SAUDIARAMCO.

NOTES:
1 2 3 3' 4 4' 5 1. ALL DIMENSIONS ARE IN MILLIMETERS AND
ELEVATIONS ARE IN METERS UNLESS OTHERWISE
NOTED.

22000 2.CONDENSATE DRAIN PIPE SIZE SHALL BE AS


VENDOR RECOMMENDATIONS.

7000 4500 5250 5250 3.TEST POINT FOR THE SMOKE DETECTOR SHALL BE
PROVIDED IN THE HVAC DUCT TO ENABLE TESTING

OF
AIR OF THE DUCT SMOKE DETECTORS.
LOCK-4

CONSENT
026 4.TYPE-I KITCHEN HOOD SHALL BE PROVIDED AND
LOCKER WORKSTATION CONNECTED TO THE EXHAUST FAN IN THE KITCHEN.
ROOM OFFICE 2 JAN
5.SMOKE DETECTORS SHALL BE INSTALLED, TESTED &
EF-3 027 025 024 023 MAINTAINED IN ACCORDANCE WITH NFPA 72, NATIONAL
FIRE ALARM & SIGNAL CODE
BDD

TTEN
A

250x200
ECD-2
SCD-21
(TYP-4)

WRI
200x200
SCD-22 200x200 EF-2
250x250

4500

THE
150x150
ECD-3
SCD-19
150x150 BDD TOILET
FSD-34 SCD-20
EDH-6
(TYP-4) 022

THOUT
250x250

300x300
250x200

200x200
D/G
RCD-15
RCD-16
VAV-6 LEGEND/ABBREVIATIONS
SCD-23 FSD-29

WI
FSD-30
B AIR
ACCU AIR COOLED CONDENSING UNIT
FSD-31

NG
200x200 LOCK-3 BDD BACK DRAFT DAMPER
SCD-24 400x300 400x250

2500

DRAWI
FSD-28 021 DDC DIRECT DIGITAL CONTROL
(TYP-2) 200x200
RCD-19 200x200
SCD-26 FSD-33 SCD-18 DG DOOR GRILLE
700x300 BELL DSD DUCT SMOKE DETECTOR
MOUTH FSD-32
FSD-27

S
ECD EXHAUST CEILING DIFFUSER

250x200
C

THI
200x200 CORRIDOR-3
SITTING AREA/

700x300
030 EDH ELECTRICAL DUCT HEATER
COMPUTER LAB

FSD-26
EF EXHAUST FAN
KITCHEN

FROM
028
020 FGL FINISH GRADE LEVEL
300x200

4500
RCD-17 FSD FIRE SMOKE DAMPER

300x250
(TYP-2) 300x250 SCD-17 150x150 DUCT
(TYP-2) CONNECTED TO
VAV-5 FSD-25 250x200 H2S HYDROGEN SULFIDE

NED
KITCHEN HOOD
CORRIDOR-2 BDD LEL LOWER EXPLOSION LIMIT
FSD-24

OBTAI
200x200 RCD-14 SCD-16
EDH-5 MD MOTORIZED DAMPER
029 (TYP-3)
400x250 ECD-1 EF-1 PACU PACKAGED AIR CONDITIONING UNIT
250x200
PSU PRECISION SPLIT TYPE UNIT
D

BE
250x250 VAV-4 RCD-13 RAG RETURN AIR GRILLE

EDH-4 (TYP-3) RCD RETURN CEILING DIFFUSER


PRAYER

PART,SHALL
SHIFT RCD-12 ROOM SAG SUPPLY AIR GRILLE
SUPERVISOR SCD-14 CONFERENCE
RCD-18 FSD-23 SCD-15 019 SCD SUPPLY CEILING DIFFUSER

4500
017 ROOM
BELL (TYP-3)
500x250 SJD SUPPLY JET DIFFUSER
MOUTH 018

FSD-22
700x400

700x400
200x200 STL SAND TRAP LOUVER
LOBBY/WAITING
VAV VARIABLE AIR VOLUME
014
DSO OFFICE RCD-11 VOLUME DAMPER

N
I
200x200
SCD-13
016 MOTORIZED DAMPER
E

FULL,OR
150x150
SCD-11
FIRE SMOKE DAMPER
(TYP-2)
HYDROGEN SULFIDE

LOWER EXPLOSION LIMIT


700x450 250x250
36500

4500

4500
SCD-10
ACCESS DOOR

N
300x250 AIR

I
FSD-21
LOCK-2

250x200
OPS RCD-9 SCD-12 REFERENCE DRAWINGS

ON
FOREMAN 300x300 RCD-10 015
DESCRIPTIONS DRAWING NO.

REPRODUCTI
013 (TYP-2) 150x200
DRAWING CONTROL FOR EWO-16S062A-001 BD-784382
VAV-3
300x300 EDH-3 CONSTRUCTION SCOPE OF WORK BE-784383
FSD-20
HVAC EQUIPMENT SCHEDULE BA-784390-001
F

200x200

150x200
HVAC EQUIPMENT SCHEDULE BA-784391-001
SCD-9
OPS HVAC AIR FLOW DIAGRAM BA-784392-001
CLERK RCD-7
STORE HVAC CONTROL DIAGRAM BA-784393-001
RCD-8

SAUDIARAMCO.NO
012 011 HVAC SEQUENCE OF OPERATION BA-784394-001
400x250 SCD-8
4500

4500
HVAC SECTIONS BA-784395-001

FSD-19
HVAC DETAILS BA-784396-001
SCD-25
BELL SCD-7

800x450
FS FOREMAN (TYP-2) HVAC DETAILS BA-975829-001
MOUTH

150x200
HTC INSTRUMENT LOCATION PLAN BA-203532-001
009 010
200x150
SCD-6 RCD-6 KEY PLAN
G
700x500

200x200
TYP-2)
INE
ON L
SSI
MI
RANS
NG T
STI
EXI
309.174

RCD-5 309.503

OF
EXISTING TRANSMISSION LINE

ROLL-UP 309.542
309.684
(

350x200 200x150 DOOR SPHA


LT R
OAD

RAMP UP NG A
STI
EXI

FS SUPERVISOR
4500

PROPERTY
350x200 VAV-2 FSD-18 250x200 NG A
STI
EXI
SPHA
LT R
OAD

007

200x150
FSD-17
EXISTING FENCE

900x450
VAV-1

ROAD
700x600

EDH-2 FS CUBICLE

ASPHALT
EDH-1 EXISTING LAYDOWN AREA

THIS SITE

NG
BELL RCD-4 GATE

STI
RCD-3

EXI
MOUTH 008 (TYP-2)
EXISTING FENCE

SCD-4 300x250
300x250
SCD-5

GATE
400x250
(TYP-2)

SOLE
FENCE
FSD-14 FSD-15
EXISTING PARKING AREA

FENCE

NG
H

STI
NORTH

EXI
LP LP LP

NG
STI
FSD-13

400x350

EXI
EXISTING PARKING AREA

200x200 FSD-16 FH

FSD-12 400x250

GATE
GATE

CORRIDOR-1
2500

MAINTENANCE

FENCE
FENCE
LP LP
SOUTH GHAWAR WELL SERVICE DIVISION

BELL
EXISTING

THE
NG
NG
SITE OFFICE NORTH HARD

STI
STI
OSB BUILDING

SCD-2 WORKSHOP

EXI
EXI

NG A SPHALT ROAD
MOUTH 005 N
SCD-3
LP

AIR FSD-9 200x200 EXISTING

FENCE
SITE OFFICE

LOCK-1 RCD-2 300x200 001

STI

NG
STI
EXI

EXI
EXISTING FENCE

FSD-11 400x250

ARE
006

FSD-7
FSD-5
850x600

900x550

200x150
EXISTING FENCE

FSD-10 250x200 300x250

N
HEREI
300x250
FSD-8
FSD-6

300x200
SAG-2 SAG-1 300x250 SJD-1
RCD-1 300x250 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0

550x400
RAG-3 RAG-2 (TYP-4)
300x250
4500

LIBRARY
PSU-1 METERS
COMM.
350x150

NED
004
ROOM SCALE: 1 :75M

CONTAI
003
DDC PANEL STL-2 SAND TRAP
UP UP
650

RAG-1 LOUVER 350x250 REVISION VALIDATION


FLOOR FSD-4
SCD-1 @ 2.4M HIGH FROM
DRAIN FSD-3 200x200
FGL THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

J REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:


FSD-1

900x600

300 800

ON
FSD-2 DSD-4 16S062A-001
MD-2

NFORMATI
900x600 DSD-2 RAD

2000
2150

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


MD-1 550x400
325

STL-1 SAND TRAP ELECT. (DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)


ACCU-1

LEL
LOUVER 1000x600

H2S
LEL LEL ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

@ 2.4M HIGH FROM DSD-1 002 AE/AIT AE/AIT


ATB ELS KWS
01/16/18 01/16/18 01/30/18
FGL
LEL
H2S

DSD-3 0765D 0765C REV.NO. DATE REVISION DESCRIPTION


LEL LEL RETURN PLENUM

I
AE/AIT AE/AIT 400x1500x700 H2S H2S 00 01/16/18 ISSUED FOR CONSTRUCTION
2200

3390

AE/AIT AE/AIT

THE
0765B 0765A 500x350 SAD JOB ORDER/EWO NO.
0766C THIS REVISION IS NOT TO BE USED FOR
550x400 0766D
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED
H2S H2S PACU-1 SEEPAGE
SAUDI ARABIAN OIL COMPANY

