Beruflich Dokumente
Kultur Dokumente
975 1 1
| 0.1 −0.005 0 |
𝑃1 = −0.56 0.005 −0.006 = 233.4746 𝑀𝑊
1 1 1
|0.008 −0.005 0 |
0 0.005 −0.006
1
1 975 1
|0.008 0.1 0 |
𝑃2 = 0 −0.56 −0.006 = 353.5593 𝑀𝑊
1 1 1
|0.008 −0.005 0 |
0 0.005 −0.006
1 1 975
|0.008 −0.005 0.1 |
𝑃3 = 0 0.005 −0.56 = 387.9661 𝑀𝑊
1 1 1
|0.008 −0.005 0 |
0 0.005 −0.006
We can see that: 𝑃3 > 𝑃3𝑚𝑎𝑥 , hence this solution is not accepted.
From equation (1) we get: 𝑃1 = 250 𝑀𝑊. Hence, 𝑃2 = 300 𝑀𝑊 and hence equation (2)
becomes:
600𝛼 + 𝛽 = 8 … (3)
From equation (1) we get: 𝑃1 = 500 𝑀𝑊. Hence, 𝑃2 = 800 𝑀𝑊 and hence equation (2)
becomes:
1600𝛼 + 𝛽 = 10 … (4)
𝜶 = 𝟎. 𝟎𝟎𝟐
𝜷 = 𝟔. 𝟖
3
Problem 3:
𝐶1 (𝑃1 ) = 5.3𝑃1 + 500, 200 ≤ 𝑃1 ≤ 450
𝐶2 (𝑃2 ) = 5.5𝑃2 + 500, 150 ≤ 𝑃2 ≤ 350
𝐶3 (𝑃3 ) = 5.8𝑃3 + 500, 100 ≤ 𝑃3 ≤ 225
𝑃𝐷 = 800 𝑀𝑊
First, we form the Lagrangian:
From equations (1), (2) and (3), we get three different values of 𝜆. Hence, these equations
cannot lead to a solution.
Considering the first-order cost functions given, we get that generator no.1 is the cheapest
generator while generator no.3 is the most expensive. Hence, we will assume generator no.1
is providing maximum power (𝑃1 = 𝑃1𝑚𝑎𝑥 = 450 𝑀𝑊) and generator no.3 is providing
minimum power (𝑃3 = 𝑃3𝑚𝑖𝑛 = 100 𝑀𝑊). So, the Lagrangian becomes:
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 5.3 − 𝜆 + 𝛾1 = 0 … (5)
𝜕𝑃1
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 5.5 − 𝜆 = 0 … (6)
𝜕𝑃2
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 5.8 − 𝜆 − 𝜇3 = 0 … (7)
𝜕𝑃3
4
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 𝑃1 + 𝑃2 + 𝑃3 − 800 = 0 … (8)
𝜕𝜆
𝑑𝐶1
= 5.3 $/𝑀𝑊ℎ < 𝜆
𝑑𝑃1
𝑑𝐶3
= 5.8 $/𝑀𝑊ℎ > 𝜆
𝑑𝑃3
For generator no.2 incremental cost is the same as system marginal cost:
𝑑𝐶2
= 𝜆 = 5.5 $/𝑀𝑊ℎ
𝑑𝑃2
5
Problem 4:
𝑑𝐶1
= 0.008 ∗ 𝑃1 + 8
𝑑𝑃1
𝑑𝐶2
= 0.012 ∗ 𝑃2 + 9
𝑑𝑃2
𝑃1 = 𝑃2 = 500 𝑀𝑊
𝐼𝐿𝐹2 = 0.2
𝑑𝐶1 𝑑𝐶2
𝑃𝐹1 ∗ = 𝑃𝐹2 ∗ =𝜆
𝑑𝑃1 𝑑𝑃2
So,
1
𝑃𝐹1 ∗ 12 = ∗ 15
1 − 𝐼𝐿𝐹2
Hence, we get:
