Sie sind auf Seite 1von 4

67-72 25/11/03 10:24 Page 67

Guan Hong Quan, SINOPEC

Efficient Beijing Yan Shan


Petrochemical Corporation
Refinery, China, discusses
the energy efficient retrofit,

retrofit based on the CCC control


system, for a methylethylke-
tone (MEK)-benzene dewax-
ing unit refrigeration station.

he refrigeration station of the MEK-benzene dewaxing (UV-501) used the suction pressure of the first stage inlet

T unit at Beijing Yan Shan Petrochemical Corporation


Refinery Business Division was built in 1969 together
with the main unit. Its main duty is to use ammonia as a
pressure as a control signal. The opening of the control
valve should ensure that the inlet flow was constant and the
compressor was not surging. The remotely operated hot
refrigerant to provide a cold source for the MEK/benzene flow antisurge control valve (HV-501) was to be used when
crystallisation section. The main equipment for the refriger- load fluctuated dramatically or during startup, when the load
ation station are five ammonia refrigeration compressors: had not yet been established, ensuring the normal operation
two for -20 ˚C evaporation system with refrigeration capacity of the compressor’s units.
of 10.5 MJ/hr/unit ammonia refrigeration compressor; and The above mentioned antisurge control design used a
three for -42 ˚C evaporation system with refrigeration capac- fixed limit flow antisurge method. The principle of this con-
ity of 5.6 MJ/hr/unit ammonia refrigeration compressor. trol method is to ensure the flow of the compressor is always
All five units were motor-driven centrifugal compressors greater than a certain pre-set flow. This ammonia compres-
made by Borsig, Germany. Since the original antisurge con- sor is at constant speed and constant inlet pressure, thus
trol system for the ammonia compressors of the refrigera- inlet flow is also constant.
tion station was outdated, the antisurge control system The advantage of this method is its simplicity. It uses rel-
could not realise precise automated control. To avoid com- atively few instruments, and has high system reliability. The
pressor surge during operation at a reduced load, operators disadvantages are that it acts too early at low compressor
had to open the antisurge valves to ensure sufficient recycle load, has a large amount of recycle flow, and wastes
flow, thus the compressors would operate away from the energy.
surge point. This unnecessarily increased the energy con- In order to protect the compressor, save as much
sumption of the compressors. Consequently, the antisurge energy as possible, and avoid the frequent opening and
control system’s electrical and auxiliary equipment had rela- closing of the antisurge valve in actual operation, the control
tively high energy consumption. In order to reduce the ener- of the compressor was often in manual operation, keeping
gy consumption, to ensure the safe operation of the com- the control of the antisurge valve in manual. When the com-
pressors and achieve optimum operation, the Refinery pressor load is reduced, motor power load was lower than
Business Division retrofitted the antisurge control system of the rated power of 1250 kW, the antisurge valve would be
the ammonia compressors in the refrigeration station. opened manually to make sure the compressor would not
operate below the rated condition. The control of the com-
The original antisurge control pressor would not realise automated precision control and
Surge is a unique phenomenon of the centrifugal compres-
the compressor operation would not be stable. When the
sor. Any centrifugal compressor according to its geometric
ammonia system condensing pressure suddenly had a
size at a given speed, had a maximum operating pressure
large increase or the evaporation pressure suddenly
and a corresponding minimum flow. When the flow to the
reduced due to the problem of the ammonia system, the
compressor is lower than this minimum value, surge will
compressor inlet flow would be too small. It could not effec-
occur.
tively avoid compressor surge. The compressor was not
The original antisurge control scheme (before retrofit) of
operating safely.
the ammonia compressor, is shown in Figure 1, (using the
-20 ˚C evaporation system’s ammonia compressor, C-501 Antisurge control after the retrofit
as example). To reduce the energy lost from the entire system and to
The process control flow shows the ammonia compres- operate the compressor safely, this retrofit replaced the
sor has two antisurge control valves. One is the cold flow compressor’s antisurge control system. The theory of this
antisurge valve (UV-501). The ammonia gas at the final dis- control system is variable constrain antisurge control. The
charge of the ammonia compressor is returned to the antisurge controller will control the compressor along the
ammonia separation drum at the inlet of the compressor safety operation line on the right hand side of the surge limit
after cooling. line to minimise the opening of the antisurge valve and to
The other was the hot flow antisurge valve (HV-501). reduce the amount of energy lost. The control system
The ammonia gas at 123 ˚C from the final discharge is design is shown in Figure 2 (still using -20 ˚C evaporation
returned directly to the ammonia separation drum of the system ammonia compressor, C-501 as example).
compressor inlet. The cold recycle antisurge control valve Firstly the CCC (Compressor Controls Corporation,

Reprinted from HYDROCARBON ENGINEERING NOVEMBER 2003


67-72 25/11/03 10:24 Page 68

 qV1 is the volumetric flow rate at compressor suction


conditions.
 p2 is the absolute discharge pressure.
 p1 is the absolute suction pressure.
 T1 is the absolute suction temperature.
 a and b are parameters determined by compressor char-
acteristics.
If, (
is less than, )
compressor will not surge;
If, is equal or higher than,
( )
compressor will go into surge state.
To further analyse the above antisurge protection equa-
Figure 1. Antisurge control diagram of compressor tion, we have the following formula:
C-501 before retrofit.