AND
AE/AIT AE/AIT PIT
0766B 0766A CONDENSATE CONDENSATE DRAWING TYPE

RETURN PLENUM BOX


DRAIN PIPE DRAIN PIPE HVAC FLOOR PLAN HVA

NG
1000x700x2000 SEEPAGE
B SUPPLY PLENUM
700x1000x600 NORTH-OPERATION SUPPORT BUILDING

DRAWI
PIT BA-784395 PACU-2
1535 4437
SH 001
1650 4050 HARADH GAS GATHERING MANIFOLD
A HARADH SAUDI ARABIA
BA-784395

S
HVAC FLOOR PLAN PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
SH 001

SCALE 1:75 M D83 K BA-784389 001 00


Saudi Aramco 2615 ENG. (05/05)

CONFIDENTIAL VECTOR CADD-01


SAUDIARAMCO.
NOTES:

PACKAGE AIR CONDITIONING UNIT SCHEDULE 1.ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE NOTED.
COOLING COIL
OUT SUPPLY FAN FILTER SECTION CONDENSER COMPRESSOR POWER SUPPLY
AIR MANUFACTURER
AMBIENT SIDE TOTAL
EQPT. TOTAL SEN. MAKE/MODEL OR
SERVING TEMP. AIR EER/IEER REMARKS
NO. COIL FACE RLA LRA INPUT MCA MOCP
CAP. E.S.P. PD PD CAP. CAP. E.A.T. E.A.T. L.A.T. L.A.T. FAN APPROVED EQUAL
°F (CFM) PRE-FILTER FINAL VELOCITY QTY. KW QTY (EACH) (EACH) KW V PH HZ

OF
KW DRIVE TYPE DB °F WB °F DB °F WB °F TYPE TYPE
(CFM) (In of Wg) (IN W.G.) FILTER (IN W.G.) MBH MBH AMPS AMPS
(m/s)
2" THICK

CONSENT
PROPELLER HERMETIC
OFFICE WASHABLE
PACU-1 125 1812 7290 2.0 7.5 BELT FC 0.5 BAG 1.0 256.11 185.37 2.5 80.60 66.78 55.00 54.28 WITH DIRECT 2 2.68 2 30.1 225 36.97 87.6 120 480 3 60 9.8/9.9 ZAMIL/PAX030
AREA ALUMINUM
SCROLL
MOTOR
2" THICK PROPELLER
MAINTENANCE HERMETIC
PACU-2 125 181 2406 2.0 2.2 BELT FC WASHABLE 0.5 BAG 1.0 59.74 57.62 2.5 77.48 63.11 55.00 54.58 WITH DIRECT 2 0.53 2 10 75 12.7 28 40 480 3 60 11.0/11.2 ZAMIL/PAX008
WORKSHOP SCROLL
ALUMINUM MOTOR LEGEND

TTEN
NOTE 1 : PACU SHALL HAVE COPPER FINS ON COPPER COILS FOR EVAPORATOR. ACCU - AIR COOLED CONDENSING UNIT

CAP - CAPACITY

WRI
CFM - CUBIC FEET PER MINUTE
EXHAUST FAN SCHEDULE VAV SCHEDULE
DB - DRY BULB

THE
POWER SUPPLY AIR QUANTITY
CAPACITY ESP MOTOR FAN RPM MANUFACTURER MAKE/ MAXIMUM
SERVING DESIGNATION TYPE DRIVE REMARKS TAG NO LOCATION SERVING (CFM) REMARKS EAT - ENTERING AIR TEMPERATURE
(CFM) (IN W.G.) (HP) (MAX) PRESSURE
V/PH/HZ MODEL OR APPROVED EQUAL ROOM NO MAX. MIN. DROP (IN W.G.)
ECD - EXHAUST CEILING DIFFUSER

THOUT
KITCHEN EF-1 WALL MOUNTED 313 0.25 DIRECT 0.2 1550 230/1/60 GREENHECK/CW-080 SEE NOTES BELOW
FS FOREMAN & UNIT COMPLETE EDH - ELECTRIC DUCT HEATER
VAV-1 FS SUPERVISOR 388 310 50
TOILET EF-2 WALL MOUNTED 321 0.25 DIRECT 0.2 1550 230/1/60 GREENHECK/CW-080 SEE NOTES BELOW FS SUPERVISOR W/THERMOSTAT
EER - ENERGY EFFICIENCY RATIO

WI
LOCKER ROOM EF-3 WALL MOUNTED 251 0.25 DIRECT 0.2 1550 230/1/60 GREENHECK/CW-080 SEE NOTES BELOW
UNIT COMPLETE EF - EXHAUST FAN
VAV-2 FS CUBICLE FS CUBICLE & HTC 415 332 50
W/THERMOSTAT

NG
EQPT - EQUIPMENT

DRAWI
NOTE 1 : EXHAUST FAN COMPLETE WITH ACCESSORIES SWITCH NEMA-1 ALUMINUM, BACK DRAFT DAMPERS, BIRD SCREEN DISCONNECT SWITCH AND AMCA RATED.
CLERK, OPS FOREMAN, UNIT COMPLETE ESP - EXTERNAL STATIC PRESSURE
VAV-3 OPS FOREMAN 576 460 50
NOTE 2 : ALL FANS SHALL BE PROVIDED WITH STARTERS WITH OPERATED SOLENOID RATED FOR 24 VAC AND THEIR CONTACTS FOR THE AMCA REQUIREMENT OF THE FANS. DSO W/THERMOSTAT
°F - DEGREE FAHRENHEIT
NOTE 3 : ALL EXHAUST FANS SHALL BE DIRECT DRIVE TYPE.
SITTING AREA, SHIFT UNIT COMPLETE FPM - FEET PER MINUTE
VAV-4 SITTING AREA 630 504

S
50

THI
SUPERVISOR W/THERMOSTAT
HP - HORSE POWER

CONFERENCE ROOM UNIT COMPLETE


ELECTRIC DUCT HEATER SCHEDULE VAV-5 CONFERENCE ROOM 1143 915 50 HZ - HERTZ

FROM
PRAYER ROOM W/THERMOSTAT
IEER - INTEGRATED ENERGY EFFICIENCY RATIO
POWER SUPPLY
SERVING MANUFACTURER MAKE/ WORKSTATION UNIT COMPLETE
AIR FLOW WIDTH HEIGHT VAV-6 WORKSTATION 841 672
EQUIP NO. CAPACITY REMARKS 50 KW - KILOWATT
ROOM NO MODEL OR APPROVED EQUAL OFFICE W/THERMOSTAT
(CFM) (MM) (MM)

NED
(KW) VOLTS Hz
PH LAT - LEAVING AIR TEMPERATURE
NOTE: 1. ALL VAV SHALL BE BY-PASS TYPE.

OBTAI
FS FOREMAN & TUTCO INC. / DHB
EDH-1 388 1.2 230 1 60 250 250 SEE BELOW NOTE-1&2 NO - NUMBER
FS SUPERVISOR
2. POWER SUPPLY FOR VAV SHALL BE SUPPLIED THROUGH DDC PANEL.
PACU - PACKAGE AIR CONDITIONING UNIT
EDH-2 FS CUBICLE & HTC 415 1.2 230 1 60 250 250 TUTCO INC. / DHB SEE BELOW NOTE-1&2
3. COORDINATE WITH DDC VENDOR FOR VAV POWER SUPPLY.
PH - PHASE
CLERK, OPS FOREMAN,

BE
EDH-3 576 1.5 230 1 60 350 250 TUTCO INC. / DHB SEE BELOW NOTE-1&2
DSO PSU - PRECISION SPLIT TYPE UNIT
SITTING AREA, SHIFT

PART,SHALL
EDH-4 630 1.5 230 1 60 350 200 TUTCO INC. / DHB SEE BELOW NOTE-1&2 -
SUPERVISE ROOM QTY QUANTITY

CONFERENCE ROOM, PRAYER TUTCO INC. / DHB RAG - RETURN AIR GRILLE
EDH-5 1143 2.0 230 1 60 400 300 SEE BELOW NOTE-1&2
ROOM
RCD - RETURN CEILING DIFFUSER
EDH-6 WORKSTATION, OFFICE 841 1.5 230 1 60 350 250 TUTCO INC. / DHB SEE BELOW NOTE-1&2
RH - RELATIVE HUMIDITY

NOTE: 1. DUCT HEATERS SHALL BE UL LISTED AND APPROVED. SAG - SUPPLY AIR GRILLE

N
I
2. CONTROL BOX SHALL BE LOCATED ON HEATER. SCD - SUPPLY CEILING DIFFUSER

FULL,OR
IN W.G. - INCHES OF WATER GAGE

V - VOLTS
FAN COIL UNIT SCHEDULE DESIGN INDOOR=72°F
VAV - VARIABLE AIR VOLUME

FAN CAP COOLING FAN MOTOR MANUFACTURE NAME & WB - WET BULB
TAG NO. QTY TYPE V PH HZ MINIMUM EER REMARKS
MODEL OR APPROVED EQUAL

N
(CFM) CAP. (M.BTU/HR) POWER (KW)

I ON
PSU-1 01 WALL MOUNTED 294 6.53 0.15 LIEBERT/DME 027E 230 1 60 11.5 STAND-BY, PRECISION UNIT

REPRODUCTI
REFERENCE DRAWINGS
DESCRIPTIONS DRAWING NO.