𝑷𝑭𝟏 = 𝟏. 𝟓𝟔𝟐𝟓
6
Problem 5:
𝐶𝐴 (𝑃𝐴 ) = 2.546𝑃𝐴2 + 23.45𝑃𝐴 + 4, 150 ≤ 𝑃𝐴 ≤ 700
𝑪𝑨 = 𝟒𝟔𝟗𝟖𝟒𝟏. 𝟓 $/𝒉𝒓
𝑪𝑩 = 𝟏𝟗𝟐𝟑𝟓𝟗𝟔. 𝟔 $/𝒉𝒓
𝑪𝑪 = 𝟖𝟕𝟖𝟑𝟖𝟓 $/𝒉𝒓
𝒅𝑪𝑨
= 𝟐𝟏𝟖𝟕. 𝟓𝟓 $/𝑴𝑾𝒉
𝒅𝑷𝑨
𝒅𝑪𝑩
= 𝟏𝟏𝟗𝟒𝟒. 𝟎𝟑 $/𝑴𝑾𝒉
𝒅𝑷𝑩
𝒅𝑪𝑪
= 𝟒𝟑𝟑𝟕. 𝟓𝟒 $/𝑴𝑾𝒉
𝒅𝑷𝑪
′
𝐶𝑝𝑜𝑜𝑙 = 𝐶𝐴 + 𝐶𝐵 + 𝐶𝐶 = 3271823.1 $/ℎ𝑟
b. If the utilities coordinate together to operate as a power pool to minimize the total
aggregated cost, then the problem becomes:
𝑀𝑖𝑛 𝐽 = ∑ 𝐶𝑖 (𝑃𝑖 )
𝑖=𝐴
7
KKT conditions will be:
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 5.092 ∗ 𝑃𝐴 + 23.45 − 𝜆 = 0 … (1)
𝜕𝑃𝐴
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 37.08 ∗ 𝑃𝐵 + 78.43 − 𝜆 = 0 … (2)
𝜕𝑃𝐵
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 10.708 ∗ 𝑃𝐶 + 54.34 − 𝜆 = 0 … (3)
𝜕𝑃𝐶
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 𝑃𝐴 + 𝑃𝐵 + 𝑃𝐶 − 1145 = 0 … (4)
𝜕𝜆
1145 1 1
| 54.98 −37.08 0 |
𝑃𝐴 = −24.09 37.08 −10.708 = 712.6283 𝑀𝑊
1 1 1
|5.092 −37.08 0 |
0 37.08 −10.708
1 1145 1
|5.092 54.98 0 |
𝑃𝐵 = 0 −24.09 −10.708 = 96.3787 𝑀𝑊
1 1 1
|5.092 −37.08 0 |
0 37.08 −10.708
1 1 1145
|5.092 −37.08 54.98 |
𝑃𝐶 = 0 37.08 −24.09 = 335.993 𝑀𝑊
1 1 1
|5.092 −37.08 0 |
0 37.08 −10.708
We can see that: 𝑃𝐴 > 𝑃𝐴𝑚𝑎𝑥 and 𝑃𝐵 < 𝑃𝐵𝑚𝑖𝑛 hence this solution is not accepted.
8
Hence, we put 𝑃𝐴 = 𝑃𝐴𝑚𝑎𝑥 = 700 𝑀𝑊 and 𝑃𝐵 = 𝑃𝐵𝑚𝑖𝑛 = 100 𝑀𝑊. We form the new
Lagrangian as follows:
Carrying out the same procedure above we get the following equations:
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 5.092 ∗ 𝑃1 + 23.45 − 𝜆 + 𝛾𝐴 = 0 … (7)
𝜕𝑃𝐴
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 37.08 ∗ 𝑃𝐵 + 78.43 − 𝜆 − 𝜇𝐵 = 0 … (8)
𝜕𝑃𝐵
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 10.708 ∗ 𝑃𝐶 + 54.34 − 𝜆 = 0 … (9)
𝜕𝑃𝐶
𝜕𝐹 𝑦𝑖𝑒𝑙𝑑𝑠
=0 → 𝑃𝐴 + 𝑃𝐵 + 𝑃𝐶 − 1145 = 0 … (10)
𝜕𝜆
Manipulating these equations as above, we get:
𝑷𝑨 = 𝟕𝟎𝟎 𝑴𝑾, 𝑷𝑩 = 𝟏𝟎𝟎 𝑴𝑾, 𝑷𝑪 = 𝟑𝟒𝟓 𝑴𝑾, 𝝀 = 𝟑𝟕𝟒𝟖. 𝟔 $/𝑴𝑾𝒉
Checking for utility-A, the incremental cost is:
𝒅𝑪𝑨
= 𝟓. 𝟎𝟗𝟐 ∗ 𝑷𝑨 + 𝟐𝟑. 𝟒𝟓 = 𝟑𝟓𝟖𝟕. 𝟖𝟓 $/𝑴𝑾𝒉 < 𝝀
𝒅𝑷𝑨
𝑪𝑨 = 𝟏𝟐𝟔𝟑𝟗𝟓𝟗 $/𝒉𝒓
