ROGUE INSPECTION SERVICES LLC

5415077674
travis@rogueinspection.com
http://www.rogueinspection.com

RESIDENTIAL REPORT
3198 Gold Mine Ave
White City OR 97503
Kaylie Williams Trevor Smidt
MAY 30, 2019

Inspector Agent
Ian Miller Alice Lema
OCHI# 2214 John L. Scott - Medford
5414992125 541-301-7980
ian@rogueinspection.com alicelema@alicelema.com
3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Table of Contents

Table of Contents 2
SUMMARY 5
1: INSPECTION DETAILS 6
2: EXTERIOR 7
3: ROOF 9
4: FOUNDATION, CRAWLSPACE & STRUCTURE 12
5: HVAC 15
6: PLUMBING 21
7: ELECTRICAL 25
8: ATTIC, INSULATION & VENTILATION 27
9: INTERIOR, DOORS, & WINDOWS 29
10: BUILT-IN APPLIANCES 30
11: GARAGE 33
12: PEST INSPECTION 35
13: SEWER SCOPE 36
14: ADDITIONAL COMMENTS / CONCERNS 37

Rogue Inspection Services LLC Page 2 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

INTRODUCTION, SCOPE, DEFINITIONS & COMPLIANCE STATEMENT

Introduction:
The following numbered and attached pages are your home inspection report. The
report includes pictures, information, and recommendations. This inspection was
performed in accordance with the current Standards of Practice and Code of Ethics of
InterNACHI (International Association of Certified Home Inspectors). The Standards
contain certain and very important limitations, expectations and exclusions to the
inspection. A copy is available upon request.

Scope:
A home inspection is intended to assist in evaluating the overall condition of the
dwelling. The inspection is based on observation of the visible, readily accessible and
apparent condition of the structure and its components on this day. The results of
this inspection are not intended to make any representation regarding the presence
or absence of concealed defects that are not reasonably ascertainable or readily
accessible in a competently performed inspection. No warranty, guarantee or
insurance by Rogue Inspection Services, LLC is expressed or implied. This report does
not include inspection for wood destroying insects, mold, lead or asbestos. A
representative sampling of the building components is viewed in areas that are
accessible at the time of the inspection. No destructive testing or dismantling of
components is performed. Not all defects will be identified during this inspection.
Unexpected repairs should be anticipated. The person conducting your inspection is
not a Structural Engineer or other professional whose license authorizes the
rendering of an opinion as to the structural integrity of a building or its other
component parts. You are advised to seek two professional opinions and acquire
estimates of repair as to any defects, comments, improvements or recommendations
mentioned in this report. Rogue Inspection Services, LLC recommends that the
professional making any repairs inspect the property further, in order to discover and
repair related problems that were not identified in the report. We recommend that all
repairs, corrections and cost estimates be completed and documented prior to
closing or purchasing the property. Feel free to hire other professionals to inspect the
property prior to closing, including Qualified HVAC, Plumbing, Electrical, Engineering
and Roofing Contractors.

Use of photos:
Your report includes many photographs which help to clarify where the inspector
went, what was looked at, and the condition of a system or component at the time of
the inspection. Some of the pictures may be of deficiencies or problem areas, these
are to help you better understand what is documented in this report and may allow
you see areas or items that you normally would not see. A pictured issue does not
necessarily mean that the issue was limited to that area only, but may be a
representation of a condition that is in multiple places. Not all areas of deficiencies or
conditions will be supported with photos.

Rogue Inspection Services LLC Page 3 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Comment Key or Definitions:


The following definitions of comment descriptions represent this inspection report. All
comments by the inspector should be considered before purchasing this home. Any
recommendations by the inspector to repair or replace suggests a second opinion or
further inspection by a qualified contractor. All costs associated with further
inspection fees and repair or replacement of item, component or unit should be
considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other
comments were made then it appeared to be functioning as intended allowing for
normal wear and tear.

Not Inspected (NI) = I did not inspect this item, component or unit and made no
representations of whether or not it was functioning as intended and will state a
reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Deficiency (D) = The item, component or unit is not functioning as intended, or needs
further inspection by a qualified contractor. Items, components or units that can be
repaired to satisfactory condition may not need replacement.

