Beruflich Dokumente
Kultur Dokumente
- Ayush Shukla
INDEX
S.NO. NAME OF CONTENTS
1. INTRODUCTION OF 132 KV
SUBSTATION
2. MAIN COMPONENTS OF
SUBSTATION
3. SINGLE LINE DIAGRAM OF
132 KV S\S
4. NAME PLATE READING OF
EQUIPMENTS
5. PLCC EQUIPMENTS
6. PARTS OF TRANSFORMER
7. TRANSMISSION LINE
PROTECTION
8. BATTERY ROOM & BATTERY
CHARGER
9. CONTROL ROOM
10. PROTECTIVE DEVICES
11. VARIOUS TYPES OF TEST
12. CAPACITOR BANK (12Mvar,
15Mvar )
13. SAFETY PRECAUTIONS.
INTRODUCTION
SUBSTATION
Power substation is a subsidiary station of
an electricity transmission and distribution
system where voltage is transformed from
high or medium to low or the reverse using
transformers. Electric power flows through
several substation between generating
plants and consumer changing the voltage
in several stages.
A substation that has a step up
transformer increases the voltage with
decreasing current, while step down
transformer decreases the voltage with
increasing the current for domestic and
commercial distribution.
132 KV SUBSTATION
The project work assigned to us was to
design 132/33KV substation. We considered
incoming power at 132 KV and the power
was transferred to main bus through
isolators-circuit breaker-isolator
combination. The power from main bus was
fed into the 63 MVA, two 40 MVA
transformer which stepped the voltage down
to 33 KV.
Conductors
Conductors
INSUALTORS
Insulators
ISOLATORS
Isolators
Bus bars
Lightening Arresters
The substation equipment such as
conductors, transformers, etc., are always
erected outdoor. Whenever light surges
occur then, a high-voltage pass through
these electrical components causing
damage to them (either temporary or
permanent damage based on the amount of
voltage surge). Therefore, to avoid this
difficulty, lightening arresters are placed to
pass the entire lightening surges to earth.
There are other arresters which are used to
ground the switching surges called as surge
arresters.
CIRCUIT BREAKERS
Circuit Breakers
For the protection of substation and its
components from the over currents or over load
due to short circuit or any other fault the faulty
section is disconnected from the healthy section
either manually or automatically. If once the fault
is rectified, then again the original circuit can be
rebuilt by manually or automatically. Different
types of circuit breakers are designed based on
different criteria and usage. But in general mostly
used circuit breakers are Oil circuit breaker, Air
circuit breaker, SF6 circuit breaker, Vacuum
Circuit Breaker, and so on.
RELAYS
Relays are used for disconnecting the circuits by
manual or automatic operation. Relay consists of
the coil which is excited or energized and such
that making the contacts of relay closed
activates the relay to break or make the circuit
connection. There are different types of
relays such as over current relays, definite time
over current relays, voltage relays, auxiliary
relays, reclosing relays, solid state relays,
directional relays,inverse time over current
relays, microcontroller relays, etc. The above
figure shows some basic relays and their
operation.
Relays
CAPACITOR BANKS
1. Laminated core
2. Windings
3. Insulating materials
4. Transformer oil
5. Tap charger
6. Oil conservator
7. Breather
8. Cooling tubes
9. Buchholz Relay
10. Explosion vent
TRANSMISSION LINE PROTECTION
As the length of electrical power
transmission line is generally long enough
and it runs through open atmosphere, the
probability of occurring fault in electrical
power transmission line is much higher than
that of electrical power transformers and
alternators. That is why a transmission line
requires much more protective schemes
than a transformer.
Protection of line should have some
special features, Such as-
During fault, the only circuit breaker closest to the fault
point should be tripped.
If the circuit breaker closest to the faulty point, fails to trip,
the circuit breaker just next to this breaker will trip as back
up.
The operating time of relay associated with protection of
line should be as minimum as possible in order to prevent
unnecessary tripping of circuit breakers associated with
other healthy parts of power system.
These above mentioned requirements cause protection of
transmission line much different from protection of
transformer and other equipment of power systems.
The main three methods of transmission line protection are
-
1. Time graded over current protection.
2. Differential protection.
3. Distance protection
BATTERY ROOM AND BATTERY CHARGER
BATTERY ROOM:-
A battery room is a room in
a facility used to house batteries for backup or
uninterruptible power systems.
There are 24 battery pin and
voltage of every battery is 15.2 V. Battery room
provides 48 volts to connect on conduction and
control that place.
PREACAUTION FOR BATTERY ROOM
1.Keep the battery room well ventilation.
2.Keep the battery and the surrounding dry
and drain.
3.Check and keep the electrical connection
always light and any connection level to
get heated.
4.Always keep the top surface of the battery
clean and dry.
Battery room is the heart of sub-
station. There are 55 batteries of 2 volts each
connected in series with situated and suitable
total capacity of this unit is 110v. D.C is used
in controlled system.
BATTERY CHARGER:-
A battery charger, or
recharger, is a device used to put energy into a
secondary cell or rechargeable battery by forcing
an electric current through it.
SPECIFICATION OF BATTERY
CHARGER
1.Oil testing:-
Transformer oil, a type of
insulating and cooling oil used in
transformer and other electrical
equipment need to be tested
periodically to ensure that it is still fit
for purpose. This is because it tends
to deteriorate over time, testing
sequence and procedure are defined
by various international standards,
many of them set by ASTM. Testing
consist of measuring breakdown and
other physical and chemical
properties of samples of the oil.
2. INSULATION RESISTENCE TESTING:-
Insulation
resistance test of transformer is
performed on the transformer to-
1. Verify insulation integrity due to the
moisture and impurity contents of
insulation.
2. Ensure that no leakage paths b/w
phases or transformer body
3.POLARITY TEST:-
We use dot convention to
identify the voltage polarity of the mutual
inductance of two windings. The two used
conventions are-
1.If a current enters the dotted terminal of
one winding then the voltage induced on
the other winding will be positive at the
dotted terminal of second winding.
2.If a current leaves the dotted terminal of
one winding then the polarity of voltage
induced in the other winding will be
negative at the dotted terminal of the
second winding.
CAPACITOR BANK
A Capacitor bank is a set of many identical
capacitors connected in series or parallel within a
enclosure and is used for the power factor
correction and basic protection of substation.
These capacitor banks are acts as a source of
reactive power, and thus, the phase difference
between voltage and current can be reduced by
the capacitor banks. They will increase the ripple
current capacity of the supply. It avoids
undesirable characteristics in the power system.
It is the most economical method for
maintaining power factor and of correction of the
power lag problems.
SAFETY PRECAUTIONS
1. Know what you are doing and alert
while doing it.
2. Know what circuit you are handling
and assume that they are alive but you
know they are definitely dead.
3. When connection up then test
instruments or change connecting stand
on insulating material and keep left hand
in your pocket.
4. The isolator bay may be kept in the
board and locked it.
5. When opening or closing any isolator,
wear rubber gloves for protection.
6. The isolator should be close or open
on no load condition.
7. The control panel should be
connected properly.
8. Suitable preventive acessaries are
necessary to minimize the charge due to
inductance in the substation.
9. Earthing should be done at suitable
place.
10. Only the proper equipment should be
used. Take and break poor circuit over
use the disconnection switch on Q.C.B
disconnecting switch can be operated in
parallel.