Kariba Power Station Analogue signal ranges Unit 1

Signal transducer LIMITS max max Ave max Remarks


MEASURE UNIT allowed measured measured
RANGE L2 L1 H1 H2 MCR 72HR NORMAL
u1 Stator Air Temp 1 0-100 4-20mA deg c 20 38 45 45 35 33
u1 Stator Air Temp 2 0-100 4-20mA deg c 20 38 45 45 37 33
u1 TGB Temp 0-120 4-20mA deg c 20 51 55 80 53 51
u1 GGB Temp 0-120 4-20mA deg c 20 75 78 80 76 73
u1 GTB Temp 0-120 4-20mA deg c 20 80 78 80 80 77
u1 Stator Temp 0-150 4-20mA deg c 20 85 95 135 89 83
u1 Rotor Temp 0-150 4-20mA deg c 20 45 50 120 47 44
u1 Rotor Current 0-1500 4-20mA A 900 950 920 n/a n/a
u1 Spiral Casing Pressure 503 4-20mA Ft/M 444/350 25% rise during 100% load rejection( Emergency shut down)
u1 Governor Oil Pressure 588 4-20mA Psi 300 285 285
u1 Governor Air Vess. Pressure 588 4-20mA Psi 300 285 285
u1 Stator Current N/A calculated A 4455 n/a n/a
u1 KiloVolts 0-36 4-20mA Kv 21 n/a n/a
u1 Water Flow 0-169 4-20mA m^3/sec 150
Rotor Volts 0-1000 4-20mA Volts 1000
Rotor insualtion 0-100 4-20mA ohms >389 386 386= normal with all stations at max
Kariba Power Station Analogue signal ranges Unit 2 6

Signal transducer LIMITS max max Ave max Remarks


MEASURE UNIT allowed measured measured
RANGE L2 L1 H1 H2 MCR to date
u2 Stator Air Temp 1 0-100 4-20mA deg 20 25 20 25 47 39
u2 Stator Air Temp 2 0-100 4-20mA deg 20 25 20 25 50 42
u2 TGB Temp 0-120 4-20mA deg 20 25 20 25 53 48 48
u2 GGB Temp 0-120 4-20mA deg 20 25 20 25 81 74
u2 GTB Temp 0-120 4-20mA deg 20 25 20 25 81 74
u2 Stator Temp 0-150 4-20mA deg 20 25 20 25 93 81
u2 Rotor Temp 0-150 4-20mA deg 20 25 20 25 62 55
u2 Rotor Current 0-1500 4-20mA A 500 500 n/a n/a
u2 Spiral Casing Pressure 503 4-20mA Ft/M 25% rise during 100% load rejection( Emergency shut down)
u2 Governor Oil Pressure 588 4-20mA Psi 285 285
u2 Governor Air Vess. Pressure 588 4-20mA Psi 285 285
u2 Stator Current N/A calculated A n/a n/a
u2 KiloVolts 0-36 4-20mA Kv n/a n/a
u2 Water Flow 0-169 4-20mA m^3/sec
Rotor Volts 0-1000 4-20mA Volts
Rotor insualtion 0-100 4-20mA ohms >389 386 386= normal whith all stations at max
Kariba Power Station Analogue signal ranges Unit 3

Signal transducer LIMITS max max Ave max Remarks


MEASURE UNIT allowed measured measured
RANGE L2 L1 H1 H2 MCR to date
u3 Stator Air Temp 1 0-100 4-20mA deg c20 25 20 25 39 30
u3 Stator Air Temp 2 0-100 4-20mA deg c20 25 20 25 40 31
u3 TGB Temp 0-120 4-20mA deg c20 25 20 25 55 50
u3 GGB Temp 0-120 4-20mA deg c20 25 20 25 74 71
u3 GTB Temp 0-120 4-20mA deg c20 25 20 25 71 68
u3 Stator Temp 0-150 4-20mA deg c20 25 20 25 125 110
u3 Rotor Temp 0-150 4-20mA deg c20 25 20 25 68 59
u3 Rotor Current 0-1500 4-20mA A 500 500 n/a n/a
u3 Spiral Casing Pressure 503 4-20mA Ft/M 25% rise during 100% load rejection( Emergency shut down)
u3 Governor Oil Pressure 588 4-20mA Psi 285 285
u3 Governor Air Vess. Pressure 588 4-20mA Psi 285 285
u3 Stator Current N/A calculated A n/a n/a
u3 KiloVolts 0-36 4-20mA Kv n/a n/a
u3 Water Flow 0-169 4-20mA m^3/sec
Rotor Volts 0-1000 4-20mA Volts
Rotor insualtion 0-100 4-20mA ohms >389 386 386= normal whith all stations at max
Kariba Power Station Analogue signal ranges Unit 4

