Beruflich Dokumente
Kultur Dokumente
Diesel
generator set
NTA855
series engine
315 kVA-400 kVA 50 Hz
300 kW 60 Hz
Description
®
This Cummins commercial generator set is a fully Cooling system – Standard integral set-mounted
integrated power generation system, providing radiator system, designed and tested for rated
optimum performance, reliability, and versatility for ambient temperatures, simplifies facility design
stationary Standby, Prime Power, and continuous requirements for rejected heat.
duty applications.
®
Control system – Standard PowerCommand
Features electronic control provides total system integration
including auto remote start/stop, alarm and status
Cummins heavy-duty engine – Rugged 4-cycle
message display.
industrial diesel delivers reliable power, low
emissions and fast response to load changes.
Enclosures – Optional sound-attenuated
Optional Permanent Magnet Generator (PMG) – enclosures are available.
Offers enhanced motor starting and fault clearing
short circuit capability. Warranty – Backed by a comprehensive warranty
and Worldwide distributor network.
Alternator – Low reactance 2/3 pitch windings; low
wave form distortion with non-linear loads, fault
clearing short-circuits capability, and class H
insulation.
power.cummins.com
©2017 Cummins Inc. | EA_T_CC_7_V1_1408 (10/17)
Generator set specifications
Governor regulation class ISO8528 G2
Voltage regulation (no load to full load) ± 1%
Steady-state voltage variation ± 0.5%
Steady-state voltage variation (no load to full load) Isochronous
Steady-state frequency variation ± 0.5%
EMC compatibility BS EN61000-6-4/BS EN61000-6-2
Engine specifications
Design 4 cycle; In-line; 6-Cylinder
Bore 140 mm (5.5 in.)
Stroke 152 mm (6 in.)
Displacement 14 L (855 in.3)
Cylinder block Cast iron
Battery capacity 360 Ah
Battery charging alternator 35 Amps
Alternator specifications
Deign Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation systems Class H
Standard temperature rise Standby, 125°C (at 40°C ambient temperature)
Exciter type Self-exciting
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone influence factor (TIF) < 50
Telephone harmonic factor (THF) < 2%
Available voltage
50 Hz Line-Neutral/Line-Line 60 Hz Line-Neutral/Line-Line
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2017 Cummins Inc. | EA_T_CC_7_V1_1408 (10/17)
Control systems Major features
Generator set control PowerCommand 1.2 – 12 or 24 VDC battery operation.
The PowerCommand 1.2 control is a microprocessor based Digital engine speed governing to provide isochronous
generator set monitoring control system. The control frequency regulation.
provides a simple operator interface to the generator set, Digital voltage regulation full wave rectified single
digital voltage regulation, digital engine speed governing, phase (Line to Line) sensing.
start/stop control, and protective functions.
Generator set monitoring monitors status of all critical
The PowerCommand 1.2 generator set control is suitable engine and alternator conditions functions.
for use on a wide range of generator sets in non-
paralleling applications. Engine starting includes relay drivers for start and Fuel
Shut Off (FSO).
The PowerCommand control can be configured for any
frequency, voltage and power configuration from 120 to Configurable inputs and outputs – two discrete inputs
600 VAC for 50 Hz or 60 Hz operation. and two dry contact relay outputs.
Power for the control is derived from the generator set Smart starting control system – integreated fuel
starting batteries. The control functions over a voltage ramping to limit black smoke and frequency overshoot.
range from 8 VDC to 35 VDC. Advanced serviceability using InPower™, a PC based
A larger HMI reduces setup time, provides more software service tool.
information per screen, enhanced navigation and Base engine protection
serviceability.
Low oil pressure shutdown.
Includes all functions to locally or remotely start and stop,
and protect the generator set. High engine temperature shutdown.
Control switch – RUN/OFF/AUTO. Under speed/sensor fail shutdown.
OFF mode – the generator set is shut down and cannot Fail to start.
be started, as well as reset faults. Battery charging alternator fail warning.
RUN mode – the generator set will execute its start
sequence. HMI220 operator interface
AUTO mode – the generator set can be started with a Back-lit graphics 128 x 128 LCD display.
start signal from a remote device.
English text and symbolic overlay
Status indications -The control has a lamp driver for
Multiple language LCD screens.
external fault/status indication. Functions include:
Dedicated manual/off/auto function switches with mode
The lamp flashes during preheat (when used) and while
LEDs and configurable access code (key switch).
the generator set is starting.
Control set-up without PC-based tool (InPower).
READY TO LOAD – flashing until the set is at rated
voltage and frequency, then on continuously. UL508 recognized/CSA certified/CE compliant.
Fault conditions are displayed by flashing a two-digit fault Multiple HMIs per generator set (one local and one
code number. remote).
LED Indicating Lamps - includes LED indicating lamps for Plug and play operation.
the following functions:
Remote start.
Warning.
Shut down.
Auto.
Run.
Remote Emergency Stop Switch input. Immediate shut
down of the generator on the operation.
power.cummins.com
©2017 Cummins Inc. | EA_T_CC_7_V1_1408 (10/17)
Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load for
the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with
ISO 8528. Fuel stop power in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
B. Enclosed
*Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
Certifications
This generator set is designed in
facilities certified to ISO 9001 and This generator set has been designed to
manufactured in facilities certified to ISO 8528 comply with ISO 8528 regulation.