What really matters in a home inspection:


The process can be stressful. A home inspection is supposed to give you reassurance
but often has the opposite effect. You will be asked to absorb a lot of information in a
short time. This often includes a written report, checklist, photographs, environmental
reports and what the inspector himself says during the inspection. All this combined
with the seller's disclosure and what you notice yourself makes the experience even
more overwhelming. What should you do? Relax. Most of your inspection will be
maintenance recommendations, life expectancies and minor imperfections. These are
nice to know about. However, the issues that really matter will fall into four
categories: 1. Major defects. An example of this would be a significant structural
failure. 2. Things that may lead to major defects. A small water leak coming from a
piece of roof flashing, for example. 3. Things that may hinder your ability to finance,
legally occupy or insure the home. Structural damaged caused by termite infestation,
for example. 4. Safety hazards. Such as a lack of AFCI/GFCI outlet protection. Anything
in these categories should be corrected. Often a serious problem can be corrected
inexpensively to protect both life and property (especially in categories 2 and 4). Most
sellers are honest and are often surprised to learn of defects uncovered during an
inspection. Realize that sellers are under no obligation to repair everything mentioned
in the report. No home is perfect.

Rogue Inspection Services LLC Page 4 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

SUMMARY

88 1 3
ITEMS INSPECTED MINOR/MAINTENANCE ISSUE RECOMMENDATION

2.1.1 Exterior - Siding, Flashing & Trim: Caulking - Substandard / Missing / Deteriorated
3.1.1 Roof - Coverings: Seal Fasteners
6.3.1 Plumbing - Supply Lines & Fixtures: Leak At Showerhead

8.3.1 Attic, Insulation & Ventilation - Vapor Retarders (Crawlspace or Basement): Vapor Barrier Damaged

Rogue Inspection Services LLC Page 5 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

1: INSPECTION DETAILS
Information

Additional Property Photos Age of Building Home Faces


Under 5 Years North

In Attendance Occupancy Soil Conditions


Client's Agent, Inspector Occupied Dry

Style Temperature Type of Building


Ranch 60-70 F Single Family

Utilities Weather Conditions


All Utilities On Clear

Limitations

General
OCCUPIED HOME
Homes that are occupied at the time of inspection may have conditions that change from the time of
inspection to the time of the closing. It would be wise for the prospective home owner to perform a walk
through inspection after the home has been vacated to determine if there are any conditions that may
have changed.

General
PHOTOS ARE REPRESENTATIVE
Photos are only a representative sample of conditions observed. There may be more than one area of
concern not shown by photo

Rogue Inspection Services LLC Page 6 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

2: EXTERIOR
IN NI NP D
2.1 Siding, Flashing & Trim X X
2.2 Exterior Doors X
2.3 Eaves, Soffits & Fascia X
2.4 Sidewalks, Patios & Driveways X
2.5 Patio / Deck Covers X
2.6 Decks & Steps X
2.7 Grounds X
2.8 Retaining Walls X
2.9 Vegetation X
2.10 Fences/Gates X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Siding, Flashing & Trim: Siding Exterior Doors: Exterior Entry Sidewalks, Patios & Driveways:
Material Door Approachment
Fiber Cement Glass, Steel Sidewalk

Sidewalks, Patios & Driveways: Grounds: Grounds


Driveway Material Level
Concrete

Limitations

Siding, Flashing & Trim


EXTERIOR LIMITATIONS
The inspector performs a visual inspection of accessible components or systems at the exterior. Items
excluded from this inspection include exterior surfaces or components obscured by vegetation, stored
items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding,
trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from
the ground or from a ladder. This may limit a full evaluation.

Deficiencies

2.1.1 Siding, Flashing & Trim Recommendation


CAULKING - SUBSTANDARD /
MISSING / DETERIORATED
COLUMN FRONT PORCH
Caulk was substandard and/or missing in some areas. Recommend
that a qualified person renew or install caulk as necessary. Where
gaps are wider than 1/4 inch, an appropriate material other than
caulk should be used.

Rogue Inspection Services LLC Page 7 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Recommendation
Contact a qualified painting contractor.

