Beruflich Dokumente
Kultur Dokumente
ir
http://www.itrans24.com/landing1.html
4628 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
Abstract—The integration of converter-interfaced distributed control philosophy [4]. Therefore, a high-quality voltage is en-
generation in microgrids has raised several technical issues, sured in each node of the microgrid, without any kind of extra
including the successful operation of protective devices during physical communication among the DERs [5].
faults. The protection issue is associated with the lack of large In case of a fault within a microgrid, the converter-interfaced
current injection during a fault, due to limits imposed by the
semiconductor switches. This paper proposes a fault-detection and
DERs are not able to contribute with large currents, as rotating
clearing control strategy method for symmetrical and asymmet- machines do [6], [7]. The fault-current capability of a converter-
rical line faults in a looped microgrid. The protection devices are interfaced DER is limited by the short-time current carrying
simple overcurrent devices with the same settings, due to the looped capacity of the semiconductor switches. The protection problem
microgrid topology. The proposed method is applied without using is even more severe in case of grid absence. In grid-connected
any kind of physical communication. The fault is detected by mea- mode, a large current can be fed from the main grid in order
suring indirectly the microgrid impedance. After the fault identifi- to detect and clear the fault [8], [9]. Previous published works
cation, the distributed energy resources (DERs) adjust their control propose the disconnection of the distributed generation during
in order to inject a current proportional to the measured micro-
the fault [10], [11]. However, such a practice cannot be adopted
grid impedance, according to a droop curve. This means that the
DER closer to the fault injects a relatively larger current, achieving in the modern grids, due to the high penetration of the converter-
by this way a selective coordination of the protection means. The interfaced distributed generation.
effectiveness of the proposed control strategy is evaluated through In the literature, the available protection techniques are based
detailed simulation and experimental tests. either on communication, local measurements, or the use of
external devices. The communication-based methods solve the
Index Terms—Distributed energy resources (DERs), droop con-
trol, microgrid protection, overcurrent devices.
protection problem by adjusting automatically the relay settings
by means of online communication systems [12]–[16]. In [12],
an extensive communication infrastructure is needed in order to
I. INTRODUCTION update the relays’ settings in an adaptive way, while in [13] a
Central Protection Unit is also added. In differential protection
HE microgrid is considered as a new approach of power
T generation and delivery system that contains converter-
interfaced distributed energy resources (DERs) and loads, along
[14], [15], a methodology for setting the differential relays prop-
erly is proposed, while in [15], communication-assisted relays
are used. In overcurrent protection [16], the fault event is rec-
with traditional rotating machines, forming a small controllable ognized by local measurements and is cleared by interbreaker
subsystem [1]. The subsystem should be able to operate either communication means. The settings of the relay are again up-
grid-connected or isolated depending on factors, such as the un- dated by a supervisory controller. The drawback of these meth-
availability of the main grid or economic reasons. Due to the ods is that the possible configurations of the microgrid should be
renewable energy growth, the microgrids present a high prolif- known before the protection implementation [17]. On the other
eration of dc/ac and ac/dc/ac converters [2]. In order to capital- hand, other methods use new type of relays based on local mea-
ize their benefits, the converter-interfaced DERs are required to surements, without the necessity of communication. In [18], the
conduct several operations, including the proper voltage and fre- voltage magnitude is used to recognize the fault, and in [19], the
quency control, the power demand sharing, the fault ride through current is measured by utilizing the principles of synchronized
capability, and the seamless transition between the operation phasor measurements. In [20], the distance from the fault is
modes. These requirements present new challenges to melio- calculated by measuring the line admittance, in order to change
rate the control strategy and tackle with the protection issues in the relay settings properly without any need for communica-
microgrids consisting of converter-interfaced sources [3]. tion, while in [21], the coordination of digital relays based on
When the microgrid operates islanded in steady-state mode, wavelet packet transform is used for detecting and clearing the
the active and reactive power of the connected DERs can be faults. Finally, there are methods that propose the use of external
determined by the frequency and the voltage magnitude of the devices, such as energy storage systems with high fault current
common ac bus, respectively, through the principles of the droop capability (e.g., flywheels) [22] and fault current limiters [23].
