Specification sheet

Diesel
generator set
NTA855
series engine
315 kVA-400 kVA 50 Hz
300 kW 60 Hz

Description
®
This Cummins commercial generator set is a fully Cooling system – Standard integral set-mounted
integrated power generation system, providing radiator system, designed and tested for rated
optimum performance, reliability, and versatility for ambient temperatures, simplifies facility design
stationary Standby, Prime Power, and continuous requirements for rejected heat.
duty applications.
®
Control system – Standard PowerCommand
Features electronic control provides total system integration
including auto remote start/stop, alarm and status
Cummins heavy-duty engine – Rugged 4-cycle
message display.
industrial diesel delivers reliable power, low
emissions and fast response to load changes.
Enclosures – Optional sound-attenuated
Optional Permanent Magnet Generator (PMG) – enclosures are available.
Offers enhanced motor starting and fault clearing
short circuit capability. Warranty – Backed by a comprehensive warranty
and Worldwide distributor network.
Alternator – Low reactance 2/3 pitch windings; low
wave form distortion with non-linear loads, fault
clearing short-circuits capability, and class H
insulation.

Standby rating Prime rating Data sheet


50 Hz kVA 60 Hz kW 50 Hz kVA 60 Hz kW
Model (kW) (kVA) (kW) (kVA) 50 Hz 60 Hz
C315 D5 315 (250) 275 (220) EA_S_CC_39
C350 D5 350 (280) 320 (256) EA_S_CC_40
C375 D5 375 (300) 340 (270) EA_S_CC_41
C400 D5 400 (320) 360 (288) EA_S_CC_42
C300 D6 300 (375) 273 (341) EA_S_CC_43

power.cummins.com
©2017 Cummins Inc. | EA_T_CC_7_V1_1408 (10/17)
Generator set specifications
Governor regulation class ISO8528 G2
Voltage regulation (no load to full load) ± 1%
Steady-state voltage variation ± 0.5%
Steady-state voltage variation (no load to full load) Isochronous
Steady-state frequency variation ± 0.5%
EMC compatibility BS EN61000-6-4/BS EN61000-6-2

Engine specifications
Design 4 cycle; In-line; 6-Cylinder
Bore 140 mm (5.5 in.)
Stroke 152 mm (6 in.)
Displacement 14 L (855 in.3)
Cylinder block Cast iron
Battery capacity 360 Ah
Battery charging alternator 35 Amps

Starting voltage 24 Volt, negative ground


Fuel system Direct injection Cummins PT
Fuel filter Spin on fuel filters with water separator
Air cleaner type Dry replaceable element with restriction indicator
Lube oil filter type(s) Spin on full flow filter
Standard cooling system 104 °F (40 °C) ambient radiator

Alternator specifications
Deign Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation systems Class H
Standard temperature rise Standby, 125°C (at 40°C ambient temperature)
Exciter type Self-exciting
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone influence factor (TIF) < 50
Telephone harmonic factor (THF) < 2%

Available voltage
50 Hz Line-Neutral/Line-Line 60 Hz Line-Neutral/Line-Line

 254/440  127/254  277/480  138/277


 240/415  120/240  266/460  133/230
 231/400  115/230  254/440  127/250
 220/380  110/220  240/416  120/240

Generator set options and accessories


Engine Enclosure Circuit breaker Silencer
 Heavy duty air filter  Sound attenuated canopy  3 pole main circuit breaker  9 dB attenuation
 Water jacket heater 220/24 V critical silencer
Alternator Warranty  25 dB residential –
Cooling  Alternator heater  5 years for Standby application delivered loose
 Antifreeze 50/50 (ethylene  Exciter voltage regulator(PMG)  2 years for Prime application
glycol)

*Note: Some options may not be available on all models - consult factory for availability.