Rogue Inspection Services LLC Page 8 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

3: ROOF
IN NI NP D
3.1 Coverings X X
3.2 Roof Drainage Systems X
3.3 Flashings X
3.4 Skylights, Chimneys & Other Roof Penetrations X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Inspection Method Roof Drainage Systems: Gutter Flashings: Material


Roof Material None
Seamless Aluminum

Skylights, Chimneys & Other Skylights, Chimneys & Other


Roof Penetrations: Chimney Roof Penetrations: Skylights
(exterior) None
Metal Flue Pipe

Life Expectancy 10+ Years


Roof was in good condition at the time of inspection. Estimate 10+ years of remaining life.

Coverings: Life Expectancy


Roof Covering
As prescribed in the inspection authorization and agreement, this is a visual inspection only. Roofing life
expectancy can vary depending on several factors. Any estimates of remaining life are approximations only.

Rogue Inspection Services LLC Page 9 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Coverings: Material
Asphalt

Limitations

General
LEAKS UNPREDICTABLE
Roofs are designed to shed water like an umbrella and are not waterproof. In events of wind driven rains,
and periods of intense rain, water can sometimes blow into areas such as ridge vents, roof vents and
valleys and present leaking conditions. This occurrence is rare, but can possibly happen in severe storm
events. Unless it is raining at the time of inspection, some roof leaks may not be identified during the
inspection process.

Deficiencies

Rogue Inspection Services LLC Page 10 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

3.1.1 Coverings Minor/Maintenance Issue


SEAL FASTENERS
ROOF FLASHING
The fasteners on the ridge cap and roof penetrations are not sealed.
I recommend sealing all exposed fasteners. As the nails (fasteners)
age, they begin to rust and shrink and that can allow water to
penetrate the hole and cause damage to the roof structure.
Recommendation
Contact a handyman or DIY project

Rogue Inspection Services LLC Page 11 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

4: FOUNDATION, CRAWLSPACE & STRUCTURE


IN NI NP D
4.1 Foundation X
4.2 Crawlspace X
4.3 Floor Structure X
4.4 Wall Structure X
4.5 Ceiling Structure X
4.6 Roof Structure & Attic X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Foundation: Material Crawlspace: Columns or Peirs Crawlspace: Crawlspace Entry


Concrete Supporting Walls Master Closet

Crawlspace: Method of Crawlspace: Percent of Floor Structure:


Observation Crawlspace Traveled Basement/Crawlspace Floor
Fully Traversed, Crawled 100% Vapor Retarder

Floor Structure: Floor Structure Floor Structure: Sub-floor Ceiling Structure: Ceiling
Wood I-Joists OSB Structure
2x4

Rogue Inspection Services LLC Page 12 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Roof Structure & Attic: Attic Info Roof Structure & Attic: Material Roof Structure & Attic: Method
Attic Hatch OSB of Observation
Walked

Roof Structure & Attic: Roof Roof Structure & Attic: Type
Structure Gable
2x4 Rafters, Engineered Wood
Trusses

Limitations

Crawlspace
CRAWL SPACE LIMITATIONS

Structural components such as joists and beams, and other components such as piping, wiring and/or
Rogue Inspection Services LLC Page 13 of 37
3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Structural components such as joists and beams, and other components such as piping, wiring and/or
ducting that are obscured by under-floor insulation are excluded from this inspection. The inspector does
not determine if support posts, columns, beams, joists, studs, trusses, etc. are of adequate size, spanning
or spacing. The inspector does not guarantee or warrant that water will not accumulate in the crawl spaces
in the future. Complete access to all crawl space areas during all seasons and during prolonged periods of
all types of weather conditions (e.g. heavy rain) would be needed to do so.The inspector attempts to locate
all crawl space access points and areas. Access points may be obscured or otherwise hidden by furnishings
or stored items. In such cases, the client should ask the property owner where all access points are that are
not described in this inspection, and have those areas inspected. Note that crawl space areas should be
checked at least annually for water intrusion, plumbing leaks and pest activity.

Rogue Inspection Services LLC Page 14 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

5: HVAC
IN NI NP D
5.1 Heating Equipment X
5.2 Cooling Equipment X
5.3 Thermostat & Filters X
5.4 Ducts & Registers X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Heating Equipment: Energy Heating Equipment: Heat Type Heating Equipment: Location
Source Gas-Fired Heat, Forced Air Attic
Natural Gas

Cooling Equipment: Brand Cooling Equipment: Cooling Equipment: Energy


Luxaire Configuration Source/Type
Central Electric, Central Air Conditioner,
Heat Pump

Cooling Equipment: Location Cooling Equipment: Thermostat & Filters: Filter


Exterior South Maintenance Location
Heat Pump Living Room
Recommend maintenance
annually.

