Waterfront Integrated Resort Project

92 S.S. Tower, Glennie Street, Colombo 02, Sri Lanka

Request for Information

Ref. No : HKN-RFI-ST-01102 Revision: A


To: The Engineer to the Contract Issue Date: 26.12.2018
Attn: Mr. Jeremy Mayhew Revision date:
No. of pages: 3 page(s) including this page. Response Due Date: 09.01.2019
Title Building 1 Level 10 Swimming pool area Concrete body Clarification

With reference to MVCC-DWG-LS-L-111036_B, S-14697_E

Pursuant to Contract Conditions Clause 1.9, notice is herewith given of the requisite information, drawing, specification, clarification or
instruction, which is required to be issued by the Engineer. If errors, omissions, ambiguities, inconsistencies, inadequacies or other
defects are found in the drawings or instructions provided by the Engineer, the details are set out as below for your review and response,
as appropriate. Please furnish the requisite response with details to us on or before the Response Due Date as indicated above, failing
which there is likely to be delay or disruption to be suffered due to the delay.
Description :

Find attached Building 1 Level 10 Terrace Swimming pool Plans/ Sections Lanscape drawing & Structural Slab
Reinforcement detail highlighting few clarification requests :

1. Please confirm we can rely and measure from the CAD file the concrete bod geometry shown in the sections.
2. Please provide highlighted areas slab thickness.
3. Please clarify concrete wall & wall Thickness.
4. Please clarify which landscape drawing highlighting detail 1 & 2.

Enclosed : 2

Name : SungTae Chun, Design Manager Initiator : Bruno Freitas

Copy to :

Reply from the Engineer :

1.We confirm HKN can rely and measure from the CAD file the concrete bod geometry shown in the
landscape sections;
2.Slab thickness is 0.15 m as it can be measured in section 3A of landscape drawing L-111011;
3.Concrete wall thickness is 0.15m as it can be measured in sections 3A and 3B of landscape drawings
L-111011 and L-11012;
4.Highlighting details 1 and 2 are typical details of the concrete bod (secondary elements) shown in
landscape drawings of terrace level 10 (building 1). These landscape drawings are L-111001 to 04,
L-111011/12.

Name : Date :
1 2 3 4 5 6 7 8

BALMOND STUDIO LONDON OFFICE


Unit 9, 190a New North Road, London N1 7BJ, UK
Tel: +44 20 7043 0651

BALMOND STUDIO COLOMBO OFFICE

3A 3B 3C Glennie Cottage, 78 Glennie Street Colombo-02, Sri Lanka


Tel: +94 11 2304476
L-111036 L-111036 L-111036

CONDITIONS OF USE:
1.7 1.8 1.9 1.10
© Copyright Balmond Studio 2011.
The author asserts the right to be identified as such.
Documentation is to be used for the intended purpose only. Balmond
A Studio accepts no liability, however arising, for misuse of drawings
and documents.

PS.
02
+35.720
CA.02 CA.02 CA.02 CA.02 Drawings must be read in conjunction with all relevant Contract
Documentation including Preliminaries, Particular Conditions,
+35.580 +35.430 +35.580 +35.430 +35.580 General Conditions, Particular Specifications, General Specifications
B
1 L12 L12
and Drawings.
1
1056
-1
L L12 L12
Any discrepancies between any drawings, specifications, documents,
+35.730 etc., should be reported to the Engineer in accordance with the
L12
Conditions of Contract.
3A L12 2A L12 2B L12 2A L12 3A
+35.730 +34.530 +35.730 +35.730 +34.530 The Contractor remains fully responsible for setting out the works.
L-111056 L-111056 L-111056 L-111056 L-111056
Do not scale drawings. Use figured dimensions only. Dimensions
+34.980 +34.980 +34.980 +34.980 +34.980 +34.980 +34.980 +34.980 +34.980 +34.980
L12 must be checked by the Contractor on site.
+35.730 +35.730

+34.383 L12 L12 L12 L12 L12 L12 L12 L12 +34.383

+34.380

3A
L-111056

+35.610 +35.610

1.H John
+34.380 +34.380
SLOPE Keells
+34.650 1.0 % +34.650
Group
+34.500 +34.500
B

+34.330 +34.330 ADÃO DA FONSECA


+34.380 engenheiros consultores
+34.330

G E T GESTÃO DE ENERGIA TÉRMICA, LDA.


var % A
1 Engenheiros Consultores

SLOPE -1
L 1
106
5 de
Alfredo Costa Pereira e Raul Vasconcelos Bessa

B
1

+35.610
-1
L 1
101
5
1.Please confirm we can rely and measure from the CAD file the
concrete body geometry shown in the sections.
+34.380

+34.650
AZ76 Consultores
PS.
02
de Investimentos
e Engenharia, Lda
+34.500
+34.380

1.J
2.Please provide highlighted areas slab thickness. VS-A
C
B
1
-1
L 1
101
5
ATELIER DO BECO

3.Please clarify concrete wall & wall Thickness.


