Beruflich Dokumente
Kultur Dokumente
Conventional
Control Panels
Technical Manual
Record of Changes
No. Date Revision Details Author
1 17.10.10 1.0 Initial Release I. Reshef
2 20.10.10 1.1 Correct the date of the Initial Release. I. Reshef
Change explanation of zone 4 PB so when configured as
member of the extinguishing group it operates in the same
way and with the same delay as the Manual Activation
panel mounted switch.
3 25.01.2012 1.12 Remove different colors, correct spelling mistakes I. Reshef
Add "Suitability of use" and "Means to limit the
consequence of faults"
Move the above from "Installation" to "Important Notes"
Move level 1 header to top of page
Update Additional System Documentation
Update Routine Testing
Delete list of changes above
Add "Instructions for immediate action" from a separate file
Note
i The terms "Control Panel" as used in NFPA 72 guideline and UL 864
standard, and "Control and Indicating Equipment" (CIE), as used in EN 54
standards, are used interchangeably throughout this manual.
Note
i The terms “Trouble” as used in NFPA 72 guideline and UL 864 standard and
“Fault” as used in EN 54 standards are used interchangeably throughout this
manual
Note
i All maintenance and repair work performed on the TSA-200 shall be
performed by qualified and authorized personnel ONLY
Note
i Do not install, operate, or maintain this product before fully reading and
thoroughly understanding this manual.
— I —
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
Table of Contents
1 INTRODUCTION ............................................................................................1
2 FUNCTIONS AND OPTIONS.........................................................................2
2.1 EN 12094-1 – COMPULSORY FUNCTIONS ....................................................... 2
2.2 EN 54-2 – OPTIONS WITH REQUIREMENTS ...................................................... 2
2.3 EN 12094-1 – OPTIONS WITH REQUIREMENTS ................................................ 3
2.4 ADDITIONAL FUNCTIONS ................................................................................. 3
2.5 SUPPORT FUNCTIONS .................................................................................... 3
5 SAFETY .......................................................................................................10
5.1 GROUNDING AND MAINS SUPPLY CONNECTION .............................................. 10
5.2 BATTERIES HANDLING AND SAFETY ............................................................... 11
6 ACCESS LEVELS........................................................................................12
7 TECHNICAL SPECIFICATIONS ..................................................................13
7.1 MAIN ELEMENTS .......................................................................................... 13
7.2 NUMBERING OF INPUTS AND OUTPUTS .......................................................... 13
7.3 TABLE OF TECHNICAL SPECIFICATIONS, TSA-1000X...................................... 14
7.4 DEFAULT PORTS ALLOCATION AND ECD CONFIGURATION .............................. 19
9 INSTALLATION ...........................................................................................23
— II —
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
— III —
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
16 COMMISSIONING........................................................................................68
17 MAINTENANCE ...........................................................................................69
— IV —
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
19 TROUBLESHOOTING .................................................................................71
19.1 MAINTENANCE ALERT ................................................................................... 71
19.2 SYSTEM STATUS DISPLAY INDICATIONS ......................................................... 71
19.3 SYSTEM FAULTS .......................................................................................... 71
19.4 PROGRAMMING FAULTS ................................................................................ 73
20 CERTIFICATION ..........................................................................................75
20.1 CE LABEL .................................................................................................... 75
— V —
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
Tables of Figures
Figure 1 TSA-1000X System Symbolic Functional Diagram 8
Figure 2 Chassis Mounting Holes 25
Figure 3 Routing cables in the TSA-1000X Enclosure 26
Figure 4 Connecting Two Detectors and a TPB-10R Break-Glass MCP 28
Figure 5 Main Board Connectors 28
Figure 6 Expansion Module Connectors 29
Figure 7 Connecting the grounding wire to the Chassis 30
Figure 8 Connecting a FIRERASER Cylinder for Automatic Extinguishing 32
Figure 9 Connecting a GCA-Activated Extinguishing Cylinder 32
Figure 10 Connecting a GreenEX Aerosol Extinguishing Container 33
Figure 11 Connecting FirePro Aerosol Generators 34
Figure 12 Connecting SAFE Solenoid Activated gas containers 34
Figure 13 Front Panel-Display and Keyboard 35
Figure 14 General LEDs Display Area 36
Figure 15 Status Display 37
Figure 16 Keyboard 38
Figure 17 Zone Indicators 38
Figure 18 Extinguishing Zone Indicators 39
Figure 19 Menu Structure 55
Figure 20 The status display representation of digits and letters 57
Figure 21 Device selection 58
Figure 22 Display during relay programming 59
Figure 23 Relay Contacts, Normal Operations and Upon Activation 59
Figure 24 Display during input programming 60
Figure 25 Display during output programming 61
Figure 26 TSA-1000X CE label 75
List of Tables
Table 1 Technical Specifications 18
Table 2 IDC cable selection 23
Table 3 Wiring Characteristics’ influence on System Performance 26
Table 4 TSA-1000X Table of States 46
— VI —
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
1 Introduction
The TSA-1000X Electrical Automatic Control and Delay Device (CDE) is designed in
accordance with EN 54-2; EN 54-4; and EN 12094-1 Standards.
