Molded Case Circuit Breakers Product Selection

Assembled Molded Case Circuit Breakers — 800 A, M-Frame

Table 49 - Interrupting Rating/Breaking Capacity — Thermal-Magnetic and Electronic Circuit Breakers


Breaking Capacity (DC),
Interrupting Rating (50/60 Hz), UL 489/CSA 22.2, No. 5 [kA] Breaking Capacity (50/60 Hz), IEC 60947-2
IEC 60947-2(1)
Interrupting
3 Poles in series 220V(3) 415V 690V 750V DC (3 Poles in series)
Code(2)
240V 480V 600V Icu Ics Icu Ics Icu Ics Icu Ics
600V DC(1)
[kA] [%Icu] [kA] [%Icu] [kA] [%Icu] [kA] [%Icu]
100 50 25 20 85 100 50 100 22 75 16 75 M5
200 65 35 35 100 100 70 100 25 75 36 75 M6
200 100 42 50 200 75 100 75 30 75 50 75 M0
(1) DC ratings applicable to thermal magnetic trip unit only.
(2) See Table 50 through Table 54 for Cat. No. selection
(3) These ratings have not been tested for the CCC listing.

Table 50 - Thermal-Magnetic
Rated Thermal Interrupting Code M5 Interrupting Code M6 Interrupting Code M0
Current In Trip [A] Magnetic Trip Protection Type Cat. No. Cat. No. Cat. No.
[A] Im
[A] Ir 3 Poles 4 Poles 3 Poles 4 Poles 3 Poles 4 Poles
600 420…600 3000…6000 140G-M5F3-D60 140G-M5F4-D60 140G-M6F3-D60 140G-M6F4-D60 140G-M0F3-D60 140G-M0F4-D60
F (Adjustable Thermal/
630(1) 441…630 3150…6300 140G-M5F3-D63 140G-M5F4-D63 140G-M6F3-D63 140G-M6F4-D63 140G-M0F3-D63 140G-M0F4-D63
Adjustable Magnetic)
800 560…800 4000…8000 140G-M5F3-D80 140G-M5F4-D80 140G-M6F3-D80 140G-M6F4-D80 140G-M0F3-D80 140G-M0F4-D80
(1) IEC only.

Table 51 - Electronic LSI (Long, Short, Instantaneous)


Rated Protection Type Interrupting Code M5 Interrupting Code M6
Current L S I Cat. No. Cat. No. Cat. No.
In [A] I1=0.4…1 x In t1=sec. I2=0.6…10 x In t2=sec. I3=(1) 3 Poles 4 Poles 3 Poles 4 Poles
600 240…600 3, 6, 12, 18 360…6000 0.05, 0.1, 0.25, 0.5 900…7200 140G-M5H3-D60 140G-M5H4-D60 140G-M6H3-D60 140G-M6H4-D60
630(2) 252…630 3, 6, 12, 18 378…6300 0.05, 0.1, 0.25, 0.5 945…7560 140G-M5H3-D63 140G-M5H4-D63 140G-M6H3-D63 140G-M6H4-D63
800 320…800 3, 6, 9, 18 480…8000 0.05, 0.1, 0.25, 0.5 1200…8400 140G-M5H3-D80 140G-M5H4-D80 140G-M6H3-D80 140G-M6H4-D80
(1) 600 A, 630 A I3max =12 In; 800 A I3 max = 10.5 In
(2) IEC only.

Rated Protection Type Interrupting Code M0


Current In L S I Cat. No.
[A] I1=0.4…1 x In t1=sec. I2=0.6…10 x In t2=sec. I3(1) 3 Poles 4 Poles
600 240…600 3, 6, 12, 18 360…6000 0.05, 0.1, 0.25, 0.5 900…7200 140G-M0H3-D60 140G-M0H4-D60
630(2) 252…630 3, 6, 12, 18 378…6300 0.05, 0.1, 0.25, 0.5 945…7560 140G-M0H3-D63 140G-M0H4-D63
800 320…800 3, 6, 9, 18 480…8000 0.05, 0.1, 0.25, 0.5 1200…8400 140G-M0H3-D80 140G-M0H4-D80
(1) 600 A, 630 A I3 max =12 In; 800 A I3 max = 10.5 In
(2) IEC only.

42 Rockwell Automation Publication 140G-SG001E-EN-P - March 2017


Molded Case Circuit Breakers Product Selection

Table 52 - Electronic LSIG (Long, Short, Instantaneous, Ground Fault)


Protection Type Interrupting Code M5 Interrupting Code M6
Rated
L S I G Cat. No. Cat. No.
Current
In [A] I1=0.4… t =sec. I2=0.6… t2=sec. I3=(1)
I4=0.2…
t4=sec. 3 Poles 4 Poles 3 Poles 4 Poles
1 x In 1
10 x In 1 x In
3, 6, 12, 0.05, 0.1, 0.25,
600 240…600 360…6000 900…7200 120…600 0.1, 0.2, 0.4, 0.8 140G-M5I3-D60 140G-M5I4-D60 140G-M6I3-D60 140G-M6I4-D60
18 0.5
3, 6, 12, 0.05, 0.1, 0.25,
630(2) 252…630 378…6300 945…7560 126…630 0.1, 0.2, 0.4, 0.8 140G-M5I3-D63 140G-M5I4-D63 140G-M6I3-D63 140G-M6I4-D63
18 0.5
0.05, 0.1, 0.25,
800 320…800 3, 6, 9, 18 480…8000 1200…8400 160…800 0.1, 0.2, 0.4, 0.8 140G-M5I3-D80 140G-M5I4-D80 140G-M6I3-D80 140G-M6I4-D80
0.5
(1) 600 A, 630 A I3 max =12 In, 800 A I3 max = 10.5 In
(2) IEC only.