DA BELA VISTA

ritaguedes ARQUITECTURA
PAISAGISTA, LDA

arquitecturapaisagista www.atelierbbv.com

KEY PLAN

6
4 5
PLAN
1A 2

3 1

KEY ELEVATION
3A 3B 3C
L-111036 L-111036 L-111036

D 1.7 1.8 1.9 1.10

0.41 1.75 0.66 1.84 0.60 1.50 0.60 4.33 0.60 1.84 0.60 1.43 1.43 0.60 1.84 0.60 4.71 0.60 1.50 0.60 1.84 0.66 1.88 0.11

+35.530 +35.380 +35.530 +35.380 +35.530


B
1
1
1056 NOTES
-1
L
0.30
0.30

For finishes and materials refer to architectural elements index L-111099


0.30

3A 2A 2B 2A 3A
+34.480 +34.480
Elements such as steel profiles, sub-frames, supports and
0.30

L-111056 L-111056 L-111056 L-111056 L-111056


+34.930 +34.930 +34.930 +34.930 +34.930 +34.930 +34.930 +34.930 +34.930 +34.930 fixings sistems are indicated as design intent.
0.30

Final detail to be as per Contractor's approved shop drawing


0.30

0.30

+34.380 +34.380
KEY
+34.350

Granite type A

3 2 3 2 3A
L-111056
Granite type B
floor finish
wall finish
- FL.38, FL.42
- WL.22, WL.32
wall coping - CO.01, CO.02, CO.03
Granite type C

+35.580 +35.580 Deck Flooring (FL.46)

1.H
+34.350 +34.350 Mosaic for Pool (FL.61 or WL.43)
E SLOPE
+34.600 1.0 % +34.600
lighting

+34.000 +34.000
L# Luminaire type

+34.300 +34.300

+34.350
+34.300

var % A
1
SLOPE -1
L 1
106
5

B
1
-1
L 1
101
5
+35.580

+34.350

+34.600

+34.350 +34.000

F
1.J

B
1
-1
L 1
101
5

B 2018.12.10 HKN-RFI-AR-00971 MC OH

A 2018.11.15 CONSTRUCTION ISSUE MC OH

Rev Date Issue Dwn Ckd

STATUS

FOR CONSTRUCTION
PLAN - SUB-BASE PROJECT
2A
1
WATERFRONT
1 B HKN-RFI-AR-00971
COLOMBO
SRI LANKA
G 1.H 1.J 1.H 1.H
DISCIPLINE

0.20 0.60 7 x 0.30 0.60 0.20 0.60 0.20


LANDSCAPE WORKS
DRAWING TITLE

Level 10 3A
L-111056
1B
L-111056
Level 10 1B
L-111056
2A
L-111056
Level 10 1B
L-111056
3A
L-111056
BUILDING 1
FFL +35.730 FFL +35.730 FFL +35.730
TERRACE 1.10.301
+35.610 +35.610 +35.610

SWIMMING POOL

0.15
1B 1B
0.15

9 x 0.15

1B
L-111051 L-111051
35.000 35.000 L-111051
35.000
+34.650 +34.650
+34.530
+34.650 PLANS / SECTIONS
FFL +34.330 FFL +34.330 FFL +34.330
SSL +34.000 SSL +34.000 SSL +34.000 Date Drawing No Revision

