Air Conditioner Solution Verification for Transport

Node

Shenzhen Envicool Technology Co., Ltd. 1/7


Shenzhen Envicool Technology Co., Ltd. 2/7
Content
1 Conclusion............................................................... 4
2 The requirement of Fitel ................................................. 4
3 Simulation of the Solution ............................................... 4
3.1 Ambient Condition .................................................. 4
3.2 Station Parameters ................................................. 5
3.3 Station Heat Output ................................................ 5
3.4 Airconditioner..................................................... 5
4 Test Procedure........................................................... 5
5 Root Cause Analysis ...................................................... 5
6 Suggestion about ATP with Fitel .......................................... 7

Shenzhen Envicool Technology Co., Ltd. 3/7


1 Conclusion

The solution is good for the project. We set the temperature to 18~22 ℃ (Air

conditioner starts when the temperature in the room is higher than 22℃, and stops

when the temperature in the room is lower than 18℃) yesterday night at 8:00PM,

and the temperature is 19.7℃ in this morning at 9:53AM. The temperature out door

is about 30℃.

2 The requirement of Fitel


- Controlar la Temperatura en el interior de los Nodos, en un rango
de 10° C a 26° C como mínimo.
- Controlar la Humedad relativa en el interior de los Nodos, en un
rango de 20% a 80% como mínimo.

3 Simulation of the Solution

3.1 Ambient Condition

 Ambient Temp: 35℃


 Sun Radiation: 1125W/m²

Shenzhen Envicool Technology Co., Ltd. 4/7


3.2 Station Parameters

 Internal Measurement(L×W×H): 3000×4600×3200mm


 Wall Thickness: 130mm

3.3 Station Heat Output

 Heat Output: 600W

3.4 Air Conditioner

 1 PC EF50HDNC1E, cooling open: 24℃, cooling stop: 20℃

4 Test Procedure
With the on-line support from our R&D, we check all the status of this air
conditioner, and revised all the parameter, there is not any abnormal case.

5 Root Cause Analysis


The solution is based on that the room is closed for long time, there will be
not any one in the room normally. The running time of the air conditioner is not
enough to reduce the temperature to the target range yesterday when we stay at
site.

Shenzhen Envicool Technology Co., Ltd. 5/7


It is summer, and the temperature out side is about 35 ℃, the highest time in
the year. It will take more time for the air conditioner to reduce the temperature
to the target.

The sealing of the door is not very good. The air convection affects a lot to
the cooling of room.

The sealing of the air conditioner is not good, that affects the cooling of the
room also.

Shenzhen Envicool Technology Co., Ltd. 6/7


6 Suggestion about ATP with Fitel
The air conditioner should be started 2 hours before Fitel team come to site,
and temperature and humidity should be checked as the first item in the ATP(we
did it for region I). As the people entering to the room, it will affect the
result of temperature and humidity in the room.
Besides, we suggest that the door should be improved, Fitel might reject this
door, except the affecting to the cooling of the room.