Signal transducer LIMITS max max Ave max Remarks


MEASURE UNIT allowed measured measured
RANGE L2 L1 H1 H2 MCR to date
u4 Stator Air Temp 1 0-100 4-20mA deg 20 25 45 30 26
u4 Stator Air Temp 2 0-100 4-20mA deg 20 25 45 32 27
u4 TGB Temp 0-120 4-20mA deg 20 25 80 58 49
u4 GGB Temp 0-120 4-20mA deg 20 25 80 69 67
u4 GTB Temp 0-120 4-20mA deg 20 25 80 71 68
u4 Stator Temp 0-150 4-20mA deg 20 25 135 79.5 69
u4 Rotor Temp 0-150 4-20mA deg 20 25 120 58 52
u4 Rotor Current 0-1500 4-20mA A 500 920 n/a n/a
u4 Spiral Casing Pressure 503 4-20mA Ft/M 444/350 25% rise during 100% load rejection( Emergency shut down)
u4 Governor Oil Pressure 588 4-20mA Psi 300 285 285
u4 Governor Air Vess. Pressure 588 4-20mA Psi 300 285 285
u4 Stator Current N/A calculated A 4455 n/a n/a
u4 KiloVolts 0-36 4-20mA Kv 21 n/a n/a
u4 Water Flow 0-169 4-20mA m^3/sec 150
Rotor Volts 0-1000 4-20mA Volts 488
Rotor insualtion 0-100 4-20mA ohms 393 >389 386 386= normal whith all stations at max
Kariba Power Station Analogue signal ran Unit 5

Signal transducer LIMITS max max Ave max Remarks


MEASURE UNIT allowed measured measured
RANGE L2 L1 H1 H2 MCR to date
u5 Stator Air Temp 1 0-100 4-20mA deg c 20 25 45 34 32
u5 Stator Air Temp 2 0-100 4-20mA deg c 20 25 45 44 38
u5 TGB Temp 0-120 4-20mA deg c 20 25 80 51 46
u5 GGB Temp 0-120 4-20mA deg c 20 25 80 70 68
u5 GTB Temp 0-120 4-20mA deg c 20 25 80 72 68
u5 Stator Temp 0-150 4-20mA deg c 20 25 135 98 77
u5 Rotor Temp 0-150 4-20mA deg c 20 25 120 55 47
u5 Rotor Current 0-1500 4-20mA A 500 920 n/a n/a
u5 Spiral Casing Pressure 503 4-20mA Ft/M 444/350 25% rise during 100% load rejection( Emergency shut down)
u5 Governor Oil Pressure 588 4-20mA Psi 300 285 285
u5 Governor Air Vess. Pressure 588 4-20mA Psi 300 285 285
u5 Stator Current N/A calculate A 4455 n/a n/a
u5 KiloVolts 0-36 4-20mA Kv 21 n/a n/a
u5 Water Flow 0-169 4-20mA m^3/sec 150
Rotor Volts 0-1000 4-20mA Volts 488
Rotor insualtion 0-100 4-20mA ohms 393 >389 386 386= normal whith all stations at max
Kariba Power Station Analogue signal rangeUnit 6

Signal transducer transducer LIMITS max max Ave max Remarks


MEASURE output UNIT allowed measured measured
RANGE RANGE L2 L1 H1 H2 MCR to date
u6 Stator Air Temp 1 0-100 4-20mA deg c 20 25 38 45 45 43 39 +39*1.05
u6 Stator Air Temp 2 0-100 4-20mA deg c 20 25 38 45 45 43 37
u6 TGB Temp 0-120 4-20mA deg c 20 25 50 55 80 55 44
u6 GGB Temp 0-120 4-20mA deg c 20 25 70 75 80 73 68
u6 GTB Temp 0-120 4-20mA deg c 20 25 76 78 80 76 74
u6 Stator Temp 0-150 4-20mA deg c 20 25 80 85 135 83 75
u6 Rotor Temp 0-150 4-20mA deg c 20 25 60 70 120 70 57
u6 Rotor Current 0-1500 4-20mA A 500 920 n/a n/a
u6 Spiral Casing Pressure 503 4-20mA Ft/M 444/350 25% rise during 100% load rejection( Emergency shut down)
u6 Governor Oil Pressure 588 4-20mA Psi 300 285 285
u6 Governor Air Vess. Pressure 588 4-20mA Psi 300 285 285
u6 Stator Current N/A calculate A 4455 n/a n/a
u6 KiloVolts 0-36 4-20mA Kv 21 n/a n/a
u6 Water Flow 0-169 4-20mA m^3/sec 150
Rotor Volts 0-1000 4-20mA Volts 488
Rotor insualtion 0-100 4-20mA ohms 393 >389 386 386= normal whith all stations at max