ISO 9001 or ISO 9002.
©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
EA_T_CC_7_V1_1408 (10/17)
» Generator set data sheet
Model: C400 D5
Frequency: 50
Fuel Type: Diesel
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 400 (320) 360 (288)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
g/kW.h N/A N/A N/A 196.6 232.2 208.8 200.6 197.2
L/hr N/A N/A N/A 83.1 22.2 39.9 57.5 75.3
Fuel flow
Maximum fuel flow, L/hr 329
Maximum fuel inlet restriction, mm Hg 101.6
Maximum fuel inlet temperature (°C) 71
©2014 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand® and “Our energy working for you.TM” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Document no.
EA_S_CC_42 V1_1408
Air Standby Rating Prime Rating
3
Combustion air, m /min 26.04 24.48
Maximum air cleaner restriction, kPa 3.74
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2014 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand® and “Our energy working for you.TM” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Document no.
EA_S_CC_42 V1_1408
Alternator data
Connection1 Temp rise °C Duty2 Alternator Voltage
Wye, 3 Phase 125/40 °C S/P HCI 444FS 380-415V
Ratings definitions
Emergency Standby Power (ESP) Limited-Time running Power (LTP): Prime Power (PRP) Base Load(Continuous) Power (COP)
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running Power hours. Prime Power (PRP) is in load for unlimited hours. Continuous
reliable utility source. Emergency (LTP) is in accordance with ISO accordance with ISO 8528. Ten Power (COP) in accordance with ISO
Standby Power (ESP) is in 8528. percent overload capability is 8528, ISO 3046, AS 2789, DIN 6271
accordance with ISO 8528. Fuel available in accordance with ISO and BS 5514.
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS
3046, AS 2789, DIN 6271 and BS 5514.
5514.
kWx1000 kWxSinglePhaseFactorx1000
Voltagex1. 73x0.8 Voltage
East Asia Asia Pacific Europe, CIS, Middle East and Africa
2 Rongchang East Street 10 Toh Guan Road #07-01 Manston Park Columbus Ave
Beijing Economic-Technological TT International Tradepark Manston, Ramsgate
Development Area Singapore 608838 Kent CT12 BF United Kingdom
Beijing 1000176 P.R China Phone 65 6417 2388 Phone 44 1843 255000
Phone86 10 5902 3000 Fax 65 6417 2399 Fax 44 1843 255902
Fax86 10 5902 319
©2014 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand® and “Our energy working for you.TM” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. Document no.
EA_S_CC_42 V1_1408
HCI 434F/444F - Technical Data Sheet
HCI434F/444F
SPECIFICATIONS & OPTIONS
2
HCI434F/444F
WINDING 311
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX321 MX341
VOLTAGE REGULATION ± 0.5 % ± 1.0 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
3
HCI434F/444F
50 Winding 311
Hz THREE PHASE EFFICIENCY CURVES
4
HCI434F/444F
60 Winding 311
Hz THREE PHASE EFFICIENCY CURVES
5
HCI434F/444F
Winding 311
50
Hz
MX SX
346V 380V 400V 415V 440V 346V 380V 400V 415V 440V
30 30
25 25
P E R C E N T T R A N S IE N T V O L T A G E D I P .
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 1400 0 100 200 300 400 500 600 700 800 900 1000
LOCKED ROTOR kVA LOCKED ROTOR kVA
60
Hz
MX SX
380V 416V 440V 460V 480V 380V 416V 440V 460V 480V
30 30
25 25
20 20
P E R C E N T T R A N S IE N T V O L T A G E D IP .
P E R C E N T T R A N S IE N T V O L T A G E D IP .
15 15
10 10
5 5
0 0
0 200 400 600 800 1000 1200 1400 0 200 400 600 800 1000 1200
LOCKED ROTOR kVA LOCKED ROTOR kVA
6
HCI434F
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am ps)
1000
100
0.001 0.01 0.1 1 10
TIME (secs)
60 10000
Hz
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am ps)
1000
100
0.001 0.01 0.1 1 10
TIME (secs)
7
HCI434F/444F
Winding 311 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254
kVA 370 370 370 370 400 400 400 400 415 430 430 430 425 450 440 440
kW 296 296 296 296 320 320 320 320 332 344 344 344 340 360 352 352
Efficiency (%) 93.5 93.8 93.9 94.0 93.2 93.4 93.6 93.8 92.9 93.0 93.2 93.5 92.8 92.8 93.1 93.4
kW Input 317 316 315 315 343 343 342 341 357 370 369 368 366 388 378 377
Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60
Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Series Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277
kVA 420 445 465 465 455 480 500 500 485 515 535 535 500 530 550 550
kW 336 356 372 372 364 384 400 400 388 412 428 428 400 424 440 440
Efficiency (%) 93.7 93.8 93.8 94.0 93.4 93.4 93.5 93.7 93.1 93.1 93.1 93.4 92.9 92.9 93.0 93.2
kW Input 359 380 397 396 390 411 428 427 417 443 460 458 431 456 473 472
DIMENSIONS
© 2006 TD_HCI4F.GB_10.06_04_GB