power.cummins.com
©2017 Cummins Inc. | EA_T_CC_7_V1_1408 (10/17)
Control systems Major features
Generator set control PowerCommand 1.2 –  12 or 24 VDC battery operation.
The PowerCommand 1.2 control is a microprocessor based  Digital engine speed governing to provide isochronous
generator set monitoring control system. The control frequency regulation.
provides a simple operator interface to the generator set,  Digital voltage regulation full wave rectified single
digital voltage regulation, digital engine speed governing, phase (Line to Line) sensing.
start/stop control, and protective functions.
 Generator set monitoring monitors status of all critical
 The PowerCommand 1.2 generator set control is suitable engine and alternator conditions functions.
for use on a wide range of generator sets in non-
paralleling applications.  Engine starting includes relay drivers for start and Fuel
Shut Off (FSO).
 The PowerCommand control can be configured for any
frequency, voltage and power configuration from 120 to  Configurable inputs and outputs – two discrete inputs
600 VAC for 50 Hz or 60 Hz operation. and two dry contact relay outputs.
 Power for the control is derived from the generator set  Smart starting control system – integreated fuel
starting batteries. The control functions over a voltage ramping to limit black smoke and frequency overshoot.
range from 8 VDC to 35 VDC.  Advanced serviceability using InPower™, a PC based
 A larger HMI reduces setup time, provides more software service tool.
information per screen, enhanced navigation and Base engine protection
serviceability.
 Low oil pressure shutdown.
 Includes all functions to locally or remotely start and stop,
and protect the generator set.  High engine temperature shutdown.
 Control switch – RUN/OFF/AUTO.  Under speed/sensor fail shutdown.
 OFF mode – the generator set is shut down and cannot  Fail to start.
be started, as well as reset faults.  Battery charging alternator fail warning.
 RUN mode – the generator set will execute its start
sequence. HMI220 operator interface
 AUTO mode – the generator set can be started with a  Back-lit graphics 128 x 128 LCD display.
start signal from a remote device.
 English text and symbolic overlay
Status indications -The control has a lamp driver for
 Multiple language LCD screens.
external fault/status indication. Functions include:
 Dedicated manual/off/auto function switches with mode
 The lamp flashes during preheat (when used) and while
LEDs and configurable access code (key switch).
the generator set is starting.
 Control set-up without PC-based tool (InPower).
 READY TO LOAD – flashing until the set is at rated
voltage and frequency, then on continuously.  UL508 recognized/CSA certified/CE compliant.
 Fault conditions are displayed by flashing a two-digit fault  Multiple HMIs per generator set (one local and one
code number. remote).
LED Indicating Lamps - includes LED indicating lamps for  Plug and play operation.
the following functions:
 Remote start.
 Warning.
 Shut down.
 Auto.
 Run.
 Remote Emergency Stop Switch input. Immediate shut
down of the generator on the operation.

power.cummins.com
©2017 Cummins Inc. | EA_T_CC_7_V1_1408 (10/17)
Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load for
the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with
ISO 8528. Fuel stop power in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.

Limited-Time Running Power (LTP):


Applicable for supplying power to a constant electrical load This outline drawing is to provide representative
for limited hours. Limited-Time Running Power (LTP) is in configuration details for Model series only.
accordance with ISO 8528.
See respective model data sheet for specific model outline
Prime Power (PRP): drawing number.
Applicable for supplying power to varying electrical load for
unlimited hours. Prime Power (PRP) is in accordance with
ISO 8528. Ten percent overload capability is available in Do not use for installation design
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.

Base Load (Continuous) Power (COP):


Applicable for supplying power continuously to a constant
electrical load for unlimited hours. Continuous Power (COP)
in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271
and BS 5514.

Weight and dimensions


A.Open

Model A, mm B, mm C, mm Dry Wt.* (kg) Wet Wt.* (kg)


C315 D5 3558 1100 2002 3037 3227
C350 D5 3558 1100 2002 3037 3227
C375 D5 3558 1100 2002 3037 3227
C400 D5 3558 1100 2002 3037 3227
C300 D6 3558 1100 2002 3037 3227

B. Enclosed

Model A, mm B, mm C, mm Dry Wt.* (kg) Wet Wt.* (kg)


C315 D5 5110 1500 2890 4921 5698
C350 D5 5110 1500 2890 4921 5698
C375 D5 5110 1500 2890 4921 5698
C400 D5 5110 1500 2890 4921 5698
C300 D6 5110 1500 2890 4921 5698

*Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Certifications
This generator set is designed in
facilities certified to ISO 9001 and This generator set has been designed to
manufactured in facilities certified to ISO 8528 comply with ISO 8528 regulation.
ISO 9001 or ISO 9002.