DRAWING CONTROL FOR EWO-16S062A-001 BD-784382


AIR COOLED CONDENSING UNIT SCHEDULE AMBIENT TEMP.= 125°F CONSTRUCTION SCOPE OF WORK BE-784383
HVAC FLOOR PLAN BA-784389-001
COMPRESSOR MANUFACTURE NAME &
TAG NO. QTY TYPE CAPACITY REFRIGERANT MOCP MCA FLA V PH HZ MINIMUM EER REMARKS
TYPE MODEL OR APPROVED EQUAL HVAC EQUIPMENT SCHEDULE BA-784391-001

SAUDIARAMCO.NO
HVAC AIR FLOW DIAGRAM BA-784392-001
SCROLL MATCHING
ACCU-1 01 FLOOR MOUNTED R-407C 30 18.4 15.4 230 1 60 LIEBERT / PFH027A-PH7 11.5 STAND-BY HVAC CONTROL DIAGRAM BA-784393-001
HERMITICALLY SEALED TO PSU-1
HVAC SEQUENCE OF OPERATION BA-784394-001
HVAC SECTIONS BA-784395-001
HVAC DETAILS BA-784396-001
HVAC DETAILS BA-975829-001

DESIGN PARAMETERS

OF
PACU-1 PACU-2 PSU-1 / ACCU-1

PROPERTY
(STAND-BY)

CONDITION-1 CONDITION-2 CONDITION-1 CONDITION-2 CONDITION-1

DESIGN OUTSIDE TEMPERATURE, DB/WB °F (SUMMER) 113/72 97/77 113/72 97/77 113/72

SOLE
DESIGN OUTSIDE TEMPERATURE, DB °F (WINTER) 41 41 41 41 41

DESIGN INDOOR TEMPERATURE, DB °F - RH % (OFFICE, ELECTRICAL ROOM, 75-50% 75-50% - - -

THE
AIR LOCK, LOCKERS, STORAGE ROOMS, KITCHEN & TOILET)

ARE
DESIGN INDOOR TEMPERATURE, DB °F - RH % (WORKSHOP) - - 75-50% 75-50% -

DESIGN INDOOR TEMPERATURE, DB °F - RH % (COMMUNICATION ROOM) 72-50% 72-50% - - 72-50%

N
HEREI
2
WALL COMPONENTS "U" FACTOR TOTAL, BTU/HR, °F, FT 0.055 0.055 0.055 0.055 0.055

2
ROOF COMPONENTS "U" FACTOR TOTAL, BTU/HR, °F, FT 0.057 0.057 0.063 0.057 0.057

NED
2
GLASS "U" FACTOR TOTAL, BTU/HR, °F, FT 0.1 0.1 0.1 0.1 0.01 SCALE:

CONTAI
AIR QUANTITY, CFM 7278 6798 2406 2059 305
REVISION VALIDATION

OUTSIDE AIR, CFM 7290 1812 181 181 15 THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
TOTAL SENSIBLE COOLING LOAD, BTU/HR 226707 185368 57619 90925 6692 16S062A-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
LIGHTING 40379 40379 8558 8558 2094
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

INTERNAL SENSIBLE HEAT GAIN, EQUIPMENT 41287 41287 15013 15013 2252 ATB ELS KWS
01/16/18 01/16/18 01/30/18
BTU/HR
REV.NO. DATE REVISION DESCRIPTION
PEOPLE 18875 18875 1815 1815 0

I
00 01/16/18 ISSUED FOR CONSTRUCTION

THE
OTHERS 54748 44292 25872 2 1819 JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

EXTERNAL SENSIBLE HEAT GAIN, BTU/HR 71418 40535 6361 3277 527
SAUDI ARABIAN OIL COMPANY

AND
TOTAL LATENT COOLING LOAD, BTU/HR 3299 70743 2119 8777 -84 DRAWING TYPE

HVAC EQUIPMENT SCHEDULE SCH

NG
EXTERNAL LATENT HEAT GAIN, BTU/HR -11001 56443 -1016 5642 -84
NORTH-OPERATION SUPPORT BUILDING

DRAWI
INTERNAL LATENT HEAT GAIN, BTU/HR 14300 14300 3135 3135 0 HARADH GAS GATHERING MANIFOLD

HARADH SAUDI ARABIA


GRAND TOTAL COOLING LOAD, BTU/HR 230007 256111 59738 55929 6608

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784390 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


SAUDIARAMCO.
NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE NOTED.
SUPPLY AIR DEVICES COMBINATION FIRE/SMOKE DAMPER SCHEDULE (MOTORIZED)
FACE SIZE NECK SIZE AIR VOLUME LOCATION SIZE
ROOM NO. QTY ROOM NAME REFERENCE TYPE THROW REMARKS WIDTH x HEIGHT QTY. REMARKS
(MM) (MM) (CFM) TAG NO.
ROOM NAME (MM)
001 4 MAINTENANCE WORKSHOP SJD-1 600x600 300{ 602 4-WAY
FSD-1 LIBRARY 900x600 1 SEE NOTES-1, 2, 3, 4

OF
002 1 ELECTRICAL ROOM SAG-1 - 300x200 384 HORIZONTAL 1 SEE NOTES-1, 2, 3, 4
FSD-2 LIBRARY 900x600

CONSENT
003 1 COMMUNICATION ROOM SAG-2 - 300x250 279 HORIZONTAL FSD-3 MAINTENANCE WORKSHOP 550x400 1 SEE NOTES-1, 2, 3, 4

004 1 LIBRARY SCD-1 600x600 300{ 602 4-WAY FSD-4 MAINTENANCE WORKSHOP 550x400 1 SEE NOTES-1, 2, 3, 4

005 1 CORRIDOR-1 SCD-2 600x600 200{ 103 4-WAY FSD-5 COMMUNICATION ROOM 300x250 1 SEE NOTES-1, 2, 3, 4

FSD-6 COMMUNICATION ROOM 300x250 1 SEE NOTES-1, 2, 3, 4


006 1 AIRLOCK-1 SCD-3 600x600 150{ 113 4-WAY

TTEN
FSD-7 ELECTRICAL ROOM 300x200 1 SEE NOTES-1, 2, 3, 4
007 1 FS SUPERVISOR SCD-4 600x600 200{ 191 4-WAY
FSD-8 ELECTRICAL ROOM 300x200 1 SEE NOTES-1, 2, 3, 4
008 2 FS CUBICLE SCD-5 600x600 200{ 135 4-WAY

WRI
FSD-9 CORRIDOR 900x550 1 SEE NOTES-1, 2, 3, 4
009 1 FS FOREMAN SCD-6 600x600 200{ 197 4-WAY
FSD-10 AIR LOCK-1 850x600 1 SEE NOTES-1, 2, 3, 4
010 1 HTC SCD-7 600x600 150{ 145 4-WAY

THE
FSD-11 AIR LOCK-1 200x150 1 SEE NOTES-1, 2, 3, 4
011 1 OPS STORE SCD-8 600x600 150{ 144 4-WAY FSD-12 CORRIDOR 400x250 1 SEE NOTES-1, 2, 3, 4

THOUT
012 1 CLERK SCD-9 600x600 200{ 188 4-WAY FSD-13 CORRIDOR 900x450 1 SEE NOTES-1, 2, 3, 4

013 1 OPS FOREMAN SCD-10 600x600 200{ 197 4-WAY FSD-14 PLANNER & MATERIAL MAN 700x600 1 SEE NOTES-1, 2, 3, 4

FSD-15 CORRIDOR 400x250 1 SEE NOTES-1, 2, 3, 4

WI
014 2 LOBBY/WAITING SCD-11 600x600 150{ 143 4-WAY
FSD-16 CORRIDOR 400x250 1 SEE NOTES-1, 2, 3, 4
015 1 AIRLOCK-2 SCD-12 600x600 250{ 238 4-WAY

NG
FSD-17 CORRIDOR 350x200 1 SEE NOTES-1, 2, 3, 4
016 1 DSO OFFICE SCD-13 600x600 200{ 191 4-WAY

DRAWI
FSD-18 CORRIDOR 350x200 1 SEE NOTES-1, 2, 3, 4
017 1 SHIFT SUPERVISOR SCD-14 600x600 200{ 191 4-WAY
FSD-19 CORRIDOR 200x150 1 SEE NOTES-1, 2, 3, 4
018 3 CONFERENCE ROOM SCD-15 600x600 200{ 237 4-WAY
FSD-20 CORRIDOR 150x200 1 SEE NOTES-1, 2, 3, 4

S
019 1 PRAYER ROOM SCD-16 600x600 200{ 432 4-WAY

THI
FSD-21 CORRIDOR 300x250 1 SEE NOTES-1, 2, 3, 4

020 1 KITCHEN SCD-17 600x600 200{ 313 4-WAY FSD-22 CORRIDOR 500x250 1 SEE NOTES-1, 2, 3, 4

FSD-23 CORRIDOR 500x250 1 SEE NOTES-1, 2, 3, 4

FROM
021 1 AIRLOCK-3 SCD-18 600x600 200{ 111 4-WAY

022 1 TOILET SCD-19 600x600 200{ 273 4-WAY FSD-24 CORRIDOR 300x250 1 SEE NOTES-1, 2, 3, 4

FSD-25 CORRIDOR 300x250 1 SEE NOTES-1, 2, 3, 4


024 1 WORKSTATION-2 SCD-20 600x600 250{ 555 4-WAY

NED
FSD-26 CORRIDOR 200x200 1 SEE NOTES-1, 2, 3, 4
025 1 OFFICE SCD-21 600x600 200{ 286 4-WAY

OBTAI
FSD-27 CORRIDOR 700x300 1 SEE NOTES-1, 2, 3, 4
026 1 AIRLOCK-4 SCD-22 600x600 150{ 143 4-WAY
FSD-28 CORRIDOR 700x300 1 SEE NOTES-1, 2, 3, 4
027 1 LOCKER ROOM SCD-23 600x600 200{ 251 4-WAY
FSD-29 CORRIDOR 250x200 1 SEE NOTES-1, 2, 3, 4
028 2 SITTING AREA/COMPUTER LAB. SCD-24 600x600 200{ 219 4-WAY FSD-30 CORRIDOR 300x300 1 SEE NOTES-1, 2, 3, 4

