The parameter XXX_Unit is used to specify the unit of measure for the corresponding input parameter (XXX stands for a specific parameter, for example,
PV_Unit). Entry is carried out in the form of a code. Exactly one unit of measure is assigned to each code and is displayed on the faceplate.
You can interconnect the XXX_Unit input parameter of a technologic block with the XXXUnit output parameter of an analog input channel block. At the
analog input channel block, enter the unit of measure at the XXXUnit input parameter (XXX stands for a specific parameter, for example PV_InUnit,
PVOutUnit).
If the parameter value of XXX_Unit is out of range (that is, the value is not defined), the faceplate displays "!undef.!" in the place of unit.
Note
Special notes for channel blocks PCS7AnIn, PCS7AnOu, FbAnIn and FbAnOu
You can use the S7_enum attribute to display the unit in plain text in the CFC editor for these blocks.
Note
In block icons, the update/refresh time of the units is 1 h. If the unit is changed from CFC, the new unit will be visible in the block icon after 1 hour or if
the process picture is reloaded. In faceplates, the update/refresh time of the units is 5 seconds, so the new unit will be visible after 5 s.
Customer-specific units
It is possible to use units which differ from the IEC 611582 standard. You can define your own units in the range 1 to 199 in an XML file.
The name of the XML should be APLCustomerUnits.xml and should be placed in the project path in the folder "GraCS" on both server and client.
The "Unit id" value should be given to XXX_Unit parameter in the function blocks.
Note
The XML is read-only once when WinCC runtime is activated. If any changes are done in the XML later, you must deactivate, close, and activate the WinCC runtime
again to reflect the changes.
Using the unit of measure with controllers for the ConPerMon block
For controller blocks, the current unit of measure is output via output parameter XX_UnitOut . If you use the ConPerMon block, you must switch this
output parameter with the corresponding input parameter XXX_Unit on the ConPerMon block.
If you set the xxx_Unit parameter to 0, the entry is displayed by the S7_Unit attribute in the faceplate and in the block symbol.
List of the most commonly used units of measure in accordance with IEC 61158
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 2 of 18
Note
Due to space constraints on the system, not all units referred to can be displayed in totality. The display of the measurement units is left-aligned. If you
want to abbreviate the unit of measurement, use the function Customer-specific units.
1000 K Kelvin
1005 Degree
1010 m Meter
1013 mm Millimeter
1018 ft Foot
1038 L Liter
1041 hl Hectoliter
1054 s Second
1059 h Hour
1060 d Day
1077 Hz Hertz
1088 kg Kilogram
1120 N Newton
1123 mN Millinewton
1130 Pa Pascal
1190 kW Kilowatt
1209 A Ampere
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 3 of 18
1211 mA Milliampere
1240 V Volt
1422 pH pH value
1000 K Kelvin
1005 Degree
1009 r Revolution
1010 m Meter
1011 km Kilometer
1012 cm Centimeter
1013 mm Millimeter
1014 μm Micrometer
1015 nm Nanometer
1016 pm Picometer
1017 Å Angstrom 2
1018 ft Foot
1019 in Inch
1020 yd Yard
1028 a Are
1029 ha Hectare
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 4 of 18
1038 L Liter
1039 cl Centiliter
1040 ml Milliliter
1041 hl Hectoliter
1054 s Second
1055 ks Kilosecond
1056 ms Millisecond
1057 μs Microsecond
1059 h Hour
1060 d Day
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 5 of 18
1077 Hz Hertz
1088 kg Kilogram
1089 g Gram
1090 mg Milligram
1091 Mg Megagram
1093 oz Ounce
1094 lb Pound
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 6 of 18
1120 N Newton
1121 MN Meganewton
1122 kN Kilonewton
1123 mN Millinewton
1124 μN Micronewton
1130 Pa Pascal
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 7 of 18
mmH2O (4°C)
1161 P Poise
1162 cP Centipoise
1163 St Stokes
1167 J Joule
1168 EJ Exajoule
1169 PJ Petajoule
1170 TJ Terajoule
1171 GJ Gigajoule
1172 MJ Megajoule
1173 kJ Kilojoule
1174 mJ Millijoule
1181 kcalth 1
Kilocalorie (thermo chemical)
1182 Mcalth 1
Megacalorie (thermo chemical)
1183 Btuth 1
British thermal unit
1186 W Watt
1187 TW Terawatt
1188 GW Gigawatt
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 8 of 18
1189 MW Megawatt
1190 kW Kilowatt
1191 mW Milliwatt
1192 μW Microwatt
1193 nW Nanowatt
1194 pW Picowatt
1198 hp Horsepower
1209 A Ampere
1210 kA Kiloampere
1211 mA Milliampere
1212 μA Microampere
1213 nA Nanoampere
1214 pA Picoampere
1215 C Coulomb
1216 MC Megacoulomb
1217 kC Kilocoulomb
1218 μC Microcoulomb
1219 nC Nanocoulomb
1220 pC Picocoulomb
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 9 of 18
2
C/m
1240 V Volt
1241 MV Megavolt
1242 kV Kilovolt
1243 mV Millivolt
1244 μV Microvolt
1245 F Farad
1246 mF Millifarad
1247 μF Microfarad
1248 nF Nanofarad
1249 pF Picofarad
1262 T Tesla
1263 mT Millitesla
1264 μT Microtesla
1265 nT Nanotesla
1266 Wb Weber
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 10 of 18
1270 H Henry
1271 mH Millihenry
1272 μH Microhenry
1273 nH Nanohenry
1274 pH Picohenry
1281 Ω Ohm1
1282 GΩ 1
Gigaohm
1283 MΩ 1
Megaohm
1284 kΩ 1
Kiloohm
1285 mΩ 1
Milliohm
1286 μΩ 1
Microohm
1287 S Siemens
1288 kS Kilosiemens
1289 mS Millisiemens
1290 μS Microsiemens
1291 Ω·m 1
Ohms times meters
1292 GΩ·m 1
Gigaohms times meters
1305 sr Steradian
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 11 of 18
1309 lm Lumen
1314 lx Lux
1316 cd Candela
1342 % Percent
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 12 of 18
1382 B Bel
1383 dB Decibel
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 13 of 18
1402 Bq Becquerel
1408 Gy Gray
1410 rd Rad
1411 Sv Sievert
1416 R Röntgen
1418 3
e/Vm
1422 pH pH value
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 14 of 18
1446 Btuth/min 1
British thermal units per minute
1447 Btuth/d 1
British thermal units per day
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 15 of 18
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 16 of 18
1517 kL Kiloliter
1560 %Sat -
1561 vpm -
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 17 of 18
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018
Selecting a unit of measure Page 18 of 18
1624 gf/cm2a
1625 gf/cm2g
1626 kgf/cm2a
1627 kgf/cm2g
1998 Unknown unit To be used when the unit of measure is not known
during configuration
1
A notation different to the PA profile must be used in order to represent this unit in conformity with the system.
2
"m2" is used instead of "m3" in the Chinese and Japanese documentation.
mk:@MSITStore:C:\Program%20Files%20(x86)\SIEMENS\STEP7\s7libs\PCS7_AP_... 6/19/2018