Rogue Inspection Services LLC Page 15 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Thermostat & Filters: Filter Size Thermostat & Filters: Filter Type Thermostat & Filters:
20x20 Disposable Thermostat
Hallway
The thermostat was operable.

Ducts & Registers: Ductwork


Insulated

Service Heating / Cooling System


HVAC
Ask the property owner when it was last serviced. If unable to determine the last service date, or if this system
was serviced more than 1 year ago, recommend that a qualified HVAC contractor service this system and make
repairs if necessary. Because this system has a compressor and refrigerant system, this servicing should be
performed annually in the future. Any needed repairs noted in this report should be brought to the attention of
the contractor when it's serviced.

Rogue Inspection Services LLC Page 16 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Heating Equipment: Appears Functional


Furnace
Heat system appears to be in working order. Supply air from the heating system should be 100 degrees
Fahrenheit or higher.
The photo(s) below is/are a thermal image of the supply air temperature at register(s) at the time of this
inspection.

Heating Equipment: Brand


Luxaire

Rogue Inspection Services LLC Page 17 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Heating Equipment: Manufacture Date


2016 Year
Typical Life Expectancy

Gas Furnace 15-25 years


Electric Furnace 15-25 years
Heat Pump 10-20 years
Boilers 20-35 years
Mini Split 8-15 years
Baseboard / Wall Heaters 12-18 years
Electric Radiant Heat (heated floor) 25-40 years

Many factors including preventive maintenance, consistency of use, and load demand can play a large factor in
the life expectancy of a heating system. Towards the end of a units life, expect to have increased energy usage
and maintenance cost.

Rogue Inspection Services LLC Page 18 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Cooling Equipment: Appears Functional


Heat Pump
The temperature split differential between the return air and supply registers was within the 14-22 degree (F)
range at time of inspection.
The photo(s) below is/are a thermal image of the air temperature at supply and return air register(s) at the time
of this inspection.

Cooling Equipment: Manufacture Date


2005 Manufacture Date
Typical Life Expectancy

Stand Alone 12-15 years


Heat Pump 10-20 years
Mini Split 8-15 years

Many factors including preventive maintenance, consistency of use, and load demand can play a large factor in
the life expectancy of a cooling system. Towards the end of a units life, expect to have increased energy usage
and maintenance cost.

Rogue Inspection Services LLC Page 19 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Limitations

General
HVAC LIMITATIONS
HVAC
The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters;
solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions;
heating components concealed within the building structure or in inaccessible areas; underground utilities
and systems; safety devices and controls (due to automatic operation). Any comments made regarding
these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life
on heating or cooling system components, does not determine if heating or cooling systems are
appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to
be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency
switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are
intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be
monitored while in operation in the future. Where buildings contain furnishings or stored items, the
inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms,
kitchens and living/dining rooms).

Rogue Inspection Services LLC Page 20 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

6: PLUMBING
IN NI NP D
6.1 Water Service X
6.2 Drain, Waste, & Vent Systems X
6.3 Supply Lines & Fixtures X X
6.4 Water Heater X
6.5 Fuel Systems X
6.6 Sump Pump X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Filters Water Service: Location Water Service: Water Source


None Street Public

Rogue Inspection Services LLC Page 21 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Water Service: Water Supply Drain, Waste, & Vent Systems: Drain, Waste, & Vent Systems:
Material Clean-out Location Drain Size
Pex Exterior 2"

Drain, Waste, & Vent Systems: Supply Lines & Fixtures: Water Heater: Capacity
Material Distribution Material 50 gallons
ABS Pex

Water Heater: Location Water Heater: Manufacture Water Heater: Power


Garage Date Source/Type
2016 Year Gas

Fuel Systems: Appliances On Gas


Water Heater, Furnace

Rogue Inspection Services LLC Page 22 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Fuel Systems: Main Gas Shut-Off


Location
Gas Meter

Water Service: Water Pressure


Not Taken
View of water pressure at the time of the inspection. 50 to 80 PSI is acceptable 60 to 75 PSI is ideal.

