Item
Actual Photo Remark/s Recommendation/s
No.
a. Busbar
corrosion/discolorat
ion.
b. Short elbow of
wires going to
breaker due to
insufficient width
Replacement of old
of the panel board
1 panel board with a new
enclosure. It may
assembly.
result to heating
and burn on circuit
breaker terminals.
c. Timeworn circuit
breakers might
malfunction during
fault conditions.
a. Indications of fault
(overload and/or
short circuit) on Replacement of old
busbar. panel board with a new
2 assembly incorporating
b. Timeworn circuit Thermal-Magnetic type
breakers might circuit breakers.
malfunction during
fault conditions.
Replacement of
existing cable tray with
an appropriate type
and size to
accommodate all the
feeder wires.
a. Congested cables
on cable tray and it
4 Rewiring of feeder and
might reduce the
branch circuits.
ampacity of wires.
Existing wires will be
subject for Megger test
and will be reuse once
test result value will
comply with the
minimum requirement.