(2)

(3)

where:
 A is the flow measuring device constant.
 ∆p1 is the differential pressure across flow measuring
device at compressor suction.
 ρ1 is the gas density at compressor suction conditions.
 M is gas molecular weight.
 Z1 is the gas compressibility factor at compressor suc-
tion conditions.
 R0 is the universal gas constant.
From formula (2) and (3) we get the following equation:
Figure 2. Antisurge control diagram of compressor
C-501 after retrofit. (4)
P2/P1

where: is nearly a constant.


S3
S1
A From equations (1) and (4) we get the following surge
S2 limit equation,

CCC defined antisurge control through a criteria ‘Ss’


4000 5000 6000 7000
(5)
qv(m3-h-1)

Figure 3. Surge lines for first section of


compressor C-501. (proximity variable to surge):
where:

USA) solution is taken into consideration for antisurge con-


trol.

(1) (6)
 Rc is the compression ratio.
Suppose:

As shown in Figure 3, curve S1 is the surge limit line for


compressor C-501. Curve S2 is its surge control line. The
surge control line is on the right of the surge limit line, and (7)
the horizontal distance between them is called the flow safe- where:
ty margin. Normally, the surge limit line is defined as follows:
where:  K is the internal scaling parameter in CCC antisurge

Reprinted from HYDROCARBON ENGINEERING NOVEMBER 2003


67-72 25/11/03 10:24 Page 69

to the suction pressure as


P shown in Figure 4.
With suction throttling, the
relationship between the dis-
B charge pressure of the ammo-
nia compressor and mass flow
B1 A will change on the straight line
P1 between operating point A and
B2 the origin. After suction throt-
tling, the safe limit also moves
P2=0.8p creating a larger stable opera-
tion range, reducing the possi-
P3=0.6p bility of the compressor operat-
ing in surge. With the operating
point already moved very close
to the control line (compared to
hot recycle control, cold recycle
control increases 3% over the
flow margin), and the load
q (kg-h-1) needs to be reduced further.
v Opening the cold recycle valve
Figure 4. Regulate performance through suction throttle valve, p = discharge (UV-502) recycled flow plus the
pressure. flow required to meet the load
will be slightly greater than the
flow at the surge point. This pre-
vents the compressor from
controller.
going into surge. If the cold recycle valve is fully opened and
Substituting (7) into (6) we get:
still cannot make the operating point within the safe area, the
(8)
hot recycle valve (UV-503) will be opened for larger recycle
flow to avoid surge.
Adversely, when the load is increased, the inlet control
valve (UV-501) will be opened more. This is beneficial for anti-
If Ss ≥ 1, the compressor will surge. So the line connect-
surge control.
ing all the points where Ss is equal to 1 is the surge limit line.
Load balance among the parallel compressors was also
In order to allow the compressor to operate as close to the
realised through equalising individual ‘S’ values to optimise
surge point as possible, reducing energy consumption while
their performance.
ensuring the compressor will not go into surge, the CCC engi-
Another significant improvement of the new control sys-
neer performed a surge test. During the commissioning after
tem is to automatically decrease the compressor load when
the compressor safety interlock system had been put into
motor current reaches its high limit. This limit control loop can
use, the surge test was performed by changing the compres-
prevent the driven motor from overload trip.
sor inlet or discharge pressure, pushing compressor opera-
tion very close to surge (or at the surge point). For the actual
compressor surge limit line (the curve S1 in Figure 3), take The main scope of the retrofit
three surge points at different conditions and line them up The main scope of the retrofit included:
smoothly.
 Installation of CCC Series 4 antisurge control system.
Then, on the right hand side of the surge limit line by
 According to the requirement of the CCC control system,
adding some flow safety margin (approximately 9%) to the
perfection of the measuring instrumentation on the com-
surge limit line, we get the surge control line (the curve S2 in
pressors, including suction temperature, discharge tem-
Figure 3). The antisurge valve will open along this line. CCC
perature at each section, pressure transmitters, and a
uses another criteria ‘S’(proximity to surge control line) to
final discharge flow measuring device. To reduce the
define the surge control line:
pressure lost at the compressor suction, the inlet flow
S = Ss + m (9) measuring openings were replaced with Venturi pipes.
where:  Replacement of five hot recycle antisurge valves and two
 m is the safety margin applied to flow measuring signal. cold recycle antisurge valves in the ammonia compressor
In the antisurge loop, S is the control variable and 1 is its systems.
setpoint. When S is greater than 1, the antisurge loop will  For the purpose of ensuring the precision of the antisurge
begin to open the recycle valve. When S is less than 1, the control and expanding the antisurge control range, the
antisurge loop will begin to close the recycle valve. refinery discussed with CCC the final antisurge control
This control solution also uses the throttle control valve on solution when the operating point runs closer to the surge
the suction line to regulate the discharge pressure of the sep- protection line. In this instance the cold recycle valve
aration drum (load share control). would be opened first. If it cannot meet the antisurge
When the load is decreased, compressor suction pres- requirement, the control will be on the hot recycle then
sure is decreased and the inlet control valve (UV-501) is used inlet throttling butterfly valve. This would increase the anti-
to throttle the flow. After suction flow is throttled, when rota- surge control range and maintain the precision of the anti-
tional speed is constant, the characteristic of volumetric flow surge control. This control solution cannot be realised in a
and compression ratio of ammonia compressor remains the traditional control system.
same. As suction pressure decreases, the ammonia com-  Removal of five excitation panels for the synchronised
pressor mass flow and discharge pressure decreases in ratio motor. Removal of five starting devices for the synchro-