The latter methods, as well as the differential methods, are still
Manuscript received April 8, 2014; revised December 5, 2014 and June 26, considered as very expensive protection solutions.
2015; accepted August 31, 2015. Date of publication September 14, 2015; date
of current version January 7, 2016. Recommended for publication by Associate This paper proposes a novel symmetrical and asymmetrical
Editor Q.-C. Zhong. fault-detection and clearing process for looped microgrids with
The authors are with the Electrical Machines Laboratory, Department of Elec- converter-interfaced DERs, without using expensive protective
trical and Computer Engineering, Aristotle University of Thessaloniki, Thessa- devices or physical communication link. The fault clearing is
loniki P.C. 54124, Greece (e-mail: oureili@yahoo.gr; chdimoul@auth.gr).
Color versions of one or more of the figures in this paper are available online carried out by the coordination of simple overcurrent protection
at http://ieeexplore.ieee.org. devices (OPD). Due to the looped topology of the microgrid,
Digital Object Identifier 10.1109/TPEL.2015.2476702 the loads can be placed arbitrarily; thus, each OPD should have
0885-8993 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html
OUREILIDIS AND DEMOULIAS: FAULT CLEARING METHOD IN CONVERTER-DOMINATED MICROGRIDS WITH CONVENTIONAL 4629
4630 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
OUREILIDIS AND DEMOULIAS: FAULT CLEARING METHOD IN CONVERTER-DOMINATED MICROGRIDS WITH CONVENTIONAL 4631
C. Fault-Protection System Design the switching of loads. For this reason, the proposed protec-
tion method cannot be applied in such cases. Instead, advanced
When a fault is identified with the aforementioned method, fault-detection devices (e.g., differential current measurement at
the protection device closer to the fault should be activated first, each branch) and additionally a communication system among
in order to disconnect only the faulty part. The protection devices the protection devices and the microgrid inverters are necessary.
can be circuit breakers (CBs) with simple overcurrent tripping, In case of a line fault within an islanded looped microgrid, the
which are triggered by measuring a current larger than the rated DERs should inject a large enough current, so that 1) the CBs
one. However, in a converter-dominated islanded microgrid, the at both ends of the faulty line are activated and 2) the current in
injected currents are limited to only a few times the nominal these two CBs is larger than the current in the remaining micro-
one for protecting the semiconductor switches. Another prob- grid CBs. Since the load still absorbs current during the fault,
lem with low-voltage microgrids is the relatively large voltage this current should be taken into account, when determining the
drops and power losses during the fault due to the large line injected by the DERs current. The worst case occurs when the
impedances. During the fault, the RL-type loads still absorb total microgrid load is assumed to be aggregated at just one
current and a significant active power is needed to cover the node. The contribution of each DER is considered separately,
increased losses. The situation is even worse in case of a high- taking into consideration the relative position of the DER with
impedance fault. Therefore, mainly active power is required respect to the load and the fault, as shown in Fig. 5. In this
during the fault due to the large ohmic losses on the distribution case, the current that flows through CB1 is calculated by con-
lines and for the remaining active power absorbed by the loads sidering two subcases. In the first, presented in Fig. 5(a), the
under reduced voltage. The required reactive power is much DER is closer to CB1 , while in the second [see Fig. 5(b)], the
less than the active one and corresponds to the consumption load is closer to CB1 . The magnitude of the corresponding fault
on the inductive parts of the distribution lines and loads under currents is calculated from (11) and (12)
reduced voltage. In case the available active power from the
DERs is not sufficient, an appropriately sized supercapacitor ZL (ZLF + ZL S ) + ZL S (ZLF + Rf ) ¯
I¯fa = Isf (11)
ESS is assumed to be connected in the dc link of each DER. The Ztot (ZL + ZLF + Rf ) − ZLF
2
supercapacitor bank with the dc/dc converter and its respective ZSF ZL − Rf ZL S
cost per energy unit are analytically presented in [32], while its I¯fb = ¯
2 Isf (12)