Water Heater: Manufacturer


State
I recommend flushing & servicing your water heater tank annually for optimal performance. Water temperature
should be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding.
Here is a nice maintenance guide from Lowe's to help.

Rogue Inspection Services LLC Page 23 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Water Heater: Working


Water Heater
The hot water heater was in good working condition at the time of inspection.

Limitations

Deficiencies

6.3.1 Supply Lines & Fixtures Recommendation


LEAK AT SHOWERHEAD
BATHROOM
The showerhead leaks from coupling. Recommend sealing threads
with Teflon tape and tightening the showerhead.
Recommendation
Recommended DIY Project

Rogue Inspection Services LLC Page 24 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

7: ELECTRICAL
IN NI NP D
7.1 Service Entrance X
7.2 Panels X
7.3 Panel Wiring & Breakers X
7.4 Lighting Fixtures, Switches & Receptacles X
7.5 Wiring X
7.6 GFCI & AFCI X
7.7 Smoke Detectors X
7.8 Carbon Monoxide Detectors X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Service Entrance: Electrical Panels: Main Panel Location Panels: Panel Capacity
Service Conductors Garage 200 AMP
Below Ground, 220 Volts

Panels: Panel Manufacturer Panels: Panel Type Panels: Sub Panel Location
Siemens Circuit Breaker None

Panel Wiring & Breakers: Branch


Wire 15 and 20 AMP
Copper

Rogue Inspection Services LLC Page 25 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Panel Wiring & Breakers: Panel Panel Wiring & Breakers: Wiring
With Cover Removed Method
Garage Romex

Carbon Monoxide Detectors:


Carbon Monoxide Alarm
Installed / Location
Yes, Living Room

GFCI & AFCI: Good working condition


GFCI Outlets
The GFCI outlets were installed in the correct areas and in good working condition at the time of inspection.

Smoke Detectors: Smoke Detector Location


Bedrooms, Hallway, Living Room
The smoke detector should be tested at common hallway to bedrooms upon moving in to home. For many years
NFPA 72, National Fire Alarm and Signaling Code, has required as a minimum that smoke alarms be installed
inside every sleep room (even for existing homes) in addition to requiring them outside each sleeping area and
on every level of the home.

Smoke Detectors: Test Smoke Detectors


Ceilings
Recommend testing all smoke and CO2 detectors upon moving into the home. According to the U.S. Fire
Administration (USFA),smoke detectors should be tested at least once a month and batteries should be replaced
at least once or twice a year.

Rogue Inspection Services LLC Page 26 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

8: ATTIC, INSULATION & VENTILATION


IN NI NP D
8.1 Attic Insulation X
8.2 Floor insulation X
8.3 Vapor Retarders (Crawlspace or Basement) X X
8.4 Attic & Crawlspace Ventilation X
8.5 Exhaust Systems X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Attic Insulation: Attic Insulation Attic Insulation: Insulation Type Floor insulation : Floor
Attic Blown, Cellulose insulation
The attic insulation was Batts
sufficient.

Attic & Crawlspace Ventilation: Attic & Crawlspace Ventilation: Exhaust Systems: Dryer Power
Attic Ventilation Type Crawlspace Ventilation Type Source
Ridge Vents, Soffit Vents Vented 220 Volt

Exhaust Systems: Dryer Vent Exhaust Systems: Exhaust Fans


Metal - Rigid Fan Only

Deficiencies

8.3.1 Vapor Retarders (Crawlspace or Recommendation


Basement)
VAPOR BARRIER DAMAGED
CRAWLSPACE
Vapor barrier is damaged in most areas of the crawlspace floor.
Recommend insulation contractor replace.

Rogue Inspection Services LLC Page 27 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Recommendation
Contact a qualified insulation contractor.

Rogue Inspection Services LLC Page 28 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

9: INTERIOR, DOORS, & WINDOWS


IN NI NP D
9.1 Doors X
9.2 Windows X
9.3 Floors X
9.4 Walls X
9.5 Ceilings X
9.6 Steps, Stairways & Railings X
9.7 Countertops & Cabinets X
9.8 Bathrooms X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Doors: Interior Doors Windows: Window Manufacturer Windows: Window Type


Hollow Core, Wood Unknown Sliders

Floors: Floor Coverings Walls: Wall Material Ceilings: Ceiling Material


Carpet, Tile Drywall Drywall

Countertops & Cabinets: Countertops & Cabinets:


Cabinetry Countertop Material
Wood Granite

Limitations

General
COSMETIC ISSUES NOT ADDRESSED
Issues that are considered as cosmetic are not addressed in this report. (Holes, stains, scratches,
unevenness, missing trim, paint and finish flaws or odors). It is not the intent of this report to make the
house new again.

