . . 1135
Fans . . . . . . . . . . . . . . . . . . . . . . 446 Fan Control . . . . . . . . . . . . . . . 1142
Heat Recovery . . . . . . . . . . . . . . 455 Fan Control - AHU . . . . . . . . . 1153
Humidification . . . . . . . . . . . . . . 475 Heating & Cooling Control -
Monitored Safeties . . . . . . . . . . . 485 2 Pipe . . . . . . . . . . . . . . . . . . 1184
Occupancy Control . . . . . . . . . . 453 Heating & Cooling Control -
Optional Equipment . . . . . . . . . . 484 Cooling . . . . . . . . . . . . . . . . . 1212
Optional Features . . . . . . . . . . . . 478 Heating & Cooling Control -
Optional Sensors . . . . . . . . . . . . 480 Heat Pump . . . . . . . . . . . . . . 1231
Temperature Control Strategy . . 452 Heating & Cooling Control -
Outdoor Air Dual Duct Applications 444 Heat Recovery . . . . . . . . . . . 1235
Outdoor Air Dual Duct Core Logic . 445 Heating & Cooling Control -
Outdoor Air Flow Calculation . . . . . 817 Heating . . . . . . . . . . . . . . . . . 1249
Outdoor Air Single Duct . . . . . . . . . 400 Humidity Control . . . . . . . . . . . 1296
Coils (Common Heating-Cooling) Lighting Control . . . . . . . . . . . 1308
. . . . . . . . . . . . . . . . . . . . . . . . . 429 Motor Protection . . . . . . . . . . . 1311
Coils (Cooling) . . . . . . . . . . . . . 421 Multizone Zone Control . . . . . 1313
Coils (Preheat) . . . . . . . . . . . . . . 415 Pass Through . . . . . . . . . . . . . . 1328
Coils (Reheat) . . . . . . . . . . . . . . 425 Sideloop . . . . . . . . . . . . . . . . . . 1330
Dehumidification Control . . . . . 436 Staged Output Control . . . . . . . 1348
Fans . . . . . . . . . . . . . . . . . . . . . . 400 Staged Output Sequencing . . . . 1365
Heat Recovery . . . . . . . . . . . . . . 410 Timing . . . . . . . . . . . . . . . . . . . 1374
Index 1573
Port Exposure (Connections) . . . . . . 228 Primary CHW Pump X Totalization
Port Name Dialog . . . . . . . . . . . . . . 225 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1380
Port Selection . . . . . . . . . . . . . . . . . . 228 Primary HW Pump X LV . . . . . . . 1374
Ports Primary HW Pump X Totalization 1380
Exposing . . . . . . . . . . . . . . . . . . 178 Primary Pump Rotation Small . . . . 1092
Exposing for Connection . . . . . . 170 Primary Pump X Control . . . . . . . . 1086
Position Adjust Output Attributes . 1435 Primary Pump X Control v2 . . . . . 1089
Position Adjust Output Commands 1439 Primary Pump X Enable LV . . . . . 1374
Position Adjust Output Object . . . . 1435 Primary States . . . . . . . . . . . . . . . . . 776
Position Adjust Output Attributes Printing . . . . . . . . . . . . . . . . . . 244, 272
. . . . . . . . . . . . . . . . . . . . . . . . 1435 Help . . . . . . . . . . . . . . . . . . . . . . . 74
Position Adjust Output Commands Logic . . . . . . . . . . . . . . . . . . . . . 193
. . . . . . . . . . . . . . . . . . . . . . . . 1439 Summary Reports . . . . . . . . . . . 116
Power . . . . . . . . . . . . . . . . . . . . . . . 1474 Printing Summary Reports . . . . . . . 109
Preferences . . . . . . . . . . . . . . . . . . . . 143 Printing the Logic Diagram . . . . . . . 193
Import and Exports . . . . . . . . . . 146 Proportional 2 Pipe Control . . . . . . 1199
Localization . . . . . . . . . . . . . . . . 147 Proportional Box Heating Control . 1268
Object Naming . . . . . . . . . . . . . . 143 Proportional Cooling Control . . . . 1219
System Selection . . . . . . . . . . . . 145 Proportional Damper Minimum OA Flow
Unit . . . . . . . . . . . . . . . . . . . . . . 145 Control . . . . . . . . . . . . . . . . . . . . 1125
Preferences-Localization Screen . . . 156 Proportional Damper Output . . . . . 1109
Preferences-Object Naming Screen . 154 Proportional EA Damper Control for
Preferences-System Selection Screen Volume Matching . . . . . . . . . . . . 1119