cost can be assumed to be of the order of €25/Wh. The sizing Ztot (ZL + ZLF + Rf ) − ZLF
of the supercapacitor depends on the nominal power of each where I¯sf is the injected current by the source, ZL is the
DER and the time duration of the fault clearing. In low-voltage impedance of the aggregated load, Ztot is the aggregated line
grids, the fault is cleared within 1–3 s. The supercapacitor will impedance, ZLF is the impedance among the load and the fault,
start discharging in order to keep the dc-link voltage constant ZSF is the impedance among the source and the fault, ZL S is
if the active power available from the renewable source is not the impedance among the load and the source, and Rf is the
sufficient. Obviously, the discharge current of the supercapac- fault impedance. In general, the aggregated fault currentI¯f , as-
itor ESS is determined by each DER during the fault, as it is suming that N sources contribute to the CB with current I¯fa and
explained later, keeping the dc-link voltage constant. Thus, it M sources with I¯fb , can be calculated as
acts as replacement of the missing renewable active power for
the 1–3 s of the fault. In case such an energy storage device is N
ZL i (ZL F i + ZL S i ) + ZL S i (ZL F i + Rf ) ¯
absent, the proposed protection system will not function prop- I¯f = Isf i
Ztot (ZL + ZL F i + Rf ) − ZL2 F i
erly, because the active power needed to feed the fault will not i=1
be available, leading to a collapse of the dc voltage of the DERs
M
ZS F j ZL − Rf ZL S j
and, thus, the collapse of the whole microgrid. + I¯sf j . (13)
Furthermore, it should be mentioned that in low-voltage dis- j =1
Ztot (ZL + ZL F j + Rf ) − ZL2 F j
tribution networks, there might be line faults with currents lower
than the rated CB currents. Such faults cause very limited vari- The rms value of this current should exceed the rated current
ation in the impedance seen by the DERs, which is similar to of the CB, in order for the CB to be tripped according to the
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html
4632 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
OUREILIDIS AND DEMOULIAS: FAULT CLEARING METHOD IN CONVERTER-DOMINATED MICROGRIDS WITH CONVENTIONAL 4633
4634 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
TABLE II
ELECTRICAL PARAMETERS OF LOADS
TABLE III
RMS VALUE OF DER CURRENTS [A] IN PHASE A
OUREILIDIS AND DEMOULIAS: FAULT CLEARING METHOD IN CONVERTER-DOMINATED MICROGRIDS WITH CONVENTIONAL 4635
TABLE IV
RMS VALUE OF CURRENTS [A] AT SOLID THREE-PHASE FAULT WITH THE
PROPOSED CONTROL STRATEGY AND TRIPPING TIME WITH CBS EQUIPPED
WITH EXTREMELY INVERSE-TIME CURVE (18) OR WITH I2 t RELEASE1
Row CB1 CB2 CB3 & 4 CB5 & 6 CB7 & 8 CB9 & 1 0 CB1 1 & 1 2
1
Δ t: time discrimination between a CB and the tripped one, Trip time: the time it takes a
CB to trip after sensing a certain current.
Fig. 12. (a) Current [A] through the CBs at the transition from normal to fault
operation. (b) Current [A] through the CBs at the transition from fault to normal
operation. (c) Output current [A] of phase a of each DER at the transition from
normal to fault operation. (d) Output current [A] of phase a of each DER at the
transition from fault to normal operation.
Fig. 11. (a) Parameter c of the proposed droop curve. (b) Reference currents is larger in case of using CBs equipped with I2 t release. Further-
Id re f and Iq re f of current control of DER1 . With In o m is denoted the nominal more, the tripping time is larger in case of implementing CBs
current of DER1 .
equipped with I2 t release, requiring larger supercapacitors. The
instantaneous current waveforms are illustrated in Fig. 12. From
(e.g., 15 cycles in [19]). During the fault, the rms value of CB1 these figures, it can be noticed that the DERs switch from droop
is 91.37 A, which is larger than the rated current, and conse- control to current control mode in approximately one period of
quently, it is triggered at t = 1.826s, i.e., the response time of the fundamental frequency, increasing the injected currents to
this CB is 0.806 s. After the trigger of CB1 , the fault current c times the nominal ones. The parameter c is different for each
that flows through CB2 becomes 161.64 A, and finally, it trips at individual DER [see Fig. 11(a)], since it depends on the location
t = 1.988 s (i.e., 162 ms after the triggering of CB1 ), isolating of the DER with respect to the location of the fault. It can be
the faulty segment of the microgrid. The triggering time of each deduced that the desired selectivity is achieved successfully.