Rogue Inspection Services LLC Page 29 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

10: BUILT-IN APPLIANCES


IN NI NP D
10.1 Dishwasher X
10.2 Range/Oven/Cooktop X
10.3 Garbage Disposal X
10.4 Built-in Microwave X
10.5 Refrigerator X
10.6 Range Hood X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Dishwasher: Brand Range/Oven/Cooktop: Range/Oven/Cooktop:


Frigidaire Range/Oven Brand Range/Oven Energy Source
Frigidaire Electric

Garbage Disposal: Brand Built-in Microwave: Brand Refrigerator: Brand


InSinkErator Whirlpool Whirlpool

Refrigerator: Working Range Hood: Brand Range Hood: Range Hood Type
Kitchen Whirlpool Vented
The refrigerator was in good
working condition at the time of
inspection.

Appliance Limitation
Appliances
The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops,
ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot
water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning
operations, thermostat or temperature control accuracy, lights, central vacuum systems, elevators and stair lifts.
Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an
estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances.
Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.

Rogue Inspection Services LLC Page 30 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Dishwasher: Working
Kitchen
The dishwasher was in good working condition at the time of inspection. It was run on a rinse cycle.

Range/Oven/Cooktop: Working
Kitchen
The cooktop and oven were tested and in good working condition at the time of inspection.

Rogue Inspection Services LLC Page 31 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Garbage Disposal: Working


Kitchen
The garbage disposal was tested and in good working condition at the time of inspection.

Built-in Microwave: Working


Kitchen
The microwave was tested And in good working condition at the time of inspection.

Range Hood: Fan On Built-In Microwave


Kitchen
The fan on the built-in microwave was in good working condition at the time of inspection.

Rogue Inspection Services LLC Page 32 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

11: GARAGE
IN NI NP D
11.1 Ceiling X
11.2 Floor X
11.3 Walls & Firewalls X
11.4 Garage Door X
11.5 Overhead Door & Opener X
11.6 Occupant Door (From garage to inside of home) X
11.7 Windows X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Garage Door: Material Overhead Door & Opener: Brand Overhead Door & Opener:
Metal, Insulated Overhead Door Material
Metal, Insulated

Overhead Door & Opener: Type


Automatic

Limitations

General
EXCESSIVE STORAGE
GARAGE
The occupants belongings restricted access and the complete
inspection of the garage.

Rogue Inspection Services LLC Page 33 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

Rogue Inspection Services LLC Page 34 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

12: PEST INSPECTION


IN NI NP D
12.1 Exterior X
12.2 Deck X
12.3 Garage X
12.4 Outbuildings X
12.5 Interior X
12.6 Attic X
12.7 Crawlspace X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Evidence Type
NONE NONE

Limitations

General
FUTURE INFESTATIONS
Future infestations of vermin, insects or other animal activity can not be known or predicted.

Rogue Inspection Services LLC Page 35 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

13: SEWER SCOPE


IN NI NP D
13.1 Entry Location X
13.2 Lateral Condition X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Information

Full Sewer Inspection Video: Lateral Length Sewer Line Material


https://youtu.be/NHXeWQbbJJQ 26' GPVC

Entry Location : Point Of Entry


Cleanout, North Exterior

Lateral Condition: Good Condition With No Obstructions


Serwer Drain
Sewer drain was inspected from clean-out to the street connection with sewer main. No repairs are
recommended.

Limitations

General
NO REPAIRS RECOMMENDED
SEWER DRAIN
No defects were observed at the time of the inspection.

Rogue Inspection Services LLC Page 36 of 37


3198 Gold Mine Ave Kaylie Williams Trevor Smidt

14: ADDITIONAL COMMENTS / CONCERNS


IN NI NP D
14.1 Observations X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies

Rogue Inspection Services LLC Page 37 of 37