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
EA_T_CC_7_V1_1408 (10/17)
» Generator set data sheet

Model: C400 D5
Frequency: 50
Fuel Type: Diesel

Spec sheet: EA_T_CC_7 V1_1408


Noise data sheet (Open/enclosed): TP_CPGC_2014_008
Airflow data sheet: TP_CPGC_2014_003
Derate data sheet (Open/enclosed):
Transient data sheet:

Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 400 (320) 360 (288)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
g/kW.h N/A N/A N/A 196.6 232.2 208.8 200.6 197.2
L/hr N/A N/A N/A 83.1 22.2 39.9 57.5 75.3

Engine Standby Rating Prime Rating

Engine manufacturer Cummins


Engine model NTA855-G4
Configuration 4 Cycle; In-line; 6 Cylinder Diesel
Aspiration Turbocharged and Aftercooled
Gross engine power output, kWm 351 317
BMEP at set rated load, kPa 2006 1811
Bore, mm 140
Stroke, mm 152
Rated speed, rpm 1500
Piston speed, m/s 7.62
Compression ratio 14.0:1
Lube oil capacity, L 38.6
Overspeed limit, rpm 2700
Regenerative power, kW 22
Governor type Electrical governor
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 329
Maximum fuel inlet restriction, mm Hg 101.6
Maximum fuel inlet temperature (°C) 71

©2014 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand® and “Our energy working for you.TM” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Document no.
EA_S_CC_42 V1_1408
Air Standby Rating Prime Rating
3
Combustion air, m /min 26.04 24.48
Maximum air cleaner restriction, kPa 3.74

Exhaust Standby Rating Prime Rating


3
Exhaust gas flow at set rated load, m /min 73.5 67.68
Exhaust gas temperature, °C 541 524
Maximum exhaust back pressure, kPa 10

Standard set-mounted radiator cooling


Ambient design, °C 40 50
Fan load, KWm 12
Coolant capacity (with radiator), L 71 78
Cooling system air flow, m3/sec @ 12.7mmH2O 10.1 9.2
Total heat rejection to coolant, BTU/min 14980 13530
Maximum cooling air flow static restriction mmH2O 12.7

Weights* Open Enclosed


Unit dry weight kgs 3037 4921
Unit wet weight kgs 3227 5698
* Weights represent a set with standard features. See outline drawing for weights of other configurations

Dimensions Length (A) Width (B) Height (C)

Standard open set dimensions,mm 3558 1100 2002


Enclosed set standard dimensions,mm 5110 1500 2890

Genset outline

Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

©2014 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand® and “Our energy working for you.TM” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Document no.
EA_S_CC_42 V1_1408
Alternator data
Connection1 Temp rise °C Duty2 Alternator Voltage
Wye, 3 Phase 125/40 °C S/P HCI 444FS 380-415V

Ratings definitions
Emergency Standby Power (ESP) Limited-Time running Power (LTP): Prime Power (PRP) Base Load(Continuous) Power (COP)

Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running Power hours. Prime Power (PRP) is in load for unlimited hours. Continuous
reliable utility source. Emergency (LTP) is in accordance with ISO accordance with ISO 8528. Ten Power (COP) in accordance with ISO
Standby Power (ESP) is in 8528. percent overload capability is 8528, ISO 3046, AS 2789, DIN 6271
accordance with ISO 8528. Fuel available in accordance with ISO and BS 5514.
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS
3046, AS 2789, DIN 6271 and BS 5514.
5514.

Formulas for calculating full load currents:

Three phase output Single phase output

kWx1000 kWxSinglePhaseFactorx1000
Voltagex1. 73x0.8 Voltage

Cummins Power Generation

East Asia Asia Pacific Europe, CIS, Middle East and Africa
2 Rongchang East Street 10 Toh Guan Road #07-01 Manston Park Columbus Ave
Beijing Economic-Technological TT International Tradepark Manston, Ramsgate
Development Area Singapore 608838 Kent CT12 BF United Kingdom
Beijing 1000176 P.R China Phone 65 6417 2388 Phone 44 1843 255000
Phone86 10 5902 3000 Fax 65 6417 2399 Fax 44 1843 255902
Fax86 10 5902 319

©2014 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand® and “Our energy working for you.TM” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Document no.
EA_S_CC_42 V1_1408
HCI 434F/444F - Technical Data Sheet
HCI434F/444F
SPECIFICATIONS & OPTIONS