CB can be verified by (18). Thus, CB1 and CB2 are correctly When the fault is cleared, the microgrid voltage returns to
tripped first, as being closer to the fault. This proves that the se- the steady-state operation. The control of the DERs remains in
lectivity coordination is carried out by the injected currents from current control mode, until parameter Vm gd rm s surpasses the λs
the DERs. The rms values of the output currents of phase a of threshold at t = 2.03 s, as shown in Fig. 9. Thus, at this moment,
each DER are presented in Table III (the per unit values are also the DERs switch to droop control again (see Fig. 11), which is
given in parenthesis), while the respective rms values of the CBs reflected in new steady-state currents, as illustrated in Fig. 12(d).
are listed in Table IV. Table IV also presents the tripping time The variation of the reference currents Idref and Iq ref of DER1
of CBs adopting the extremely inverse time curve of (18) (rows during the simulation test can be seen in Fig. 11(b). When
2 and 7) and the alternative type of I2 t characteristic (rows 4 and DER1 operates in droop control mode, the reference currents are
9). It is obvious from Table IV that the selectivity is ensured, first calculated from the output of the voltage controller. During the
for CB1 and then for CB2 , while the respective time difference fault, the DER control switches from droop to current control
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html
4636 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
TABLE VI
RMS VALUE OF CURRENTS [A] AT HIGH-IMPEDANCE FAULT
WITH CURRENT COEFFICIENT c = 3
t [s] CB1 CB2 CB3 & 4 CB5 & 6 CB7 & 8 CB9 & 1 0 CB1 1 & 1 2
Fig. 15. Feedback d-axis voltage V m g d rm s [V] from the OSG-SOGI PLL of
phase A.
Fig. 14. Parameter c of the proposed droop curve.
TABLE V
RMS VALUE OF CURRENTS [A] AT HIGH-IMPEDANCE FAULT
WITH THE PROPOSED CONTROL STRATEGY
t [s] CB1 CB2 CB3 & 4 CB5 & 6 CB7 & 8 CB9 & 1 0 CB1 1 & 1 2
B. High-Impedance Three-Phase Fault Fig. 16. Three-phase voltage profile [V] at the point of connection of load
L 1 : (a) during all the simulation time period and (b) during the fault-detection.
In this simulation case, the fault impedance is Rf = 0.5 Ω.
The fault takes place at t = 0.5 s. The difference between a solid
and a high-impedance fault is reflected in the variation of the 0.35 Ω and the fault occurs at t = 0.5 s. The objective dur-
parameter c, which determines the injected currents during the ing an asymmetrical fault is that the healthy phases should re-
fault. The discretization is better in case of a high-impedance main unaffected. The fault-detection parameter Vm gd rm s , as it
fault, as the measured microgrid impedance is larger for all is measured by the OSG-SOGI PLL of the voltage of phase a,
DERs. The feedback voltage Vm gd rm s and the respective impact appears in Fig. 15. At t = 1.913 s, the CB1 of phase a trips,
on the parameter c are illustrated in Figs. 13 and 14. In this test, while at t = 2.123 s, CB2 of phase a trips too, isolating the
the current of CB1 becomes equal to 76.62 A, causing its tripping fault. The overcurrent sensors of the healthy phases do not
at t = 2.5 s. Subsequently, the current of CB2 becomes equal to sense any fault, because their currents continue to be as in the
142.94 A, causing its tripping at t = 2.76 s. The rms value of prefault condition.
the currents at each CB appears in Table V. The three-phase voltage at the point of connection of load
In order to show the effectiveness of the proposed method for L1 is presented in Fig. 16. The voltage of the faulty phase
implementing the selectivity with the simple overcurrent CBs, a decreases during the fault, while the healthy phases remain
the same simulation is carried out, but now coefficient c is set unaffected by the fault. Furthermore, after the fault clearance,
equal to 3 for all DERs. The rms values of each CB current are the voltage recovers very quickly, with a seamless transient.
