3.1 Purpose
This test will be performed to confirm CT secondary wiring connection is correct and to check
continuity of CT secondary wiring including cables from CT's to Transformer Differential Relay.
BB-1 AD03
EXISTING
BB-2 R Y B
31.1 A Q1 Q2 P1
Q51
500/1 A
Q0 P2
Q52
3Φ 380V
R03.1
Tap ; 10
NO. 3
73 MVA 87T
Z = 31.1 % (MICOM
110kV / 15/6.6 kV
P633)
Q8
Q0 P1
4000/1 A
P2
AH13 R Y B
BB-2
228 A AH15
Q0
Page 2 OF 10
AT1
73 x 1000 0.380
Ip = x = 4.24 (A)
√3 x 110 x 0.312 110
73 x 1000 0.380
Is = x = 228.0 (A)
√3 x 15.00 0.3122 15
On HV Winding On LV Winding
3.4 Preparation
Confirm CT's Polarity check by DC kick method was performed before this test and CT's Cores are
3.5 Transformer Differential Protection Relay Stability Test for 110kV Switchyard
One of the 110kV GIS Earthing Switch of Transformer bay is closed and 380V Low Voltage is applied
to 15kV winding of the transformer. CT secondary current will be measured at transformer differential
protection relay. Please refer to one line diagram for details.
AECC SITE INSPECTION & TEST RECORD Page 3 OF 10
Q51
500/1 A
Q0
2. Procedure and test result
31.1 A
1) GIS at AD03 status should be as follows.
Q52
Q1-Open Q0-Closed
Tap ; 10
Q2-Open Q52-Open
AT1 Q51-Closed
73 MVA
Z = 31.1 %
110kV / 15 kV
2) MCS at AH15 status should be as follows.
Q0-Close
Q8-Open
AH13
5) Connect power outlet of 3phase 380V to
BB-2
cable termination in AH13.
AH15
6) Apply 3 phase 380V on LV & HV side.
Close AH15=Q0 and AH13=Q0.
Q0
228 A
3Φ 380V
DATE of Test :
TESTING ENGINEER SEC-WR
Signature ; Signature ;
Name ; Mr. Name ; Mr.
DATE of Test :
TESTING ENGINEER SEC-WR
Signature ; Signature ;
Name ; Mr. Name ; Mr.
Remarks ;
DATE of Test :
TESTING ENGINEER SEC-WR
Signature ; Signature ;
Name ; Mr. Name ; Mr.
Page 5 OF 10
4. Transformer Restricted Earth Fault Protection relay (64P & 64S) Stability Test
4.1 Purpose
This test will be performed to confirm CT secondary wiring connection is correct and to check
continuity of CT secondary wiring including cables from CT's to Transformer Restricted Earth Fault
(REF) Protection Relay.
BB-1 AD03
EXISTING
BB-2
Q1 Q2 R03.1
Q51
Remove Earth-Link. 64P
300/1 A
Short single phase to ground (5B3)
by temporary Earth.
Q0
20 A
Q52
Tap ; 10
T1
73 MVA
Z = 31.4 % 500/1 A
110kV / 15 kV
4000/1 A
R03.1
Q0
4000/1 A
64S
(5B3)
AH13
BB-1
AH15
Q0
130 A
3Φ 380V
Page 6 OF 10
73 x 1000 / √3 0.380
Ip = x = 2.43 (A)
√3 x 110 x 0.314 110
4.4 Preparation
Confirm CT's Polarity check by DC kick method was performed before this test and CT's Cores are
4.5 Restricted Earth Fault Relay Stability Test for 110kV Switchyard
3 phase 380V, applied on LV side and closed HV side Circuit breaker R phase only, and Q51 closed.
Measure CT secondary current and voltage across VDR at REF Relay. Reverse polarity at NCT and
then measure them again. The test will be repeated for every phase. Please refer to one line diagram
for details.
AECC SITE INSPECTION & TEST RECORD Page 7 OF 10
3Φ 380V
DATE of Test :
TESTING ENGINEER SAUDCONSULT SEC-WR
3 phase 380V, applied on LV & HV side and shorted single phase to ground via temporary earth at Q51.
a) R phase to ground
HV side REF (64P) @R03.1
REF Relay; 64P
Relay
Measured Primary Secondary
NCT Polarity Current
Current (A) (mA)
Remarks ;
DATE of Test :
TESTING ENGINEER SEC-WR
Signature ; Signature ;
Name ; Mr. Name ; Mr.
b) Y phase to ground
HV side REF (64P) @R03.1
REF Relay; 64P
Relay
Measured Primary Secondary
NCT Polarity Current
Current (A) (mA)
Remarks ;
DATE of Test :
TESTING ENGINEER SEC-WR
Signature ; Signature ;
Name ; Mr. Name ; Mr.
c) B phase to ground
HV side REF (64P) @R03.1
REF Relay; 64P
Relay
Measured Primary Secondary
NCT Polarity Current
Current (A) (mA)
Remarks ;
DATE of Test :
TESTING ENGINEER SEC-WR
Signature ; Signature ;
Name ; Mr. Name ; Mr.