STANDARDS WINDINGS & ELECTRICAL PERFORMANCE


Newage Stamford industrial generators meet the All generator stators are wound to 2/3 pitch. This
requirements of BS EN 60034 and the relevant section eliminates triplen (3rd, 9th, 15th …) harmonics on the
of other international standards such as BS5000, VDE voltage waveform and is found to be the optimum
0530, NEMA MG1-32, IEC34, CSA C22.2-100, AS1359. design for trouble-free supply of non-linear loads. The
Other standards and certifications can be considered on 2/3 pitch design avoids excessive neutral currents
request. sometimes seen with higher winding pitches, when in
parallel with the mains. A fully connected damper
VOLTAGE REGULATORS winding reduces oscillations during paralleling. This
winding, with the 2/3 pitch and carefully selected pole
AS440 AVR - STANDARD and tooth designs, ensures very low waveform
With this self-excited system the main stator provides distortion.
power via the Automatic Voltage Regulator (AVR) to the
exciter stator. The high efficiency semi-conductors of TERMINALS & TERMINAL BOX
the AVR ensure positive build-up from initial low levels Standard generators are 3-phase reconnectable with 12
of residual voltage. ends brought out to the terminals, which are mounted
The exciter rotor output is fed to the main rotor through on a cover at the non-drive end of the generator. A
a three-phase full-wave bridge rectifier. The rectifier is sheet steel terminal box contains the AVR and provides
protected by a surge suppressor against surges ample space for the customers' wiring and gland
caused, for example, by short circuit or out-of-phase arrangements. It has removable panels for easy
paralleling. access.
The AS440 will support a range of electronic
accessories, including a 'droop' Current Transformer SHAFT & KEYS
(CT) to permit parallel operation with other ac All generator rotors are dynamically balanced to better
generators. than BS6861:Part 1 Grade 2.5 for minimum vibration in
operation. Two bearing generators are balanced with a
MX341 AVR half key.
This sophisticated AVR is incorporated into the
Stamford Permanent Magnet Generator (PMG) control INSULATION/IMPREGNATION
system. The insulation system is class 'H'.
The PMG provides power via the AVR to the main All wound components are impregnated with materials
exciter, giving a source of constant excitation power and processes designed specifically to provide the high
independent of generator output. The main exciter build required for static windings and the high
output is then fed to the main rotor, through a full wave mechanical strength required for rotating components.
bridge, protected by a surge suppressor. The AVR has
in-built protection against sustained over-excitation, QUALITY ASSURANCE
caused by internal or external faults. This de-excites Generators are manufactured using production
the machine after a minimum of 5 seconds. procedures having a quality assurance level to BS EN
An engine relief load acceptance feature can enable full ISO 9001.
load to be applied to the generator in a single step.
If three-phase sensing is required with the PMG system The stated voltage regulation may not be maintained in
the MX321 AVR must be used. the presence of certain radio transmitted signals. Any
We recommend three-phase sensing for applications change in performance will fall within the limits of
with greatly unbalanced or highly non-linear loads. Criteria 'B' of EN 61000-6-2:2001. At no time will the
steady-state voltage regulation exceed 2%.
MX321 AVR
The most sophisticated of all our AVRs combines all the
features of the MX341 with, additionally, three-phase
rms sensing, for improved regulation and performance.
Over voltage protection is built-in and short circuit
current level adjustments is an optional facility. NB Continuous development of our products entitles us
to change specification details without notice, therefore
they must not be regarded as binding.

Front cover drawing typical of product range.