presented in Table VI. First, CB1 is correctly activated. How- The parameters c of the currents are shown in Fig. 17(a), while
ever, consequently, the current through CB7&8 is the larger one, Table VII indicates the rms value of phase a currents through
activating them incorrectly and isolating the microgrid segment each CB. It is evident that proper selectivity has been achieved
that includes the two loads and the DER2 . for asymmetrical faults, too. Fig. 17(b)–(e) presents the DER
phase currents. The current of the faulty phase a is increased
when the fault is identified, while the currents of the healthy
C. High-Impedance Phase-to-Ground Fault
phases remain unaffected after a short transient. Furthermore,
The final case concerns a high-impedance phase a-to-ground it can be noticed that the control system detects the fault after
fault. In simulation terms, the fault resistance Rf is equal to approximately three cycles, while there is a transient period of
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html
OUREILIDIS AND DEMOULIAS: FAULT CLEARING METHOD IN CONVERTER-DOMINATED MICROGRIDS WITH CONVENTIONAL 4637
TABLE VII
RMS VALUE OF CURRENTS [A] AT HIGH-IMPEDANCE
PHASE-TO-GROUND FAULT
t [s] CB1 CB2 CB3 & 4 CB5 & 6 CB7 & 8 CB9 & 1 0 CB1 1 & 1 2
4638 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
Fig. 19. (a) Phase voltages [V] measured at the load at the transition from
normal to fault operation, (b) at the transition back to normal operation (red
line: phase a, blue line: phase b, green line: phase c). (c) Phase currents [A] at
branch L 1 at the transition from normal to fault operation, (d) at the triggering
of CB2 (red line: phase a, blue line: phase b, green line: phase c).
OUREILIDIS AND DEMOULIAS: FAULT CLEARING METHOD IN CONVERTER-DOMINATED MICROGRIDS WITH CONVENTIONAL 4639
Fig. 20. (a) Branch currents [A] at the transition from normal to fault opera-
REFERENCES
tion, (b) at tripping of CB2 , (c) at tripping of CB1 and transition back to normal [1] M. Fotuhi-Firuzabad, R. Iravani, F. Aminifar, N. Hatziargyriou, and
operation (blue line: branch L 1 , red line: branch L 2 , green line: branch L 3 , M. Lehtonen, “Guest editorial special section on microgrids,” IEEE Trans.
black line: branch L 4 ). (d) Output current [A] of each DER during fault (blue Smart Grid, vol. 3, no. 4, pp. 1857–1859, Dec. 2012.
line: DER1 , red line: DER2 ). [2] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodrı́guez, “Control of power
converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27,
no. 11, pp. 4734–4749, Nov. 2012.
[3] H. J. Laaksonen, “Protection principles for future microgrids,” IEEE
as in Section IV-A. First, the two poles of CB2 (corresponding Trans. Power Electron., vol. 25, no. 12, pp. 2910–2918, Dec. 2010.
[4] Y. A-R. I. Mohamed and E. F. El-Saadany, “Adaptive decentralized droop
to phases a and b) are activated, as the current of branch L2 is controller to preserve power sharing stability of paralleled inverters in
relatively larger than the current of branch L1 . Subsequently, distributed generation microgrids,” IEEE Trans. Power Electron., vol. 23,
the respective two poles of CB1 are triggered, and finally, the no. 6, pp. 2806–2816, Nov. 2008.
fault is cleared. Fig. 20(a)–(c) shows the current of phase a in [5] K. Oureilidis and C. Demoulias, “An enhanced role for an energy storage
system in a microgrid with converter-interfaced sources,” IET J. Eng.,
all branches, while Fig. 20(d) presents the current injections of 2014, Open-access.
the two DERs. It is evident that, with the proposed method, [6] P. Nuutinen, P. Peltoniemi, and P. Silventoinen, “Short-circuit protection
the healthy phase remains unaffected and the required overcur- in a converter-fed low-voltage distribution network,” IEEE Trans. Power
rents to achieve selective protection are focused only on the Electron., vol. 28, no. 4, pp. 1587–1597, Apr. 2013.