The TSA-1000X is a combined conventional (i.e. Non Addressable) Fire Alarm Control
Panel (Control and Indication Equipment, CIE) and an Extinguishing Control and Delay
Device (CDE).
It supports one flooding zone and four inputs, of which three are detector zones inputs
and one input is a programmable Detector/MCP/Auxiliary/Manual Activation input. All
four inputs can contribute to the extinguishing decision group (referred to in this manual
also as the decision matrix).
The TSA-1000X has an internal and integral Power Supply/Charger, the PS_40W,
designed and certified to EN 54-4.
In addition to being a Gas Extinguishing system, the TSA-1000X, due to its flexibility and
the additional options it supports, can also control other extinguishing systems, such as
water and aerosol systems.
Using Telefire's proprietary adapters, the extinguisher output can drive different
extinguishing devices, such as solenoids, GCA, Detonators, etc.
Most inputs and outputs of the TSA-1000X are pre-assigned and fixed function, and it is
shipped with a default configuration and parameters. However, Input No. 4 of the Main
Board, output 4 of the Main Board and relay 6 of the EM083 expansion board can be
programmed, and the Control Panel can be configured to adapt to different extinguisher
systems and sites' requirements (Using Telefire's proprietary extinguishing adapters).
– Page 1 of 1 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
– Page 2 of 2 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
– Page 3 of 3 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
3 Important Notes
3.1 Manual Triggering Devices
An integral Manual Triggering device (Push Button) is installed on the front panel of the
ECD.
This is a double action, positive activation device.
It is designed to prevent accidental activation, but it can be easily activated if the
operator deliberately chooses to operate it.
Note
i The Manual triggering device mounted on the front panel of the TSA-1000X
ECD is not in accordance to EN 12094-3.
Note
i If a remote (non panel mounted) extinguishing manual triggering device is
used, then USE ONLY an approved and certified Extinguishing Triggering
Device of the correct color as per EN 12094-3.
Note
i If a remote (non panel mounted) extinguishing manual triggering device is
used, then USE ONLY an approved and certified Extinguishing Triggering
Device of the correct color as per EN 12094-3.
– Page 4 of 4 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
Note
i If a remote (non panel mounted) Manual Call Point is used, then USE ONLY
an approved and certified Device of the correct color as per EN 12094-3 and
EN 54-2.
If two zones coincidence is not required by your national regulations, you may change
the configuration so the ECD activates on any single zone which is configured as a
member of the Extinguishing Decision Group.
Note
i Trigger on coincidence of more than two independent sources does not
comply with the 12094-1 standard.
Note
i If zones which are not members of the extinguishing decision group are
triggered, the ECD changes state to "Fire Alarm", BUT DOES NOT ENTER
THE PREACTIVATED/ACTIVATED states, and the extinguisher is NOT
ACTIVATED even if two such zones are triggered.
In the default Configuration, zone 3 and zone 4 are NOT MEMBERS of the extinguishing
decision group.
– Page 5 of 5 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
If the zone Alarm Delay is programmed ON, there is a 30 seconds alarm Delay. During
the delay period alarms are ignored. This is followed by a 180 seconds confirmation
period.
When a zone programmed for alarm verification is first triggered, the control panel resets
the zone in alarm, waits for 30 seconds (if Delay is ON) and enters a 180 seconds (3
minutes) confirmation period. During the 30 seconds delay period, alarms are ignored.
During the 180 seconds confirmation period, the control panel enters the alarm state
immediately if a trigger from the same zone or from another zone is received, even if the
other zone is programmed for alarm delay and confirmation).
If, during the alarm confirmation period, no alarm is received, the ECD reestablishes the
quiescent condition.
Each detectors zone can be independently programmed for Alarm Delay and
Confirmation, (Alarm Verification).
The dependencies supported, as per EN 54-2, paragraph 7.12 are type A or type B,
depending on the configuration of the TSA-200X.
Note
i By default, the TSA-1000X is programmed for Two Zones Coincidence, and
NO Alarm Delay (No Alarm Verification).
To modify these and additional settings, the TSA-1000X must be
programmed accordingly.
