AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

1. Capture data for analysis by using ModScan32 tool.

 Open ModScan32 software.

 Set address- 0001, Length-50, Device ID-60 (Refer P15 parameter in governor),
Point type- 03:Holding Register.

PREPARED BY- HARJIT Page 1


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

 Click on setup from toolbar, select data definition, set scan rate -100ms & press ok.

 Click on setup from toolbar, select display options, select show data & integer.

PREPARED BY- HARJIT Page 2


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

 Click on connection from toolbar, select connect, change settings as below & press ok. Once system
is connected to governor then **Device Not Connected!** error will be disappear . (Choose
communication port as USB to RS232 converter configuration in computer manager/com_port.)

 Click on setup from toolbar, select text capture. After selecting text capture a new window will pop-
up. Select location where you want to save the file, Delete * from file name *.txt & save file as - 123.txt
( you can choose any name instead of 123) & press save.

123.txt

PREPARED BY- HARJIT Page 3


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

 After above procedure the data capturing will be activated. Give a start command to governor &
continue till you want to analysis the system (Up to auxiliary start/stop sequence, no-load operation,
load operation & load throw of test). Once the test sequence is finished, select setup from toolbar &
press capture off.

NOTE- THE CAPTURED FILE WILL BE SAVED AS TEXT FORMAT.

2. Convert text file to xls. format for analysis tool.

 Create new excel file & select option to open existing file as shown.

PREPARED BY- HARJIT Page 4


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

 New window will pop-up. Select format to All Files (*.*) & browse the location where you have saved
the captured file (123.txt) & open.

 After Open .txt file a new window will pop-up in excel. Use the setting as mentioned in below
screenshots. Select Delimited-Press next, select tab, semicolon, comma, space, other & press next &
press finish key.

NOTE- NOW CAPTURED DATA IS CONVERTED IN TO 123.xls. SAVE THE FILE.

PREPARED BY- HARJIT Page 5


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

3. Use analysis tool for test.

 Copy all data from 123.xls file which you have converted from text format. For copy all captured data
select A1 cell, press combination of “ Ctrl + Shift “ continue & Press right key once then down
key once. All the data will be selected (display turn blue) leave all the keys what you have pressed
on keyboard. Copy data by right click on mouse or “Ctrl + C “.

 Open “AIMS_ANALYSIS_TOOL_REV_7.xlsb” & click on “Enable content”. Click on DATA from below
worksheet. Select A2 cell & paste data by right click on mouse or “Ctrl + V “. Save the file after copy
captured data.

PREPARED BY- HARJIT Page 6


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

 Click “DATA_CALIBRATION” from worksheet & fill the data marked in green color (C2 to C18) as per
project parameters. RB & GV min/max values shall be observed through dry stroke capturing from
governor. Move RB/GV from 0-100% & note down the Modbus min/max value from RB/GV feedback
registers. The same value shall be used for data calibration sheet.

 For further analysis click required plot from worksheet to analysis the data in graph formation. Move
the slide bar in left or right direction for analysis. Use the same process for all the plots.

PREPARED BY- HARJIT Page 7


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

4. Test start/stop sequence & running parameters observation.

 Click “IO_STATUS” from worksheet. Press “PRESET FOR TEST” button.

 Press Scroll bar to start manual sequence. With this condition the data will float manually by
pressing up/down bar keys.

PREPARED BY- HARJIT Page 8


AIMS GOVERNOR ANALYSIS TOOL TESTING PRODEDURE

 To start the auto sequence, Press slider ( as shown below) with left click and slightly move
mouse/touchpad little down, stop the mouse and release left click from mouse/touchpad. This will
activate auto scroll and your sequence will start in auto mode. Once auto mode is activated the bar
color will change to dark grey. Do not scroll mouse/touchpad or press any key when auto sequence
is activated otherwise sequence will be deactivated.

NOTE- observe the sequence in accordance with site requirements.

PREPARED BY- HARJIT Page 9