𝑪𝑩 = 𝟏𝟗𝟑𝟐𝟒𝟔 $/𝒉𝒓
𝑪𝑪 = 𝟔𝟓𝟔𝟎𝟏𝟔. 𝟏𝟓 $/𝒉𝒓
𝑪𝒑𝒐𝒐𝒍 = 𝑪𝑨 + 𝑪𝑩 + 𝑪𝑪 = 𝟐𝟏𝟏𝟑𝟐𝟐𝟏. 𝟏𝟓 $/𝒉𝒓
9
′ (𝑓𝑟𝑜𝑚 𝑝𝑎𝑟𝑡 𝑎) − 𝐶𝑝𝑜𝑜𝑙
ii. 𝑃𝑜𝑜𝑙 𝑠𝑎𝑣𝑖𝑛𝑔𝑠 = 𝐶𝑝𝑜𝑜𝑙
iv. The sketch below shows the optimal transactions between the utilities in pool operation:
𝑷𝑨𝑪 = 𝑷𝑫𝑪 − 𝑷𝑪 = 𝟓𝟓 𝑴𝑾
Utility-A Utility-B
PAB = 220 MW
PA = 700 MW PB = 100 MW
Utility-C
PC = 345 MW
PDC = 400 MW
10
Problem 6:
𝐶1 (𝑃1 ) = 0.00253𝑃12 + 3.19𝑃1 + 850, 100 ≤ 𝑃1 ≤ 850
𝐶2 (𝑃2 ) = 0.00325𝑃22 + 5.11𝑃2 + 1687, 100 ≤ 𝑃2 ≤ 600
𝑃𝑙𝑜𝑠𝑠 (𝑃1 , 𝑃2 ) = 11 ∗ 10−5 𝑃12 + 6 ∗ 10−5 𝑃22 𝑀𝑊
𝑃𝐷 = 1200 𝑀𝑊
The iterative procedure to find the optimal dispatch that minimizes generation cost is as follows:
1. We start with initial guess for 𝑃1 and 𝑃2 . From the cost functions given, we can see that
generator no.2 is more expensive than generator no.1.Hence, our initial guess will be
𝑃1 = 700 𝑀𝑊 and 𝑃2 = 500 𝑀𝑊.
2. Penalty factors are calculated based on the assumed 𝑃1 and 𝑃2 where:
1
𝑃𝐹𝑖 = , 𝑖 = 1, 2
𝜕𝑃
1 − 𝑙𝑜𝑠𝑠
𝜕𝑃𝑖
3. We calculate the losses.
4. We calculate the required generation to supply the demand and the losses where:
𝑃𝐷′ = 𝑃𝐷 + 𝑃𝑙𝑜𝑠𝑠
5. We solve the coordination equations with the demand supply balance equation to get the new
values for 𝑃1 and 𝑃2 (two equations solved simultaneously):
𝑑𝐶1 𝑑𝐶2
𝑃𝐹1 ∗ = 𝑃𝐹2 ∗ =𝜆
𝑑𝑃1 𝑑𝑃2
And,
𝑃1 + 𝑃2 = 𝑃𝐷′
6. Repeat steps 2 to 5 till a fair degree of accuracy is reached.
11
Problem 7:
𝑑𝐶1
= 0.00643𝑃1 + 3.37
𝑑𝑃1
𝑑𝐶2
= 0.00364𝑃2 + 7.19
𝑑𝑃2
𝜆 = 30 $/𝑀𝑊ℎ
For optimal dispatch, the following equations apply:
𝑑𝐶1 𝑑𝐶2
𝑃𝐹1 ∗ = 𝑃𝐹2 ∗ =𝜆
𝑑𝑃1 𝑑𝑃2
Where:
1 1
𝑃𝐹1 = =
𝜕𝑃 1 − 0.00022𝑃1 − 0.0045𝑃2
1 − 𝑙𝑜𝑠𝑠
𝜕𝑃1
And,
1 1
𝑃𝐹2 = =
𝜕𝑃 1 − 0.00012𝑃2 − 0.0045𝑃1
1 − 𝑙𝑜𝑠𝑠
𝜕𝑃2
So,
0.00643𝑃1 + 3.37
= 30 … (1)
1 − 0.00022𝑃1 − 0.0045𝑃2
And,
0.00364𝑃2 + 7.19
= 30 … (2)
1 − 0.00012𝑃2 − 0.0045𝑃1
12
Problem 8:
Reading no. ΔCt ($/hr) ΔP1 ΔP2 ΔP3
1 0 1 1 -2
2 30 1 1 1
3 -20 -3 1 1
Which is an undefined value. We cannot determine the system marginal cost (𝜆).