BE
029 2 CORRIDOR-2 SCD-25 600x600 150{ 113 4-WAY FSD-31 CORRIDOR 200x200 1 SEE NOTES-1, 2, 3, 4

PART,SHALL
030 1 CORRIDOR-3 SCD-26 600x600 150{ 134 4-WAY FSD-32 CORRIDOR 250x200 1 SEE NOTES-1, 2, 3, 4 LEGEND
FSD-33 CORRIDOR 200x200 1 SEE NOTES-1, 2, 3, 4

FSD-34 AIR LOCK-4 150x150 1 SEE NOTES-1, 2, 3, 4 CFM - CUBIC FEET PER MINUTE

ECD - EXHAUST CEILING DIFFUSER

NOTE: FSD - FIRE SMOKE DAMPER

N
NO - NUMBER

I
1. COMBINATION FIRE & SMOKE DAMPER SHALL COMPLY WITH REQUIREMENTS OF UL 555 AND UL 555S.
EXHAUST/RETURN AIR DEVICES
QTY - QUANTITY

FULL,OR
AIR VOLUME 2. COMBINATION FIRE & SMOKE DAMPER SHALL BE UL LISTED AND BEAR IN THE LABEL OF AN APPROVED
FACE SIZE NECK SIZE
ROOM NO. QTY ROOM NAME REFERENCE REMARKS TESTING AGENCY INDICATING COMPLIANCE WITH 2009 IBC SECTION 716.3 AND NFPA 90A. RAG - RETURN AIR GRILLE
(MM) (MM) (CFM)
RCD - RETURN CEILING DIFFUSER
001 1 MAINTENANCE WORKSHOP RAG-1 - 550x350 2225 3. COMBINATION FIRE & SMOKE DAMPER SHALL HAVE 1.5 HRS FIRE RATING.
SAG - SUPPLY AIR GRILLE
002 1 ELECTRICAL ROOM RAG-2 - 300x200 372 4. POWER SUPPLY FOR ALL FSD'S SHALL BE FROM DDC PANEL.

N
I
SCD - SUPPLY CEILING DIFFUSER
003 1 COMMUNICATION ROOM RAG-3 - 300x250 253

ON
004 1 LIBRARY RCD-1 600x600 450x450 267

REPRODUCTI
005 1 CORRIDOR-1 RCD-2 600x600 450x450 103 REFERENCE DRAWINGS
DESCRIPTIONS DRAWING NO.
007 1 FS SUPERVISOR RCD-3 600x600 450x450 173
DRAWING CONTROL FOR EWO-16S062A-001 BD-784382
008 2 FS CUBICLE RCD-4 600x600 450x450 243
CONSTRUCTION SCOPE OF WORK BE-784383
009 1 FS FOREMAN RCD-5 600x600 450x450 177 HVAC FLOOR PLAN BA-784389-001
HVAC EQUIPMENT SCHEDULE BA-784390-001
010 1 HTC RCD-6 600x600 450x450 129

SAUDIARAMCO.NO
HVAC AIR FLOW DIAGRAM BA-784392-001
011 1 OPS STORE RCD-7 600x600 450x450 128
HVAC CONTROL DIAGRAM BA-784393-001
012 1 CLERK RCD-8 600x600 450x450 170 HVAC SEQUENCE OF OPERATION BA-784394-001

013 1 OPS FOREMAN RCD-9 600x600 450x450 177 HVAC SECTIONS BA-784395-001
HVAC DETAILS BA-784396-001
014 2 LOBBY/WAITING RCD-10 600x600 450x450 130
HVAC DETAILS BA-975829-001
016 1 DSO OFFICE RCD-11 600x600 450x450 173

017 1 SHIFT SUPERVISOR RCD-12 600x600 450x450 173

018 3 CONFERENCE ROOM RCD-13 600x600 450x450 197

OF
019 1 PRAYER ROOM RCD-14 600x600 450x450 367

PROPERTY
020 1 KITCHEN ECD-1 600x600 225x225 313

022 4 TOILET ECD-2 325x325 150x150 70

024 1 WORKSTATION-2 RCD-15 600x600 450x450 520

025 1 OFFICE RCD-16 600x600 450x450 267

SOLE
027 1 LOCKER ROOM ECD-3 600x600 225x225 251

028 2 SITTING AREA/COMPUTER LAB. RCD-17 600x600 450x450 203

029 1 CORRIDOR-2 RCD-18 600x600 450x450 206

THE
030 1 CORRIDOR-3 RCD-19 600x600 450x450 154

ARE N
HEREINED
SCALE:

CONTAI
REVISION VALIDATION

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
16S062A-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

ATB ELS KWS


01/16/18 01/16/18 01/30/18

REV.NO. DATE REVISION DESCRIPTION

I
00 01/16/18 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

HVAC EQUIPMENT SCHEDULE SCH

NG
NORTH-OPERATION SUPPORT BUILDING

DRAWI
HARADH GAS GATHERING MANIFOLD

HARADH SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784391 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


SAUDIARAMCO.
NOTES:

1. ALL I/O POINTS ARE CONNECTED TO THE DDC


UNLESS NOTED OTHERWISE.

2. ACTUAL CONTROL & WIRING ARE PREPARED BY


THE AUTHORIZED CONTROL SYSTEM CONTRACTOR.

3. HVAC INSTRUMENTS AND EQUIPMENT SHALL BE

OF
MONITORED AND CONTROLLED THROUGH A DEDICATED
DDC SYSTEM.

CONSENT
4. DDC PANEL SHALL HAVE 20% OF THE TOTAL I/O
POINTS AS SPARE

TTEN
WRI
THE
TO FACP

THOUT
TO LOCAL GAS TO DDC TO DDC TO DDC TO DDC TO DDC TO DDC TO DDC
DETECTION PANEL PANEL PANEL PANEL PANEL PANEL PANEL PANEL
DSD-2 TO DDC
PANEL

WI
7290 CFM FSD-2 FSD-10
RA

FSD-14
TO DDC

NG
DRAWI
TO DDC BELL
PANEL FSD-15 FSD-16 MOUTH
LEL LEL H2S H2S
AE/AIT AE/AIT AE/AIT AE/AIT 7290 CFM FSD-1 FSD-9 FSD-17
SA

FSD-13
TS-3
0766A 0766B 0765A 0765B FSD-18

S
THI
STL-1 BELL VAV-1 VAV-3
DSD-1 TS-1 AF-1 MOUTH EDH-2
1836 CFM TO DDC
MD-1 AF-2

FROM
VAV-2
FRESH AIR INTAKE VD VD
TO DDC EDH-1 EDH-3
SAND TRAP LOUVER TO FACP
TO DDC TO DDC LEGEND
FSD-11
CFM

@ 1836 CFM

NED
FSD-5

FSD-7

FSD-8
TS-2

FSD-6

FSD-12
TO DDC

AF AIR FLOW SWITCH

OBTAI
7289

BDD BACK DRAFT DAMPER


295 253 113 279 267 384 372 103 103 191 173 197 177 243 270 145 129 188 170 197 177 191 173
TO DDC CFM CUBIC FEET PER MINUTE
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM
C DDC DIRECT DIGITAL CONTROLLER

BE
DSD DUCT SMOKE DETECTOR

PART,SHALL
EF EXHAUST FAN

PACU-1 FACP FIRE ALARM CONTROL PANEL


M TO DDC
FSD FIRE SMOKE DAMPER
AIR COMM. FS FOREMAN OPS
ELECT. CORRIDOR-1 FS SUPERVISOR FS CUBICLE
LIBRARY ROOM HTC CLERK DSO OFFICE FOREMAN
LOCK-1 H2S HYDROGEN SULFIDE
C 004 006 003 002 005 007 009 008 010 012 016 013
LEL LOWER EXPLOSION LIMIT

N
I
FINAL FILTER MD MOTORIZED VOLUME DAMPER
PRE-FILTER

FULL,OR
WASHABLE ALUMINUM PACU PACKAGE AIR CONDITIONING UNIT
PDS PDS
PDS PRESSURE DIFFERENTIAL SWITCH

RA RETURN AIR

SA SUPPLY AIR
TO DDC TO DDC TO DDC
TO DDC AF-7 TO DDC AF-6 AF-5

N
TS TEMPERATURE SENSOR

I
VD VOLUME DAMPER

ON
TO DDC TO DDC TO DDC TO DDC TO DDC

REPRODUCTI
PANEL PANEL PANEL PANEL PANEL
TO DDC TO DDC TO DDC TO DDC REFERENCE DRAWINGS
EF-3 EF-2 EF-1
PANEL PANEL PANEL PANEL
BDD BDD BDD DESCRIPTIONS DRAWING NO.

