Sie sind auf Seite 1von 7

2.

TECHNICAL DATA

2.1. Self supporting 3-wire 24 kV cable with conductive mesh, possibility of laying in the ground,
overhead and water uninterrupted without cable connection, overground range of at least 80
m, current load at overhead installation at least 70 A at outdoor temperature temperature
65 C, allowable laying temperature is less than -15 C, (No. 1 in BOQ).
o o

unit needed offered

1. General

Manufacturer: -

Country: -

label of cable type: -

cable construction: 3-wire

Rated cable voltage: kV 24

Nominal frequency: Hz 50

Total Diameter: mm ≤ 42

IEC 60502-2/05
According to IEC 60502-2/05,IEC 60322-3/92 yes/no
IEC 60322-3/92

2. CONSTRUCTIVE CHARACTERISTICS OF THE CABLE

2.1. Conductor

Material: Cu

Nominal cross section: mm2 10

Diameter mm ≤ 3,60

Max resistance at 200C: Ω/km R≤1,85

2.2. Conductor screen

Material: conductive XLPE

2.3. Insulation

Material: XLPE

Nominal thickness: mm < 5,7

Diameter: mm < 16

Signature: ___________________________ Date:_______________

5/11
unit needed offered

2.4. Insulation screen

Material: conductive XLPE

2.5. Cable screen

Cu protected from
Material:
corrosion

design mesh

2.6. External protective shield

Material: yes/no LLD PE

Nominal thickness: mm < 2.7

Needed:Manufacturer's name, year of production, label series cable type, conductor/screen construction
Label: U0/U (Um) length in meters
Offered:

3. MECHANICAL CHARACTERISTICS

3.1. possibility of laying in the ground, overhead and


yes
water continuously without coupling
3.2. minimum permissible cable laying o
C ≤ -15
temperature

3.3. net weight of the cable kg/m ≤ 1,25

3.4. calculation force for the cable kN ≥ 8.5

3.5. the average dynamic force of the cable breaking kN ≥ 22

3.6. the average static power of slow cable breaking kN ≥ 15

3.7. maximum permissible range between poles at


m ≥ 80 m
overhead laying:

4. ELECTRICAL CHARACTERISTICS

4.1. Minimum permissible continuous conductor current


- in air (self supporting) at 25 oC air temp
and 65oC conductor temp. A 70
- in ground at 15 oC environment temp and 90 A 90
o
C conductor temp.

4.2. Permissible short-term tolerable current (1s) at kA ≥ 2.0


250oC

4.3. Permissible earth-connection current A/km ≥ 1,1

Signature: ___________________________ Date:_______________

6/11
2.2. Self supporting 3-wire 24 kV cable with conductive mesh, possibility of laying in the ground,
overhead and water uninterrupted without cable connection, overground range of at least
110 m, current load at overhead installation at least 160 A at outdoor temperature 65oC,
allowable laying temperature is less than -15 oC, (No. 2 in BOQ).

unit needed offered

1. GENERAL

Manufacturer: -

Manufacturer country: -

Label of cable type: -

cable construction: 3-wire

Rated cable voltage: kV 24

Nominal frequency: Hz 50

total diameter mm ≤ 50

IEC 60502-2/05
according to IEC 60502-2/05,IEC 60322-3/92 yes/no
IEC 60322-3/92

2. CONSTRUCTIVE CHARACTERISTICS OF THE CABLE

2.1. CONDUCTOR

Material: Al alloy

Nominal cross section: mm2 70

diameter mm ≤ 10

max resistance at 200C: Ω/km R<0,45

2.2. conductor screen

Material: conductive XLPE

2.3. Insulation

Material: XLPE

Nominal thickness: mm ≤ 4,5

diameter: mm ≤ 20

Signature: ___________________________ Date:_______________

7/11
unit needed offered

2.4. Insulation screen

Material: conductive XLPE

2.5. Cable screen

Cu protected
Material:
from corrosion

Izvedba mesh

2.6. External protective shield

Material: yes/no LLD PE

Nominal thickness: mm ≤ 2,7

Needed:name of manufacturer production year serie label cable type conductor/screen construction U0/U
Label: (Um) lenght
Offered:

3. MECHANICAL CHARACTERISTICS

3.1. possibility of laying in the ground,overhead and


yes
water continuously without coupling
3.2. minimum permissible cable laying o
C ≤ -15
temperature

3.3. net weight of the cable kg/m ≤2

3.4. calculation force for the cable kN ≥ 27

3.5. the average dynamic force of the cable breaking kN ≥ 56

3.6. the average static power of slow cable breaking kN ≥ 49

3.7. maximum permissible range between poles at


m ≥ 110
overhead laying:

4. ELECTRICAL CHARACTERISTICS

4.1. Minimum permissible continuous conductor current


- in air (self supporting) at 25 oC air temp
and 65oC conductor temp. A ≥160
- in ground at 15 C ambient temp and 90 C
o o
A ≥190
conductor temp.

4.2. Permissible short-term tolerable current (1s) at kA ≥8


250oC

4.3. Permissible earth-connection current A/km ≥ 2,6

Signature: ___________________________ Date:_______________

8/11
3. DRAWINGS

3.1. Carrying clamp with rubber insert (like SO86) for 3-wire self supporting universal cable
conductor diameter 3x10 mm (No. 3 in BOQ).
2

3.2. angle double suspension console for 3wire self supporting universal cable 3x10 mm (No.
2

4 in BOQ).

9/11
3.3 Tightening end-of-spiral suspension ( like PLP 130-GRD-38 ) for 3-wire self supporting
universal cable with conductor diameter 3x10 mm (No. 9 in BOQ)..
2

3.4 Tightening end-of-spiral suspension ( like PLP 200-GRD-44/48/C/I ) for 3-wire self supporting
universal cable 3x70mm (No. 10 in BOQ).
2

Note: Tightening clamps must be adapted to the required forces

10/11
3.5. Cable labeling nameplates
Material PVC, dimensions 220x80mm (ž(yellow background, black letters, red triangle, black arrow),
UV resistant, waterproof with montage holes , (No. 11 and 12 in BOQ).

11/11

Das könnte Ihnen auch gefallen