Protection Type Interrupting Code M0


Rated
L S I G Cat. No.
Current In
[A] I3=1…
I1=0.4…1 x In t1=sec. I2=0.6…10 x In t2=sec. I4=0.2…1 x In t4=sec. 3 Poles 4 Poles
10 x In(1)
600 240…600 3, 6, 12, 18 360…6000 0.05, 0.1, 0.25, 0.5 900…7200 120…600 0.1, 0.2, 0.4, 0.8 140G-M0I3-D60 140G-M0I4-D60
630(2) 252…630 3, 6, 12, 18 378…6300 0.05, 0.1, 0.25, 0.5 945…7560 126…630 0.1, 0.2, 0.4, 0.8 140G-M0I3-D63 140G-M0I4-D63
800 320…800 3, 6, 9, 18 480…8000 0.05, 0.1, 0.25, 0.5 1200…8400 160…800 0.1, 0.2, 0.4, 0.8 140G-M0I3-D80 140G-M0I4-D80
(1) 600 A, 630 A I3max =12 In, 800 A I3 max = 10.5 In
(2) IEC only.

Table 53 - Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode)
Protection Type Interrupting Code M5 Interrupting Code M6
Rated
L S I G Cat. No. Cat. No.
Current In
[A] I1=0.4…1 I2=0.6 I3=1…1 I4=0.2…1
t1=sec. t =sec. t4=sec. 3 Poles 4 Poles 3 Poles 4 Poles
x In …10 x In 2 0 x In(1) x In
360… 0.05, 0.1, 900… 0.1, 0.2, 0.4,
600 240…600 3, 6, 12, 18 120…600 140G-M5K3-D60 140G-M5K4-D60 140G-M6K3-D60 140G-M6K4-D60
6000 0.25, 0.5 7200 0.8
378… 0.05, 0.1, 945… 0.1, 0.2, 0.4,
630(2) 252…630 3, 6, 12, 18 126…630 140G-M5K3-D63 140G-M5K4-D63 140G-M6K3-D63 140G-M6K4-D63
6300 0.25, 0.5 7560 0.8
480… 0.05, 0.1, 1200… 0.1, 0.2, 0.4,
800 320…800 3, 6, 9, 18 160…800 140G-M5K3-D80 140G-M5K4-D80 140G-M6K3-D80 140G-M6K4-D80
8000 0.25, 0.5 8400 0.8
(1) 600 A, 630 A I3max =12 In, 800 A I3 max = 10.5 In
(2) IEC only.

Table 54 - Electronic LSIG-MM (Long, Short, Instantaneous, Ground Fault - Maintenance Mode)
Protection Type Interrupting Code M0
Rated
L S I G Cat. No.
Current In
[A] I2=0.6… I3=1…
I1=0.4…1 x In t1=sec. t2=sec. I4=0.2…1 x In t4=sec. 3 Poles 4 Poles
10 x In 10 x In(1)
600 240…600 3, 6, 12, 18 360…6000 0.05, 0.1, 0.25, 0.5 900…7200 120…600 0.1, 0.2, 0.4, 0.8 140G-M0K3-D60 140G-M0K4-D60
630(2) 252…630 3, 6, 12, 18 378…6300 0.05, 0.1, 0.25, 0.5 945…7560 126…630 0.1, 0.2, 0.4, 0.8 140G-M0K3-D63 140G-M0K4-D63
800 320…800 3, 6, 9, 18 480…8000 0.05, 0.1, 0.25, 0.5 1200…8400 160…800 0.1, 0.2, 0.4, 0.8 140G-M0K3-D80 140G-M0K4-D80
(1) 600 A, 630 A I3max =12 In, 800 A I3 max = 10.5 In
(2) IEC only.

Rockwell Automation Publication 140G-SG001E-EN-P - March 2017 43


Molded Case Circuit Breakers Product Selection

Maintenance Mode (MM)


Maintenance Mode (MM) offers a preset set of protection parameters. MM allows systems testing when the molded case circuit
breaker is energized or ON. The following table lists the preset values for Maintenance Mode.

Rated Current In L S I G MM
[A] I1=1 x In t1=MAX sec. I2=OFF t2=OFF sec. I3=4 x In I4=OFF t4=OFF sec. I5=2.5 x In
600 600 18 — — 2400 — — 1500
630(1) 630 18 — — 2520 — — 1575
800 800 18 — — 3200 — — 2000
(1) IEC only.

Figure 8 - Maintenance Mode Basic Wiring Diagram

Requires Cat. No. 140G-K-CC and 140G-K-CIC terminal connectors.


1
2
3 3
4 4
5 - +
6 24V
7 MM Input
8 (Customer Connection)
140G-K-CC
X4 Connector Terminal
LSIG-MM Block

1
2
3
4
5
6
7
MM Output
8
140G-K-CIC (Customer Connection)
X3 Connector Terminal
Block
140G-K
Electronic Trip Unit

44 Rockwell Automation Publication 140G-SG001E-EN-P - March 2017