Reprinted from HYDROCARBON ENGINEERING NOVEMBER 2003


67-72 25/11/03 10:24 Page 70

nised motor. Removal of 10 control and switching panels with November 1998, reduced by 288 760 kWh.
for the synchronised motors. Removal of five synchro-  The power consumption of December 1999 compared
nised motor ventilation systems and five synchronised with December 1998, reduced by 238 080 kWh.
motors. Removal of two auxiliary power switching panels The energy reduction was also due to the removal of the
and original power and control cables. original auxiliary equipment, such as the ventilator, excitation
 Installation of five sets of induction motors, each with equipment, starting devices, etc. The synchronised motors
1600 kW rated power. Installation of seven new power were replaced by more efficient induction motors (the original
switching panels, two operating consoles, installation of a synchronised motor was rated 1500 kW at 179 A. The new
new lighting switching panel, installation of 6000 V induc- induction motor was 1600 kW at 182 A. Thus the rated power
tion motor power cables 500 m, and 5000 m instrumenta- increased by 100 kW, while the maximum current only
tion cables etc. increased by 3 A.)
The MEK/Benzen dewaxing unit had an average pro-
Conclusion cessing capacity of 600 000 tpy. Calculating using the cost of
This retrofit was implemented in July 1999. The units were in electricity as 0.55 Yuan/kWh. The refrigeration station can
operation at once. It was in continuous operation for more reduce the power consumption by 1.56kWh per t of material.
than one year. The annual saving will be 1.56 x 600 000 x 0.55 = 514 800
The refrigeration station load optimisation and compres- yuan (1 US$ = 8.26 Yuan).
sors antisurge control system were in fully automatic control Another key benefit from retrofit is the avoidance of an
and the compressors and station operation were smooth. unscheduled shutdown. Before the retrofit, annual unsched-
According to the compressor operating curve display, the uled shutdown ranged between 5 - 10 times. Effectively, there
compressors’ operating status can be observed very clearly has been no unscheduled shutdown after the retrofit. The
and easily. They reduced the workload of the operators, and economic benefit is certainly more significant than the energy
increased compressor reliability for safe operation and savings alone.
process stability.
Great economical benefits were achieved by using a vari- References
1. GUO QING TONG, BAI SHOU SAN, ZHAO WEI XIN, Cryogenics
able limiting flow control solution, effectively controlling the
Engineering Manual, Published by China Construction Industry
recycle flow of the ammonia gas and greatly reducing energy Publishing House, Beijing, 1985.
consumption of the compressors. 2. LU DE MIN, Petrochemical Automation Control Design Manual, 3rd
Edition, Published by Chemical Industry Publishing House, Beijing, 1993.
The process unit electrical power consumption was
3. JIANG MAO SUN, YU QUAN SHOU, Process Control Engineering,
greatly reduced: SINOPEC Publishing House, Beijing, 1988.
 The power consumption of October 1999 compared with 4. ‘Using the Series 4 Antisurge Controller’, Publication UM4102 (3.3),
Compressor Controls Corporation, 2001.
October 1998, reduced by 194 660 kWh. 5. ‘Using the Series 4 Performance Controller’, Publication UM4104 (3.1.1),
 The power consumption of November 1999 compared Compressor Controls Corporation, 1999.

Compressor Controls Corporation


International Headquarters
4725 121-st Street
Des Moines IA 50323-2316 USA
Phone: 515-270-0857
e-mail: solutions@cccglobal.com
www.cccglobal.com

CCC Worldwide:
Houston, Texas USA - Rio de Janeiro, Brazil - London, UK - Amsterdam, The
Netherlands - Milan, Italy - Moscow, Russia - Singapore, Republic of Singapore
- Dammam, Saudi Arabia - Dubai, United Arab Emirates - Beijing, China
Publication #MS123 Reprinted from HYDROCARBON ENGINEERING NOVEMBER 2003

Das könnte Ihnen auch gefallen