Meter Configuration Report for Meter1 (SN# 600071766)

Report created on jueves, 16 de mayo de 2019 17:18:17


Report generated by RV-FTS

Basic Setup
===========
System Type 3Ph 3Wire Ungrounded Wye
CT Primary 5000
CT Secondary 5 Amp
VT Primary 120
VT Secondary 120 Volts
Nominal Voltage 460
Nominal Current 5
Nominal Frequency 60 Hz
Nominal Power Factor 0,8
Phase Rotation ABC

Device Label
============
Meter Identification Power Meter

Metering Standards
==================
Load Timer Setpoint 5
Peak Current Demand 0

Front Panel Display


===================
Contrast 5
Screen Timeout 0
Backlight Timeout 5
Language Spanish
Date Format MM/DD/YYYY
Time Format 24 Hr
HMI Mode IEC

Serial Port Settings


====================
Protocol Modbus RTU
Address 30
Baud Rate 19200
Parity Even

Advanced Serial Settings


========================
Modbus Mode Slave Mode
Modbus Broadcast Disabed
Response Timeout 3 seconds
Delay Between Frames 50 milliseconds
Silent Interval Extension 6 characters

Demand Setup
============
Power Demand Mode Timed Interval Block
Power Demand Interval 15 minutes
Power Demand DO Association None

Current Demand Mode Timed Interval Block


Current Demand Interval 15 minutes
Current Demand DO Association None

Input Demand Mode Timed Interval Block


Input Demand Interval 15 minutes
Input Demand DO Association None

Clock Sync Offset 0:00

Multi-Tariff
============
Tariff Mode Time of Day

Energy Pulsing
==============
Front Panel LED
Control Disabled

Digital Output D1
Control Alarm

Digital Output D2
Control Alarm

Input Metering
==============

InpMtr Chan 1
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate No units
Assigned Inputs None

InpMtr Chan 2
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate No units
Assigned Inputs None

InpMtr Chan 3
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate
Assigned Inputs None

InpMtr Chan 4
Pulse Weight 0.00000
Mode Pulse
Units No units
Rate No units
Assigned Inputs None

I/O Setup
=========
Digital Input S1
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds

Digital Input S2
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds

Digital Input S3
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds

Digital Input S4
Type Digital Input
Control Mode Normal
Debounce 10 milliseconds

Digital Output D1
Type Digital Output
Control Mode Alarm
Behavior Mode Normal
On Time 1 second

Digital Output D2
Type Digital Output
Control Mode Alarm
Behavior Mode Normal
On Time 1 second

Data Log #1
===========
Status Enable
Interval 15 minutes
Mode Circular
Channels 6
Channel 01 Active Energy Delivered
Channel 02 Active Power Total
Channel 03 Apparent Energy Delivered
Channel 04 Current Avg
Channel 05 Reactive Energy Delivered
Channel 06 Voltage L-L Avg

Alarming
========
Over Phase Current Disabled

Under Phase Current Disabled

Over Neutral Current Disabled

Over Ground Current Disabled

Over Voltage L-L Disabled

Under Voltage L-L Disabled

Over Voltage L-N Disabled


Under Voltage L-N Disabled

Over Active Power Disabled

Over Reactive Power Disabled

Over Apparent Power Disabled

Leading True PF Disabled

Lagging True PF Disabled

Leading Disp PF Disabled

Lagging Disp PF Disabled

Over Present Active Power Demand Disabled

Over Last Active Power Demand Disabled

Over Predicted Active Power Demand Disabled

Over Present Reactive Power Demand Disabled

Over Last Reactive Power Demand Disabled

Over Predicted Reactive Power Demand Disabled

Over Present Apparent Power Demand Disabled

Over Last Apparent Power Demand Disabled

Over Predicted Apparent Power Demand Disabled

Over Frequency Disabled

Under Frequency Disabled

Over Voltage Unbalance Disabled

Over Voltage THD Disabled

Phase Loss Disabled

Digital Alarm S1 Disabled

Digital Alarm S2 Disabled

Digital Alarm S3 Disabled

Digital Alarm S4 Disabled

Meter Power Up Enabled


Priority Low (3)
Associated Digital Outputs None

Meter Reset Enabled


Priority Medium (2)
Associated Digital Outputs D2
Meter Diagnostic Disabled

Phase Reversal Disabled

Logic Alarm 1 Disabled

Logic Alarm 2 Disabled

Logic Alarm 3 Disabled

Logic Alarm 4 Disabled

Logic Alarm 5 Disabled

Logic Alarm 6 Disabled

Logic Alarm 7 Disabled

Logic Alarm 8 Disabled

Logic Alarm 9 Disabled

Logic Alarm 10 Disabled

Custom Alarm 01 Disabled

Custom Alarm 02 Disabled

Custom Alarm 03 Disabled

Custom Alarm 04 Disabled

Custom Alarm 05 Disabled