DRAWING CONTROL FOR EWO-16S062A-001 BD-784382


FSD-26 FSD-27 CONSTRUCTION SCOPE OF WORK BE-784383

321 CFM
FSD-19
HVAC FLOOR PLAN BA-784389-001
BELL FSD-22 HVAC EQUIPMENT SCHEDULE BA-784390-001
MOUTH

SAUDIARAMCO.NO
FSD-23 BELL HVAC EQUIPMENT SCHEDULE BA-784391-001
MOUTH
FSD-31 FSD-32 FSD-33 HVAC CONTROL DIAGRAM BA-784393-001
FSD-28
HVAC SEQUENCE OF OPERATION BA-784394-001
FSD-21
VAV-4 HVAC SECTIONS BA-784395-001
VAV-5
HVAC DETAILS BA-784396-001

FSD-24 HVAC DETAILS BA-975829-001


FSD-20 FSD-29 FSD-34 EDH-6
EDH-4 EDH-5 INSTRUMENT LOCATION PLAN BA-203532-001
FSD-30
FSD-25 VAV-6

OF
PROPERTY
286 260 144 128 238 191 173 438 406 591 711 367 432 226 206 251 251 143 286 267 555 520 134 154 43 278 278 313 313 111
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM

SOLE
T D/G

43
CFM
OPS AIR SHIFT SITTING AREA/ PRAYER CONFERENCE LOCKER WORKSTATION AIR
AIR

THE
LOBBY/WAITING SUPERVISOR COMPUTER LAB CORRIDOR-2 2
STORE LOCK-2 ROOM ROOM ROOM LOCK-4 OFFICE CORRIDOR-3 JANITOR TOILET KITCHEN LOCK-3
014 011 015 017 028 019 018 029 027 026 025 024 030 023 022 020 021

ARE N
HEREINED
SCALE: NTS

CONTAI
REVISION VALIDATION

THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
16S062A-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

ATB ELS KWS


01/16/18 01/16/18 01/30/18

REV.NO. DATE REVISION DESCRIPTION

I
00 01/16/18 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

HVAC AIR FLOW DIAGRAM HVA

NG
NORTH-OPERATION SUPPORT BUILDING

DRAWI
HARADH GAS GATHERING MANIFOLD

HARADH SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784392 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


SAUDIARAMCO.
NOTES:
1. ALL I/O POINTS ARE CONNECTED TO THE DDC
UNLESS NOTED OTHERWISE.

2. ACTUAL CONTROL & WIRING ARE PREPARED BY


THE AUTHORIZED CONTROL SYSTEM CONTRACTOR.

3. HVAC INSTRUMENTS AND EQUIPMENT SHALL BE


MONITORED AND CONTROLLED THROUGH A DEDICATED

OF
OUTDOOR AIR DAMPER SHUTDOWN COMMAND FROM GAS DETECTION PANEL UPON GAS DETECTION OR DISCREPANCY BETWEEN SENSORS DDC SYSTEM.
DI DDC PANEL

CONSENT
POWER SUPPLY (230VAC) 4. DDC PANEL SHALL HAVE 20% OF THE TOTAL I/O
POINTS AS SPARE
POWER SUPPLY #2 FROM 230VDC PANEL (BACK UP)

DO 5. POWER SUPPLY FOR FSD, VAV ACTIVATORS SHALL


FROM FIRE ALARM CONTROL PANEL (FACP)
OPERATOR PANEL BE PROVIDED THROUGH DDC PANEL.
DI

TTEN
PRE-FILTER STATUS PACU-1
DI

FINAL FILTER STATUS PACU-1

WRI
DI
PRE-FILTER STATUS PACU-2
DI

THE
FINAL FILTER STATUS PACU-2
DI
PACU-1
SUPPLY FAN MOTOR ON/OFF & STATUS PACU-1

THOUT
DO FF PF FUSE

SUPPLY FAN MOTOR ON/OFF & STATUS PACU-2


DO RUN FAIL MUTE

WI
DI
EXHAUST FAN ON/OFF STATUS (EF-1)
DO LIGHT

NG
PACU-2
DI
EXHAUST FAN ON/OFF STATUS (EF-2)

DRAWI
DO FF PF
DI LEGEND
EXHAUST FAN ON/OFF STATUS (EF-3)
DO RUN FAIL
BUZZER

S
THI
DI
TELECOM ROOM HUMIDITY CONTROLLER
DO AF AIR FLOW SWITCH
TELECOM ROOM TEMPERATURE EF-1 EF-2

FROM
AI ANALOG INPUT
AI
CFM CUBIC FEET PER MINUTE
TELECOM ROOM HIGH TEMPERATURE ALARM
TO DDC DO EF-3 DDC DIRECT DIGITAL CONTROLLER
TO DDC

NED
PACU-1 COMPRESSORS RUN/FAIL STATUS DI DIGITAL INPUT
DO

OBTAI
EDH-1 EDH-2 DO DIGITAL OUTPUT
SUPPLY AIR TEMPERATURE PACU-1
DI
DSD DUCT SMOKE DETECTOR

TS-4 AF-3 PACU-2 COMPRESSORS RUN/FAIL STATUS EDH-3 EDH-4 EDH ELECTRICAL DUCT HEATER
DO
TO LOCAL GAS

BE
EF EXHAUST FAN
DETECTION PANEL SUPPLY AIR TEMPERATURE PACU-2
2406 CFM DI
2406 FACP FIRE ALARM CONTROL PANEL
SA EDH-5 EDH-6

PART,SHALL
CFM PACU-1 FRESH AIR TEMPERATURE
VD FSD-3 AI FF FINAL FILTER

FSD FIRE SMOKE DAMPER


DSD-3 TO DDC RETURN AIR TEMPERATURE PACU-1
TO DDC TO DDC DI
PANEL H2S HYDROGEN SULFIDE
SYSTEM
PACU-2 FRESH AIR TEMPERATURE
AI START LEL LOWER EXPLOSION LIMIT

RETURN AIR TEMPERATURE PACU-2 MD MOTORIZED VOLUME DAMPER


LEL LEL H2S H2S TO FACP

N
DI STOP

I
AE/AIT AE/AIT AE/AIT AE/AIT TO DDC PDS PRESSURE DIFFERENTIAL SWITCH
TS-6 AF-4

FULL,OR
STL-2 PANEL AIR FLOW SWITCH (AF) EF-1
0766C 0766D 0765C 0765D PF PRE FILTER
DI
RESET
PSU PRECISION SPLIT TYPE UNIT
181 CFM 2225 CFM FSD-4
AIR FLOW SWITCH (AF) EF-2
2225 DI SA SUPPLY AIR
CFM
CFM

MD-2 AIR FLOW SWITCH (AF) EF-3 TS TEMPERATURE SENSOR


DI

N
PSU-1 VAV VARIABLE AIR VOLUME
2466

I
FRESH AIR INTAKE DSD-4 AIR FLOW PACU-1 SUPPLY
SAND TRAP LOUVER TO DDC DI
RUN FAIL VD VOLUME DAMPER

ON
@ 181 CFM

REPRODUCTI
AIR FLOW PACU-1 RETURN
DI REFERENCE DRAWINGS
TO DDC TS-5
AIR FLOW PACU-2 SUPPLY ACCU-1 DESCRIPTIONS DRAWING NO.
TO FACP DI
DRAWING CONTROL FOR EWO-16S062A-001 BD-784382
RUN FAIL
AIR FLOW PACU-2 RETURN CONSTRUCTION SCOPE OF WORK BE-784383
DI
HVAC FLOOR PLAN BA-784389-001
TO DDC DO HVAC EQUIPMENT SCHEDULE BA-784390-001
FIRE SMOKE DAMPER OPEN/CLOSE FSD-1 TO FSD-34 (34 NOS)

SAUDIARAMCO.NO
C DI VAV-1 VAV-2 HVAC EQUIPMENT SCHEDULE BA-784391-001
MAINTENANCE DO HVAC AIR FLOW DIAGRAM BA-784392-001
MOTORIZED DAMPER OPEN/CLOSE MD-1 TO MD-4 (4 NOS)
WORKSHOP DI HVAC SEQUENCE OF OPERATION BA-784394-001
VAV-3 VAV-4
DO HVAC SECTIONS BA-784395-001
001 TELECOM ROOM PSU-1 ON/OFF
DI HVAC DETAILS BA-784396-001

PACU-2 DO VAV-5 VAV-6 HVAC DETAILS BA-975829-001


TO DDC TELECOM ROOM ACCU-1 ON/OFF
M INSTRUMENT LOCATION PLAN BA-203532-001
DI

PACU-1 SPACE TEMPERATURE (T1)


AI

OF
PACU-2 SPACE TEMPERATURE (T2)
C AI

DO

PROPERTY
EDH-1 ON/OFF STATUS
FINAL FILTER DI
PRE-FILTER DO
EDH-2 ON/OFF STATUS
WASHABLE ALUMINUM DI
PDS PDS DO
EDH-3 ON/OFF STATUS
DI
DO
EDH-4 ON/OFF STATUS

SOLE
DI
DO
EDH-5 ON/OFF STATUS
TO DDC TO DDC DI

THE
DO
EDH-6 ON/OFF STATUS
DI
DO
VAV-1 ON/OFF STATUS

ARE
DI
DO
VAV-2 ON/OFF STATUS
DI

N
HEREI
DO
VAV-3 ON/OFF STATUS
DI
DO
VAV-4 ON/OFF STATUS
DI

NED
DO
VAV-5 ON/OFF STATUS SCALE: NTS
DI

CONTAI
DO
VAV-6 ON/OFF STATUS
DI REVISION VALIDATION

SPARE
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
SPARE 16S062A-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
SPARE (DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

ATB ELS KWS


SPARE 01/16/18 01/16/18 01/30/18

REV.NO. DATE REVISION DESCRIPTION

I
SPARE 00 01/16/18 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

HVAC CONTROL DIAGRAM HVA

NG
NORTH-OPERATION SUPPORT BUILDING

DRAWI
HARADH GAS GATHERING MANIFOLD

HARADH SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784393 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


SAUDIARAMCO.
NOTES:

1. ALL I/O POINTS ARE CONNECTED TO THE DDC


SEQUENCE OF OPERATION (DDC PANEL): UNLESS NOTED OTHERWISE.