Note
i See Routing cables into the ECD and maintaining the protection level,
page 25, for information about maintaining the protection level.
Note
i Do not operate the ECD outside the specified limits.
– Page 6 of 6 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
Note
i Relays' contacts are neither monitored nor limited.
Connect external protective circuitry to the relays' contacts circuitry.
– Page 7 of 7 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
– Page 8 of 8 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
TERM MEANING
Event A change which is detectable by the ECD and causes a response
– Page 9 of 9 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
5 Safety
Note
i Do not install commission, operate, or maintain this product before fully
reading this manual.
Note
i Whenever possible, disconnect all power sources (Line AND Battery) from
the product before performing any work on the ECD.
Note
i All installation, maintenance work and connecting/Disconnecting of the ECD
to power sources shall be performed according to applicable international,
national, regional and local codes and regulations, and the specific
instructions by the manufacturer.
Note
i All maintenance work should only be performed by trained, qualified and
certified personnel only.
Personnel that work on this equipment must fully read and comprehend this
manual.
Note
i Connection/Disconnection of the control panel to the mains should be
performed by QUALIFIED AND AUTHORIZED personnel ONLY
Note
i Disconnect all mains power wires (Line AND Neutral) to the circuit to which
you intent to connect the control panel, before actually connecting the mains
input power cable to the ECD.
Verify that the ECD enclosure is properly grounded before applying power.
– Page 10 of 10 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
Note
i Batteries require special care and safety precautions.
Refer to the batteries’ manufacturer literature for full information.
Note
i If batteries show any signs of swelling, rupture, fluid leakage, emission of
gases or fluids, heating or discoloration, or accumulation of corrosion
products near the terminals, OR YOU HEAR A HISSING SOUND, disconnect
the batteries and replace with a new pair of the appropriate type.
Follow the manufacturer’s instructions for cleaning the batteries and the enclosure, if
necessary
Dispose of batteries properly
Do not short-circuit, puncture, crush, or dispose of batteries in fire.
Do not connect batteries to makeshift chargers or power supply.
Do not expose the batteries or its terminals to mechanical stress
Handling of materials that leak from the batteries should be done by qualified personnel
using the appropriate protective gear, materials, and procedures.
If the ECD indicates a battery fault, check the wiring.
If necessary, replace the batteries
– Page 11 of 11 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
6 Access Levels
The control panel provides protection from unauthorized access of certain functions by
various access levels.
The TSA-1000X includes electronic and mechanical mechanisms that enact 4 access
levels, as per EN 12094-1 Annex A:
• Access level 1 – not limited, immediate access by operator
• Access level 2 (operator) – protected by an operator password. Provides all of
access level 1 functions and allows access to additional functions that are
performed on a regular basis by the system’s operator.
Note
i To avoid multiple PW key punching, there is a 3 minutes period after the
operator's PW has been entered, when the PW remains valid and effective,
which enables the operator to perform several tasks continuously without
entering the PW separately for each action.
(Since. In the password delay, the reentering of level 2 PW is not required,
level 2 access appears to be level 1 access, and level 3 appears to be level 2
access).
Note
i Access levels 2 and 3 have different passwords. This is not correlated to the
number of times the password has to be keyed in to access a certain menu.
Some sub-menus which are accessible at level 3, require that the level 3
(programmer) password be entered in a single menu, while others (for
additional safety) require the level 3 password to be entered in to different
menus.
– Page 12 of 12 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 201
7 Technical Specifications
7.1 Main Elements
The TSA-1000X comprises the following major elements:
• A metal enclosure with a hinged and mechanically lockable door. The door also
serves as the front panel
• PS40W Power Supply / Charger
• TSA-1000X Main Board (1 change polarity output, 5 level activation outputs, 4
inputs, 3 relays)
• TSA-1000XE8 expansion board (8 inputs)
• TSA-1000XEM083 expansion board (8 Open Collector outputs, 3 relays)
• TSA-1000XD Display board
• Flat Cable for connecting the Main Board to the Display board
• Two 12V 5AH batteries (Connected in series).
• Link wire for connecting the two batteries in series
• Two (single) wires for connecting the batteries to the PS "BATTERY" TBs.
• Flat Cable for connecting the PS to the main Board
• Two 4 wire cables for connecting the MB to the TSA-1000E8 card.
• Clamp On ferrite on AC input cable
• Clamp On ferrite on flat cable from MB to the display board.
Note
i The ports numbers appearing in the silkscreen layer of the PCB are the local
numbers.