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 155 Proportional Fan Control . . . . . . . . 1142
Preheat Availability Determination . 917 Proportional Heating Control . . . . . 1268
Preheat Coil Pump Pass Through . 1328 Proportional OA Damper Control . 1112
Preheat Control Status LV . . . . . . . 1374 Proportional OA Damper Control for
Preheat Max Cap Fract LV . . . . . . 1374 Relief Fan . . . . . . . . . . . . . . . . . . 1115
Preheat Percent Cmd LV . . . . . . . . 1374 Proportional Steam Humidification
Preheat Proportional Valve Output 1292 Control . . . . . . . . . . . . . . . . . . . . 1299
Preheat Proportional Valve with Return Proportional Supplemental Heating
Water Control . . . . . . . . . . . . . . . 1292 Control . . . . . . . . . . . . . . . . . . . . 1268
Preheat Pump Alarms . . . . . . . . . . . 866 Proportional Unit Vent 1 Damper Control
Preheat Pump Blocking Protection 1311 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106
Preheat Pump Command LV . . . . . 1374 Proportional Unit Vent 2-W Damper
Preheat Pump Status Alarm Control . . . . . . . . . . . . . . . . . . . . 1106
Determination . . . . . . . . . . . . . . . . 806 Proportional Unit Vent 3 Damper Control
Preheat Sequencing . . . . . . . . . . . . . 975 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1109
Preheat X LV . . . . . . . . . . . . . . . . . 1374 Proportional Valve 2 Pipe Control . 1207
Preheat X Totalization . . . . . . . . . . 1380 Proportional Valve Cooling Control
Primary CHW Pump Rotation Small . . . . . . . . . . . . . . . . . . . . . . . . . . . 1221
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1092 Proportional Valve Preheat Control 1274
Primary CHW Pump X Control . . . 1086 Proportional Valve Reheat Control 1274
Primary CHW Pump X Control v2 1089 Psychrometric . . . . . . . . . . . . . . . . 1475
Primary CHW Pump X LV . . . . . . 1374 Pump Control . . . . . . . . . . . . . . . . . 1086
Pump Control v2 . . . . . . . . . . . . . . 1089
PVDC . . . . . . . . . . . . . . . . . . . . . . . 1461
Index 1575
Rooftop Control Logic System Secondary HW Pump X Control v2 1089
Selection . . . . . . . . . . . . . . . . . . . . 510 Secondary HW Pump X LV . . . . . 1374
Rooftop Core Logic . . . . . . . . . . . . . 487 Secondary HW Pump X Totalization
Rooftop Mechanical System Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 1380
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 488 Secondary Pump PID . . . . . . . . . . . 1097
Rotation Small . . . . . . . . . . . . . . . . 1092 Secondary Pump X Enable LV . . . 1374
RTU . . . . . . . . . . . . . . . . . . . . . . . . . 486 Secondary Variable Speed Chill Water
Pumping
S Central Cooling . . . . . . . . . . . . . 723
Central Cooling Modules . . . . . . 724
Save .caf . . . . . . . . . . . . . . . . . . . . . . 109
Secondary Variable Speed Hot Water
Saving Results for Box Flow Test . . 282
Pumping
SC
Central Heating . . . . . . . . . . . . . 759
Attribute Type . . . . . . . . . . . . . . 775
Central Heating Modules . . . . . . 760
SCHWP PID LV . . . . . . . . . . . . . . 1374
Select System . . . . . . . . . . . . . . . . . . . 83
SCHWPX Alarms . . . . . . . . . . . . . . 866
Selecting
SCHWPX Blocking Protection . . . 1311
Block from the Control Block Palette
SCHWPX Status Alarm Determination
. . . . . . . . . . . . . . . . . . . . . . . . . 176
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 806
System . . . . . . . . . . . . . . . . . . . . 164
Search Pane . . . . . . . . . . . . . . . . . . . . 67
Selection . . . . . . . . . . . . . . . . . . . . . 1482
Search Tab . . . . . . . . . . . . . . . . . . . . . 67
Sideloop . . . . . . . . . . . . . . . . . . . 692
Searching
Sensor(s) for Zones
for a Block Using the Block Finder
Multizone (Mixed Air Dual Duct)
. . . . . . . . . . . . . . . . . . . . . . . . . 176