PACKAGED AIR CONDITIONING UNIT (PACU-1 & PACU-2): 2. ACTUAL CONTROL & WIRING ARE PREPARED BY
THE AUTHORIZED CONTROL SYSTEM CONTRACTOR.
SYSTEM START AND STOP:
3. HVAC INSTRUMENTS AND EQUIPMENT SHALL BE

OF
MONITORED AND CONTROLLED THROUGH A DEDICATED
1. OFFICE AREA SHALL BE SERVED BY ONE PACKAGED AIR
DDC SYSTEM.
CONDITIONING UNIT PACU-1.

CONSENT
4. DDC PANEL SHALL HAVE 20% OF THE TOTAL I/O
2. WORKSHOP SHALL BE SERVED BY ONE PACKAGED POINTS AS SPARE
AIR CONDITIONING UNIT PACU-2.

3. POWER SUPPLY TO HVAC UNITS SHALL BE ENABLED MANUALLY.

TTEN
4. SYSTEM START AND STOP SHALL BE COMMANDED BY THE DDC
PANEL. BLOWER MOTOR OF PACU SHALL START WHEN VOLUME

WRI
DAMPERS ARE FULLY OPEN.

5. WHEN THE SYSTEM IS COMMANDED TO STOP THRU DDC PANEL,

THE
PACU AND THEIR ASSOCIATED MOTORIZED DAMPER SHALL CLOSE.

THOUT
DIRTY FILTER:

1. WHEN THE PRE-FILTER OR FINAL FILTER OF PACU IS DIRTY, THE

WI
PRESSURE DIFFERENTIAL SWITCH (PDS) ACROSS EACH FILTER
SHALL INITIATE AN ALARM ON THE DDC PANEL. THE ALARM

NG
SHALL BE RESET AFTER FILTERS ARE CLEANED OR REPLACED.

DRAWI
2. PRE-FILTER DIRTY CONDITION SHALL BE SET AT 125 PA
(0.5 IN OF WG) PRESSURE DIFFERENTIAL SWITCH (PDS) ACROSS
EACH FILTER.

S
THI
3. FINAL FILTER DIRTY CONDITION SHALL BE SET AT 250 PA
(1.0 IN OF WG) PRESSURE DIFFERENTIAL SWITCH (PDS) ACROSS
EACH FILTER.

FROM
POWER INPUT/OUTPUT:
294
1. POWER SUPPLY TO DDC PANEL SHALL BE 230V, 1PH, 60HZ.

NED
CFM
2. ON-OFF STATUS OF ALL PACU AND EXHAUST FANS

OBTAI
SHALL BE DISPLAYED AT DDC PANEL.
PSU-1
3. POWER SUPPLY FOR ALL FSD'S, VAV'S SHALL BE PROVIDED THROUGH
(STAND BY) LEGEND
DDC PANEL. VAV POWER SUPPLY SHALL BE CO-ORDINATED WITH DDC
294
VENDOR.

BE
CFM
ACCU AIR COOLED CONDENSING UNIT

PART,SHALL
TELECOM ROOM: DCS DISTRIBUTED CONTROL SYSTEM

1. PACU SHALL BE INTER LOCKED WITH PSU-1. WHEN PACU-1 DDC DIRECT DIGITAL CONTROLLER
STOPS THEN DDC PANEL SHALL ENERGIZE PSU-1 TO
FACP FIRE ALARM CONTROL PANEL
MAINTAIN TELECOM ROOM TEMPERATURE. T TO DDC
PANEL GDS GAS DETECTION PANEL
2.TELECOM ROOM IS SERVED BY ONE WALL MOUNTED
H2S HYDROGEN SULFIDE
PRECISION TYPE UNIT AS STAND BY (PSU-1) INSIDE

N
I
THE CEILING, CORRESPONDING UNIT (ACCU-1) IS LEL LOWER EXPLOSION LIMIT
TO DDC PANEL
LOCATED OUTSIDE OF THE BUILDING.

FULL,OR
MD MOTORIZED VOLUME DAMPER

3. TELECOM ROOM SHALL HAVE HIGH TEMPERATURE SENSOR PACU PACKAGE AIR CONDITIONING UNIT
(SET POINT 80°F). COMM.
PDS PRESSURE DIFFERENTIAL SWITCH
ROOM
PSU PRECISION SPILT TYPE UNIT
003
SA SUPPLY AIR

N
TEMPERATURE CONTROL:

I
TS TEMPERATURE SENSOR

ON
1. THE TEMPERATURE SENSOR (TS) ON THE SUPPLY AIR DUCT

REPRODUCTI
OF PACU COMMUNICATES WITH THE DDC PANEL AND SUPPLY
REFERENCE DRAWINGS
AIR TEMPERATURE IS MAINTAINED AT AROUND 55°C.
DESCRIPTIONS DRAWING NO.

DRAWING CONTROL FOR EWO-16S062A-001 BD-784382


AIR FLOW SWITCH:
CONSTRUCTION SCOPE OF WORK BE-784383
ACCU-1
HVAC FLOOR PLAN BA-784389-001
1. UPON DETECTION OF NO FLOW BY THE AIR FLOW SWITCH (STAND BY)
INSTALLED IN MAIN DUCT OF PACU-2 AN AUDIO VISUAL HVAC EQUIPMENT SCHEDULE BA-784390-001
CONTROL DIAGRAM FOR

SAUDIARAMCO.NO
ALARM SHALL BE INITIATED AT DDC PANEL. HVAC EQUIPMENT SCHEDULE BA-784391-001
STAND BY UNIT
HVAC AIR FLOW DIAGRAM BA-784392-001
DETAIL-1
SMOKE/FIRE DETECTION: HVAC CONTROL DIAGRAM BA-784393-001
HVAC SECTIONS BA-784395-001
1. WHEN SMOKE OR FIRE IS DETECTED WITHIN THE SPACES OR HVAC DETAILS BA-784396-001
INSIDE THE AIR STREAM BY THE DUCT SMOKE DETECTOR,
HVAC DETAILS BA-975829-001
SIGNAL SHALL BE SENT FROM FIRE ALARM CONTROL PANEL
(FACP) THRU DDC PANEL TO DE-ENERGIZE ALL OPERATING
PACU AND EXHAUST FANS.

OF
EQUIPMENT FAILURE:

PROPERTY
1. IN CASE OF EQUIPMENT FAILURE OR ANY ALARM SIGNALS, AN
AUDIBLE ALARM SHALL BE INITIATED AND VISUAL INDICATION
SHALL BE DISPLAYED AT DDC PANEL. AUDIBLE ALARM SHALL
HAVE THE PROVISION TO BE MUTE SILENCED. HOWEVER, VISUAL
ALARM SHALL LAST UNTIL THE FAULT IS ATTENDED AND RESET.

SOLE
H2S/LEL GAS DETECTION:

1. TWO (2) H2S & TWO (2) LEL GAS SENSOR LOCATED IN THE OUTSIDE AIR DUCT

THE
SHALL OPERATE SIMULTANEOUSLY. IN CASE OF A DEVIATION BETWEEN THE
SAMPLING MEASUREMENTS OF THE INSTALLED GAS DETECTORS GREATER

ARE
THAN 10%, AN ALARM SHALL BE SENT TO THE GAS DETECTION PANEL
INDICATING FAULTY SENSORS. GAS DETECTION PANEL SHALL ANNUNCIATE AN
AUDIO VISUAL ALARM. GAS DETECTION PANEL SHALL SEND A SIGNAL TO DDC

N
TO SHUT DOWN THE OUTSIDE AIR DUCT MOTORIZED DAMPER MD-1 & MD-2 TO

HEREI
OPERATE PACU ON FULL CIRCULATION MODE.

2.WHEN CONCENTRATION OF COMBUSTIBLE GAS EXCEEDS 5% LEL OR HYDROGEN


SULFIDE EXCEEDS 5PPM A SIGNAL IS SENT FROM GAS DETECTION PANEL TO

NED
THE DDC PANEL TO CLOSE THE OUTSIDE AIR DAMPER MD-1 & MD-2. DUTY PACU SCALE: NTS

CONTAI
SHALL CONTINUE TO OPERATE ON FULL RE-CIRCULATION.

REVISION VALIDATION
3.WHEN CONCENTRATION OF COMBUSTIBLE GAS EXCEEDS 10% LEL OR HYDROGEN
SULFIDE EXCEEDS 10PPM A SIGNAL IS SENT FROM GAS DETECTION PANEL TO THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:


THE DDC PANEL TO SHUT DOWN THE DUTY PACU.

ON
16S062A-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

ATB ELS KWS


01/16/18 01/16/18 01/30/18

REV.NO. DATE REVISION DESCRIPTION

I
00 01/16/18 ISSUED FOR CONSTRUCTION

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

HVAC SEQUENCE OF OPERATION HVA

NG
NORTH-OPERATION SUPPORT BUILDING

DRAWI
HARADH GAS GATHERING MANIFOLD

HARADH SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784394 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


SAUDIARAMCO.
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS AND
ELEVATIONS ARE IN METERS UNLESS OTHERWISE
NOTED.