15.11.2018

Scale

1:100 @ A1
L-111036 B
BS Job No

1090

CAD File Name

H L-111036_B.dwg
SECTION SECTION SECTION
3A 3B 3C c

1 B HKN-RFI-AR-00971

BUILDING 1 - TERRACE 1.10.301 - SWIMMING POOL - PLANS / SECTIONS


H1
SCALE:1:100 @ A1
www.balmondstudio.com
Registered in England & Wales No. 7225351
1 2 3 4 5 6 7 8
STRUCTURAL MATERIALS BALMOND STUDIO LONDON OFFICE
(according to british standards) Unit 9, 190a New North Road, London N1 7BJ, UK
Tel: +44 20 7043 0651
3T16
Concrete:
Piles and pile caps: C30/37 BALMOND STUDIO COLOMBO OFFICE
T10@0.125m Foundations, foundations beams and slabs: C30/37 Glennie Cottage, 78 Glennie Street Colombo-02, Sri Lanka
+36.83 Ground slab and pre-cast covers: C30/37 Tel: +94 11 2304476
Slab reinforcement Beams, slabs and stairs: C30/37
1.25 Retaining walls and water tanks: C30/37 CONDITIONS OF USE:
Slab reinforcement Cores, shear walls and prestressed beams: C40/50 U.N.O.
T10@0.125m © Copyright Balmond Studio 2011.
2T12 Columns and plints in pile caps: C50/60 U.N.O.
The author asserts the right to be identified as such.
T6@0.125m Documentation is to be used for the intended purpose only. Balmond
A (every step)
T10@0.125 0.50 Reinforcement: Studio accepts no liability, however arising, for misuse of drawings
Bars: B500 B and B500 C where scheduled
Mesh: B500 B
and documents.
Slab reinforcement 1T8
0.50 T10@0.125 Drawings must be read in conjunction with all relevant Contract
(every step) Top reinforcement
0.50 Documentation including Preliminaries, Particular Conditions,
Slab reinforcement T12@0.125m
1T8 (see plan S-14695) Cover:
(every step) Earth retaining walls and water tanks: 30 mm
General Conditions, Particular Specifications, General Specifications
35T
0.50 Inside building cores, shear walls, slabs and stairs: 30 mm and Drawings.
0.20 T6@0.125m
0.50
0.45 External cores, shear walls, slabs and stairs: 40 mm Any discrepancies between any drawings, specifications, documents,
T10@0.125m T12@0.125m (every step) Inside building beams and columns: 35 mm etc., should be reported to the Engineer in accordance with the
T12@0.125m
T16@0.125m T12@0.125m 0.70 External beams and columns: 45 mm Conditions of Contract.
0.50 1.00 T20@0.125 Foundations and foundation slabs: 45 mm The Contractor remains fully responsible for setting out the works.
0.70
Foundation beams and pile caps: 50 mm Do not scale drawings. Use figured dimensions only. Dimensions
+35.60

0.2
Piles: 85 mm
T10@0.125m must be checked by the Contractor on site.

5
0.70
Botton reinforcement
T20@0.125m (see plan S-14695)
Steel:
T10@0.125m T6@0.125m
Steel Plates: S355J0: t < 40 mm
0.70 (every step)
T8@0.125m Top reinforcement 35T S355J2: 40 mm < t < 60 mm
(see plan S-14695) T12@0.125 S355K2,M,N: 60 mm < t < 75 mm
1T8 35T
T10@0.125m T8@0.125m S355ML,NL: 75 mm < t < 110 mm
(every step) +35.10 T10@0.125
0.50
Top reinforcement
0.40
(see plan S-14695) Steel
T8@0.125m
0.70
T20@0.125m 35T Sections I,H,U:S355J0: t < 40 mm
S355J2: 40 mm < t < 60 mm
0.70 S355K2,M,N: 60 mm < t < 75 mm
S355ML,NL: 75 mm < t < 110 mm
T8@0.125m John
T10@0.125m Hollow
Botton reinforcement Sections: S355J0H: t < 40 mm
Keells
Slab reinforcement
(see plan S-14695) S355J2H: 40 mm < t < 60mm Group
35T S355K2H,MH,NH: 60 mm < t < 75 mm
B Botton reinforcement S355MLH,NLH: 75 mm < t < 110 mm
(see plan S-14695)
Hot-Rolled Sections are required U.N.O.
35T
Slab reinforcement
Bolts:
SECTION A-A SECTION B-B SECTION C-C Class 8.8 U.N.O.
Preloaded bolts: Preloading force = 0.6 fub As
REINFORCEMENT DETAIL REINFORCEMENT DETAIL REINFORCEMENT DETAIL ADÃO DA FONSECA
engenheiros consultores
Scale 1/20 Scale 1/20 Scale 1/20 Pins:
Class 34 CrNiMo6 U.N.O.
GET GESTÃO DE ENERGIA TÉRMICA, LDA.
Welds: Engenheiros Consultores
de
0.80 All fillet welds: a = 0.7 x minimum thickness of the Alfredo Costa Pereira e Raul Vasconcelos Bessa
2T12 plates to be welded, all around the periphery of the
1.25
surfaces in contact U.N.O.
Slab reinforcement Slab reinforcement Slab reinforcement
(See Section H) (See S-14696) (See S-14696) General Notes:
Refer to "General notes and details" drawings