– Page 13 of 13 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
POWER RATINGS
Mains Supply 230VAC+10% -15%, 50Hz, 0.6A TB line connection
Mains Supply Fuse 3.15A 250VAC 5x20mm glass Fast Blow Bussman S500-3.15-R or equiv.
Power Supply output rating, 27.5V±0.3V, 8 pin header
Total output current 1.5A electronic current limit (including charge current),
5V output rating 5V, ±0.2V 0.5A electronic current limit
Max Ripple Voltage 28V & Charger out: 320mV, 5V out: 80 mV
Battery Type Two 12V 5AH connected in series Yuasa NP 12-5 or equivalent
Battery Charge Voltage 27.3V±0.2V Modulated DC
Battery Charge Current 0.3A max.
– Page 14 of 14 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
MB INTERFACES
Fire Alarm Relay (1) contacts rating 48V DC, 1.5A, not monitored Dry contact SPDT
Fire Alarm Relay (2) contacts rating 48V DC, 1.5A, not monitored Dry contact SPDT
Fault Relay (3) contacts rating 48V DC, 1.5A, not monitored Dry contact SPDT NC when unpowered
OUTPUTS MB outputs are monitored
Outputs EOL 3.9 K ±5% Only required for MB outputs
MB output 1, Extinguisher Change Polarity, 1.4A electronic current limit OFF-6V. ON +24V, Change Polarity DC
Extinguisher release delay Programmable, 0-50 seconds, ±10% 5 seconds steps
Extinguisher release duration Programmable, 20-495 Seconds ±10% 5 seconds steps
Reset Inhibit period Programmable, 1-15 minutes 1 minute steps
MB out 2, Extinguishing Level Activation 24V DC, 0.8A electronic Flashes in Activated state. ON Modulated DC
Sounder /Strobe current limit in Released state,
– Page 15 of 15 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
E8 (inputs) Expansion card See above for inputs characteristics E8 card Inputs are monitored
Inputs 5 (Local 1) Abort
– Page 16 of 16 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 17 of 17 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
GENERAL
Input nominal quiescent voltage, 18.5v, 5.0mA Current Limit
current
Terminal block wire capacity 12-18 AWG
Max number of detectors per zone 32
Number of detection zones 3/4 Depends on input 4
programming
Total number of detectors 96/128, Depends on input 4
programming
CABLING SEE "INSTALLATION"
Table 1 Technical Specifications
Note
i Specifications are subject to change without prior notice.
– Page 18 of 18 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 19 of 19 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 20 of 20 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i For proper operation of extinguishing equipment proprietary and dedicated
adapters are required, as explained before.
Wiring openings knockouts allow for a bottom or top mains cable entry to the Control
Panel box, and a bottom, top, or back, low-voltage cables entry.
Two 12V, 5Ah sealed Lead Acid batteries are positioned at the bottom of the box.
Note
i Replace ONLY with a fuse of the same type, size and rating.
The PS40_W provides 27.5±0.3 V (referred to as the 24V supply rail) for powering the
ECD and for charging the battery, and has a +5V 0.5A output for powering the ECD MB
logic.
Max "24V" supply load current is 1.5A (including the 0.3A charging current)
The maximum battery charging current is 0.3A, electronically limited. The max allowed
load on the battery (when the mains power is disconnected or OFF) is 3A, limited by a
PTC.
Type and rating of batteries;
The ECD requires two 12V, 5AH sealed Lead Acid batteries, connected in series.
(Yuasa NP 5-12 or equivalent)
– Page 21 of 21 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 22 of 22 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
9 Installation
9.1 Pre-Installation Planning
Planning of quantity and location of detectors, push buttons, notification appliances and
extinguishing devices shall be done according to the local codes and regulations and in
accordance to the planning consultant's requirements.
9.1.1 Capacity Planning
Ensure that the total number of input initiating devices does not exceed local regulations
of the number of initiating devices per zone, area or other limitations. Ensure that the
number of zones satisfy the requirements of the consulting planner,
You can connect up to 5 sounders, beacons, or sounders-beacons to programmable
output 4 and the horn output.
Note
i Do not connect devices that should be supervised to the TSA-1000-EM083.
– Page 23 of 23 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i When installing a system at a site adjacent to high power cables, heavy
industrial machinery, or any kind of high electromagnetic fields, shielded
cables should be used and an EPI-3000 module should be connected to each
TSA-1000X.
9.2 Mounting
9.2.1 Environmental Limits
The TSA-1000X is a class A (-5°C to +40°C, RH max 95%) temperature range device.
Its environmental protective level is IP30.
Note
i See "installation instructions" for information about maintaining the protection
level.
Note
i Do not operate the ECD outside the specified limits.