2
HCI434F/444F
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

CONTROL SYSTEM SELF EXCITED


A.V.R. AS440
VOLTAGE REGULATION ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT WILL NOT SUSTAIN A SHORT CIRCUIT

INSULATION SYSTEM CLASS H


PROTECTION IP23
RATED POWER FACTOR 0.8
STATOR WINDING DOUBLE LAYER LAP
WINDING PITCH TWO THIRDS
WINDING LEADS 12
STATOR WDG. RESISTANCE 0.0073 Ohms PER PHASE AT 22°C SERIES STAR CONNECTED
ROTOR WDG. RESISTANCE 1.37 Ohms at 22°C
EXCITER STATOR RESISTANCE 18 Ohms at 22°C
EXCITER ROTOR RESISTANCE 0.068 Ohms PER PHASE AT 22°C
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6317 (ISO)
BEARING NON-DRIVE END BALL. 6314 (ISO)
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 1160 kg 1160 kg
WEIGHT WOUND STATOR 535 kg 535 kg
WEIGHT WOUND ROTOR 463 kg 440 kg
WR² INERTIA 5.4292 kgm2 5.2304 kgm2
SHIPPING WEIGHTS in a crate 1230 kg 1230 kg
PACKING CRATE SIZE 155 x 87 x 107(cm) 155 x 87 x 107(cm)
50 Hz 60 Hz
TELEPHONE INTERFERENCE THF<2% TIF<50
COOLING AIR 0.8 m³/sec 1700 cfm 0.99 m³/sec 2100 cfm
VOLTAGE SERIES STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
VOLTAGE PARALLEL STAR 190/110 200/115 208/120 220/127 208/120 220/127 230/133 240/138
VOLTAGE SERIES DELTA 220/110 230/115 240/120 254/127 240/120 254/127 266/133 277/138
kVA BASE RATING FOR
400 400 400 400 455 480 500 500
REACTANCE VALUES
Xd DIR. AXIS SYNCHRONOUS 2.72 2.45 2.28 2.03 3.28 3.09 2.95 2.71
X'd DIR. AXIS TRANSIENT 0.18 0.16 0.15 0.13 0.18 0.17 0.16 0.15
X''d DIR. AXIS SUBTRANSIENT 0.13 0.12 0.11 0.10 0.13 0.12 0.12 0.11
Xq QUAD. AXIS REACTANCE 2.35 2.12 1.97 1.75 2.90 2.73 2.61 2.39
X''q QUAD. AXIS SUBTRANSIENT 0.31 0.28 0.26 0.23 0.43 0.41 0.39 0.35
XL LEAKAGE REACTANCE 0.06 0.05 0.05 0.04 0.07 0.07 0.06 0.06
X2 NEGATIVE SEQUENCE 0.23 0.20 0.19 0.17 0.29 0.27 0.26 0.24
X0 ZERO SEQUENCE 0.08 0.08 0.07 0.06 0.10 0.09 0.09 0.08
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.08s
T''d SUB-TRANSTIME CONST. 0.019s
T'do O.C. FIELD TIME CONST. 1.7s
Ta ARMATURE TIME CONST. 0.018s
SHORT CIRCUIT RATIO 1/Xd

3
HCI434F/444F
50 Winding 311
Hz THREE PHASE EFFICIENCY CURVES

4
HCI434F/444F
60 Winding 311
Hz THREE PHASE EFFICIENCY CURVES

5
HCI434F/444F
Winding 311

Locked Rotor Motor Starting Curve

50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30

25 25

P E R C E N T T R A N S IE N T V O L T A G E D I P .
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 1400 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA

60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30

25 25

20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .

P E R C E N T T R A N S IE N T V O L T A G E D IP .

15 15

10 10

5 5

0 0
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200
LOCKED ROTOR kVA LOCKED ROTOR kVA

6
HCI434F

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50
Hz
10000

SYMMETRICAL

ASYMMETRICAL
CURRE NT (Am ps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 1,750 Amps

60 10000
Hz
SYMMETRICAL

ASYMMETRICAL
CURRE NT (Am ps)

1000

100
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 2,000 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v X 1.00 416v X 1.00 Minimum x 1.00 x 1.80 x 3.20
400v X 1.05 440v X 1.06 Sustained x 1.00 x 1.50 x 2.50
415v X 1.09 460v X 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v X 1.16 480v X 1.15 All other times are unchanged
Note 3
The sustained current value is constant irrespective
of voltage level Curves are drawn for Star (Wye) connected machines. For other
connection the following multipliers should be applied to current
values as shown :
Parallel Star = Curve current value X 2

7
HCI434F/444F
Winding 311 / 0.8 Power Factor

RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254

kVA 370 370 370 370 400 400 400 400 415 430 430 430 425 450 440 440

kW 296 296 296 296 320 320 320 320 332 344 344 344 340 360 352 352

Efficiency (%) 93.5 93.8 93.9 94.0 93.2 93.4 93.6 93.8 92.9 93.0 93.2 93.5 92.8 92.8 93.1 93.4

kW Input 317 316 315 315 343 343 342 341 357 370 369 368 366 388 378 377

Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Series Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277

kVA 420 445 465 465 455 480 500 500 485 515 535 535 500 530 550 550

kW 336 356 372 372 364 384 400 400 388 412 428 428 400 424 440 440

Efficiency (%) 93.7 93.8 93.8 94.0 93.4 93.4 93.5 93.7 93.1 93.1 93.1 93.4 92.9 92.9 93.0 93.2

kW Input 359 380 397 396 390 411 428 427 417 443 460 458 431 456 473 472

DIMENSIONS

Barnack Road • Stamford • Lincolnshire • PE9 2NB


Tel: 00 44 (0)1780 484000 • Fax: 00 44 (0)1780 484100

© 2006 TD_HCI4F.GB_10.06_04_GB