13
2. For data set no.(2):
∆𝐶𝑡 = 30 and ∆𝑃𝑡 = 3, hence:
∆𝐶𝑡
= 10
∆𝑃𝑡
So, from points 2 and 3, the system is not operating at a constant incremental cost within
few minutes. Therefore, system is not on economic dispatch. Jill was correct to say that
Jack is wrong.
14
Problem 9:
𝐸1 (𝑃1 ) = 0.0275𝑃12 + 3.5𝑃1 + 25, 50 ≤ 𝑃1 ≤ 650
𝐸2 (𝑃2 ) = 0.065𝑃22 + 6.2𝑃2 + 48, 30 ≤ 𝑃2 ≤ 400
𝑃𝐷1 = 575 𝑀𝑊
𝑃𝐷2 = 325 𝑀𝑊
When utilities are on a joint operation, the total emissions minimization problem becomes:
2
𝑀𝑖𝑛 𝐽 = ∑ 𝐸𝑖 (𝑃𝑖 )
𝑖=1
Subject to:
15
In this case (joint operation), the emissions can be calculated using the values of 𝑃1 and 𝑃2
obtained and we get:
𝑬𝒕𝒐𝒕𝒂𝒍 = 𝑬𝟏 + 𝑬𝟐 = 𝟏𝟗𝟓𝟕𝟖. 𝟒𝟑𝟐 𝒌𝒈/𝒉𝒓
If the utilities are operating independently, then:
𝑃1 = 𝑃𝐷1 = 575 𝑀𝑊 and 𝑃2 = 𝑃𝐷2 = 325 𝑀𝑊 and we can calculate the total emissions
then:
𝑬′𝒕𝒐𝒕𝒂𝒍 = 𝑬′𝟏 + 𝑬′𝟐 = 𝟐𝟎𝟎𝟓𝟖. 𝟑𝟏𝟐𝟓 𝒌𝒈/𝒉𝒓
Hence, the total reduction in system emissions because of the joint dispatch is:
16
Problem 10:
2
𝐶𝑇𝐻 (𝑃𝑇𝐻 ) = 0.04𝑃𝑇𝐻 + 11𝑃𝑇𝐻 + 100, 30 ≤ 𝑃𝑇𝐻 ≤ 200
𝑞𝐻 (𝑃𝐻 ) = 0.0075𝑃𝐻2 + 25𝑃𝐻 + 300, 0 ≤ 𝑃𝐻 ≤ 250
𝐸𝐻 = 28000 𝑀𝑊ℎ, 𝑃𝑙𝑜𝑎𝑑 = 200 𝑀𝑊 for one week.
The condition for optimum (to minimize the operating cost) is that the thermal unit should
operate at a constant incremental cost for each interval which means that:
∗
𝑃𝑇𝐻 = 𝑃𝑇𝐻 at all intervals, and:
∗
𝑎
𝑃𝑇𝐻 =√
𝑐
Where: 𝑎 = 100 and 𝑐 = 0.04 from the second-order thermal unit cost characteristics
above. Hence:
𝑷∗𝑻𝑯 = 𝟓𝟎 𝑴𝑾
Also,
∗
𝐸𝑇𝐻 = 𝐸𝑙𝑜𝑎𝑑 − 𝐸𝐻 = 200 ∗ 168 − 28000 = 5600 𝑀𝑊𝐻 = 𝑃𝑇𝐻 ∗ 𝑇𝑇𝐻
Hence,
𝑻𝑻𝑯 = 𝟏𝟏𝟐 𝒉𝒐𝒖𝒓𝒔
a. The water discharge when hydro unit is operating with the thermal unit is:
𝑞𝐻1 = 0.0075 ∗ (200 − 50)2 + 25 ∗ (200 − 50) + 300 = 4218.75 𝑎𝑐𝑟𝑒. 𝑓𝑡/ℎ𝑟
When only the hydro unit is operating, the water discharge is:
𝑞𝐻2 = 0.0075 ∗ 2002 + 25 ∗ 200 + 300 = 5600 𝑎𝑐𝑟𝑒. 𝑓𝑡/ℎ𝑟
Hence, the total water volume discharged over the week is:
With the same optimal thermal power obtained above (and hence same 𝑞𝐻1 and 𝑞𝐻2
calculated above), this new water volume can be expressed as follows:
Where: 𝑇𝑇𝐻1 is the new time that the thermal unit has to operate for.