– Page 24 of 24 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 25 of 25 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Warning
! Disconnect all power supplies, main and batteries before connecting or
disconnecting cables to the control panel.
– Page 26 of 26 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i Input and output lines must be wired as a single radial circuit, without stubs or
T- junctions.
Warning
! Disconnect all power supplies, (main and batteries) before connecting
or disconnecting cables to the control panel.
Verify that the system operates normally and that there are no zones in
alarm prior to connecting or replacing extinguishing devices.
Note
i Input and output lines must be wired as a single radial circuit, without stubs or
T-junctions.
Test all wiring and fix all faults before connecting the devices to the ECD.
Note
i Telefire's detectors can be activated for testing the system by bringing a
magnet close to a defined area of the detectors, simplifying testing.
– Page 27 of 27 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i Work on the ECD shall be performed when all power to the control power is
disconnected (AC and batteries disconnected).
Warning
! Do not connect the extinguishing activation circuits at this time. Use a
dummy load.
– Page 28 of 28 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 29 of 29 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 30 of 30 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i When extinguishing adapters are installed, addition of EOL resistors is not
required!
Note
i Please consult the manufacturer for solutions regarding activation of
additional extinguishing devices.
Note
i Connect a single extinguishing adaptor to the extinguishing activation output.
This adaptor will activate a single extinguishing device, except for the TLA-
44/4 that can activate up to 4 FirePro aerosol extinguishers.
Please consult the manufacturer for solutions regarding activations of
additional extinguishing devices
– Page 31 of 31 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 32 of 32 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i When connecting a TLA-3K module to programmable output 1 in a
TSA-1000X, verify that jumpers JP5 and JP6 are shorted.
When connecting a TLA-3K module to programmable all other outputs in a
TSA-1000X verify that jumpers JP1 and JP2 are shorted and jumpers JP4
and JP5 are shorted.
See above.
– Page 33 of 33 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 34 of 34 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i The term "outputs" in the following table refers to any or all outputs, including
Horn output, Fire Dialer output, FWRE output, programmable outputs, or
relays.
– Page 35 of 35 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 36 of 36 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
11.3 Keyboard
The keyboard has 7 keys. The table below details their functions.
Figure 16 Keyboard
– Page 37 of 37 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 38 of 38 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i As described in EN 12094-1, Para. 4.21.5, FOR TEST PURPOSES ONLY, a
“Terminate” switch Input is provided, enabling the termination the
extinguishing pulse.
Note
i DISCONNECT AND REMOVE THE "TERMINATE" SWITCH AND WIRES
AT THE END OF THE TEST
– Page 39 of 39 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 40 of 40 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Quiescent (Idle)
Power LED ON
Fig.8. scrolls right
– Page 41 of 41 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 42 of 42 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Pre-discharge warning (Ext. Stb/Sdr continues flash 1/1) RESET, DISABLE STILL
time INHIBITED
Delay LED ON
Status display: Count Down HOLD,ABORT effective
Hold LED ON
Status display Initial Delay time
Buzzer Ticks
Released LED ON
Status display: EEE
Delay LED OFF
– Page 43 of 43 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Reset Performed (Fault Relay, LEDs, buzzer remain IF events removed, then Alarm
ON)
ALL alarm indications OFF Outputs & Indications cleared
All Outputs and relays OFF* Fault LEDS, relay ON
– Page 44 of 44 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i This is the 1st stage of the automatic-release process.
Note
i This is the 2nd stage of the automatic release process,
– Page 45 of 45 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 46 of 46 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
To do this, using the ECD keyboard, select the menu>PG, press Enter. Type password>
and then perform RESET.
The ECD will then return to the quiescent state.
– Page 47 of 47 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
13 Operating Instructions
13.1 Default Operation
If the ECD is in the quiescent state, the Manual/Automatic switch is in the Automatic&
manual mode, then alarms in fire decision detection zones/Call points, or manual
activation, will start the extinguishing process according to the programmed
configuration and timing parameters. If the process was not interrupted by other inputs
or faults (i.e. Hold, Abort), the Extinguishant is released.
Note
i The pushbutton cover is yellow and is labeled “Extinguishant Release”
To activate the manual Extinguisher Release, forcibly pull the yellow hinged lid up to tear
the securing nylon tie wrap, and then press the Push Button.
This input is latched.
13.4 Abort
The operator can abort the extinguishing process (as long as the extinguisher is not
triggered yet), by asserting the "abort" input.
Asserting the Abort input (pressing the Abort switch), switches the Abort LED and the
Abort output ON, aborts the Extinguishing process, and prevents the ECD from entering
the Released state.
All active "Alarm" outputs and indications remain ON.