T10@0.125 AZ76 Consultores


de Investimentos
Slab reinforcement Slab reinforcement e Engenharia, Lda
T10@0.125 (See Section H) (See S-14695) Slab reinforcement
T12@0.125
(See S-14695)

40T
0
0.5

T10@0.125 5T20
VS-A
0.45

Slab reinforcement 0.25


0.45

T12@0.125 T10@0.125 T10@0.125 T12@0.125 0.40


5T12 2T10 2T16
T10@0.125
C 0.40 0.40
Slab reinforcement T10@0.125m T10@0.125m

0.33
ATELIER DO BECO

T10@0.125m
T10@0.125m ritaguedes DA BELA VISTA
ARQUITECTURA
PAISAGISTA, LDA
T12@0.125 T12@0.125

0.58
+34.00 atsig
asia
prutcet iu
qra www.atelierbbv.com
0.30

Slab reinforcement

0.63
T10@0.125m
0.30

KEY PLAN

0.25
T12@0.125
40T
T16@0.125m
0.60
T10@0.125
0.40
T10@0.125 6
0.60 2T16
0.40
0.40
0.40
a = 9º (TRUSS 2; 3 and 4) 4 5

40T
a a = 7º (TRUSS 5)
T10@0.125 T10@0.125
Slab reinforcement Slab reinforcement
2
Slab reinforcement
Slab reinforcement SECTION G-G
40T (See S-14696) BEAM ABOVE TRUSS 2 TO TRUSS 5 3 1
Slab reinforcement Slab reinforcement
REINFORCEMENT DETAIL
Scale 1/20

Slab reinforcement
KEY ELEVATION
(See S-14695)

SECTION D-D SECTION E-E SECTION F-F


D REINFORCEMENT DETAIL REINFORCEMENT DETAIL REINFORCEMENT DETAIL +34.45
Scale 1/20 Scale 1/20 Scale 1/20 +34.33
T8@0.125m T16@0.125m

0.50 0.60
2T20
+34.00
0.20 0.15
0.20
4.Please clarify which landscape drawing highlighting detail 1 & 2.
2T12 NOTES
T10@0.125m
2T12 +34.45 2T12 T8@0.125m 3T16 T16@0.125m T10@0.125m
0.50
0.25 0.35x(0.35) 0.25
0.15

T10@0.125m 0.15
0.35
Slab reinforcement 35T 35T Slab reinforcement
4T12 4T12
2T10
T10@0.125m T10@0.125m 0.30
0.15 0.30
T8@0
1.25
T8@0
1.25 T10@0.125m
0.40 0.40 0.35 T8@0
1.25 0.40 0.30 2T10

0.49
T8@0
1.25 0.35
0.15 T8@0
1.25 T10@0
1.25
T10@0.125m Slab reinforcement T10@0.125 T10@0.125 Slab reinforcement T12@0.125m
0.15 T10@0.125m 0.30 T10@0
1.25
0.30
T8@0.125m 0.30
2T12 0.10 0.10 T10@0.125m T16@0.125m 4T8 Slab reinforcement

0.15
0.30 0.30 0.30 T8@0
1.25 0.40 0.40
0.35 T16@0.125m Smeteleschofncaesrb
tl80mm
2T16 0.35

0.25
0.35
0.30 0.30
a
ero
tcesrf(ubb
-anse
id
sle
ati T8@0
1.25 0.30 T8@0
1.25 T12@0.125
2T8 0.35
T10@0
1.25
0.17