Modules . . . . . . . . . . . . . . . . . 555
Secondary Chill Water Options
Sensors
Central Cooling . . . . . . . . . . . . . 734
Fan Coil . . . . . . . . . . . . . . . . . . . 572
Central Cooling Modules . . . . . . 735
Fan Coil Modules . . . . . . . . . . . 573
Secondary Chill Water Pump PID v2
Heat Pump . . . . . . . . . . . . . . . . . 610
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1097
Heat Pump Modules . . . . . . . . . 611
Secondary CHW Pump Rotation Small
Unit Ventilator . . . . . . . . . . . . . . 591
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1092
Unit Ventilator Modules . . . . . . 592
Secondary CHW Pump Sequencing 895
VAV Dual Duct . . . . . . . . . . . . . 666
Secondary CHW Pump X LV . . . . 1374
VAV Dual Duct Modules . . . . . 667
Secondary CHW Pump X Modulating
VAV Single Duct . . . . . . . . . . . . 635
Control . . . . . . . . . . . . . . . . . . . . 1086
VAV Single Duct Modules . . . . 636
Secondary CHW Pump X Modulating
VAV Slave Dual Duct . . . . . . . . 684
Control v2 . . . . . . . . . . . . . . . . . . 1089
VAV Slave Dual Duct Modules 684
Secondary CHW Pump X Totalization
VAV Slave Single Duct . . . . . . . 653
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1380
VAV Slave Single Duct Modules
Secondary Hot Water Options
. . . . . . . . . . . . . . . . . . . . . . . . . 653
Central Heating . . . . . . . . . . . . . 770
Sequenced Output . . . . . . . . . . . . . 1099
Central Heating Modules . . . . . . 770
Sequenced Valves Preheat Control 1278
Secondary Hot Water Pump PID v2
Sequenced Valves Reheat Control . 1278
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1097
Sequencer 01 through Sequencer 16
Secondary Hot Water Pump Rotation
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1365
Small . . . . . . . . . . . . . . . . . . . . . . 1092
Series Fan Control . . . . . . . . . . . . . 1151
Secondary HW Pump Sequencing . . 895
Series Fan Determination . . . . . . . . 1060
Secondary HW Pump X Control . . 1086
Index 1577
Sideloop Maximum Selector . . . 857 MSC 01 through MSC 12 . . . . 1348
Sideloop Minimum Selector . . . 858 Staged Output Sequencing . . . . . . . 1365
Sideloop Sum Inputs . . . . . . . . . 859 Sequencer 01 through Sequencer 16
Sideloop Sum Inputs . . . . . . . . . . . . 859 . . . . . . . . . . . . . . . . . . . . . . . . 1365
Signals . . . . . . . . . . . . . . . . . . . . . . . 144 Staged Preheat Control . . . . . . . . . 1288
Simulation . . . . . . . . . . . . . . . . . . . . 161 Staged Reheat Control . . . . . . . . . . 1288
Starting . . . . . . . . . . . . . . . . . . . . 242 Staged Supplemental Heating Control
Stopping . . . . . . . . . . . . . . . . . . . 242 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1282
Simulation and Commissioning Modes Standard Dual Duct Endpoint Calculation
Only . . . . . . . . . . . . . . . . . . . . . . . 775 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 843
Simulation Mode . . . . . . . . . . . . . . . . 81 Start Stop Sequencing . . . . . . . . . . . 947
Simulation Overview . . . . . . . . . . . . 241 Start Stop Sequencing (AHU 100% OA)
Simulation Screen . . . . . . . . . . . . . . 245 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 942
Simulation Tasks . . . . . . . . . . . . . . . 119 Start Stop Sequencing (AHU Mixed Air)
SIN . . . . . . . . . . . . . . . . . . . . . . . . . 1474 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 947
Single Speed Fan Control . . . . . . . 1146 Start Stop Sequencing DA-T . . . . . . 947
SL . . . . . . . . . . . . . . . . . . . . . . . . . . . 691 Start Stop Sequencing Zone . . . . . . . 947
Slave CD Constant Flow Setpoint Starting
Control . . . . . . . . . . . . . . . . . . . . 1078 Simulation . . . . . . . . . . . . . . . . . 242
Slave CD Flow Setpoint Control . . 1078 Test Mode . . . . . . . . . . . . . . . . . 273