– Page 48 of 48 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
When "Abort" is pressed, most of the Extinguishing Group Members are inhibited: The
Extinguishing strobe/sounder, the extinguisher output, "Extinguisher Activated" sign, and
the Released output are OFF until the Abort state is removed.
Note
i The 1st and 2nd stage relays are not affected.
13.5 Hold
Sometimes, when the alarm is triggered and the extinguishing imminent, some additional
delay is required before release. This can be achieved by pressing Hold.
Activating the hold input (pressing its PB) switches the Hold LED and Output ON, stops
the Delay Count down, and the Pre Discharge Warning Time and its display are
reinitialized to 30 seconds. In the default case,
The countdown starts again when the Hold is deactivated, i.e. when the switch is
released.
During the Pre Discharge Warning time, the extinguishing strobe sounder pulses one
second ON and one second OFF.
If Hold is activated during that time, the buzzer sounds the Fault signal (1 second ON, 4
seconds OFF), and so does the Extinguishing Sounder/Strobe.
This is done so people are informed audibly that Hold was activated.
This input has no effect after Extinguishant release has started.
Note
i This is to be connected and used for TEST PURPOSES ONLY!
– Page 49 of 49 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i Disconnect and remove at the end of the test.
Terminate pulse as quickly as possible, to avoid depleting the Extinguishant.
Note
i This input is tested by the ECD for correct logic transition only, AND IS NOT
MONITORED OTHERWISE
13.9 Reset
Pressing the Reset key resets the ECD if it is in the Quiescent, Alarm and Preactivated
states. From the start of the Activated state to the end of the Reset Inhibit period, reset is
not possible.
If all events and problems are cleared and resolved, reset (when enabled) reestablishes
the quiescent state, with one exception.
After the reset inhibit period has elapsed, reset will change the state of the ECD as
described earlier and only after entering and exiting the programming mode, and then
pressing the reset key again(if all issues are resolved. i.e. no events) will the Quiescent
state be established.
13.10 Silencing
The Control Panel (ECD) has a FIRE ALARM Sounder output referred to as the Horn,
which is the MB local output 6.
(See remark about numbering of ports)
This output operates on ANY alarm signal, even if the trigger source does not belong to
the extinguishing decision group. (i.e. will not cause the Preactivated or activated state,
and will not cause the extinguisher to operate)
Silencing of the FIRE ALARM sounder Main Board (MB) local output 6, typically a Horn,
is possible at access level 2, as it requires the Operator's password.
However, the EN 12094-1 Alarm Device (4.3.2 c), which is referred to in this Technical
Manual as the Extinguishing Sounder/Strobe, MB local output No. 2, operates when the
ECD enters the Activated state. The Extinguishing Sounder Strobe flashes in the Pre
Discharge Warning Time, and is continuously ON in the Released state.
It cannot be silenced from the start of the Activated state until the end of the Reset
Inhibit period, at ANY access level, as required by this standard! If the Fire Alarm Horn
(Output 6) is ON, it can be silenced by pressing the Silence key of the keyboard. Also, all
outputs programmed as silenceable are switched OFF. The internal buzzer is silenced,
too
Any Alarm event will re-sound the Horn.
The silenced devices can resound again if the Silence key is pressed again for a longer
period.
The Silenced condition is indicated by a dedicated LED in the General Display area.
The Extinguishing strobe/sounder cannot be silenced.
Silencing is possible when Reset is enabled, and is inhibited when reset is inhibited
– Page 50 of 50 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
13.11 Disablement
It is sometimes necessary to disable certain functions or interfaces of the ECD. (For
example, if some welding is done near detectors, the ECD might be activated, and it is
required to disable the affected zones, and rely on Manual Activation for protection
against fire)
The control panel will ignore alarms from disabled zones and will not activate disabled
outputs or relays.
Programming the Disablement is possible only when Reset is enabled.
Note
i Disabling the Extinguisher also disables the outputs and relays associated
with it, (i.e. the Fire Extinguishing Group).
Flow Switch Actuation: Even if the Extinguisher is disabled, If the FS is actuated, all
the appropriate alarm, outputs, relays, and released state outputs and indications are
ON. (Except the extinguisher output)
13.12 Fault
The ECD monitors most of its inputs and outputs for faults.
When a fault is detected, the following occurs:
Flashing fault LEDs: general fault LED, zone fault LED (if applicable), Ext, Zone LED (if
applicable)
Also, the specific fault LED in the general area left column is ON, the Fault status
Led is On, the status displays the zone # where the fault occurred and the fault details.
The buzzer sounds the Fault signal (1-4 ON-OFF ratio)
Fault relays are activated (default RL3)
Correct and repair faults when they are discovered.
