DUCT CONSTRUCTION TABLE

CONSTRUCTIONAL REQUIREMENT – RECTANGULAR DUCTS


PRESSURE: LOW PRESSURE – 2" (up to 500 Pa)

Max. Duct Sheet Longitudinal Maximum Transverse Joint


Size (mm) Joints Spacing
(Longer mm
Side)
mm
Grooved/ 1220 Opposite sides , Hemmed S Cleat
0-300 0.55 Pittsburgh And Drive Cleat.
Seam
Grooved/ 1220 Opposite sides, Hemmed standing
301 – 550 0.55 Pittsburgh S Slip 11/8"x 22G and Drive Slip.
Seam
Grooved/ 1220 Opposite sides, Hemmed standing
551-750 0.55 Pittsburgh S Slip 11/8"x 20G and Drive Slip.
Seam
Grooved/ 1220 20mm – Cray flange Slide on flanges
751-1000 0.70 Pittsburgh fitted with Corners and Cleats.
Seam
Grooved/ 1220 20mm – Cray flange Slide on flanges
1001-1200 0.85 Pittsburgh fitted with Corners and Cleats.
Seam
Grooved/ 1220 30mm – Cray flange Slide on flanges
1201-2000 1.00 Pittsburgh fitted with Corners and Cleats.
Seam
Grooved/ 1220 40mm – Cray flange Slide on flanges
2001-2100 1.00 Pittsburgh fitted with Corners and Cleats.
Seam
Grooved/ 1220 40mm – Cray flange Slide on flanges
2101-2400 1.20 Pittsburgh fitted with Corners and Cleats.
Seam
1220 40mm – Cray flange Slide on flanges
Grooved/
fitted with Corners and Cleats.
2401-3000 1.20 Pittsburgh
Reinforcement Stiffener 40mm
Seam
Slide on Flange at 600mm centre.
'SS': Stiffened Sheet by means of Z Profiling along the duct @ 150mm pitch

Reference:
SMACNA HVAC Duct Construction Standards.
Slide On Flange System: CRAYFLANGE Technics Limited