Slave HD Flow Setpoint Control . . 1078 State Determination . . . . . . . . . . . . . 999
Slave Supply Flow Setpoint Control Application Mode Determination
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1076 . . . . . . . . . . . . . . . . . . . . . . . . 1000
Slave Supply Flow Setpoint Control Dual Energy Hold Off Determination
Duct . . . . . . . . . . . . . . . . . . . . . . 1078 . . . . . . . . . . . . . . . . . . . . . . . . 1002
Smoke Control Sequencing for UL-864- Fan Alarm Status . . . . . . . . . . . 1005
UUKL . . . . . . . . . . . . . . . . . . . . . . 932 Fan Determination (Terminal Units)
Smoke Control Support UL-864-UUKL . . . . . . . . . . . . . . . . . . . . . . . . 1007
VAV Slave Dual Duct . . . . . . . . 685 Occupancy Mode Determination
VAV Slave Dual Duct Modules 685 . . . . . . . . . . . . . . . . . . . . . . . . 1010
VAV Slave Single Duct . . . . . . . 654 Occupancy Mode Determination
VAV Slave Single Duct Modules (MZ) . . . . . . . . . . . . . . . . . . . 1014
. . . . . . . . . . . . . . . . . . . . . . . . . 654 System Mode Determination . . 1016
Sorting Unit Enable Determination . . . 1018
Object Naming Preferences . . . . 149 Zone Low Limit Determination 1021
Span . . . . . . . . . . . . . . . . . . . . . . . . 1444 State Generation . . . . . . . . . . . . . . . . . 88
SQRT . . . . . . . . . . . . . . . . . . . . . . . 1474 State Generation Module
Staged Box Heating Control . . . . . 1282 Adding . . . . . . . . . . . . . . . . . . . . 204
Staged Compressor Control . . . . . . 1231 State Generation Module Selection . 219
Staged Cooling Control . . . . . . . . . 1225 State Generators . . . . . . . . . . . . . . . . 865
Staged Device Enable Determination State Generators Modules
Parallel . . . . . . . . . . . . . . . . . . . . . 802 Alarm Management . . . . . . . . . . 866
Staged Device Enable Determination Central Plant . . . . . . . . . . . . . . . 870
Series . . . . . . . . . . . . . . . . . . . . . . 804 Device Enable . . . . . . . . . . . . . . 915
Staged Heating Control . . . . . . . . . 1282 General Sequencing . . . . . . . . . . 926
Staged Humidification Control . . . 1305 Occupied Sequencing . . . . . . . . 952
Staged Output Control . . . . . . . . . . 1348 Pass Through . . . . . . . . . . . . . . . 997
Index 1579
Rooftop Control Logic . . . . . . . . 510 Rooftop . . . . . . . . . . . . . . . . . . . 492
Rooftop Mechanical . . . . . . . . . . 488 Rooftop Modules . . . . . . . . . . . . 493
Unit Ventilator Control Logic . . 595 Test Mode
Unit Ventilator Mechanical . . . . 583 Starting . . . . . . . . . . . . . . . . . . . . 273
VAV Dual Duct Control Logic . 669 Working with . . . . . . . . . . . . . . . 273
VAV Dual Duct Mechanical . . . 658 Three Speed Fan Control . . . . . . . . 1148
VAV Single Duct Mechanical . . 628 Timer . . . . . . . . . . . . . . . . . . . . . . . 1484
VAV Slave Dual Duct Control Logic Timing . . . . . . . . . . . . . 860, 1374, 1484
. . . . . . . . . . . . . . . . . . . . . . . . . 685 Last Value (Boolean, Enum, Float)
VAV Slave Dual Duct Mechanical . . . . . . . . . . . . . . . . . . . . 860, 1374
. . . . . . . . . . . . . . . . . . . . . . . . . 677 Toolbar (Logic View) . . . . . . . . . . . 100
VAV Slave Single Duct Mechanical Totalization . . . . . . . . . . . . . 1380, 1444
. . . . . . . . . . . . . . . . . . . . . . . . . 647 Totalization (Enum Runtime) . 1380
System Selection Preferences . . . . . 145 Totalization (Enum Runtime) . . . . 1380
Exporting . . . . . . . . . . . . . . . . . . 152 Tower Control . . . . . . . . . . . . . . . . 1100
Importing . . . . . . . . . . . . . . . . . . 152 Tower Control v2 . . . . . . . . . . . . . . 1103
Resetting . . . . . . . . . . . . . . . . . . 151 Tower Fan X Control . . . . . . . . . . . 1100