OF
CONSENT
TTEN
WRI
J H G F E D C B A

THE
36500

THOUT
7000 4500 4500 4500 4500 4500 2500 4500

WI NG
DRAWI
T.O.P. +5.50

1000
SA 550x900 SA 450x900
250x300 SA 450x800 SA 400x700 SA 300x700 T.O.S. +4.50
RA 600x850 RA 600x700 FSD-14
150x350 200x250 200x200 FSD-13 RA 500x700 SA 450x700 RA 400x700 RA 300x700

S
THI
1100
DSD-1 FSD-1
STL-1 SAND TRAP FSD-29 FSD-34
FSD-2
LOUVER 600x1000

FROM
1000
@ 2.4M HIGH FROM 600x900

5500
FGL 250x500
250x400 200x350 250x300 200x200 250x250

4500
250x400 250x300

600x900
FSD-10 BELL MOUTH 150x150

H2S LEL
RCD-2 BELL MOUTH 150x200 SCD-25 RCD-18 SCD-25 SCD-22

3697
BELL

3597
3497
3397
SCD-1 FSD-9

NED
3250
RCD-1 MOUTH
3120

PACU-1
DSD-2 LEGEND / ABBREVIATIONS

2400
2281

2400

OBTAI
AIR LOCK
CORRIDOR-2 -4
LIBRARY
FFL FINISH FLOOR LEVEL
029 026
004 F.F.L. +0.00
FGL -0.15 FGL FINISH GRADE LINE

BE
FSD FIRE SMOKE DAMPER
MD-1
H2S HYDROGEN SULFIDE
350x500

PART,SHALL
LEL LOWER EXPLOSION LIMIT
2200 2150
MD MOTORIZED DAMPER

PACU PACKAGED AIR CONDITIONING UNIT

RAG RETURN AIR GRILLE

RCD RETURN CEILING DIFFUSER

SCD SUPPLY CEILING DIFFUSER

N
I
SJD SUPPLY JET DIFFUSER
A SECTION

FULL,OR
BA-784389
STL SAND TRAP LOUVER
SCALE 1:75 M
SH 001
VOLUME DAMPER

MOTORIZED DAMPER

FIRE SMOKE DAMPER

N
HYDROGEN SULFIDE

I
LOWER EXPLOSION LIMIT

ON
REPRODUCTI
REFERENCE DRAWINGS
DESCRIPTIONS DRAWING NO.

DRAWING CONTROL FOR EWO-16S062A-001 BD-784382


CONSTRUCTION SCOPE OF WORK BE-784383
HVAC FLOOR PLAN BA-784389-001
HVAC EQUIPMENT SCHEDULE BA-784390-001

SAUDIARAMCO.NO
HVAC EQUIPMENT SCHEDULE BA-784391-001
HVAC AIR FLOW DIAGRAM BA-784392-001
HVAC CONTROL DIAGRAM BA-784393-001
HVAC SEQUENCE OF OPERATION BA-784394-001
HVAC DETAILS BA-784396-001
HVAC DETAILS BA-975829-001

G H J

OF
PROPERTY
11500

4500 7000

T.O.P. +8.80

1000

SOLE
T.O.S. +7.80

SUPPLY PLENUM

THE
DSD-3 600x700x1000

350x400 400x550

ARE
250x300 RAG-1
SJD-1 (TYP-2)
FSD-4

7800
(TYP-2)

N
FSD-3 DSD-4

HEREI
8800
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0
400x550

550x400

6350
METERS

NED
5750
6350

SCALE: 1 :75M

CONTAI
200x200 REVISION VALIDATION

LEL
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
2400

MAINTENANCE H2S REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
MD-2

1327
WORKSHOP

ON
16S062A-001
F.F.L.

NFORMATI
001 PACU-2 +0.00
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

STL-2 SAND TRAP ATB ELS KWS


LOUVER 250x350 2000 3390 FGL -0.15 01/16/18 01/16/18 01/30/18

@ 2.4M HIGH FROM REV.NO. DATE REVISION DESCRIPTION

I
FGL 00 01/16/18 ISSUED FOR CONSTRUCTION

RETURN PLENUM

THE
JOB ORDER/EWO NO.
700x400x1500 THIS REVISION IS NOT TO BE USED FOR
16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

HVAC SECTIONS HVA


B SECTION

NG
BA-784389 NORTH-OPERATION SUPPORT BUILDING

DRAWI
SCALE 1:75 M
SH 001
HARADH GAS GATHERING MANIFOLD

HARADH SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784395 001 00
Saudi Aramco 2615 ENG. (05/05)

CONFIDENTIAL VECTOR CADD-01


SAUDIARAMCO.
FLEXIBLE DUCT
NOTES:
CONNECTION ( MIN LENGTH 1. INSULATION INSTALLED EXPOSED OUTDOORS SHALL
3 IN. MAX LENGTH 10 IN.) BE METAL CLADDED OR PROTECTED BY AN APPROVED
NOTE: AIR DUCT
AND ACCEPTABLE METHOD FROM MOISTURE AND
NON- HARDENING CUT A 12"x12" ACCESS HOLE IN THE DUCT ADJACENT SUNLIGHT DEGRADATION.
MASTIC SEALER TO THE HOUSING TO PERMIT CHECKING AND CLEANING
2.CONDENSATE DRAIN PIPE SIZE SHALL BE AS PER
SELF TAPPING SCREW. ALL AROUND (TYP.) OF THE SAMPLING TUBES. THE ACCESS HOLE MUST BE MAX. WIDTH
STEEL ANGLE SIZE VENDOR RECOMMENDATIONS.
NO. 14 x 1" LG COVERED AND SEALED WHEN NOT IN USE. OF DUCT OR
(MM & INCH)

OF
FAN IN MM

INSULATED L38x38x6 ALL AROUND

CONSENT
0 TO 1060 L-25x25x3 (1"x1"x„")
AIR DUCT FASTENED ON SLEEVE

UNIT 1061 TO 2420 L-40x40x4 (1•"x1•"x‰")


A/ HOUSING
C
AI DU OVER 2420 L-50x50x6 (2"x2"x‚")
R C
OU T
AC SU TL

TTEN
CE PP ET
SS INL LY SA
HO ET OR MP
DU LE

WRI
C SA R LI
NG NO. 8x16 mm METAL 16mm 2
DE T M RU MP ET
TE O BB LI UR TU SCREW @ 305mm O.C. INSULATED COPPER
CT N U N N BE
ER G CONNECTING (GROUNDING)
ƒ OR TE AI

THE
"
{ D PL TUB R SHEET METAL WIRE. (TYPICAL)
& F SM UG E
CO LE OK "U" STRIP (TYP.)
50 50 GU N X E
NE I BL STEEL ANGLE

THOUT
A C E
WI C C TO CO
TH ON R
ƒ ND
RS " DU LI QU UI AIR DUCT
{ I
T T
C ID
HU B

WI
( T
3/ B OX
4" ES I GH
{ T
)C

NG
ON
ALUM. DUCT TAPE CONCRETE GROUT NE

DRAWI
CT
OR
UNIT
HOUSING
Ga.20 GALV. SHEET
COMPRESSED

S
THI
SLEEVE ALL AROUND
FIBER GLASS
INSULATION

10mm. MACH. BOLT

FROM
3mm CANVASS FLEXIBLE
W/NUT & WASHER
DUCT CONNECTION
DUCT THRU WALL DUCT SMOKE DETECTOR DETAILS (MIN LENGTH 3 IN,
MAX LENGTH 10 IN)
FLEXIBLE CONNECTION DETAIL

NED
BETWEEN DUCT AND HVAC UNIT

OBTAI
BE
PART,SHALL
PACU
1" DIA. UNION
ANTI-VIBRATION
PAD
PIPE SUPPORT

LEGEND
L 1" NIPPLE
WHERE L=1/3 W (MIN.)
PIPE 200MM ABOVE
IN. - INCH

N
I
GRADE LEVEL
PACU - PACKAGE AIR CONDITIONING UNIT

FULL,OR
W

1" PIPE
MIN - MINIMUM
30° MAX PLUG (SCREWED)

CLEAR)
45 DEGREE ENTRY 0 = 45° MAX - MAXIMUM
CONCRETE PAD
CLOSE OPENING 1" ELBOW
SEE CIVIL DWG DIA - DIAMETER
AT CORNERS

50

N
(

I
50

ON
GRADE LEVEL

REPRODUCTI
REFERENCE DRAWINGS
BRANCH CONNECTION DETAIL ECCENTRIC TRANSITION FLOOR DESCRIPTIONS DRAWING NO.
DRAIN DRAWING CONTROL FOR EWO-16S062A-001 BD-784382
1" TEE CONSTRUCTION SCOPE OF WORK BE-784383
HVAC FLOOR PLAN BA-784389-001
HVAC EQUIPMENT SCHEDULE BA-784390-001
CONDENSATE DRAIN

SAUDIARAMCO.NO
HVAC EQUIPMENT SCHEDULE BA-784391-001
HVAC AIR FLOW DIAGRAM BA-784392-001
HVAC CONTROL DIAGRAM BA-784393-001
HVAC SEQUENCE OF OPERATION BA-784394-001
HVAC SECTIONS BA-784395-001
‚"{ MASONRY ANCHOR HVAC DETAILS BA-975829-001
DUCT INSULATION
15mm WIDE GALVANIZED
W/ FACTORY APPLIED
STEEL STRAP BAND
NO. 14 SELF TAPPING ALUMINUM FOIL
W @ 300 mm O.C.
SCREW ( FOR METAL WALL)
DE

VAPOR BARRIER
NSI

ALUMINUM FOIL

OF
W-10
PINS WELDED TO DUCT LAP JOINT
I

@ 450 mm O.C.

PROPERTY
UNIT NO. W H
DUCT

PACU-1 1000 600 ND DS D 25x25x100mm.