[7] N. Nimpitiwan, G. T. Heydt, R. Ayyanar, and S. Suryanarayanan, “Fault
faulty phases. current contribution from synchronous machine and inverter based dis-
Downloaded from http://iranpaper.ir
http://www.itrans24.com/landing1.html
4640 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 31, NO. 6, JUNE 2016
tributed generators,” IEEE Trans. Power Del., vol. 22, no. 1, pp. 634–641, [28] J. He, Y. W. Li, J. M. Guerrero, F. Blaabjerg, and J. C. Vasquez, “An island-
Jan. 2007. ing microgrid power sharing approach using enhanced virtual impedance
[8] T. Ghanbari and E. Farjah, “Unidirectional fault current limiter: An ef- control scheme,” IEEE Trans. Power Electron., vol. 28, no. 11, pp. 5272–
ficient interface between the microgrid and main network,” IEEE Trans. 5282, Nov. 2013.
Power Syst., vol. 28, no. 2, pp. 1591–1598, May 2013. [29] M. Ciobotaru, V. G. Agelidis, R. Teodorescu, and F. Blaabjerg, “Accu-
[9] T. Loix, T. Wijnhoven, and G. Deconinck, “Protection of microgrids rate and less-disturbing active antiislanding method based on PLL for
with a high penetration of inverter-coupled energy sources,” in Proc. grid-connected converters,” IEEE Trans. Power Electron., vol. 25, no. 6,
CIGRE/IEEE PES Joint Symp. Integr. Wide-Scale Renewable Resources pp. 1576–1584, Jun. 2010.
Power Del. Syst., 2009, pp. 1–6. [30] Voltage Characteristics of Electricity Supplied by Public Distribution Sys-
[10] B. Li, Y. Li, Z. Bo, and A. Klimek, “Design of protection and control tem, Standard EN 50160:2004, 2004.
scheme for microgrid systems,” in Proc. IEEE 44th Int. Universities Power [31] P. Rodriguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos, and D. Boroye-
Eng. Conf., 2009, pp. 1–5. vich, “Decoupled double synchronous reference frame PLL for power
[11] H. Wan, K. K. Li, and K. P. Wong, “An adaptive multiagent approach converters control,” IEEE Trans. Power Electron., vol. 22, no. 2, pp. 584–
to protection relay coordination with distributed generators in indus- 592, Mar. 2007.
trial power distribution system,” IEEE Trans. Ind. Appl., vol. 46, no. 5, [32] S. Gkavanoudis and C. Demoulias, “A combined fault ride-through and
pp. 2118–2124, Sep. 2010. power smoothing control method for full-converter wind turbines em-
[12] S. M. Brahma and A. A Girgis, “Development of adaptive protection ploying supercapacitor energy storage system,” Elect. Power Syst. Res.,
scheme for distribution systems with high penetration of distributed gen- vol. 106, pp. 62–72, Jan. 2014.
eration,” IEEE Trans. Power Del., vol. 19, no. 1, pp. 56–63, Jan. 2004. [33] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, “A new single-phase PLL
[13] T. S. Ustun, C. Ozansoy, and A. Ustun, “Fault current coefficient and structure based on second order generalized integrator,” in Proc. IEEE
time delay assignment for microgrid protection system with central pro- 37th Power Electron. Spec. Conf., 2006, pp. 1–6.
tection unit,” IEEE Trans. Power Syst., vol. 28, no. 2, pp. 598–606, May. [34] P. Rodrı́guez, A. Luna, R. S. Muñoz-Aguilar, I. Etxeberria-Otadui,
2013. R. Teodorescu, and F. Blaabjerg, “A stationary reference frame grid syn-
[14] M. Dewadasa, A. Ghosh, and G. Ledwich, “Protection of microgrids using chronization system for three-phase grid-connected power converters un-
differential relays,” in Proc. 21st Australasian Univ. Power Eng. Conf., der adverse grid conditions,” IEEE Trans. Power Electron., vol. 27, no. 1,
2011, pp. 1–6. pp. 99–112, Jan. 2012.
