Basic Setup
===========
System Type 3Ph 3Wire Ungrounded Wye
CT Primary 5000
CT Secondary 5 Amp
VT Primary 120
VT Secondary 120 Volts
Nominal Voltage 460
Nominal Current 5
Nominal Frequency 60 Hz
Nominal Power Factor 0,8
Phase Rotation ABC
Device Label
============
Meter Identification Power Meter
Metering Standards
==================
Load Timer Setpoint 5
Peak Current Demand 0
Demand Setup
============
Power Demand Mode Timed Interval Block
Power Demand Interval 15 minutes
Power Demand DO Association None
Multi-Tariff
============
Tariff Mode Time of Day
Energy Pulsing
==============
Front Panel LED
Control Disabled
Digital Output D1
Control Alarm
Digital Output D2
Control Alarm
Input Metering
==============
InpMtr Chan 1
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate No units
Assigned Inputs None
InpMtr Chan 2
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate No units
Assigned Inputs None
InpMtr Chan 3
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate
Assigned Inputs None
InpMtr Chan 4
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate No units
Assigned Inputs None
I/O Setup
=========
Digital Input S1
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds
Digital Input S2
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds
Digital Input S3
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds
Digital Input S4
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds
Digital Output D1
Type Digital Output
Control Mode Alarm
Behavior Mode Normal
On Time 1 second
Digital Output D2
Type Digital Output
Control Mode Alarm
Behavior Mode Normal
On Time 1 second
Data Log #1
===========
Status Enable
Interval 15 minutes
Mode Circular
Channels 6
Channel 01 Active Energy Delivered
Channel 02 Active Power Total
Channel 03 Apparent Energy Delivered
Channel 04 Current Avg
Channel 05 Reactive Energy Delivered
Channel 06 Voltage L-L Avg
Alarming
========
Over Phase Current Disabled