BA AN DE
DE

M B ED UL GALV. SHEET
NU 3- AC MO ION
OUTSI

PACU-2 350 250 I GALV. METAL


M DE SP OF CORNER BEADING

SOLE
SELF-EMPTYING SAND U I { AT
51

25 102 51 AL OV LY MM L SHEET DUCT


DRAIN HOLES PR AL 00 N) MM NSU NON-FLAMMABLE
( I
U 9
EQ R IO 50 E
VERT. BLADES E LAT PIP DUCT ADHESIVE
P U

THE
W+102
INS

INDOOR DUCT INSULATION DETAIL

ARE
OUTSIDE DUCT INSIDE

M
76 76 INT NU D
I
JO UM SE ON CA
L

N
25

HEREI
ION .AL PO ATI NI
A
AT K EX UL
CH
UL TH R NS ME
I
NO. 14 SELF TAPPING NS
I mm
O
F R N
I
40 ET HE G
SCREW (FOR METAL 0. CK AT I N
E N DUCT INSULATION

NED
WALL) JA W UN ALUMINUM CLADDING
PE
SCALE:
O R W/ FACTORY APPLIED
PI T D 0.04mm THICK

CONTAI
NT AN OM ALUMINUM FOIL
RA RO VAPOR BARRIER
GE REVISION VALIDATION
FRI ALUMINUM FOIL
RE S PINS WELDED TO DUCT LAP JOINT THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

AS REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:


H+102

GL NG @ 450 mm O.C.
H-10

SAND

ON
I
H

16S062A-001
TRAP VE IZE GG
SI S LA

NFORMATI
LOUVER HE E H DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
AD PR OT (DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)

ING CL ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

ND ATB ELS KWS


BO 01/16/18 01/16/18 01/30/18

GALV. METAL REV.NO. DATE REVISION DESCRIPTION

I
SHEET DUCT 00 01/16/18 ISSUED FOR CONSTRUCTION

NON-FLAMMABLE

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
25

DUCT ADHESIVE
VERT. BLADES 16S062A CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
W+102 ‚"{ MASONRY REFRIGERANT PIPE INSULATION DETAIL DRAWING TYPE
ANCHOR
FINE MESH SELF-EMPTYING HVAC DETAILS HVA

NG
SCREEN SAND DRAIN
NORTH-OPERATION SUPPORT BUILDING

DRAWI
HOLES
HARADH GAS GATHERING MANIFOLD
OUTDOOR/ EXPOSED DUCT INSULATION DETAIL
SAND TRAP LOUVERS HARADH SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
D83 K BA-784396 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01


SAUDIARAMCO.
NOTES:

1. PRE-INSULATED DOUBLE WALL FLEXIBLE DUCTS


SHALL BE USED AT THE CONNECTION OF AIR
DIFFUSING DEVICES, IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 90A. FLEXIBLE DUCTS
LOW VELOCITY CONCRETE WALL SHALL NOT EXCEED 1. FOOT (0.3 METER) IN
SUPPLY DUCT OVERALL LENGTH AND SHALL NOT HAVE MORE

OF
THAN 1 BEND NO GREATER THAN 45°.
VOLUME …" MASONRY ANCHOR

DAMPER

CONSENT
NG
OPENI

TTEN
WALL
FRAME
GALV. STEEL CINCH CLAMP

WRI
CAM LOCK

ROUND NECK SUPPLY


CONTINUOUS HINGE
CEILING DIFFUSER

THE
152 127 152
EXHAUST AIR GRILLE DOOR FRAME
FIXED BLADE TYPE NO. 14x•" LG.

THOUT
TAPPING SCREW
DOOR PLATE TYP. SECTION
CEILING

BACK-DRAFT DAMPER
EXHAUST FAN

WI
OPPOSED BLADE ( INTEGRAL WITH UNIT) AIR DUCT FIELD JOINT
UNIT
VOLUME DAMPER S-SLIP (TYP.)

NG
DRAWI
FIRE/SMOKE
DUCT ACCESS PANEL

S
LINK ASSEMBLY

THI
DAMPER
ASSEMBLY
ACTUATOR

SUPPLY CEILING DIFFUSER INSTALLATION DETAIL WALL EXHAUST FAN DETAIL SHAFT

FROM
RIVETS @ 305mm
(MAX. O.C).
ON SLEEVE

NED
DUCT ACCESS
PANEL

OBTAI
FUSIBLE LINK
18 GA. SLEEVE
UL LISTED

BE
L-38x38x6 STEEL ANGLE
SEALANT ALL AROUND

PART,SHALL
ALL AROUND

EQUIPMENT FIRE RATED WALL STARTER TAB

HOUSING
DUCT
DUCT SUPPORT

EQUIPMENT BASE
STUD CONTINUOUS THREADED FIRE/SMOKE DAMPER
13{ NUT

N
ROUND BAR 12mm (1/2") DIA

I
MAIN DUCT & WASHER
CAST VINYL GASKET

FULL,OR
NEOPRENE VIBRATION
ANGLE BAR CARBON
MOUNTING PAD
STEEL (38x38x6.4mm)
VD 75mm MIN. THICKNESS FRAME (GALV. STEEL)
13{ ANCHOR
BOLT DOOR PLATE
(GALV. STEEL)

N
I
CONCRETE PAD

25mm FIBERGLASS CAM LOCK

ON
CEILING DIFFUSER INSULATION

REPRODUCTI
DOOR FRAME REFERENCE DRAWINGS
CEILING LINE (GALV. STEEL)
DESCRIPTIONS DRAWING NO.

DRAWING CONTROL FOR EWO-16S062A-001 BD-784382


DIFFUSER FACE PLATE CONSTRUCTION SCOPE OF WORK BE-784383
RESTING ON T-RUNNER DUCT ACCESS PANEL TYP. SECTION HVAC FLOOR PLAN BA-784389-001
HVAC EQUIPMENT SCHEDULE BA-784390-001

SAUDIARAMCO.NO
HVAC EQUIPMENT SCHEDULE BA-784391-001
HVAC AIR FLOW DIAGRAM BA-784392-001
HVAC CONTROL DIAGRAM BA-784393-001
TYPICAL DUCT INSTALLATION DETAIL
VIBRATION PAD MOUNTING DETAIL HVAC SEQUENCE OF OPERATION BA-784394-001
HVAC SECTIONS BA-784395-001
HVAC DETAILS BA-784396-001

OF
PROPERTY
HANGER
ANGLES HANGER RODS
STRAPS

SOLE
DUCT DUCT DUCT

10mm BOLT FIXTURE


CLIPS
(MINIMUM) H

THE
ANGLE H
PUSH NUTS

R
25mm 25mm

ARE
(ALT.-1) (ALT.-2) (ALT.-3)

F
ANGLE
H
W

N
W

HEREI
RECOMMENDED CONSTRUCTION FOR RECTANGULAR SHEET METAL DUCTS
W
TYPE RE 3
GI SHEET GAGE RECOMMENDED CONSTRUCTION

NED
DUCT DIMENSIONS RADIUS ELBOW
TRANSVERSE JOINTS, BRACING AND REINFORCING
TYPE RE 4 SCALE:
WITH VANES

CONTAI
(IN.) DUCT SLIP
TYPE RE 2
SQUARE THROAT ELBOW
UP TO 24 24 24 POCKET SLIP OR BAR S- SLIP, SPACED NOT MORE THAN EIGHT FEET APART. WITHOUT VANES SQUARE THROAT ELBOW REVISION VALIDATION

(1000 FPM MAXIMUM VELOCITY) WITH VANES THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
24 TO 30 24 24 REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
POCKET SLIP OR BAR S- SLIP, SPACED NOT MORE THAN FOUR FEET APART.

W2
16S062A-001
31 TO 60 22 22

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)
REINFORCED POCKET SLIP OR REINFORCED BAR S- SLIP, SPACED NOT MORE THAN FOUR FEET APART
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
61 TO 72 20 20 1-1/2 X 1-1/2 X 1/8" DIAGONAL ANGLE REINFORCING OR 1-1/2 X 1-1/2 X 1/8" GIRTH ANGLE REINFORCING ATB ELS KWS
01/16/18 01/16/18 01/30/18
LOCATED MIDWAY BETWEEN JOINTS.
REV.NO. DATE REVISION DESCRIPTION

I
00 01/16/18 ISSUED FOR CONSTRUCTION
REINFORCED POCKET SLIP OR REINFORCED BAR S- SLIP, SPACED NOT MORE THAN FOUR FEET APART

THE
R2
JOB ORDER/EWO NO.
1-1/2 X 1-1/2 X 1/8" DIAGONAL ANGLE REINFORCING OR 1-1/2 X 1-1/2 X 1/8" GIRTH ANGLE REINFORCING H THIS REVISION IS NOT TO BE USED FOR
73 TO 90 20 20 16S062A

R1
CONSTRUCTION UNTIL CERTIFIED AND DATED
LOCATED MIDWAY BETWEEN JOINTS.
R

H H SAUDI ARABIAN OIL COMPANY

AND
1-1/4 X 1/8" BAND IRON STAY BRACING FOR DUCT WIDTH 73" TO 90".
W1 W DRAWING TYPE
F

REINFORCED POCKET SLIP OR REINFORCED BAR S- SLIP, SPACED NOT MORE THAN FOUR FEET APART
HVAC DETAILS HVA
W

NG
1-1/2 X 1-1/2 X 1/8" DIAGONAL ANGLE REINFORCING OR 1-1/2 X 1-1/2 X 1/8" GIRTH ANGLE REINFORCING TYPE RE 1 NORTH-OPERATION SUPPORT BUILDING

DRAWI
91 AND UP 18 20 LOCATED MIDWAY BETWEEN JOINTS. TYPE RE 5 MITERED ELBOW
RADIUS ELBOW HARADH GAS GATHERING MANIFOLD
(CENTERLINE R =3W/2 = STD RADIUS) DUAL RADIUS ELBOW
1-1/4 X 1/8" BAND IRON STAY BRACING FOR DUCT WIDTH 91" TO 120". HARADH SAUDI ARABIA

S
1-1/4 X 1/8" BAND IRON STAY BRACING SPACED 48" APART FOR DUCT WIDTH 121" AND UP. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
RECTANGULAR ELBOWS DETAIL
D83 K BA-975829 001 00
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01