13.12.1 FWRE (Fault Dialer) Output
This is an INPUT PORT, USED AS AN OUTPUT. It is used as a FWRE (Fault Warning
Routing Equipment, or fault dialer) connection as specified in EN 54-2.
During normal operation, the output is powered. When a fault occurs in the ECD, the
power to this output is OFF.
13.13 Supervisory
An Input programmed as “Supervisory” will switch ON the "Supervisory" LED when
triggered.
This is used to indicate that an event has occurred, which is neither an alarm nor a fault,
but which needs some action to be resolved.
Supervisory events do not latch – at the end of the event; the system returns to the
previous state without intervention.
In the TSA-1000X, only input 4 can be programmed as Supervisory.
Also, output 4 can be configured as "Supervisory" which will switch ON when a
Supervisory input is triggered.
– Page 51 of 51 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
13.14 Auxiliary
When a fault occurs in an output which was configured as "General, Not Silenceable",
the Auxiliary Fault LED is switched ON.
In the TSA-1000X, this refers, in the default configuration, to output 4 only.
13.17 Evacuation
If it is necessary to activate the Fire Alarm Sounder (Horn) output ONLY, without
activating other outputs and/or relays (For example, for Evacuation drill), the Evacuation
function, which switches ON (only) the General alarm output (out 4), The Alarm Dialer
and the Fire Alarm Sounder (Horn), can be activated at access level 2 (i.e. a password is
required) using the keyboard.
Note
i No Other output, and NO relay are activated.
– Page 52 of 52 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 53 of 53 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 54 of 54 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 55 of 55 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 56 of 56 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
• Press the Menu key to move the cursor to select the event type with the LEDs to the
right of the Status display
• Press the Menu key to move the cursor to select the delay. Each LED in this field
represents a delay of 5 seconds
• Press the Menu key to move the cursor to select verification for input devices or
silenced for output devices
• Press the Menu key to move the cursor to select the input zones for the matrix
(alarm LED of the in the zone display area)
– Page 57 of 57 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
During relay programming the left digit will be r (relay). The center digit represents the
relay number. The rightmost digit represents the relay's operating mode (G – General; A
– logical "And" of selected inputs, b – logical "Or" of selected inputs).
– Page 58 of 58 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i Some of the input types may have additional fields such as verification and
delay. Refer to the appropriate sections for details.
14.9.1 Zones
Zones 1, 2, and 3 can only be configured for delay (0 – 50 seconds) and for verification
– Page 59 of 59 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Input 4 can be configured as a detector zone (d), manual alarm call point (P). It can be
configured as a supervisory or alarm input, and can be configured for delay (0 – 50
seconds) and for verification
14.9.2 Fixed Function Inputs
Note
i Abort, Hold, Flow Switch, Pressure Switch, Manuel/Automatic and Manual
Only Mode Key Switch, Extinguishant Release Push Button are Fixed-
function inputs, and cannot be modified.
– Page 60 of 60 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 61 of 61 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 62 of 62 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 63 of 63 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 64 of 64 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Page through the menus until the display shows ALC. Press Enter. The system will
request the password (PAS). Enter the password (default 2222) and press Enter. The
display will show the alarm count.
– Page 65 of 65 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Warning
! When reestablishing the default configuration, all existing system
configuration and programming (including passwords, activation
conditions and matrices) are reset to the factory default values.
Disconnect all extinguishing devices and other critical activation
outputs before reestablishing the factory default configuration.
Reconfigure the panel for the site's specific requirements and verify
that the ECD is in the quiescent state and properly configured before
reconnecting any extinguishers or other critical outputs.
– Page 66 of 66 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
16 Commissioning
• Verify that ALL POWER SOURCES are disconnected
• Verify that THE EXTINGUISHER IS DISCONNECTED (both wires), connect
DUMMY extinguisher load
• Verify that all required interfaces are connected. Verify correct wiring
• Verify presence of required EOL resistors
• Connect mains and battery
• Fix all faults
• When ALL faults are fixed and ECD is in the quiescent state, configure and program
the ECD as required.
• Update site specific data and date and time
• Change the level 2 and 3 passwords
• Verify that the POWER LED lit and that the character 8 scrolls form left to right in
the alphanumeric display.
• Perform a full Field Test,
• Perform an activation test
• Test and verify correct operation from detectors and from manual activation
• Verify that the ECD lock and switch keys are available and accessible to operators
• Attach the required documentation to or near the Control Panel
• Disconnect ALL power, Remove dummy load, connect the extinguisher output
• Connect power
• Verify that the ECD is in the quiescent state
16.1.1 Additional System Documentation
In different countries and according to some CP installation regulations, it is sometimes
required to place a document containing condensed system information and operating
instructions on, or near the CP.