Setting . . . . . . . . . . . . . . . . . . . . 151 Tower Fan X Control v2 . . . . . . . . 1103
System Selection Tree . . . . . . . . . . . 160 Tower Fan X Enable LV . . . . . . . . 1374
System Selection Wizard . . . . . . . . . 158 Tower Fan X LV . . . . . . . . . . . . . . 1374
System Selections Tower Fan X Totalization . . . . . . . 1380
Modifying . . . . . . . . . . . . . . . . . 166 Tower Rotation Small . . . . . . . . . . 1092
Viewing . . . . . . . . . . . . . . . . . . . 166 Tower Sequencing-1 Speed . . . . . . . 902
System Types and Configurations . . 159 Tower Sequencing-2 Speed . . . . . . . 905
System Upgrades . . . . . . . . . . . . . . . 121 Tower Sequencing-3 Speed . . . . . . . 908
Backup Files . . . . . . . . . . . . . . . 139 Tower Sequencing-Vernier . . . . . . . 911
New Modules . . . . . . . . . . . . . . . 125 Troubleshooting . . . . . . . . . . . . . . . 1495
Upgraded Modules . . . . . . . . . . . 122 Two Position Exhaust Damper Control
Upgraded System Types . . . . . . 122 . . . . . . . . . . . . . . . . . . . . . . . . . . . 1122
Upgrading a System . . . . . . . . . . 140 Two Position Min OA Damper Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1122
T TWR Iso Valve (Pass Through) . . . 1328
TwrFanX Alarms . . . . . . . . . . . . . . . 866
TAN . . . . . . . . . . . . . . . . . . . . . . . . 1474
TwrFanX Blocking Protection . . . . 1311
Temperature Control Strategy
TwrFanX Status Alarm Determination
Mixed Air Dual Duct . . . . . . . . . 364
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 806
Mixed Air Dual Duct Modules . 364
Type . . . . . . . . . . . . . . . . . . . . . . . . . 775
Mixed Air Single Duct . . . . . . . . 305
Mixed Air Single Duct Modules 306
Multizone (Mixed Air Dual Duct)
U
. . . . . . . . . . . . . . . . . . . . . . . . . 525 UI . . . . . . . . . . . . . . . . . . . . . 75, 77, 111
Multizone (Mixed Air Dual Duct) Unit Enable Determination . . . . . . 1018
Modules . . . . . . . . . . . . . . . . . 525 Unit Preferences . . . . . . . . . . . . . . . . 145
Outdoor Air Dual Duct . . . . . . . 452 Unit Ventilator
Outdoor Air Single Duct . . . . . . 405 ASHRAE Cycle Control . . . . . . 595
Outside Air Dual Duct Modules 452 ASHREA Cycle Control Modules
Outside Air Single Duct Modules . . . . . . . . . . . . . . . . . . . . . . . . . 596
. . . . . . . . . . . . . . . . . . . . . . . . . 406 Coils . . . . . . . . . . . . . . . . . . . . . . 585
Index 1581
Variable Capacity Return Fan Volume Fan Determination (VAV Parallel
Match Control . . . . . . . . . . . . . . 1170 Temp Based) . . . . . . . . . . . . 1058
Variable Capacity Supply Fan Control Fan Determination (VAV Series)
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1178 . . . . . . . . . . . . . . . . . . . . . . . . 1060
Variable Speed Fan Clg Twr Sequencing VAV Single Duct . . . . . . . . . . . . . . . 624
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 895 Box Fan . . . . . . . . . . . . . . . . . . . 630
VAV . . . . . . . . . . . . . . . . . . . . . . . . . 623 Box Fan Modules . . . . . . . . . . . . 630
VAV Applications . . . . . . . . . . . . . . 623 Coils . . . . . . . . . . . . . . . . . . 631, 650
VAV Dual Duct . . . . . . . . . . . . . . . . 655 Coils Modules . . . . . . . . . . . . . . 631
Coils . . . . . . . . . . . . . . . . . . . . . . 663 Exhaust Damper Actuator . . . . . 629
Coils Modules . . . . . . . . . . . . . . 663 Exhaust Damper Actuator Modules
Cold Deck Damper Actuator . . . 658 . . . . . . . . . . . . . . . . . . . . . . . . . 629
Cold Deck Damper Actuator Heating Priority . . . . . . . . . . . . . 640
Modules . . . . . . . . . . . . . . . . . 658 Misc . . . . . . . . . . . . . . . . . . . . . . 638
Control Scheme . . . . . . . . . . . . . 669 Misc Modules . . . . . . . . . . . . . . 638
Exhaust Damper Actuator . . . . . 662 Occupancy . . . . . . . . . . . . . . . . . 639
