Equal Friction Method of Designing Ducts

Given:
Duct system for general office (Layout on next slide).
Total air quantity = 5400 cfm, 0.15in.wg SP at each outlet
Radius elbows, R/D = 1.25

Find:
1. Initial duct velocity, area, size and friction rate in the 
duct section from the fan to the first branch.
2. Size of remaining duct runs.
3. Total equivalent length of duct run with highest 
resistance.
4. Total static pressure required at fan discharge

DUCT LAYOUT 

1
5/16/2018

Solution:
1. From table 7 select an initial velocity of 1500 fpm.
Duct area = 5400 cfm = 3.60 sq ft
1500 fpm
From table 6, select a duct size ‐ 24 in. x 24 in.
Initial friction rate is determined from Chart 7 
using the air quantity (5400), and the equivalent 
round duct diameter from Table 6. Equivalent 
round duct diameter = 24.1 in.

2
5/16/2018

Friction rate= 0.145 in. wg per 100 ft of 
equivalent length.

2. The duct areas, are calculated using Table 13  and 
duct sizes are determined from Table 6. The 
following tabulates the design information:  

3
5/16/2018

AIR CFM DUCT DUCT


DUCT QUANTITY CAPACITY AREA AREA SIZE
SECTION (cfm) (%) (%) (sq. ft.) (in.)
(Table 13)

To A 5400 100 100.0 3.60 24 X 24


A-B 3600 67 73.5 2.646 24 X 18
B -13 1800 33 41.0 1.476 24 X 10
13 -14 1500 28 35.5 1.278 20 X 10
14 -15 1200 22 29.5 1.062 16 X 10
15 -16 900 17 24.0 0.864 14 X 10
16 -17 600 11 17.5 0.630 10 X 10
17 -18 300 6 10.5 0.378 10 X 6

4
5/16/2018

5
5/16/2018

•Percent of cfm = air quantity in duct section
total air quantity

† Duct area = percent of area times initial duct area  
(fan to A)

Duct sections B thru 12 and A thru 6 have the same 
dimension as the corresponding duct sections in B thru 
18.

3. It appears that the duct run from the fan to 
terminal 18 has the highest resistance. Tables 10 and 
12 are used to determine the losses thru the fittings. 
The following list is a tabulation of the total 
equivalent length in this duct run:

6
5/16/2018

DUCT ITEM LENGTH ADD. EQUIV.


SECTION LENGTH (ft)

To A Duct 60
Elbow / 12
A-B Duct 20
B – 13 Duct 30
-- Elbow 7
13 – 14 Duct 20
14 – 15 Duct 20
15 – 16 Duct 20
16 – 17 Duct 20
17 – 18 Duct 20

4. The total friction loss in the ductwork from the 
fan to last terminal 18 is shown in the following:

Loss= total equiv length x friction rate
= 229 x 0.145 in. wg = 0.332 in.wg
100 ft

Total static pressure required at fan discharge is 
the sum of the terminal operating pressure and 
the loss in the ductwork. Credit can be taken for 
the velocity regain between the first and last 
sections of duct

7
5/16/2018

Velocity in initial section = 1700 fpm
Velocity in last section = 590 fpm
Using a 75 % regain coefficient

Regain = 0.75 [(1700/ 4000)2 – (590/4000)2]
= 0.75 ( 0.18 ‐ 0.02 ) = 0.12 in. wg

Therefore, the total static pressure at fan discharge:
= duct fiction + terminal pressure – regain
= 0.33 + 0.15 ‐ 0.12
= 0.36 in. wg