Beruflich Dokumente
Kultur Dokumente
SIEMENS
6ES5942-7UB11
OTHER SYMBOLS:
6ES59427UB11, 6ES5942 7UB11, 6ES5942-7UB11
biuro@rgbelektronika.pl
+48 71 325 15 05
www.rgbautomatyka.pl
www.rgbautomatyka.pl
www.rgbelektronika.pl
YOUR
PARTNER IN
MAINTENANCE
Repair this product with RGB ELEKTRONIKA ORDER A DIAGNOSIS ∠
LINEAR
ENCODERS PLC
SYSTEMS
INDUSTRIAL
COMPUTERS
ENCODERS CNC
CONTROLS
SERVO AMPLIFIERS
MOTORS
CNC
MACHINES
OUR SERVICES
POWER
SUPPLIERS
OPERATOR
SERVO
PANELS
DRIVERS
At our premises in Wrocław, we have a fully equipped servicing facility. Here we perform all the repair
works and test each later sold unit. Our trained employees, equipped with a wide variety of tools and
having several testing stands at their disposal, are a guarantee of the highest quality service.
Design Power supply modules are supply modules with only one voltage as soon as the first
available with one or two backup battery, the backup one fails. This also applies
backup batteries, depending voltage is supplied via sockĆ when it is removed for reĆ
on the model. These can be ets during replacement. In placement.
replaced even when the those with two backup batterĆ Five power supply modules
power supply is switched off. ies, the second battery beĆ are available for the
In the case of the power gins to supply the backup S5Ć115U/H programmable
controller.
Technical specifications
Power supply module 6ES5 951-7LB21 6ES5 951-7LD21 6ES5 951-7NB21 6ES5 951-7ND51 6ES5 951-7ND41
Supply voltage
S Rated value 230/120 V AC 230/120 V AC 24 V DC 24 V DC 24 V DC
S Ripple Vpp max. Ċ Ċ 3.6 V 3.6 V 3.6 V
S Permissible range 187Ă...Ă264 V 187Ă...Ă264 V 19.2Ă...Ă30 V 9.2Ă...Ă30 V 9.2Ă...Ă30 V
(including ripple) 94Ă...Ă132 V 94Ă...Ă132 V
S Frequency range 47Ă...Ă63 Hz 47Ă...Ă63 Hz Ċ Ċ Ċ
Current consumption
S Rated value IN 0.4/0.6 A 0.4/0.6 A 1.5 A 5A 5.6 A
S Inrush current max. 0.8/1.4 A 0.8/1.4 A 15ĂxĂIN 15ĂxĂIN 15ĂxĂIN
S Iā2ā t 15ĂxĂIN 15ĂxĂIN 0.4 A2s 16 A2s 4.5 A2s
15ĂxĂIN 15ĂxĂIN
0.2 A2s 0.2 A2s
1.8 A2s 1.8 A2s
Mains buffering 20 ms 20 ms 20 ms 20 ms 20 ms
Output voltage V1 +Ă5 V ±Ă1.5Ă% +Ă5 V ±Ă1.5Ă% +Ă5 V ±Ă1.5Ă% +Ă5 V ±Ă1.5Ă% +Ă5 V ±Ă1.5Ă%
Auxiliary voltages
S V2 (e.g. for programmers) +Ă5.2 V (1 A) +Ă5.2 V (2.5 A) +Ă5.2 V (1 A) +Ă5.2 V (2.5 A) +Ă5.2 V (2.5 A)
S V3 (e.g. for CP 525) +Ă24 V (0.2 A) +Ă24 V (0.35 A) +Ă24 V (0.2 A) +Ă24 V (0.35 A) +Ă24 V (0.35 A)
Output current1)
S Rated value for operation
Without fan 3A 7A 3A 7A 7A
With fan 3A 15 A 3A 15 A 15 A
S Permissible range 0.3Ă...Ă3 A 0.3Ă...Ă15 A 0.3Ă...Ă15 A 0.3Ă...Ă15 A 0.3Ă...Ă15 A
1ĂxĂĂlithium battery 2ĂxĂĂlithium battery 1ĂxĂĂlithium battery 2ĂxĂĂlithium battery 2ĂxĂlithium battery
Backup battery
Size C, Size AA, Size C, Size AA, Size AA,
(3.6 V/5 Ah) (3.6 V/2ĂxĂ1.75 Ah) (3.6 V/5 Ah) (3.6 V/2ĂxĂ1.75 Ah) (3.6 V/2ĂxĂ1.75 Ah)
S Backup time min. 1 year (at 0.3 mA, 25 _C and uninterrupted buffering)
S External backup voltage +Ă3.4Ă...Ă+Ă9 V
ShortĆcircuit protection Electronic
OpenĆcircuit protection Yes
Fuse (primary circuit) Integral
Class of protection Class 1
Galvanic isolation Yes Yes No No Yes
Test voltage 2.5 kV AC 2.5 kV AC Ċ Ċ 500 V AC
RI specification A in acc. with A in acc. with A in acc. with A in acc. with A in acc. with
VDE 0871 VDE 0871 VDE 0871 VDE 0871 VDE 0871
Weight approx. 1.6 kg (3.5 lb) 1.9 kg (4.1 lb) 1.6 kg (3.5 lb) 1.6 kg (3.5 lb) 1.6 kg (3.5 lb)
Design The PS 951 power supply where the input circuit of the The lines with the supply
module is potentialĆisolated I/O modules is operated withĆ voltage are connected to the
and is suitable for applicaĆ out ground connection. bottom of the power supply
tions module with the help of screw
terminals.
Technical specifications
PS 951 power supply module 6ES5 951-7ND41 Backup battery (lithium battery) 6ES5 980-0AE11
for S5-115F Size AA, 3.6 V/1.75 Ah
for internal power supply
(without backup battery)
24 V DC; 5 V, 7 A;
nonĆfloating