17
Solving equations (1) & (2) for 𝑇𝑇𝐻1 , we get:
So, the thermal unit will have to operate for additional 28.456 hours.
18
Problem 11:
𝐶(𝑃𝑆 ) = 0.0027𝑃𝑆2 + 9𝑃𝑆 + 200, 30 ≤ 𝑃𝑇𝐻 ≤ 400
𝑞(𝑃𝐻 ) = 5.64𝑃𝐻 + 180, 0 ≤ 𝑃𝐻 ≤ 600
𝑄𝑇𝑜𝑡 = 25000 𝑎𝑐𝑟𝑒. 𝑓𝑡 over 8-hour load period.
725 𝑀𝑊, ℎ𝑜𝑢𝑟 1 − 4
𝑃𝑙𝑜𝑎𝑑 = {
615 𝑀𝑊, ℎ𝑜𝑢𝑟 5 − 8
a. The problem is formulated as follows:
2
19
b. 𝜆 − 𝛾 iterative method is used to solve equations (1) to (7) starting with:
𝛾 = 2 $/(𝑎𝑐𝑟𝑒. 𝑓𝑡), the following table can be constructed:
Error in
𝜸 𝝀𝟏 𝝀𝟐 𝑷𝑺𝟏 𝑷𝑺𝟐 𝑷𝑯𝟏 𝑷𝑯𝟐
𝑸
($/(acre.ft)) ($/MWh) ($/MWh) (MW) (MW) (MW) (MW)
(acre.ft)
2 45.12 45.12 422.222 422.222 302.778 192.778 -12380.267
1.8 40.608 40.608 213.333 213.333 511.667 401.667 -2955.2
1.75 39.48 39.48 161.111 161.111 563.889 453.889 -598.933
1.74 39.2544 39.2544 150.667 150.667 574.333 464.333 -127.68
1.737 39.18672 39.18672 147.533 147.533 577.467 467.467 13.696
1.7373 39.1935 39.1935 147.847 147.847 577.153 467.153 -0.4416
Where:
𝐸𝑟𝑟𝑜𝑟 𝑖𝑛 𝑄 = 4 ∗ (5.64𝑃𝐻1 + 180) + 4 ∗ (5.64𝑃𝐻2 + 180) − 25000
When we get a negative value in discharge error, then this means that we are on the
expensive side of shadow price of water (water is underutilized). Hence, we decrease 𝛾.
20
Problem 12:
𝐶(𝑃𝑆 ) = 0.0027𝑃𝑆2 + 9𝑃𝑆 + 200, 30 ≤ 𝑃𝑇𝐻 ≤ 400
𝑞(𝑃𝐻 ) = 0.0075𝑃𝐻2 + 25𝑃𝐻 + 300, 0 ≤ 𝑃𝐻 ≤ 600
𝑄𝑇𝑜𝑡 = 75000 𝑎𝑐𝑟𝑒. 𝑓𝑡 over 8-hour load period.
725 𝑀𝑊, ℎ𝑜𝑢𝑟 1 − 4
𝑃𝑙𝑜𝑎𝑑 = {
615 𝑀𝑊, ℎ𝑜𝑢𝑟 5 − 8
a. The problem is formulated as follows:
2
21
b. 𝜆 − 𝛾 iterative method is used to solve equations (1) to (7) starting with:
𝛾 = 0.35 $/(𝑎𝑐𝑟𝑒. 𝑓𝑡) and 𝜆1 = 𝜆2 = 40 $/𝑀𝑊ℎ, the table in the next page can be
constructed:
Where:
2 2
𝐸𝑟𝑟𝑜𝑟 𝑖𝑛 𝑄 = 4 ∗ (0.0075𝑃𝐻1 + 25𝑃𝐻1 + 300) + 4 ∗ (0.0075𝑃𝐻2 + 25𝑃𝐻2 + 300) − 75000
When we get a negative value in discharge error, then this means that we are on the
expensive side of shadow price of water (water is underutilized). Hence, we decrease 𝛾
and vice versa.
𝑷𝑺𝟏 = 𝟑𝟔𝟕. 𝟏𝟑 𝑴𝑾
𝑷𝑺𝟐 = 𝟑𝟏𝟐. 𝟓 𝑴𝑾
22