[15] E. Sortomme, S. S. Venkata, and J. Mitra, “Microgrid protection using [35] Maxwell Technologies, Maxwell BOOSTCAP Ultracapacitors—Small
communication-assisted digital relays,” IEEE Trans. Power Del., vol. 25, Module Technical Papers. (2013). [Online]. Available: http://www.
no. 4, pp. 2789–2796, Oct. 2010. maxwell.com/products/ultracapacitors/
[16] R. J. Best, D. J. Morrow, and P. A. Crossley, “Communication assisted
protection selectivity for reconfigurable and islanded power networks,” in
Proc. IEEE 44th Int. Univ. Power Eng. Conf., 2012, pp. 1–5.
[17] S. Mirsaeidi, D. M. Said, M. W. Mustafa, M. H. Habibuddin, and Kimia
Ghaffari, “An analytical literature review of the available techniques for
the protection of micro-grids,” Int. J. Elect. Power Energy Syst., vol. 58,
pp. 300–306, Jun. 2014.
[18] R. M. Tumilty, M. Brucoli, G. M. Burt, and T. C. Green, “Approaches to Konstantinos O. Oureilidis (M’07) was born in
network protection for inverter dominated electrical distribution systems,” 1984. He received the Dipl. and Ph.D. degrees in
in Proc. 3rd IET Int. Conf. Power Electron., Mach. Drives, 2006, pp. 622– electrical engineering from the Aristotle University
626. of Thessaloniki, Thessaloniki, Greece, in 2008 and
[19] M. A. Zamani, T. S. Sidhu, and A. Yazdani, “A protection strategy 2015, respectively.
and microprocessor-based relay for low-voltage microgrids,” IEEE Trans. He is currently a Researcher in the Electrical
Power Del., vol. 26, no. 3, pp. 1873–1883, Jul. 2011. Machines Laboratory, Department of Electrical and
[20] M. Dewadasa, R. Majumder, A. Ghosh, and G. Ledwich, “Control and Computer Engineering, Aristotle University of Thes-
protection of a microgrid with converter interfaced micro sources,” in saloniki. His research interests include the fields of
Proc. Int. Conf. Power Syst., 2009, pp. 1–6. power electronics, distributed generation, power sys-
[21] S. A. Saleh, “Signature-coordinated digital multirelay protection for mi- tem protection, and renewable energy sources.
crogrid systems,” IEEE Trans. Power Electron., vol. 29, no. 9, pp. 4614–
4623, Sep. 2014.
[22] F. Van Overbeeke, “Fault current source to ensure the fault level in inverter-
dominated networks,” in Proc. 20th Int. Conf. Exhib. Elect. Distrib., 2009,
pp. 1–4.
[23] A. Oudalov, A. Fidigatti, T. Degner, B. Valov, C. Hardt, and J. Yarza,
“Novel protection systems for microgrids,” TC2 Tech. Requirements
Netw. Protection, Contract No. SES6-019864, 2009. Charis S. Demoulias (M’96–SM’11) was born in
[24] IEEE Standard Inverse-Time Characteristic Equations Overcurrent Re- 1961. He received the Dipl. and Ph.D. degrees in
lays, IEEE Std C37112-1996, 1997. electrical engineering from the Aristotle University
[25] Low Voltage Molded Case Circuit Breakers up to 1200A. (2008). Technical of Thessaloniki, Thessaloniki, Greece, in 1984 and
catalog. [Online]. Available: http://www.abb.com/ 1991, respectively.
[26] (2011, Sep.). SACE Tmax XT New Low Voltage Moulded-Case Circuit- He is currently an Assistant Professor in the Elec-
Breakers up to 250 A. [Online]. Available: http://www.abb.com/ trical Machines Laboratory, Department of Electrical
[27] J. M. Guerrero, J. Matas, L. G. De Vicuña, M. Castilla, and J. Miret, and Computer Engineering, Aristotle University of
“Wireless-control strategy for parallel operation of distributed-generation Thessaloniki. His research interests include the fields
inverters,” IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1461–1470, Oct. of power electronics, harmonics, electric motion sys-
2006. tems, and renewable energy sources.