It is recommended to attach the condensed document to the system’s front panel, or
frame it and place it in a prominent, highly visible position nearby:
It is recommended that the document shall at least contain the following;
• Actions to be taken upon events of alarm or fault by the operators
• A list of areas/zones as installed in the protected premises, and blank spaces for
their details and description
• Text referring to The name, address and phone number of the service
representative, and blank spaces to fill in the details after installation
• Text referring to the name, address and phone number of the Installing
representative, and blank spaces to fill in the details after installation.
• Document issue number and date
• If the document is not attached to the CP front panel, a note at the bottom stating
that it shall be framed and placed near the CP for ready reference
A sample form is attached at the end of this manual.
– Page 67 of 67 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
17 Maintenance
No specific maintenance is required for the TSA100X.
Keep the TSA100X clean and dry. If necessary, clean the outside of the enclosure with a
slightly damp cloth.
The batteries should be tested and replaced according to the instructions of the battery's
manufacturer.
If the batteries show any signs of swelling, leakage or corrosion, or the ECD indicates a
battery fault, replace with a new set.
Maintenance routine:
Verify that the field wires are fully inserted into the TB, and no wires are broken.
Tighten the TBs, if necessary
Verify ECD is in the quiescent condition
– Page 68 of 68 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
18 Routine Testing
The TSA-100X shall be tested weekly as specified in the next paragraph.
The system should be fully tested at least twice a year, or as required by national and/or
local fire codes. All devices, system wiring and component functions should be tested
and maintained. These inspections should be performed in addition to the routine
maintenance activities such as cleaning the detectors (which should be performed in
accordance with Telefire’s instructions).
Perform a Field Test of each zone.
Maintenance and test actions shall be conducted by a company or service technician
authorized by Telefire.
Records of all inspection and maintenance activities should be kept.
Note
i Testing shall be performed by authorized service personnel that are
employed by authorized companies.
– Page 69 of 69 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
19 Troubleshooting
Note
i The # symbol in sections to represent the number of the input, output' relay'
expansion module, etc.
– – – Field Test
V # Zone # verification
9 ┌┘ Manual–only switch was activated
5 A Abort switch was activated
6 H Hold (H) was activated
u
# # Input ## disabled
u
# #. Output ## disabled
U
r # Relay # is disabled
E E E Extinguishing active
E 1. A Extinguishing Activated – replace extinguishant
– Page 70 of 70 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 71 of 71 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
Note
i Ground leakage faults may affect output fault display. Resolve the ground
fault issues first.
– Page 72 of 72 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
– Page 73 of 73 –
TSA-1000X
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.12 April 2012
20 Certification
Telefire’s TSA-1000X has the following certification and approvals:
• EN 54-2 and EN 54-4 Certified
• SI 1220 part two Certified
• EN 12094-1 Certified
• CE Marked
• GOST Compliant
20.1 CE Label
– Page 74 of 74 –
TSA-1000X Instructions for Immediate Action
Normal "Power" LED is ON and the digital display scrolls a figure 8 from
left to right.
Alarm Condition "Alarm" LEDs, internal buzzer and the Alarm Sounder are ON.
Action Take appropriate actions in accordance with the pertinent
instructions at your site, and notify the relevant entities.
Silencing
To silence the Alarm Sounder press "Silence/Resound" key.
Return to After taking the actions detailed above, restore the system to
Normal Operation normal operation by pressing the "Reset" key.
from Alarm
Automatic Extinguishing is performed automatically, without human
Extinguishing intervention (Except for triggering by Manual Release).
After the extinguishing pulse ends, the TSA-1000 enters the
"Extinguishing Fault" state.
Call the service representative listed below if the extinguishers
were activated, to replenish the extinguishant, restore extinguishing
capability and return to normal operation.
Fault Condition The General and specific "Fault" LEDs turns on, and the internal
buzzer sounds.
Action Take appropriate actions in accordance with the pertinent
instructions at your site.
Resolving the fault will automatically restore the system to normal
operating conditions.
Silencing To silence the internal buzzer press the "Buzzer Off" key.
Please refer to the TSA-1000X Technical Manual for further details.
Zone Description
1
2
3
4
Service Representative
Name:______________ ____________________________________________
Address:_____ ___________________________________________________
Phone:__________________________________________________________
Installing Representative:
Name:______________ __________________________________________________________________
Address:_________ ____________________________________________________________________
Phone:__________ _____________________________________________________________________
This document shall be framed, details filled, and placed adjacent to the control unit