Exhaust Damper Actuator Modules Occupancy Modules . . . . . . . . . 639
. . . . . . . . . . . . . . . . . . . . . . . . . 662 Optional Equipment . . . . . . . . . . 634
Flow Sensor Location . . . . . . . . 660 Optional Equipment Modules . . 634
Flow Sensor Locations Modules 660 Optional Features . . . . . . . . . . . . 640
Hot Deck Damper Actuator . . . . 659 Optional Features Modules . . . . 642
Hot Deck Damper Actuator Modules Sensor Modules . . . . . . . . . . . . . 636
. . . . . . . . . . . . . . . . . . . . . . . . . 659 Sensors . . . . . . . . . . . . . . . . . . . . 635
Misc . . . . . . . . . . . . . . . . . . . . . . 668 Supply Damper Actuator . . . . . . 628
Misc Modules . . . . . . . . . . . . . . 668 Supply Damper Actuator Modules
Occupancy . . . . . . . . . . . . . . . . . 671 . . . . . . . . . . . . . . . . . . . . . . . . . 628
Optional Equipment . . . . . . . . . . 665 VAV Single Duct Applications . . . . 624
Optional Equipment Modules . . 665 VAV Single Duct Core Logic . . . . . 626
Optional Features . . . . . . . . . . . . 672 VAV Single Duct Mechanical System
Sensor Modules . . . . . . . . . . . . . 667 Selection . . . . . . . . . . . . . . . . . . . . 628
Sensors . . . . . . . . . . . . . . . . . . . . 666 VAV Single Duct Minimum Flow
VAV Dual Duct Applications . . . . . 655 Determination . . . . . . . . . . . . . . . . 846
VAV Dual Duct Constant Flow Endpoint VAV Slave DD . . . . . . . . . . . . . . . . 675
Calculation . . . . . . . . . . . . . . . . . . 839 VAV Slave Dual Duct . . . . . . . . . . . 675
VAV Dual Duct Control Logic System Coils . . . . . . . . . . . . . . . . . . . . . . 682
Selection . . . . . . . . . . . . . . . . . . . . 669 Coils Modules . . . . . . . . . . . . . . 682
VAV Dual Duct Core Logic . . . . . . 657 Cold Deck Damper Actuator . . . 677
VAV Dual Duct Mechanical System Cold Deck Damper Actuator
Selection . . . . . . . . . . . . . . . . . . . . 658 Modules . . . . . . . . . . . . . . . . . 677
VAV Dual Duct Minimum Flow Control Scheme . . . . . . . . . . . . . 686
Determination . . . . . . . . . . . . . . . . 841 Exhaust Damper Actuator . . . . . 681
VAV Dual Duct Variable Flow Endpoint Exhaust Damper Actuator Modules
Calculation . . . . . . . . . . . . . . . . . . 843 . . . . . . . . . . . . . . . . . . . . . . . . . 681
VAV Fan Determination . . . . . . . . 1055 Flow Sensor Location . . . . . . . . 679
Fan Determination (VAV Parallel Flow Sensor Locations Modules 679
Flow Based) . . . . . . . . . . . . . 1055 Hot Deck Damper Actuator . . . . 678
Index 1583
Zone Heating Availability Determination Zone Staged Htg Mode Pass Through SG
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 917 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 997
Zone Heating Control Status LV . . 1374 Zone Unoccupied Sequencing . . . . 1029
Zone Htg Valve Mode Pass Through Zone X Damper Control . . . . . . . . 1314
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1328 Zone X Max Cap Fract LV . . . . . . 1374
Zone Htg Valve Mode Pass Through SG Zone X MSC 2 Position Heating . . 1348
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 997 Zone X MSC Staged Heating XX . 1348
Zone Loop Control Zone X with 2 Position Heating Valve
Central Heating . . . . . . . . . . . . . 764 Control . . . . . . . . . . . . . . . . . . . . 1316
Central Heating Modules . . . . . . 764 Zone X with Proportional Heating Valve
Zone Low Limit Determination . . . 1021 Control . . . . . . . . . . . . . . . . . . . . 1320
Zone Sequencing . . . . . . . . . . . . . . . 978 Zone X with Staged Heating Control
Zone Staged Htg Mode Pass Through . . . . . . . . . . . . . . . . . . . . . . . . . . . 1324
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1328 Zooming . . . . . . . . . . . . . . 192, 244, 272