T10@0.125m an
ldscape
darw
ng
is)
E T8@0.125m
0.05

T8@0
1.25 T8@0
1.25 0.45 0.45
0.15

0.05 T10@0
1.25
0.30
T12@0.125
0.15

0.15

0.15
0.15

0.35 T8@0
1.25 T12@0.125
0.08

2T16 0.45 0.45


T10@0.125m
5T8 4T8
T10@0.125m 2T16 T8@0
1.25
0.35 0.35 T8@0
1.25 0.30
T8@0
1.25
0.35
SECTION I-I
TERRACE SUB-BASE TERRACE SUB-BASE TERRACE SUB-BASE MAIN DRAIN
TYPICAL REINFORCEMENT DETAIL 3 - POOL AREA TYPICAL REINFORCEMENT DETAIL 1 TYPICAL REINFORCEMENT DETAIL 2 Scale 1/20
(REFER TO LANDSCAPE DRAWINGS) (REFER TO LANDSCAPE DRAWINGS) (REFER TO LANDSCAPE DRAWINGS)
scale 1/20 scale 1/20 scale 1/20

SECTION H-H
0.60

1 BEAM ABOVE TRUSS 1


0.20
REINFORCEMENT DETAIL
2T16 Scale 1/20
0.60
2T16 +35.63

1.00 0.20
F
T8@0.20 m 6T16 INFINITY BAR ADDED
16T16 E 19.11.2018 GENERAL AMENDMENTS ASD ROB
Ø10//0.125m (DETAIL ADDED)
D 19.09.2018 GENERAL AMENDMENTS ASD ROB
0.20

0.30

T8@0.20 m
E p
cVao
c
ielu
to
srtm
ln
C 06.02.2018 HIGHLIGHTED AMENDMENTS ASD ROB
T6@0.20 m B 03.02.2017 LANDSCAPE ISSUE VHB ROB
A 07.09.2015 CONSTRUCTION ISSUE VHB ROB
COLUMN C1.110 COLUMN C1.111
Ø10//0.125m

Ø10//0.125m

Ø10//0.125m

Anchoargce
oufm
lont(s 0.60
0.60 Rev Date Issue Dwn Ckd
REINFORCEMENT DETAIL REINFORCEMENT DETAIL 2T16
0.60 be p
aclen
2d
n
id
phase)
#T16@01.25m
Scale 1/20 Scale 1/20 Rn o
ecfiremo b
etn
et STATUS
o
n
b
h
tP
ie
co
lncen
r2td
n
id
phase 0.55 (x0.55) p
aclen
1p dsihtase

2.53
T10@0.125m T10@0.125m
FOR CONSTRUCTION
PROJECT

0.56
0.60 Cealn
ano d rugh
concesratufcre n
1
psihta
S
ea
1o
vb
l0
tbslu
e
toe
ei
lf WATERFRONT
T10@0.125m COLOMBO

4.03
0.20
Ø10//0.125m
2T16 +35.63 SRI LANKA
0.25
S
B
etelam
G 0.20
DISCIPLINE
2T16 +35.63
0.60

+33.10
2T20
1.20
PLINTH 1 - REINFORCEMENT DETAIL STRUCTURAL WORKS
(REFER TO DRAWING S-11017)

0.25
T12@0.125m
scale 1/20 DRAWING TITLE
VAR.

T10@0.125m

SUP. SLAB REINFORCEMENT T10@0.125m 0.70

BUILDING 1

1.59
0.80 VAR.
VAR.

LEVEL 10 SLAB
0.25

1.98
Ø10//0.125m

1.00
REINFORCEMENT DETAILS
0.65

2T16
1.88

+35.63
0.60

SLAB REINFORCEMENT 2T16


T10@0.125m
INF. SLAB REINFORCEMENT
Date Drawing No Revision

0.25
VAR.

+31.85 +34.00 07.09.2015


T8@0.125m
Scale

0.70
S-14697 E
0.25

0.25
T12@0.125m 1:20@A0
SUP. SLAB REINFORCEMENT
BS Job No

0.14
+34.00 2T16 2T16
0.50 1090
0.25

2T16 CAD File Name


0.20
H 1 S-14697_ E.dwg
3T16 0.80

INF. SLAB REINFORCEMENT c

B1.10.03 B1.10.07 - ELEVATION B1.10.07 - SECTION 1-1 B1.10.08 B1.10.09


REINFORCEMENT DETAIL REINFORCEMENT DETAIL REINFORCEMENT DETAIL REINFORCEMENT DETAIL REINFORCEMENT DETAIL
Scale 1/20 Scale 1/20 Scale 1/20 Scale 1/20 Scale 1/20

www.balmondstudio.com
Registered in England & Wales No. 7225351

Das könnte Ihnen auch gefallen